0% found this document useful (0 votes)
43 views36 pages

ELKM3 Digital Controller Manual

The document provides mounting and wiring instructions for an ELKM3 digital controller instrument. It states that the instrument is intended for permanent indoor installation within an electrical panel. When mounting, ensure easy access and minimum vibration with no corrosive gases, water, or wide temperature/humidity variations. Wiring instructions are provided for various input types including thermocouples, RTDs, infrared sensors, and current loops. Proper wiring is important to avoid measurement errors from line resistance or leakage currents.

Uploaded by

Florin Negru
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
43 views36 pages

ELKM3 Digital Controller Manual

The document provides mounting and wiring instructions for an ELKM3 digital controller instrument. It states that the instrument is intended for permanent indoor installation within an electrical panel. When mounting, ensure easy access and minimum vibration with no corrosive gases, water, or wide temperature/humidity variations. Wiring instructions are provided for various input types including thermocouples, RTDs, infrared sensors, and current loops. Proper wiring is important to avoid measurement errors from line resistance or leakage currents.

Uploaded by

Florin Negru
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 36

2.

1 Mounting requirements

ELKM3 This instrument is intended for permanent installation, for


indoor use only, in an electrical panel which encloses the
rear housing, exposed terminals and wiring on the back.
Select a mounting location having the following characteristics:
1. It should be easily accessible;
DIGITAL 2. There is minimum vibrations and no impact;
CONTROLLER 3. There are no corrosive gases;
4. There are no water or other fluids (i.e. condensation);
5. The ambient temperature is in accordance with the
operative temperature (0... 50°C);
6. The relative humidity is in accordance with the instrument
specifications (20... 85%);
The instrument can be mounted on panel with a maximum
thickness of 15 mm.

Engineering Manual When the maximum front protection (IP65) is desired, the
optional gasket must be monted.
Code : ISTR-MKR1-3ENG03 - Vr. 3.0 (ENG)
EL.CO. S.r.l. 2.2 General notes about wiring
Via Lago di Molveno, 20 - 36015 Schio (VI) • ITALY 1. Do not run input wires together with power cables.
Tel.: +39 0445 661722 - Fax: +39 0445 661792 2. External components (like zener barriers, etc.) connected
www.elco-italy.com between sensor and input terminals may cause errors in
e-mail: [email protected] measurement due to excessive and/or not balanced line
resistance or possible leakage currents.
1. Outline dimensions (mm)
3. When a shielded cable is used, it should be connected at
Instrument with non removable terminals one point only.
4. Pay attention to the line resistance; a high line resistance
may cause measurement errors.
78 5 64 14
2.3 Inputs
2.3.1 Termocouple Input
35

PV

AT

1 2
2. Connection diagram
+ -
Passive TX,
2 wires, Relay Out 1: 4 (4) A/250 VAC
4... 20 mA Relay Out 2, 3: 2 (1) A/250 VAC (*) External resistance: 100Ω max., maximum error 25 mV.
SSR Out 1, 2 , 3: 10 VDC/15 mA
0/12... 60 mV,
Out1: 4... 20 mA (KR3 only)
Cold junction: automatic compensation between 0... 50°C.
0/1... 5V,
0/2... 10V + SSR Out4: 12 VDC/20 mA Cold junction accuracy: 0.05°C/°C after a warm-up of
* KR3 servodrive models: both Out2 and Out3
4... 20 mA are to be selected as “M” in Configuration code;
20 minutes.
(active) +
Out2: open, Out3: close Input impedance: > 1 MΩ.
Pt1000
Pt100 DI2 DI1 Calibration: According to EN 60584-1.
RS485
TC + Note: For TC wiring use proper compensating cable
D- D+ preferable shielded.

+ - Out1
Out4
Out3 Out2

C NO C NO C NC NO
Power
Supply

EL.CO. - ELKM3 - ENGINEERING MANUAL -Vr. 01 (UK) PAG. 1


2.3.2 Infrared Sensor Input 2.3.6 mA Input
0/4... 20 mA input wiring for passive transmitter
Exergen using the auxiliary pws

4...20 mA
2 wires
Transmitter
- +
1 2
+ -
External resistance: not relevant.
Cold junction: automatic compensation between 0... 50°C.
1 2 3 4
Cold junction accuracy: 0.05°C/°C.
Input impedance: > 1 MΩ. Input impedance: < 53Ω.
Internal auxiliary PWS: 12 VDC (±10%), 20 mA max..
2.3.3 RTD Pt 100 Input
0/4... 20 mA input wiring for passive transmitter
using an external pws
RTD

0/4...20 mA
passive
transmitter
- +
1 2 3 +

External
Input circuit: Current injection (150 µA).

PWS
Line resistance: Automatic compensation up to 20Ω/wire
with maximum error ±0.1% of the input span.
Calibration: According to EN 60751/A2. -
Note: The resistance of the 3 wires must be the same.

2.3.4 RTD Pt 1000, NTC and PTC Input 1 2


+ -
Pt1000

0/4... 20 mA input wiring for active transmitter

0/4... 20 mA
active
transmitter
2 3
+ -

Line resistance: Not compensated.


Pt 1000 input circuit: Current injection (15 µA).
Pt 1000 calibration: According to EN 60751/A2. 1 2
2.3.5 V and mV Input + -
mV
V
+ -

1 2
+ -
Input impedance: > 1 MΩ for mV Input
500 kΩ for Volt Input.

EL.CO. - ELKM3 - ENGINEERING MANUAL -Vr. 01 (UK) PAG. 2


2.3.7 Logic Inputs SSR Output
Safety notes: SSR
––Do not run logic input wiring together with power cables; + -
––The instrument needs 150 ms to recognize a contact 22 24
status variation;
––Logic inputs are NOT isolated by the measuring input.
A double or reinforced isolation between logic inputs and Logic level 0: Vout < 0.5 VDC
power line must be assured by the external elements. Logic level 1: 12 V ± 20%, 15 mA max.

Logic input driven by dry contact Current Analogue Output


mA
Digital + -
Digital
input 2
input 1 22 24

4 5 6 11 mA output: 0/4... 20 mA, galvanically isolated, RL max. 600Ω.


Voltage Analogue Output
Maximum contact resistance: 100Ω.
Contact rating: DI1 = 10 V, 6 mA; V
DI2 = 12 V, 30 mA. + -
22 24
Logic inputs driven by 24 VDC
+ -
Digital V output: 0/2... 10 V, galvanically isolated, RL min.: 500Ω.
input 2 + - Digital
input 1 2.4.2 Output 2 (OP2)
Relay Output
4 5 6 11

Logic status 1: 6... 24 VDC; 17 18


Logic status 0: 0... 3 VDC.

2.4 Outputs C NO
Safety notes: OP1 contact rating: - 2 A /250 V cosj = 1
- 1 A /250 V cosj = 0.4
––To avoid electrical shocks, connect power line at last.
Operation: 1 x 105
––For supply connections use No. 16 AWG or larger wires
rated for at last 75°C. SSR Output
––Use copper conductors only. SSR
––SSR outputs are not isolated. A reinforced isolation must + -
be assured by the external solid state relays. 17 18
––For SSR, mA and V outputs if the line length is longer than
30 m use a shielded wire. + -
WARNING! Before connecting the output actuators, Logic level 0: Vout < 0.5 VDC
we recommend to configure the parameters to Logic level 1: 12 V ± 20%, 15 mA max.
suit your application (e.g.: input type, Control
strategy, alarms, etc.). 2.4.3 Output 3 (OP3)
2.4.1 Output 1 (OP1) Relay Output
Relay Output
15 16

22 23 24
C NO

C NC NO OP1 contact rating: - 2 A /250 V cosj = 1


- 1 A /250 V cosj = 0.4
OP1 contact rating: - 4 A /250 V cosj =1 Operation: 1 x 105
- 2 A /250 V cosj =0.4
Operation: 1 x 105

EL.CO. - ELKM3 - ENGINEERING MANUAL -Vr. 01 (UK) PAG. 3


SSR Output 2.6 Power Supply
SSR
+ - Power 9 10
15 16 Supply

+ -
Neutral Line
Logic level 0: Vout < 0.5 VDC
Logic level 1: 12 V ± 20%, 15 mA max. Supply Voltage: - 24 VAC/DC (±10%)
- 100... 240 VAC (-15... +10%)
2.4.4 Output 2 and Output 3 Servomotor Drive Notes: 1. Before connecting the instrument to the power
Close Open line, make sure that line voltage is equal to the
voltage shown on the identification label;
C NO C NO
2. The polarity of the power supply has no importance;
15 16 17 18
3. The power supply input is NOT fuse protected.
Please, provide a T type 1A, 250 V fuse externally.
Out3 Out2
4. When the instrument is powered by the A01 key,
OP2/3 contact rating: - 2 A /250 V cosj = 1; the outputs are NOT supplied and the instrument
- 1 A /250 V cosj = 0.4. can show the ouLd (Out 4 Overload) indication.
Operation: 1 x 105.
3. Technical characteristics
2.4.5 Output 4 (OP4) Case: Plastic, self-extinguishing degree: V-0 according to UL 94;
SSR Output Front protection: IP 65 (when the optional panel gasket is
+ - mounted) for indoor locations according to EN 60070-1;
Terminals protection: IP 20 according to EN 60070-1;
Installation: Panel mounting;
4 11
+ - Terminal block:24 M3 screw terminals, for cables from
0.25... 2.5 mm2 (AWG 22... AWG 14) with connection
SSR
diagrams;
Logic level 0: Vout < 0.5 VDC; Dimensions: 78 x 35 depth 69.5 mm (3.07 x 1.37 depth 2.73 in.)
Logic level 1: 12 V ± 20%, 20 mA max..
Panel cutout: 71(+0.6) x 29(+0.6) mm [2.79(+0.023) x 1.14+(+0.023) in.]
Note: Overload protected. 71 x 29 (-0... +0.5 mm)
Weight: 180 g max..
2.5 Serial Interface
Power supply: • 24 VAC/DC (±10% of the nominal value);
RS485 D+ • 100... 240 VAC (-15... +10% of the
nominal value);
C
Power consumption: 5 VA max.;
D-
Insulation voltage: 2300 V rms according to EN 61010-1;
D+ Display updating time: 500 ms;
8 9 10 D- Sampling time: 130 ms;
D- D+ Resolution: 30000 counts;

GND Total Accuracy: ±0.5% F.S.V. ±1 digit @ 25°C of room


D+
temperature;
D-
Electromagnetic compatibility and safety requirements
Interface type: Isolated (50 V) RS-485; Compliance: directive EMC 2004/108/CE (EN 61326-1),
Voltage levels: According to EIA standard; directive LV 2006/95/CE (EN 61010-1);
Protocol type: MODBUS RTU; Installation category: II;
Byte format: 8 bit with no parity;
Pollution category: 2;
Stop bit: 1 (one);
Baud rate: Programmable between 1200... 38400 baud; Temperature drift: It is part of the global accuracy;
Address: Programmable between 1... 255. Operating temperature: 0... 50°C (32... 122°F);
Notes: 1. RS-485 interface allows to connect up to 30 Storage temperature: -30... +70°C (-22... +158°F);
devices with one remote master unit. Humidity: 20... 85% RH, not condensing.
2. The cable length must not exceed 1.5 km at
9600 baud.

EL.CO. - ELKM3 - ENGINEERING MANUAL -Vr. 01 (UK) PAG. 4


3.1 How to order
Modello
ELKM3 = Controller
ELKM3T = Controller+timer
Power supply
240 = 100... 240 VAC
24 = 24 VAC/DC
Analogue input + Digital Input DI1 (standard)
C = J, K, R, S, T, PT100, PT 1000 (2 wires), mA, mV, V
E = J, K, R, S, T, NTC, PTC, mA, mV, V
Output 1
R = Relay SPDT 4 A/250Vac (resistive load)
O = VDC for SSR 12 Vdc/20mA
Output 2
- = Not available
2R = Relay SPST NO 2 A/250Vac (resistive load)
2S = VDC for SSR 12 Vdc/20 mA
Output 3
- = Not available
3R = Relay SPST NO 2 A/250Vac (resistive load)
3S = VDC for SSR 12 Vdc/20 mA
Input/Output 4
4D = Output 4 (VDC for SSR)/Pow. Supply/Dig. Input DI2
Serial Communications
- = TTL Modbus
S = RS485 Modbus + TTL Modbus

EL.CO. - ELKM3 - ENGINEERING MANUAL -Vr. 01 (UK) PAG. 5


4. CONFIGURATION PROCEDURE 4.3 How to enter the
“Configuration modes”
4.1 Introduction
Note: The ELKM3 controller is equipped with two different
When the instrument is powered, it starts immediately to work “configuration” methods:
according to the parameters values loaded in its memory. A) The “code” configuration method;
The instrument behaviour and its performance are governed B) The “complete” configuration method.
by the value of the stored parameters. The “code” configuration method is really fast but modifies
At the first start up the instrument will use a “default” only the most common configuration parameters.
parameter set (factory parameter set); this set is a generic The “complete” configuration method allows to take
one (e.g. a TC J input is programmed). advantage of all instrument features, giving more capabilities
WARNING! Before connecting the output actuators, it requires more actions and time.
we recommend to configure the parameters to Note that you can take advantage by both methods because if
suit your application (e.g.: input type, Control
you use the code configuration and then you enter in the
strategy, alarms, etc.).
complete configuration, all selections made by code are still valid.
To change these parameters you need to enter the
In both cases the instrument have one complete parameter set.
“Configuration mode”.
We call this set “configuration parameter set” (or
4.2 Instrument behaviour at “configuration parameters”).
Power ON When code configuration method is used all the parameters
not modified by the code will maintain their default values.
At power ON the instrument can start in one of the following
mode depending on its configuration: In both cases the access to the configuration parameters is
protected by a password (a specific password for each method).
Auto mode
Note: The instrument will show only the parameters consis-
––The upper display will show the measured value; tent with the specific hardware and in accordance with
––The lower display will show the Set point value; the value assigned to the previous parameters
––The decimal figure of the less significant digit of the lower (e.g.: if you set an output as “not used” the instrument
display is OFF; will mask all other parameters related to this output).
–– The instrument is performing the standard closed loop control. 4.3.1 “Code” configuration procedure
Manual mode (OPLO). The controller configuration (Input type, Control mode, etc.)
––The upper display will show the measured value; can be made entering two 4-digit codes.
Before to enter into code configuration we suggest you to
––The lower display will show alternately the power output prepare the two codes according to the tables that follow.
and the message oPLo and the MAN LED will lite;
Notes: 1. During the Code configuration procedure there is
––The instrument does not perform Automatic control; no timeout.
––The control output is equal to 0% and can be manually 2. To leave, at any time, the Configuration session
modified by and buttons. without saving the settings made, press the
Stand by mode (St.bY). button.
––The upper display will show the measured value; To enter into code configuration proceed as follows:
––The lower display will show alternately the set point value 1. Push the button for more than 3 seconds.
and the message St.bY or od; The upper display will show PASS while the lower display
will show 0;
––The instrument does not perform any control (the control
outputs are OFF); 2. Using and buttons set the password programmed
in parameter [121] PAS4. The factory default password
––The instrument is working as an indicator.
for Code configuration is 300;
We define all the above described conditions as
3. Push the button;
“Standard Display”.
If the password is correct the instrument will show one of
the following conditions:
• If no code is present, the display shows codE on the
upper display and oFF on the lower display.
Push the button to continue.
The upper display will flash cod1 while the lower display
shows 0000.
• If a previous code was stored, the upper display will
flash cod1 while the lower display shows the value of
cod1 stored in memory.

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 6


4. Using and buttons set the code 1 value according 5. Push the button.
to the following tables. The upper display shows cod2 flashing while the lower
L M N O display shows 0000 or the cod2 value stored in memory.
Prepare your code 1
6. Using and buttons set the code 2 value according
Input Type and Range L M to the following tables.
TC J -50... +1000°C 0 0
P Q R S
TC K -50... +1370°C 0 1
Prepare your code 2
TC S -50... 1760°C 0 2
TC R -50... +1760°C 0 3 Alarm 3 R
TC T -70... +400°C 0 4 Alarm 2 Q
Infrared J -50... +785°C 0 5 Alarm 1 P
Infrared K -50... +785°C 0 6 Not used 0 0 0
PT 100/PTC KTY81-121 -200... +850°C/-55... +150°C 0 7 Sensor break 1 1 1
PT 1000/NTC 103-AT2 -200... +850°C/-50... +110°C 0 8 High 2 2 2
Absolute
Linear 0... 60 mV 0 9 Low 3 3 3
Linear 12... 60 mV 1 0 External High/Low 4 4 4
Absolute High/Low
Linear 0... 20 mA (this selection forces Out 4 = TX) 1 1 Internal High/Low 5 5 5
Linear 4... 20 mA (this selection forces Out 4 = TX) 1 2 Deviation high 6 6 6
Deviation
Linear 0... 5 V 1 3 Deviation low 7 7 7
Linear 1... 5 V 1 4 External band 8 8 8
Band
Linear 0... 10 V 1 5 Internal band 9 9 9
Linear 2... 10 V 1 6
TC J -58... +1832°F 1 7
TC K -58... +2498°F 1 8
c%d2: P Q R S

TC S -58... 3200°F 1 9
Auxiliary functions activation S
TC R -58... +3200°F 2 0
None 0
TC T -94... +752°F 2 1
Wattmeter (instantaneous power expressed in W) 1
Infrared J -58... +1445°F 2 2
Wattmeter (energy expressed in Wh) 2
Infrared K -58... +1445°F 2 3
Absolute worked time (expressed in days) 3
PT 100/PTC KTY81-121 -328... +1562°F/-67... +302°F 2 4
Absolute worked time (expressed in hours) 4
PT 1000/NTC 103-AT2 -328... +1562°F/-58... +230°F 2 5
7. Push the button.
c%d1: L MN O If the just entered codes are accepted, the upper display
shows code flashing while the lower display shows good.
Control mode OP1 OP2 OP3 OP4 N O
8. Push the button to save the configuration code and
H AL1 AL2 AL3 0 0
ON/OFF heating = H exit the Code configuration procedure.
NU AL1 AL2 H 0 1
C AL1 AL2 AL3 0 2 Note: After using the “Code configuration” method, it will
ON/OFF cooling = C
NU AL1 AL2 C 0 3 always be possible to modify the parameters using the
H C AL2 AL3 0 4 “Complete configuration” method. If the value of a
H AL1 AL2 C 0 5 parameter among those included in the configuration
ON/OFF with neutral C H AL2 AL3 0 6 codes (cod1 - cod2) gets modified, the instrument
zone (H/C) NU H AL2 C 0 7 will acquire the change while maintaining all the other
C AL1 AL2 H 0 8 parameters.
NU C AL2 H 0 9
H AL1 AL2 AL3 1 0
Attention! After a parameter change made as described in the
PID heating = H previous “Note”, when retrieving the configuration
NU AL1 AL2 H 1 1
C AL1 AL2 AL3 1 2 codes (cod1 - cod2), the lower display will
PID cooling = C show “oFF” to alert the operator that one of the
NU AL1 AL2 C 1 3
H C AL2 AL3 1 4 parameters has been changed.
H AL1 AL2 C 1 5
C H AL2 AL3 1 6
PID double action (H/C)
NU H AL2 C 1 7
C AL1 AL2 H 1 8
NU C AL2 H 1 9

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 7


4.3.2 Complete configuration procedure 4.5 Factory reset - default
The configuration parameters are collected in various parameters loading procedure
groups. Every group defines all parameters related with a Sometime, e.g. when you re-configure an instrument
specific function (e.g.: control, alarms, output functions). previously used for other works or from other people or when
1. Push the button for more than 5 seconds. you have made too many errors during configuration and
The upper display will show PASS while the lower display you decided to re-configure the instrument, it is possible to
will show 0. restore the factory configuration.
2. Using and buttons set the programmed password. This action allows to put the instrument in a defined
Notes: 1. The factory default password for configuration condition (the same it was at the first power ON).
parameters is equal to 30. The default data are those typical values loaded in the
2. During parameter modification the instrument instrument prior to ship it from factory.
continue to perform the control. To load the factory default parameter set, proceed as follows:
In certain conditions, when a configuration chan- 1. Press the button for more than 5 seconds;
ge can produce a heavy bump to the process, it is
advisable to temporarily stop the controller from 2. The upper display will show PASS while the lower display
controlling during the programming procedure shows 0;
(control output will be OFF). 3. Using and buttons set the value -481;
A password equal to 2000 + the programmed 4. Push button;
value (e.g. 2000 + 30 = 2030).
5. The instrument will turn OFF all LEDs for a few seconds,
The control will restart automatically when the
then the upper display will show dFLt (default) and then
configuration procedure will be manually closed.
all LEDs are turned ON for 2 seconds. At this point the
Push the button instrument restarts as for a new power ON.
If the password is correct the display will show the acronym
The procedure is complete.
].
of the first parameter group preceded by the symbol: Note: The complete list of the default parameters is available
In other words the upper display will show: pinp in Appendix A.
(group of the Input parameters).
4.6 configurinG All The parameters
The instrument is in configuration mode.
In the following pages we will describe all the parameters of
4.3.3 How to exit the “Configuration mode” the instrument. However, the instrument will only show the
parameters applicable to its hardware options in accordance
Push button for more than 5 seconds, the instrument will
with the specific instrument configuration (i.e. setting AL1t
come back to the “standard display”.
[Alarm 1 type] to nonE [not used], all parameters related to
4.4 Keyboard functions during alarm 1 will be skipped).
parameter changing ]inP Group - Main and auxiliary input
A short press allows to exit from the current parameter
configuration
group and select a new parameter group.
A long press allows you to close the configuration [1] SEnS - Input type
parameter procedure (the instrument will come back Available: Always
to the “standard display”). Range: • When the code of the input type is equal to C
When the upper display is showing a group and the (see “How to order” paragraph).
lower display is blank, this key allows to enter in the J TC J
selected group. crAL TC K
When the upper display is showing a parameter and S TC S
the lower display is showing its value, this key allows r TC R
to store the selected value for the current parameter t TC T
and access the next parameter within the same group. ir.J Exergen IRS J
Allows to increase the value of the selected parameter. ir.cA Exergen IRS K
Allows to decrease the value of the selected parameter. Pt1 RTD Pt 100
+ These two keys allow to return to the previous Pt10 RTD Pt 1000
group. Proceed as follows: 0.60 0... 60 mV linear
Push the button and maintaining the pressure, 12.60 12... 60 mV linear
then push the button; release both the buttons. 0.20 0... 20 mA linear
Note: The group selection is cyclic as well as the selection 4.20 4... 20 mA linear
of the parameters in a group. 0.5 0... 5 V linear
1.5 1... 5 V linear
0.10 0... 10 V linear
2.10 2... 10 V linear

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 8


• When the code of the input type is equal to E [5] unit - Engineering unit
(see “How to order” paragraph). Available: When a temperature sensor is selected by [1]
J TC J SenS parameter.
crAL TC K Range: °c = Centigrade
S TC S °F = Fahrenheit
r TC R
t TC T
[6] FiL - Digital filter on the measured value
ir.J Exergen IRS J Available: Always
ir.cA Exergen IRS K Range: oFF (No filter) 0.1 to 20.0 s
Ptc PTC Note: This is a first order digital filter applied on the
ntc NTC measured value. For this reason it will affect the
0.60 0... 60 mV linear measured value but also the control action and the
12.60 12... 60 mV linear alarms behaviour.
0.20 0... 20 mA linear [7] inE - Selection of the Sensor Out of Range type
4.20 4... 20 mA linear
that will enable the safety output value
0.5 0... 5 V linear
1.5 1... 5 V linear Available: Always
0.10 0... 10 V linear Range: our = When an overrange or an underrange is
2.10 2... 10 V linear detected, the power output will be forced to
the value of [8] oPE parameter.
Notes: 1. When a TC input is selected and a decimal figure
or = When an overrange is detected, the power
is programmed (see the next parameter) the
output will be forced to the value of [8] oPE
maximum displayed value becomes 999.9°C or
parameter.
999.9°F.
ur = When an underrange is detected, the po-
2. Every change of the SEnS parameter setting wer output will be forced to the value of [8]
will force the [2] dP = 0 and it will change all oPE parameter.
parameters related with dP (e.g. set points,
[8] oPE - Safety output value
proportional band, etc.).
Available: Always
[2] dP - Decimal point position Range: -100... 100 % (of the output).
Available: Always. Notes: 1. When the instrument is programmed with one
Range: When [1] SenS = Linear input: 0... 3. control action only (heat or cool), setting a
When [1] SenS different from linear input: 0 or 1. value outside of the available output range, the
Note: Every change of the dP parameter setting will produce instrument will use Zero.
a change of the parameters related with it (e.g.: set E.g. When heat action only has been
points, proportional band, etc.). programmed, and oPE is equal to -50% (cooling)
[3] SSc - Initial scale read-out for linear inputs the instrument will use the zero value.
Available: when a linear input is selected by [1] SenS. 2. When ON/OFF control is programmed and an out
Range: -1999... 9999. of range is detected, the instrument will perform
the safety output value using a fixed cycle time
Notes: 1. SSc allows the scaling of the analogue input to
equal to 20 seconds.
set the minimum displayed/measured value.
The instrument will show a measured value up to [9] io4.F - I/O4 function selection
5% less then SSc value and than it will show an Available: Always
underrange error. Range: on = The out 4 will be ever ON (used as a
2. It is possible to set a initial scale read-out higher transmitter power supply);
then the full scale read-out in order to obtain a out4 = used as digital output 4;
reverse read-out scaling dG2.c = Digital input 2 for contact closure;
E.g.: dG2.U= Digital input 2 driven by 12... 24 VDC.
0 mA = 0 mBar and 20 mA = -1000 mBar (vacuum). Notes: 1. Setting [9] io4.F = dG2.C o dG2V, the [24] O4F
[4] FSc - Full scale read-out for linear input parameter becomes not visible while [11] diF2
parameter will become visible.
Available: When a linear input is selected by [1] SenS.
Range: -1999... 9999 2. Setting [9] io4F = on the [24] O4F parameter and
the [11]diF2 parameter will NOT be visible.
Notes: 1. Fsc allows the scaling of the analogue input to set
the maximum displayed/measured value. 3. Setting [9] io4F different from dG2.c or dG2.U,
The instrument will show a measured value up to the instrument will force [12] diF2 parameter
5% higher than [4] FSc value and then it will show equal to nonE
an overrange error. If [11] diF1 was equal to (SP4 or UPDN) it will be
forced to nonE.
2. It is possible to set a full scale read-out lower
than the initial scale read-out in order to obtain a 4. The transfer from [9] io4F = on to [9] io4F = Out
reverse read-out scaling. 4 will make the [24] O4F parameter visible equal
E.g.: to nonE.
0 mA = 0 mBar and 20 mA = -1000 mBar (vacuum).

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 9


[10] diF1 - Digital input 1 function 12 Timer run/reset with a special “lock” at the end of
Available: Always. the time count (in order to restart the time count
Range: oFF = No function the instrument must detect a run command co-
1 Alarm Reset [status] ming from serial link keyboard or digital input 2).
2 Alarm acknowledge (ACK) [status]. 18 Sequential set point selection [transition]
3 Hold of the measured value [status]. (see “Note about digital inputs”)
4 Stand by mode of the instrument [status]. 19 SP1/SP2 selection [status]
When the contact is closed the instrument oper- 20 Binary selection of the set point made by digital
ates in stand by mode. input 1 (less significant bit) and digital input 2
5 Manual mode (most significant bit) [status].
6 HEAt with SP1 and CooL with “SP2” [status] 21 Digital input 1 will work in parallel with the
(see “Note about digital inputs”) button while digital input 2 will work in parallel
7 Timer Run/Hold/Reset [transition]. with the button.
Short closure allows to start timer execution Notes: 1. When [10] diF1 or [11] diF2 (e.g. diF1) = 6 the
and to suspend it while a long closure (longer instrument operates as follows:
than 10 seconds) allows to reset the timer. • When the contact is open, the control action is
8 Timer Run [transition] a short closure allows to an heating action and the active set point is SP.
start timer execution. • When the contact is closed, the control
9 Timer reset [transition] a short closure allows to action is a cooling action and the active set
reset timer count. point is SP2.
10 Timer run/hold [Status] 2. When [10] diF1 = 20, [11] diF2 setting is forced to
- Contact closure = timer RUN 20 and diF2 cannot perform another function.
- Contact open = timer Hold
3. When [10] diF1 = 20 and [11] diF2 = 20, the set
11 Timer run/reset [status]
point selection will be in accordance with the
12 Timer run/reset with a special “lock” at the end of
following table:
the time count (in order to restart the time count
the instrument must detect a run command co- Dig In1 Dig. In2 Operative set point
ming from serial link keyboard or digital input 2). Off Off Set point 1
18 Sequential set point selection [transition]
On Off Set point 2
(see “Note about digital inputs”)
19 SP1/SP2 selection [status] Off On Set point 3
20 Binary selection of the set point made by digital On On Set point 4
input 1 (less significant bit) and digital input 2
(most significant bit) [status]. 4. When [10] diF1 = 21, [11] diF2 setting is forced
21 Digital input 1 will work in parallel with button to up.du (21 value) and cannot perform another
while digital input 2 will work in parallel with the function.
button. 5. When a “Sequential set point selection” is used
Note: When [11] diF2 is not available the item 20 and 21 are (diF1 or diF2 = 18), every closure of of the logic
not visible. input increase the value of SPAT (active set point)
[11] diF2 - Digital input 2 function of one step. The selection is cyclic:
SP -> SP2 -> SP3 -> SP4.
Available: When [9] Io4.F = diG2.
Range: oFF = No function
1 Alarm Reset [status]
]out Group - Output parameters
2 Alarm acknowledge (ACK) [status]. [12] o1.F - Out 1 function
3 Hold of the measured value [status]. Available: Always
4 Stand by mode of the instrument [status] Range: • When the out 1 is a linear output (KR3 only)
When the contact is closed the instrument ope- nonE = Output not used. With this setting the status
rates in stand by mode. of the this output can be driven directly
5 Manual mode from serial link;
6 HEAt with SP1 and CooL with “SP2” [status] H.rEG = Heating output;
(see “Note about digital inputs”) c.rEG = Cooling output.
7 Timer Run/Hold/Reset [transition] r.inP = Analogue retransmission of the measured
Short closure allows to start timer execution value.
and to suspend it while a long closure (longer r.Err = Analogue retransmission of the measured
than 10 seconds) allows to reset the timer. error (PV-SP).
8 Timer Run [transition] a short closure allows to r.SP = Analogue retransmission of the operative
start timer execution. set point.
9 Timer reset [transition] a short closure allows to r.SEr = Analogue retransmission of a value coming
reset timer count. from serial link.
10 Timer run/hold [Status] • When the out 1 is a digital output (relay or SSR)
- Contact closure = timer RUN nonE = Output not used. With this setting the sta-
- Contact opend = timer Hold tus of the this output can be driven directly
11 Timer run/reset [status] from serial link.

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 10


H.rEG =Heating output c.rEG = Cooling output
c.rEG =Cooling output AL = Alarm output
AL = Alarm output t.out = Timer output
t.out =Timer output t.HoF = Timr out - OFF in Hold
t.HoF =Timer out - OFF in Hold or.bo = Out-of-range or burnout indicator
or.bo =Out-of-range or burnout indicator P.FAL = Power failure indicator
P.FAL =Power failure indicator bo.PF = Out-of-range, burnout and Power failure
bo.PF =Out-of-range, burnout and Power failure indicator
indicator St.By = Stand By status indicator
St.By = Stand By status indicator diF1 = The output repeates the digital input 1 status
diF1 = The output repeates the digital input 1 status diF2 = The output repeates the digital input 2 status
diF2 = The output repeates the digital input 2 status on = Out 2 ever ON
on = Out 1 always ON. For other details see [12] o1F parameter.
Notes: 1. When two or more outputs are programmed in the
[16] o2.AL - Alarms linked up with Out 2
same way, these outputs will be driven in parallel.
Available: When [15] o2F = AL
2. The power failure indicator will be reset when the Range: 0... 63 with the following rule:
instrument detect an alarm reset command by +1 = Alarm 1
key, digital input or serial link. +2 = Alarm 2
3. When no control output is programmed, all the +4 = Alarm 3
relative alarm (when present) will be forced to +8 = loop break alarm
“nonE” (not used). +16 = Sensor break (burnout)
+32 = Overload on Out 4 (short circuit on OP4).
[13] o1.AL - Alarms linked up with the out 1
For more details see [13] o1.AL parameter.
Available: When [12] o1F = AL
Range: 0... 63 with the following rules: [17] o2Ac - Out 2 action
+1 = Alarm 1 Available: When [15] o2F is different from “nonE”
+2 = Alarm 2 Range: dir = Direct action
+4 = Alarm 3 rEU = Reverse action
+8 = Loop break alarm dir.r = Direct action with revers LED indication
+16 = Sensor break (burnout) rEU.r = Reverse action with reverse LED indication.
+32 = Overload on Out 4 (short circuit on the Out 4) For more details see [14] o1.Ac parameter.
Example 1: Setting 3 (2+1) the output will be driven by the
alarm 1 and 2 (OR condition). [18] o3F - Out 3 function
Available: When the instrument has out 3 option
Example 2: Setting 13 (8+4+1) the output will be driven by
Range: nonE = Output not used. With this setting the status
alarm 1 + alarm 3 + loop break alarm.
of the this output can be driven directly
[14] o1.Ac - Out 1 action from serial link.
Available: When [12] o1F is different from “nonE” H.rEG = Heating output
Range: dir = Direct action c.rEG = Cooling output
rEU = Reverse action AL = Alarm output
dir.r = Direct action with revers LED indication t.out = Timer output
rEU.r = Reverse action with reverse LED indication. t.HoF = Timer out - OFF in Hold
Notes: 1. Direct action: the output repeats the status of the or.bo = Out-of-range or burnout indicator
driven element P.FAL = Power failure indicator
Example: the output is an alarm output with direct bo.PF = Out-of-range, burnout and Power failure
action. When the alarm is ON, the relay will be indicator.
energized (logic output 1). St.By = Stand By status indicator
diF1 = The output repeats the digital input 1 status
2. Reverse action: the output status is the opposite diF2 = The output repeats the digital input 2 status
of the status of the driven element. on = Out 3 ever ON
Example: the output is an alarm output with
For other details see [12] o1F parameter.
reverse action. When the alarm is OFF, the relay
will be energized (logic output 1). This setting is [19] o3.AL - Alarms linked up with Out 3
usually named “fail-safe” and it is generally used in Available: When [18] o3F = AL
dangerous process in order to generate an alarm Range: 0... 63 with the following rule:
when the instrument power supply goes OFF or +1 = Alarm 1
the internal watchdog starts. +2 = Alarm 2
[15] o2F - Out 2 function +4 = Alarm 3
+8 = Loop break alarm
Available: When the instrument has out 2 option.
+16 = Sensor break (burnout)
Range: nonE = Output not used. With this setting the status
+32 = overload on Out 4 (short circuit on OP 4)
of the this output can be driven directly
from serial link. For more details see [13] o1.AL parameter.
H.rEG = Heating output

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 11


[20] o3Ac - Out 3 action • When no output is programmed as control output
Available: when [18] o3F is different from “nonE” nonE = Alarm not used
Range: dir = Direct action LoAb = Absolute low alarm
rEU = Reverse action HiAb = Absolute high alarm
dir.r = Direct action with revers LED indication LHAo = Absolute band alarm with alarm indication
rEU.r = Reverse action with reverse LED indication. out of the band
For more details see [14] o1.Ac parameter. LHAi = Absolute band alarm with alarm indication
inside the band
[21] o4F - Out 4 function SE.br = Sensor break
Available: When the [9] io4.F = Out4 Notes: 1. The relative and deviation alarms are “relative” to
Range: nonE = Output not used. With this setting the status the operative set point value.
of the this output can be driven directly
PV PV
from serial link. AL1
H.rEG = Heating output HAL1
HAL1
c.rEG = Cooling output AL1
AL = Alarm output
t.out = Timer output OUT time OUT time
off ON off ON off off ON off ON off
t.HoF = Timr out - OFF in Hold AL1 AL1
LoAb HiAb
or.bo = Out-of-range or burnout indicator
P.FAL = Power failure indicator
PV PV
bo.PF = Out-of-range, burnout and Power failure AL1H HAL1 AL1H HAL1
indicator SP
St.By = Stand By status indicator AL1L HAL1 -AL1L HAL1
For other details see [12] o1F parameter.
OUT time time
ON off ON off OUT ON off ON off
[22] o4.AL - Alarms linked up with Out 4 AL1 off
AL1
off

Available: When [21] o4F = AL LHAb LHde


Range: 0... 63 with the following rule. 2. The (SE.br) sensor break alarm will be ON when
+1 = Alarm 1 the display shows ---- indication.
+2 = Alarm 2
+4 = Alarm 3 [25] Ab1 - Alarm 1 function
+8 = loop break alarm Available: When [24] AL1t is different from “nonE”.
+16 = Sensor break (burnout) Range: 0... 15 with the following rule:
+32 = overload on Out 4 (short circuit on OP4) +1 = Not active at power up.
For more details see [13] o1.AL parameter. +2 = Latched alarm (manual reset)
+4 = Acknowledgeable alarm
[23] o4Ac - Out 4 action +8 = Relative alarm not active at set point change
Available: When [21] o4F is different from “nonE” Example: Setting Ab1 equal to 5 (1+4) the alarm 1 will be
Range: dir = Direct action “not active at power up” and “Acknowledgeable”.
rEU = Reverse action
Notes: 1. The “not active at power up” selection allows to
dir.r = Direct action with revers LED indication
inhibit the alarm function at instrument power up
rEU.r = Reverse action with reverse LED indication.
or when the instrument detects a transfer from:
For more details see [14] o1.Ac parameter.
• Manual mode (oplo) to auto mode;
• Stand-by mode to auto mode.
]AL1 Group - Alarm 1 parameters The alarm will be automatically enabled when
[24] AL1t - Alarm 1 type the measured value reaches, for the first time,
Available: Always. the alarm threshold ± hysteresis (in other words,
Range: • When one or more outputs are programmed as when the initial alarm condition disappears).
control output PV
nonE = Alarm not used AL1

LoAb = Absolute low alarm


time
HiAb = Absolute high alarm Ab1 = +0 ON off ON off
LHAo = Absolute band alarm with alarm indication
out of the band Ab1 = +1 off ON off
LHAi = Absolute band alarm with alarm indication PWR ON
inside the band
SE.br = Sensor break 2. A “Latched alarm” (manual reset) is an alarm
LodE = Deviation low alarm (relative) that will remain active even if the conditions that
HidE = Deviation high alarm (relative) generated the alarm no longer persist. Alarm
LHdo = Relative band alarm with alarm indication reset can be done only by an external command
out of the band ( button, digital inputs or serial link).
LHdi = Relative band alarm with alarm indication
inside the band

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 12


PV the Alarm threshold value and the point the Alarm
AL1 automatically resets.
2. When the alarm threshold plus or minus the
time
Ab1 = +0 off ON off hysteresis is out of input range, the instrument
will not be able to reset the alarm.
Ab1 = +2 off ON off
Example: Input range 0... 1000 (mBar).
Alarm reset Alarm reset
––Set point equal to 900 (mBar);
3. An “Acknowledgeable” alarm is an alarm that can
––Deviation low alarm equal to 50 (mBar);
be reset even if the conditions that generated the
alarm are still present. Alarm acknowledge can ––Hysteresis equal to 160 (mBar)
be done only by an external command ( button, the theoretical reset point is 900 - 50 + 160 = 1010 (mBar)
digital inputs or serial link). but this value is out of range.
The reset can be made only by turning the instrument
PV
AL1 OFF, removing the condition that generate the alarm and
then turn the instrument ON again.
time ––All band alarms use the same hysteresis value for both
Ab1 = +0 off ON off
thresholds;
Ab1 = +4 off ON off ON off ––When the hysteresis of a band alarm is bigger than the
Alarm ACK Alarm ACK programmed band, the instrument will not be able to reset
A “relative alarm not active at set point change” the alarm.
is an alarm that masks the alarm condition after Example: Input range 0... 500 (°C).
a set point change until process variable reaches ––Set point equal to 250 (°C);
the alarm threshold ± hysteresis.
––Relative band alarm;
Sp2 PV
AL1 ––Low threshold equal to 10 (°C);
Sp1 ––High threshold equal to 10 (°C);
AL1
time
––Hysteresis equal to 25 (°C).
Ab1 = +0 ON off ON off ON off
[30] AL1d - Alarm 1 delay
ON off ON off
Ab1 = +8 Available: When [24] AL1t is different from “nonE”.
Range: From oFF (0) to 9999 seconds.
4. The instrument does not store in EEPROM the
Note: The alarm goes ON only when the alarm condition
alarm status. For this reason, the alarm status
persists for a time longer than [30] AL1d time but the
will be lost if a power down occurs.
reset is immediate.
[26] AL1L - For High and low alarms, it is the low [31] AL1o - Alarm 1 enabling during Stand-by
limit of the AL1 threshold mode and out of range indications
- For band alarm, it is low alarm t
Available: When [24] AL1t is different from “nonE” or
hreshold [24] AL1t is different from “SE.br”.
Available: When [24] AL1t is different from “nonE” or Range: 0 = Never
[24] AL1t is different from “SE.br”. 1= During stand by
Range: From -1999 to [27] AL1H engineering units. 2= During overrange and underrange
[27] AL1H - For High and low alarms, it is the high 3= During overrange, underrange and stand-by
limit of the AL1 threshold ]AL2 Group - Alarm 2 parameters
- For band alarm, it is the high alarm
[32] AL2t - Alarm 2 type
threshold
Available: Aways
Available: When [24] AL1t is different from “nonE” or Range: • When one or more outputs are programmed as
[24] AL1t is different from “SE.br”. control output:
Range: From [26] AL1L to 9999 engineering units. nonE = Alarm not used
[28] AL1- Alarm 1 threshold LoAb = Absolute low alarm
Available: When: HiAb = Absolute high alarm
[24] AL1t = LoAb - Absolute low alarm LHAo = Absolute band alarm with alarm indication
[24] AL1t = HiAb - Absolute high alarm out of the band
[24] AL1t = LodE - Deviation low alarm (relative) LHAi = Absolute band alarm with alarm indication
[24] AL1t = LidE - Deviation high alarm (relative) inside the band
Range: From [26] AL1L to [27] AL1H engineering units. SE.br = Sensor break
LodE = Deviation low alarm (relative)
[29] HAL1 - Alarm 1 hysteresis
HidE = Deviation high alarm (relative)
Available: When [24] AL1t is different from “nonE” or LHdo = Relative band alarm with alarm indication
[24] AL1t is different from “SE.br”. out of the band
Range: 1... 9999 engineering units LHdi = Relative band alarm with alarm indication
Notes: 1. The hysteresis value is the difference between inside the band

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 13


• When no output is programmed as control output: Range: 0 = Never
nonE = Alarm not used 1= During stand by
LoAb = Absolute low alarm 2= During overrange and underrange
HiAb = Absolute high alarm 3= During overrange, underrange and stand-by
LHAo = Absolute band alarm with alarm indication
out of the band ]AL3 Group - Alarm 3 parameters
LHAi = Absolute band alarm with alarm indication
[40] AL3t - Alarm 3 type
inside the band
SE.br = Sensor break Available: Always.
Range: • When one or more outputs are programmed as
Note: The relative alarm are “relative” to the current set point
control output:
(this may be different from the Target setpoint if you
nonE = Alarm not used
are using the ramp to set point function).
LoAb = Absolute low alarm
[33] Ab2 - Alarm 2 function HiAb = Absolute high alarm
Available: When [32] AL2t is different from “nonE” LHAo = Absolute band alarm with alarm indication
Range: 0... 15 with the following rule: out of the band
+1 = Not active at power up. LHAi = Absolute band alarm with alarm indication
+2 = Latched alarm (manual reset) inside the band
+4 = Acknowledgeable alarm SE.br = Sensor break
+8 = Relative alarm not active at set point change LodE = Deviation low alarm (relative)
Example: Setting Ad2 equal to 5 (1+4) the alarm 2 will be HidE = Deviation high alarm (relative)
“not active at power up” and “Acknowledgeable”. LHdo = Relative band alarm with alarm indication
out of the band
Note: For other details see [25] Ab1 parameter. LHdi = Relative band alarm with alarm indication
[34] AL2L inside the band
- For High and low alarms, it is the low limit • When no output is programmed as control output:
of the AL2 threshold nonE = Alarm not used
- For band alarm, it is low alarm threshold LoAb = Absolute low alarm
HiAb = Absolute high alarm
Available: When [32] AL2t is different from “nonE” or [32]
LHAo = Absolute band alarm with alarm indication
AL2t is different from “SE.br”.
out of the band
Range: -1999 to [35] AL2H engineering units.
LHAi = Absolute band alarm with alarm indication
[35] AL2H inside the band
- For High and low alarms, it is the high limit SE.br = Sensor break
of the AL2 threshold Note: The relative alarm are “relative” to the current set point
- For band alarm, it is high alarm threshold (this may be different to the Target set point if you are
Available: When [32] AL2t is different from “nonE” or using the ramp to set point function).
[32] AL2t is different from “SE.br”. [41] Ab3 - Alarm 3 function
Range: From [34] AL2L to 9999 engineering units.
Available: When [40] AL3t is different from “nonE”.
[36] AL2 - Alarm 2 threshold Range: 0... 15 with the following rule:
Available: When: +1 = Not active at power up.
[32] AL2t = LoAb Absolute low alarm +2 = Latched alarm (manual reset)
[32] AL2t = HiAb Absolute high alarm +4 = Acknowledgeable alarm
[32] AL2t = LodE Deviation low alarm (relative) +8 = Relative alarm not active at set point change
[32] AL2t = LidE Deviation high alarm (relative) Example: Setting Ad3 equal to 5 (1+4) the alarm 3 will be
Range: From [34] AL2L to [35] AL2H engineering units. “not active at power up” and “Acknowledgeable”.
[37] HAL2 - Alarm 2 hysteresis Note: For other details see [25] Ab1 parameter.
Available: When [32] AL2t is different to “nonE” or [42] AL3L - For High and low alarms, it is the
[32] AL2t is different from “SE.br”.
low limit of the AL3 threshold
Range: 1... 9999 engineering units.
- For band alarm, it is low alarm threshold
Note: For other details see [29] HAL1 parameter.
Available: When [40] AL3t is different from “nonE” or
[38] AL2d - Alarm 2 delay [40] AL3t is different from “SE.br”.
Available: When [32] AL2t different form “nonE”. Range: -1999 to [43] AL3H engineering units.
Range: From oFF (0) to 9999 seconds. [43] AL3H - For High and low alarms, it is the
Note: The alarm goes ON only when the alarm condition high limit of the AL3 threshold
persist for a time longer than [38] AL2d time but the - For band alarm, it is high alarm threshold
reset is immediate.
Available: When [40] AL3t is different from “nonE” or
[39] AL2o - Alarm 2 enabling during Stand-by mode [40] AL3t is different from “SE.br”.
and out of range indications Range: From [42] AL3L to 9999 engineering units.
Available: When [32] AL2t is different to “nonE” or
[32] AL2t is different from “SE.br”.

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 14


[44] AL3 - Alarm 3 threshold [49] LbSt - Delta measure used by LBA during
Available: When: Soft start
• [40] AL3t = LoAb Absolute low alarm; Available: When [48] LbAt is different from oFF
• [40] AL3t = HiAb Absolute high alarm; Range: • oFF = loop break alarm is inhibit during soft start
• [40] AL3t = LodE Deviation low alarm (relative); • 1... 9999 engineering units.
• [40] AL3t = LidE Deviation high alarm (relative).
[50] LbAS - Delta measure used by loop break
Range: From [42] AL3L to [43] AL3H engineering units.
alarm (loop break alarm step)
[45] HAL3 - Alarm 3 hysteresis Available: when [48] LbAt is different from oFF
Available: When [40] AL3t is different to “nonE” or Range: From 1 to 9999 engineering units.
[40] AL3t is different from “SE.br”.
[51] LbcA - Condition for LBA enabling
Range: 1... 9999 engineering units.
Available: when [48] LbAt is different from oFF
Note: For other details see [29] HAL1 parameter.
Range: uP = Enabled when the PID requires the maxi-
[46] AL3d - Alarm 3 delay mum power only.
Available: When [40] AL3t different form “nonE”. dn = Enabled when the PID requires the mini-
Range: From oFF (0) to 9999 seconds. mum power only
Note: The alarm goes ON only when the alarm condition both = Enabled in both condition (when the PID re-
persist for a time longer than [46] AL3d time but the quires the maximum or the minimum power).
reset is immediate. LBA application example:
LbAt (LBA time) = 120 seconds (2 minutes)
[47] AL3o - Alarm 3 enabling during Stand-by mode
LbAS (delta LBA) = 5°C
and out of range indications
The machine has been designed in order to reach 200°C in
Available: When [40] AL3t is different from “nonE” or
20 minutes (20°C/min).
[40] AL3t is different from “SE.br”.
Range: 0 = Never; When the PID demands 100% power, the instrument starts
1 = During stand by; the time count.
2 = During overrange and underrange; During time count if the measured value increases more
3 = During overrange, underrange and stand-by. than 5°C, the instrument restarts the time count. Otherwise
if the measured value does not reach the programmed delta
] LbA group - Loop break alarm (5°C in 2 minutes) the instrument will generate the alarm.
General note about LBA alarm.
]rEG group - Control parameters
The LBA operate as follows:
The rEG group will be available only when at least one
Applying the 100% of the power output to a process, the output is programmed as control output (H.rEG or C.rEG).
process variable, after a time due to the process inertia,
begins to change in a known direction (increases for an [52] cont - Control type:
heating action or decreases for a cooling action). Available: When at least one output is programmed as con-
Example: If I apply 100% of the power output to a furnace, trol output (H.rEG or C.rEG).
the temperature must go up unless one of the component in Range: When two control action (heat & cool) are programmed:
the loop is faulty (heater, sensor, power supply, fuse, etc...) Pid = PID (heat and cool)
nr = Heat/Cool ON/OFF control with neutral zone
The same philosophy can be applied to the minimum power.
PV
In our example, when I turn OFF the power to a furnace, the HSEt
SP
temperature must go down, if not the SSR is in short circuit, HSEt
the valve is jammed, etc..
LBA function is automatically enabled when the PID requires time
OUTH.rEG ON off ON
the maximum or the minimum power. (heating)
OUTc.rEG
When the process response is slower than the programmed (cooling)
off ON off
limit the instrument generates an alarm.
When one control action (heat or cool) is programmed:
Notes: 1. When the instrument is in manual mode, the LBA Pid = PID (heat or cool)
function is disabled. On.FA = ON/OFF asymmetric hysteresis
2. When LBA alarm is ON the instrument continues On.FS = ON/OFF symmetric hysteresis
to perform the standard control. If the process 3Pt = Servomotor control (available when Output
response comes back into the programmed limit, 2 and Output 3 have been ordered as “M”).
the instrument automatically resets the LBA alarm.
3. This function is available only when the programmed
control algorithm is equal to PID (Cont = PID).
[48] LbAt - LBA time
Available: When [52] Cont = PID
Range: • oFF = LBA not used;
• 1... 9999 seconds.

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 15


PV PV
4= FAST auto-tune with automatic restart at all
SP set point change.
HSEt HSEt
SP 5= SmartTune with automatic restart at every
time time power up;
OUT OUT 6= SmartTune with automatic start at the first
ON off ON off ON ON off ON off ON
H.rEG C.rEG power up only;
HEAt - On.FA C oo L - O n .FA 7= SmartTune with manual start;
PV 8= SmartTune with automatic restart at all set
HSEt PV
SP HSEt
point change.
HSEt SP
HSEt Note: All auto-tunes are inhibited during program execution.
time time
OUT OUT [54] Aut.r - Manual start of the auto-tune
ON off ON off ON ON off ON off ON
H.rEG H.rEG Available: When [52] cont = PID.
HEAt - On.FS C oo L - O n .FS Range: oFF = The instrument is not performing the auto-tune;
Notes: 1. ON/OFF control with asymmetric hysteresis: on = The instrument is performing the auto-tune.
• OFF when PV > SP [55] SELF - Self-tune enable
• ON when PV < (SP - hysteresis) The self-tuning is an adaptive algorithm able to optimize
2. ON/OFF control with symmetric hysteresis: continuously the PID parameter value.
• OFF when PV > (SP + hysteresis) This algorithm is specifically designed for all process subjected to
• ON when PV < (SP - hysteresis) big load variation able to change heavily the process response.
[53] Auto - Auto tune selection Available: When [52] cont = PID
EL.CO. has developed three auto-tune algorithms: Range: YES = self-tune active;
no = self-tune not active.
––Oscillating auto-tune;
––Fast auto-tune;
[56] HSEt - Hysteresis of the ON/OFF control
Available: When [52] cont is different from PID.
––SmartTune.
Range: 0... 9999 engineering units.
1. The oscillating auto-tune is the usual auto-tune and:
[57] cPdt - Time for compressor protection
• It is more accurate;
Available: When [52] cont = nr
• Can start even if PV is close to the set point;
Range: OFF = Protection disabled
• Can be used even if the set point is close to the
1... 9999 seconds.
ambient temperature.
2. The fast type is suitable when: [58] Pb - Proportional band
• The process is very slow and you want to be opera- Available: When [52] cont = PID and [55] SELF = no
tive in a short time; Range: 1... 9999 engineering units.
• When an overshoot is not acceptable; Note: Auto-tune functions calculate this value.
• In multi loop machinery where the fast method [59] ti - Integral time
reduces the calculation error due to the effect of the Available: When [52] cont = PID and [55] SELF = no
other loops. Range: OFF = Integral action excluded
3. The SmartTune type is suitable when: 1... 9999 seconds
• You have no information about your process; inF= Integral action excluded
• You can not be sure about the end user skills; Note: Auto-tune functions calculate this value.
• You desire an auto tune calculation independently
[60] td - Derivative time
from the starting conditions (e.g. set point change
during tune execution, etc). Available: When [52] cont = PID and [55] SELF = no
Range: oFF - derivative action excluded
Note: Fast auto-tune can start only when the measured
1... 9999 seconds
value (PV) is lower than (SP + 1/2SP).
Note: Auto-tune functions calculate this value.
Available: When [55] cont = PID
Range: -4... 8 where:
-4 = Oscillating auto-tune with automatic restart
at all set point change;
-3 = Oscillating auto-tune with manual start;
-2 = Oscillating auto-tune with automatic start at
the first power up only;
-1 = Oscillating auto-tune with automatic restart
at every power up;
0= Not used;
1= Fast auto tuning with automatic restart at
every power up;
2= Fast auto-tune with automatic start at the
first power up only;
3= FAST auto-tune with manual start;

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 16


[61] Fuoc - Fuzzy overshoot control If a short power down occurs, the process restarts with a
This parameter reduces the overshoot usually present at process variable close to the set point while the instrument
instrument start up or after a set point change and it will be starts with an integral action equal to zero.
active only in this two cases. Setting a manual reset equal to the average power output
Setting a value between 0.00 and 1.00 it is possible to slow (in our example 30%) the instrument will start with a power
down the instrument action during set point approach. output equal to the value it will use at steady state (instead
of zero) and the undershoot will become very little (in theory
Setting Fuoc = 1 this function is disabled. equal to zero).
PV
SP
2 Available: When [52] cont = PID.
1 Range: -100.0... +100.0%.
[66] od - Delay at power up
3
Available: When at least one output is programmed as
control output.
time
Range: • oFF: Function not used;
• 0.01... 99.59 hh.mm.
Available: When [52] cont = PID and [55] SELF = no.
Notes: 1. This parameter defines the time during which
Range: 0... 2.00.
(after a power up) the instrument remains in stand
Note: Fast auto-tune calculates the Fuoc parameter while by mode before to start all other function (control,
the oscillating one sets it equal to 0.5. alarms, program, etc.).
[62] tcH - Cycle time of the heating output 2. When a program with automatic start at power up
Available: When at least one output is programmed in order and od function are programmed, the instrument
to be the heating output (H.rEG), performs od function before to start the program
[52] cont = PID and [55] SELF = no. execution.
Range: 1.0... 130.0 seconds 3. When an auto-tune with automatic start at power
[63] rcG - Power ratio between heating and cooling up and od function are programmed, the autotune
action (relative cooling gain) will start at the end of od delay.
The instrument uses the same PID parameter set for heat [67] St.P - Maximum power output used during soft
and for cool action but the efficiency of the two actions are start
usually different. Available: When at list one output is programmed as control
This parameter allows to define the ratio between the efficien- output.
cy of the heating system and the efficiency of the cooling one. Range: -100... +100%.
An example will help us to explain you the philosophy. Notes: 1. When St.P parameter have a positive value, the
limit will be applied to the heating output(s) only.
Consider one loop of a plastic extruder. The working tem-
perature is equal to 250°C. 2. When St.P parameter have a negative value, the
limit will be applied to the cooling output(s) only.
When you want to increase the temperature from 250 to
270°C (DT = 20°C) using 100% of the heating power (resis- 3. When a program with automatic start at power
tor), you will need 60 seconds. up and soft start function are programmed, the
instrument performs the soft start and than the
On the contrary, when you want to decrease the temperature
program function.
from 250 to 230°C (DT = 20°C) using 100% of the cooling
power (fan), you will need 20 seconds only. 4. The auto-tune function will be performed after
soft start function.
In our example the ratio is equal to 60/20 = 3 ([63] rcG = 3)
and it say that the efficiency of the cooling system is 3 time 5. The Soft start function is available also when ON/
more efficient of the heating one. OFF contro l is used.
Available: When two control action are programmed [68] SSt - Soft start time
(H.rEG and c.rEG) and Available: When at list one output is programmed as control
[52] cont = PID and output.
[55] SELF = no Range: oFF = Function not used;
Range: 0.01... 99.99 0.01... 7.59 hh.mm;
Note: auto-tune functions calculate this value. inF = soft start always active.
[64] tcc - Cycle time of the cooling output [69] SS.tH - Threshold for soft start disabling
Available: When at least one output is programmed in order Available: When at list one output is programmed as control
to be the cooling output (c.rEG), [52] cont = PID output.
and [55] SELF = no Range: -1999... 9999 engineering units.
Range: 1.0... 130.0 seconds. Notes: 1. When the power limiter have a positive value (the
[65] rS - Manual reset (integral pre-load) limit is applied to the heating action) the soft start
function will be aborted when the measured value
It allows to drastically reduce the undershoot due to a
is greater or equal to SS.tH parameter.
hot restart. When your process is steady, the instrument
operates with a steady power output (e.g.: 30%). 2. When the power limiter have a negative value

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 17


(the limit is applied to the cooling action) the soft Range: From “SP” to [70] nSP.
start function will be aborted when the measured Notes: 1. A [77] A.SP change produces the following actions:
value is lower or equal to SS.tH parameter. • When [78] SP.rt = SP - the remote set point
will be forced to be equal to the active set poin;
]SP Group - Set point parameters • When [78] SP.rt = trin - the remote set point
The SP group will be available only when at least one output will be forced to zero;
is programmed as control output (H.rEG or C.rEG). • When [78] SP.rt = PErc - the remote set
point will be forced to zero.
[70] nSP - Number of used set points
2. SP2, SP3 and SP4 selection will be shown
Available: When at least one output is programmed as only when the relative set point is enabled (see
control output. [70] nSP parameter).
Range: 1... 4.
Note: When you change the value of this parameter, the [78] SP.rt - Remote set point type
instrument operates as follows: These instruments will communicate with each other, using
• [77] A.SP parameter will be forced to SP. RS 485 serial interface without a PC. An instrument can be
• The instrument verifies that all used set point are set as a Master while the other are (as usual) Slave units. The
within the limits programmed by [71] SPLL end [72] Master unit can send his operative set point to the slave units.
SPHL. If an SP is out of this range, the instrument In this way, for example, it is possible to change
forces it to the maximum acceptable value simultaneously the set point of 20 instruments by changing
[71] SPLL - Minimum set point value the set point of the master unit (e.g. hot runner application).
Available: When at least one output is programmed as SP.rt parameter defines how the slaves units will use the
control output. value coming from serial link.
Range: From -1999 to [72] SPHL engineering units The [101] tr.SP (Selection of the value to be retransmitted
Notes: 1. When you change the [71] SPLL value, the (Master)) parameter allows to define the value sent by
instrument checks all local set points (SP, SP2, SP3 master unit.
and SP4 parameters). If an SP is out of this range, Available: When at least one output is e programmed as
the instrument forces it to the maximum acceptable control output and the serial interface is present.
value Range: rSP = The value coming from serial link is used
2. A [71] SPLL change produces the following actions: as remote set point (RSP).
• When [78] SP.rt = SP the remote set point will trin = The value coming from serial link will be
be forced to be equal to the active set point algebraically added to the local set point
• When [78] SP.rt = trim the remote set point selected by A.SP and the sum becomes
will be forced to zero the operative set point.
• When [78] SP.rt = PErc the remote set point PErc = The value coming from serial will be scaled
will be forced to zero on the input range and this value will be
used as remote set point.
[72] SPHL - Maximum set point value
Note: A [78] SPrt change produces the following actions:
Available: When at least one output is programmed as
control output. • When [78] SP.rt = rSP - the remote set point
Range: From [71] SPLL to 9999 engineering units will be forced to be equal to the active set point
• When [78] SP.rt = trin - the remote set point
Note: For other details see [71] SPLL parameter.
will be forced to zero
[73] SP - Set Point 1 • When [78] SP.rt = PErc - the remote set
Available: When at least one output is programmed as point will be forced to zero
control output. Example: A 6 zone reflow-oven for PCB.
Range: From [71] SPLL to [72] SPHL engineering units. The master unit sends its set point value to 5 other zones
[74] SP 2 - Set Point 2 (slave controllers).
Available: When at least one output is programmed as con- The Slave zones use it as a set point trim.
trol output and [70] nSP > 2. The first zone is the master zone and it uses a set point
Range: From [71] SPLL to [72] SPHL engineering units. equal to 210°C.
[75] SP 3 - Set Point 3 The second zone has a local set point equal to -45°C.
Available: When at least one output is programmed as con- The third zone has a local set point equal to -45 (°C).
trol output and [70] nSP > 3. The fourth zone has a local set point equal to -30.
Range: From [71] SPLL to [72] SPHL engineering units.
The fifth zone has a local set point equal to +40.
[76] SP 4 - Set Point 4
The sixth zone has a local set point equal to +50.
Available: When at least one output is programmed as con-
trol output and [70] nSP =4. In this way, the thermal profile will be the following:
Range: From [71] SPLL to [72] SPHL engineering units. ––Master SP = 210°C;
[77] A.SP - Selection of the active Set point ––Second zone SP = 210 -45 = 165°C;
Available: When at least one output is programmed as ––Third zone SP = 210 -45 = 165°C;
control output.
––Fourth zone SP = 210 - 30 = 180°C;

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 18


––Fifth zone SP = 210 + 40 = 250°C; Delayed start at power up with a delay time and a “end of
––Sixth zone SP = 210 + 50 = 260°C. cycle” time.
Changing the SP of the master unit, all the other slave units Tr.t1 Tr.t2
will immediately change their operative set point. Start
[79] SPLr - Local/remote set point selection off ON off
OUT
Available: When at list one output is programmed as control PWR UP
output. Feed-through.
Range: Loc = Local set point selected by [77] A.SP;
rEn = Remote set point (coming from serial link). Tr.t1
Start
[80] SP.u - Rate of rise for positive set point change
ON off
(ramp up) OUT
Available: When at list one output is e programmed as Reset
control output.
Range: 0.01... 99.99 units per minute; Asymmetrical oscillator with start in OFF.
inF = ramp disabled (step transfer).
Tr.t2 Tr.t2 Tr.t2
[81] SP.d - Rate of rise for negative set point Start Tr.t1 Tr.t1 Tr.t1
change (ramp down) off ON off ON off ON
OUT
Available: When at list one output is e programmed as
Reset
control output.
Range: 0.01... 99.99 units per minute; Asymmetrical oscillator with start in ON.
inF = ramp disabled (step transfer).
Tr.t2 Tr.t2 Tr.t2
General note about remote set point: when the remote set Start Tr.t1 Tr.t1 Tr.t1
point (RSP) with trim action is programmed, the local set
ON off ON off ON off
point range becomes the following: OUT
from [71] SPLL+ RSP to [72] SPHL - RSP Reset

]tin group - Timer function parameters Notes: 1. The instrument can receive the start, hold and
reset commands by button, by logic inputs
Five timer types are available: and/or by serial link.
Delayed start with a delay time and a “end of cycle” time. 2. An HOLD command can suspend the time count.
Tr.t1 Tr.t2 [82] tr.F= Independent timer function
Start
Available: Always.
OUT off ON off
Range: nonE = Timer not used
i.d.A = Delayed start timer
––Setting tr.t2 = Inf the timer out remains in ON condition
i.uP.d = Delayed start at power up
until a reset command is detected.
i.d.d = Feed-through timer
Tr.t1 Tr.t2 = inF i.P.L = Asymmetrical oscillator with start in OFF
Start i.L.P = Asymmetrical oscillator with start in ON
off ON off [83] tr.u - Engineering unit of the time
OUT
Available: When [82] tr.F is different form nonE.
Reset Range: hh.nn = Hours and minutes
nn.SS = Minutes and seconds
SSS.d = Seconds and tenth of seconds
Note: When the timer is running, you can see the value of
this parameter but you can NOT modify it.
[84] tr.t1 - Time 1
Available: When [82] tr.F is different form nonE.
Range: When [83] tr.u = hh.nn = 00.01... 99.59
When [83] tr.u = nn.SS = 00.01... 99.59
When [83] tr.u = SSS.d = 000.1... 995.9
[85] tr.t2 - Time 2
Available: When [82] tr.F is different form nonE
Range: When [83] tr.u = hh.nn = 00.01... 99.59 + inF
When [83] tr.u = nn.SS = 00.01... 99.59 + inF
When [83] tr.u = SSS.d= 000... 995.9 + inF.
Note: Setting [85] tr.t2 = inF, the second time can be stopped
by a reset command only.

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 19


[86] tr.St - Timer status [91] diSP - Display management
Available: When [82] Tr.F is different form nonE Available: Always
Range: run = Timer Run Range: nonE = Standard display
HoLd = Timer Hold Pou = Power output
rES = Timer reset SPF = Final set point
Note: This parameter allows to manage timer execution by a Spo = Operative set point
parameter (without digital inputs or button). AL1 = Alarm 1 threshold
AL2 = Alarm 2 threshold
]PAn group - Operator HMI AL3 = Alarm 3 threshold
ti.uP = When the timer is running, the display will
[87] PAS2 - Level 2 password: show the timer counting up.
Limited access level At the end of the counting, the instrument
Available: Always. will show “t.End” messages alternately with
Range: oFF = Level 2 not protected by password the measured value.
(as level 1 = Operator level); ti.du = When the timer is running, the display will
1... 200. show the timer counting down.
[88] PAS3 - Level 3 password: complete At the end of the counting, the instrument
will show “t.End” messages alternately with
configuration level
the measured value.
Available: Always. PErc = Percent of the power output used during soft
Range: 3... 200. start (when the soft start time is equal to
Note: Setting [87] PAS2 equal to [88] PAS3, the level 2 will infinite, the limit is ever active and it can be
be masked. used also when ON/OFF control is selected).
[89] PAS4 - Level 4 password: [92] di.CL - Display colour
CODE configuration level Available: Always.
Available: Always Range: 0 = The display colour is used to show the
Range: 201... 400. actual deviation (PV - SP);
[90] uSrb - button function during RUN TIME 1= Display red (fix);
2= Display green (fix);
Available: Always.
3= Display orange (fix).
Range: nonE = No function;
tunE = Auto-tune/self-tune enabling [93] AdE - Deviation for display colour management
A single press (longer than 1) starts the Available: When [92] di.CL = 0.
auto-tune. Range: 1... 9999 engineering units.
oPLo = Manual mode. [94] diS.t - Display time out
The first pressure puts the instrument in
Available: Always.
manual mode (OPLO) while a second one
Range: oFF = The display is ever ON;
puts the instrument in Auto mode.
0.1... 99.59 minutes and seconds.
AAc = Alarm reset.
ASi = Alarm acknowledge Note: This function allows to turn OFF the display when no
chSP = Sequential set point selection (see note alarm is present and no action is made on the instrument.
below). When diS.t is different from OFF and no button is
St.by = Stand by mode pressed for more than the programmed time out, the
The first press puts the instrument in stand display goes OFF and only 4 segments of the less
by mode while a second one puts the in- significant digit are turned ON in sequence in order to
strument in Auto mode. show that the instrument is working correctly.
Str.t = Timer run/hold/reset (see note below). If an alarm occures or a buton is pressed, the display
will come back to the normal operation.
Notes: 1. When “Sequential set point selection” is used,
every press of the button (longer than 1 [95] FiLd - Filter on the displayed value
second) increase the value of A.SP (active set Available: Always
point) of one step. Range: oFF = Filter disabled;
The selection is cyclic: SP -> SP2 -> SP3 -> SP4 From 0.0 (oFF) to 20.0 engineering units.
When a new set point is selected using the Note: This is a “window filter” related to the set point; it is
key, the display will show for 2 seconds the applied to the displayed value only and it have no
acronym of the new set point (e.g. SP2). effect on the other functions of the instrument (control,
2. When “Sequential set point selection” is used, the alarms, etc.).
number of set points selectable is limited by [70] nSP. [96] dSPu - Status of the instrument at power up
3. When “Timer run/hold/reset” is selected, a short Available: Always.
press starts/stops(hold) timer count while a long Range: AS.Pr = Starts in the same way it was prior to the
press (longer than 10 second) resets the timer. power down;
Auto = Starts in Auto mode;
oP.0 = Starts in manual mode with a power output

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 20


equal to zero. [101] trSP - Selection of the value to be
St.bY = Starts in stand-by mode retransmitted (Master)
Notes: 1. When you change the value of [97] oPr.E, the Available: When [99] Add different from oFF.
instrument forces [98] oPEr parameter equal to Range: nonE = Retransmission not used (the instrument is
Auto. a slave)
2. During program execution the instrument rSP = The instrument become a Master and it
memorize the segment currently in use and, by a retransmits the operative set point.
30 minutes interval, it memorize also the elapsed PErc = The instrument become a Master and it
time of the soaks. retransmits the power output.
If a power down occurs during program execution, at Note: For more details see [78] SP.rt (Remote set point type)
the next power up the instrument is able to continue parameter.
the program execution starting from the segment in
progress at power down and, if the segment was a ]COn Group - Consumption parameters
soak, it is also capable to restart from the soak time [102] Co.tY - Measurement type
minus the elapsed time memorized.
Available: Always.
In order to obtain this features, the “[96] dSPu - Range: oFF = Not used
Status of the instrument at power up” parameter 1= Instantaneous power (kW)
must be set to “AS.Pr”. 2= Power consumption (kW/h)
If the “[96] dSPu” parameter is different from “AS. 3= Energy used during program execution.
Pr” The memorization function is inhibited. This measure starts from zero when a
[97] oPr.E - Operative modes enabling program runs end stops at the end of the
program. A new program execution will
Available: Always.
reset the value.
Range: ALL = All modes will be selectable by the next
4= Total worked days with threshold. It is the
parameter.
number of hours that the instrument is
Au.oP = Auto and manual (OPLO) mode only will be
turned ON divided for 24.
selectable by the next parameter.
5= Total worked hours with threshold. It is
Au.Sb = Auto and Stand-by modes only will be se-
the number of hours that the instrument is
lectable by the next parameter.
turned ON.
Note: When you change the value of [97] oPr.E, the
Note: Selections 3 and 4 are an internal counter for machine
instrument forces [98] oPEr parameter equal to Auto
service inspection intervals. It works every time the
[98] oPEr - Operative mode selection instrument is turned ON.
Available: Always. When the count reaches the programmed threshold,
Range: When [97] oPr.E = ALL: the display shows alternately the standard display
Auto = Auto mode and the message “r. iSP” (requested Inspection).
oPLo = Manual mode The count reset can be done only by changing the
St.bY = Stand by mode threshold value.
When [97] oPr.E = Au.oP:
[103] UoLt - Nominal Voltage of the load
Auto = Auto mode
oPLo = Manual mode Available: When [102] Co.tY = ist or
When [97] oPr.E = Au.Sb [102] Co.tY = h or
Auto = Auto mode [102] Co.tY = S.S.
St.bY = Stand by mode Range: 1... 9999 (V).
[104] cur - Nominal current of the load
]Ser group - Serial link parameter Available: When [102] Co.tY = ist or
[99] Add - Instrument address [102] Co.tY = h or
[102] Co.tY = S.S.
Available: Always
Range: 1... 999 (A).
Range: oFF = Serial interface not used
1... 254 [105] h.Job - Threshold of the working period
[100] bAud - Baud rate Available: When [102] Co.tY = tot.d or
[102] Co.tY = tot.H.
Available: When [99] Add different from oFF
Range: oFF = Threshold not used
Range: 1200 = 1200 baud
1... 9999 days when [102] Co.tY = 4;
2400 = 2400 baud
1... 9999 hours when [102] Co.tY = 5.
9600 = 9600 baud
19.2 = 19200 baud [106] t.Job - Worked time (not resettable)
38.4 = 38400 baud Available: Always.
Range: 1... 9999 days.

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 21


]CAL group - User calibration group 5. PARAMETER PROMOTION
This function allows to calibrate the complete measuring Another important step of the instrument configuration is due
chain and to compensate the errors due to: to the possibility to create a custom HMI (interface) in order
––Sensor location; to make the instrument easy to use for the operator and
comfortable for the assistance.
––Sensor class (sensor errors);
By a special procedure, named promotion, the OEM can
––Instrument accuracy. create two parameter subsets.
[107] AL.P - Adjust Low Point The first one is the “limited access” level. This subset is protected
Available: Always. by the password programmed by [87] PAS2 parameter.
Range: -1999... (AH.P - 10) engineering units. The last subset is the “Operator” set (Level1). This level is
Note: The minimum difference between AL.P and AH.P is NOT password protected.
equal to 10 Engineering Units.
Notes: 1. The “limited access” parameter are collected in a list.
[108] ALo - Adjust Low Offset 2. The sequence of the “limited access” parameters
Available: Always. is programmable and can be made according to
Range: -300... +300 engineering units. your needs.
[109] AH.P - Adjust High Point 3. The parameter sequence of the operator level is
Available: Always. the same programmed for “limited access” level
Range: From (AL.P + 10) to 9999 engineering units. but only specified parameters can be displayed
Note: The minimum difference between AL.P and AH.P is and modified. This set must be create according
equal to 10 Engineering Units. to your requirements.

[110] AH.o - Adjust High Offset 5.1 Parameter promotion


Available: Always. procedure
Range: -300... +300 Engineering Units.
The limited access parameter set is a list, so that, before to
Example: Environmental chamber with an operative range:
start promotion procedure, we suggest to operate as follows:
10... 100°C.
1. Prepare the exact parameter list you want to make
1. Insert in the chamber a reference sensor connected with
accessible for limited access.
a reference instrument (usually a calibrator).
2. Number the desired parameters in the same sequence
2. Start the control of the instrument, and set a set point equal to
you want to have in the limited access.
the minimum value of the operative range (e.g.: 10°C). When
the temperature in the chamber is steady, take note of the 3. Define which of the selected parameter will be available
temperature measured by the reference system (e.g.: 9°C). in Operator level also.
3. Set [107] AL.P = 10 (low working point) and [108] ALo = -1 Example: I would like to obtain the following limited access list:
(it is the difference between the reading of the instrument • OPEr - Operative mode selection
and the reading of the reference system). Note that after • SP - first set point
this set the measured value of the instrument is equal to • SP2 - Second set point
the measured value of the reference system. • A.SP - Set point selection
4. Set a set point equal to the maximum value of the • AL1 - Alarm 1 threshold
operative range (e.g. 100°C). When the temperature • AL2 - Alarm 2 threshold
in the chamber is steady, take note of the temperature • Pb - Proportional band
measured by the reference system (e.g. 98°C). • ti - Integral time
• td - Derivative time
5. Set [109] AH.P = 100 (low working point) and [110] AHo = +2 • Aut.r - Manual start of the auto-tune
(it is the difference between the reading of the instrument
But I want that the operator to be able to change: the
and the reading of the reference system). Note that after
operative mode, the SP value and the AL1 value. In this
this set the measured value of the instrument is equal to
case the promotion will be the following:
the measured value of the reference system.
Parameter Promotion Limited Access Operator
AH.o = 2 - OPEr - o1 OPEr OPEr
Modified curve
- SP - o2 SP SP
Real curve - SP2 - A3 SP2
AL.o = -1
- A.SP - A4 A.SP
AH.P 10°C AH.P 100°C
- AL1 - o5 AL1 AL1
The most important step of the configuration procedure is
- AL2 - A6 AL2
completed.
- Pb - A7 Pb
In order to exit from configuration parameter procedure,
proceed as follows: - ti - A8 ti
• Push button. - td - A9 td
• Push button for more than 10 s. The instru- - Aut.r - A 10 Aut.r
ment will come back to the “standard display”.

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 22


Now, proceed as follows: 6. OPERATIVE MODES
1. Push the button for more than 3 seconds. As we said at paragraph 4.1, when the instrument is
2. The upper display will show PASS while the lower display powered, it starts immediately to work according to the
will show 0. memorized parameter value.
3. By and buttons set a password equal to -81. In other words, the instrument has one status only, the “run
4. Push button. time” status.
The instrument will show the acronym of the first During “run time” we can force the instrument to operate
configuration parameter group “]inP”. in three different modes: Automatic mode, Manual mode or
5. By button select the group of the first parameter of Stand by mode:
your list. ––In Automatic mode the instrument drives automatically
6. By button select the first parameter of your list the control output according to the parameter value set
and the set point/measured value.
7. The upper display will show the acronym of the parameter
while the lower display will show his current promotion level. –– In Manual mode the the upper display shows the measured
The promotion level is defined by a letter followed by a value while the lower display shows the power output
number. alternately to the “oPLo” messages and the instrument
The letter can be: allows you to set manually the control output power.
c: It shows that this parameter is NOT promoted No Automatic action will be made.
and it is present only in configuration. ––In Stand by mode the instrument operates as an indicator.
In this case the number is forced to zero. It will show on the upper display the measured value and
A: It shows that this parameter has been promoted on the lower display the set point alternately to the “St.bY”
to the limited access level. messages and forces the control outputs to zero.
The number will show the position in the limited
As we have seen, it is always possible to modify the value
access list.
assigned to a parameter independently from the operative
o: It shows that the parameter has been promoted
modes selected.
to the Operator level.
The number will show the position in the limited
6.1 Modify a parameter during
access list.
8. By and buttons assign to this parameter the
“Operator level”
desired position. The instrument is showing the “standard display”.
Note: Setting a value different from 0 the letter c will change 1. Press the button.
automatically to A and the parameter is automatically 2. The upper display will show the acronym of the first
promoted to the limited access level. parameter promoted to this level while the lower display
9. In order to modify the level from limited access to will show its value.
operator and vice versa, push button and, maintaining 3. By and button assign to this parameter the
the pressure, push button. desired value.
The letter will change from A to o and vice versa.
4. Press the button in order to memorize the new value
10.Select the second parameter that you want to add to the and go to the next parameter.
assistance level and repeat step 6, 7 and 8.
5. When you want to come back to the “standard display”
11.Repeat step 5, 6, 7, 8 until the list has been completed. push the button for more than 5 seconds.
12.When you need to exit from promotion procedure, push Note: The parameter modification of the Operator level
button and maintain the pressure for more than 10 s. is subject to a time out. If no button is pressed for
The instrument will show the “standard display”. more than 10 seconds, the instrument goes back to
Note: When you set the some number to two parameter, the “standard display” and the new value of the last
the instrument will use only the last programmed selected parameter will be lost.
parameter.
Example: In the previous example, I have set for SP2 a 6.2 Enter the “Limited access level”
promotion value equal to A3. The instrument is showing the “standard display”.
If now I set for SP3 a promotion value equal to o3, the 1. Press the button for more than 5 seconds;
Limited Access list and the operator list becomes. 2. The upper display will show PASS while the lower display
Parameter Promotion Limited Access Operator will show 0;
- OPEr - o1 OPEr OPEr 3. By and buttons set the value assigned to
[117] PAS2 (Level 2 password).
- SP - o2 SP SP
Notes: 1. The factory default password for configuration
- SP3 - o3 SP3 SP3
parameters is equal to 20.
- A.SP - A4 A.SP
2. All parameter modification are protected by a
- AL1 - o5 AL1 AL1 time out. If no button is pressed for more than
10 second the instrument comes automatically
back to the Standard display, the new value of the

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 23


last selected parameter is lost and the parameter 6.4 Automatic Mode
modification procedure is closed.
When you desire to remove the time out (e.g. 6.4.1 Keyboard function when the instrument
for the first configuration of an instrument) you is in Auto mode
can use a password equal to 1000 plus the Performs the action programmed by [90] uSrb
programmed password ( button function during RUN TIME) parameter.
(e.g. 1000 + 20 [default] = 1020). Allows entry into parameter modification procedures.
It is always possible to manually End the Allows you to start the “Direct set point modification”
parameter configuration procedure (see below). function (see below).
Allows you to display the “additional informations” (see
3. During parameter modification the instrument
below).
continues to perform the control.
In certain conditions (e.g. when a parameter 6.4.2 Direct set point modification
change can produces a heavy bump to the This function allows to modify rapidly the set point value
process) it is advisable to temporarily stop the selected by [77] A.SP (selection of the active Set point).
controller from controlling during the programming
The instrument is showing the “standard display”.
procedure (its control output will be Off). A
password equal to 2000 + the programmed value 1. Push button.
(e.g. 2000 + 20 = 2020) will switch the control out The upper display shows the acronym of the selected set
off during configuration. The control will restart point (e.g. SP2) and the lower display will show its value.
automatically when the para-meter modification 2. By and buttons, assign to this parameter the
procedure will be manually ended. desired value
4. Push button. 3. Do not push any button for more than 5 second or push
5. The instrument will show on the upper display the the button.
acronym of the first parameter promoted to this In both cases the instrument memorize the new value and
level and on the lower display its value. come back to the “standard display”.
6. By and buttons assign to this parameter Note: If the selected set point has not been promoted to the
the desired value. Operator level, the instrument allows you to see the
7. Press the button in order to memorize the new value but not to modify it.
value and go to the next parameter.
6.4.3 Additional information
8. When you want to come back to the “standard
This instrument is able to show you some additional
display” push the button for more than 5 s.
informations that can help you to manage your system.
6.3 How to see but not modify the “limited The additional informations are related to how the instrument
access parameters” is programmed, hence in many cases, only part of this
Sometime it is necessary to give to the operator the possibility information is available.
to see the value assigned to the parameter promoted in the 1. When the instrument is showing the “standard display”
Limited Access level but it is important that all changes are push button.
made by authorized personnel only. The lower display will show H or c followed by a number.
In this cases, proceed as follows: This value is the current power output applied to the
1. Press the button for more than 5 seconds process. The H show you that the action is a Heating action
while the c show you that the action is a Cooling action.
2. The upper display will show PASS while the lower display
will show 0; 2. Push button again. When the wattmeter function is
running the lower display will show U followed by the
3. By and button set the value -181. measured energy.
4. Push button. Note: The energy calculation will be in accordance with the
5. The upper display will show the acronym of the first [102] Co.tY parameter setting.
parameter promoted to the level 2 and lower display will 3. Push button again. When the “Worked time count”
show its value. is running the lower display will show d for days or h for
6. Using button it is possible to see the value assigned to hours followed by the measured time.
all parameter present in level 2 but it will not be possible 4. Push button again. The instrument returns to the
to modify it. “standard display”.
7. It is possible to come back to the “standard display” by Note: The additional information visualization is subject to
pushing the button for more than 3 seconds or by a time out. If no button is pressed for more than 10
pushing no pushbutton for more than 10 seconds. second the instrument comes automatically back to
the Standard display.

6.4.4 Display management


This instrument allows you to program (see parameter [94]
diS.t the time out of the display.

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 24


This function allows to turn OFF the display when no alarm with the control (wattmeter, independent timer,
is present and no action is made on the instrument. “worked time”, etc) continue to operate normally.
When [94] diS.t is different to OFF (display ever ON) and 4. When the instrument is swapped from stand
no button is pressed for more than the programmed time by to auto modes, the instrument will start
out, the display goes OFF and only 4 segments of the less automatically the alarm masking, the soft start
significant digit are turned ON in sequence in order to show functions and the auto-tune (if programmed).
that the instrument is working correctly.
7. ERROR MESSAGES
If an alarm occurs or a button is pressed, the display will
come back to the normal operation.
7.1 Out of range signals
6.4.5 The display colour shows the Deviation The upper display shows the OVER-RANGE and UNDER-
This instrument allows to program the deviation (PV - SP) for RANGE conditions with the following indications:
colour display change (see parameter [93] AdE). Over-range Under-range
In this way the upper display will be:
––Amber when PV is lower than SP - AdE.
––Green when (SP - AdE) < PV<SP + AdE) The sensor break will be signalled as an out of range
––Red when PV is higher than SP+AdE

6.5 Manual mode Note: When an over-range or an under-range is detected,


This operative mode allows you to deactivate automatic the alarms operate as in presence of the maximum or
control and manually program the percentage power output the minimum measurable value respectively.
to the process. To check the out of span Error condition, proceed as follows:
When the instrument is in manual mode, the upper display 1. Check the input signal source and the connecting line.
will show the measured value while the lower display will
show alternately the power output [preceded by H (for 2. Make sure that the input signal is in accordance with the
heating action) or C (for cooling action)] and the message instrument configuration.
oPLo (open loop). Otherwise, modify the input configuration (see section 4).

When manual control is selected, the instrument will start to 3. If no error is detected, send the instrument to your
operate with the same power output as the last one supplied supplier to be checked.
by automatic mode and can be modified using the and
buttons.
7.2 List of possible errors
ErAT Fast Auto-tune cannot start. The measure value is too
In case of ON/OFF control, 0% corresponds to the close to the set point.
deactivated output while any value different from 0 Push the button in order to delete the error message.
corresponds to the activated output. ouLd Overload on the out 4
As in the case of visualization, the programmable values The messages shows that a short circuit is present on
range from H100 (100% output power with reverse action) to the Out 4 when it is used as output or as a transmitter
C100 (100% output power with direct action). power suply. When the short circuit disappears the
Notes: 1. During manual mode, the alarms are operative. output restart to operate.
NoAt Auto-tune not finished within 12 hours.
2. If you set manual modes during self-tune
ErEP Possible problem of the instrument memory.
execution, the self- tune function will be aborted.
The messages disappears automatically.
3. During manual mode, all functions not related When the error continues, send the instrument to your
with the control (wattmeter, independent timer, supplier.
“worked time”, etc) continue to operate normally. RonE Possible problem of the firmware memory.
When this error is detected, send the instrument to
6.6 Stand by mode your supplier.
This operative mode also deactivates the automatic control Errt Possible problem of the calibration memory.
but forces the control output to zero. When this error is detected, send the instrument to
In this mode the instrument operates as an indicator. your supplier.
When the instrument is in stand by mode the upper display 8. GENERAL NOTES
will show the measured value while the lower display will
show alternately the set point and the message “St.bY”. 8.1 Proper use
Notes: 1. During stand by mode, the relative alarms are Every possible use not described in this manual must be
disabled while the absolute alarms are operative consider as a improper use.
or not according to the ALxo (Alarm x enabling
This instrument is in compliance with EN 61010-1 “Safety
during Stand-by mode) parameter setting.
requirements for electrical equipment for measurement,
2. If you set stand by mode during self-tune control and laboratory use”; for this reason it coud not be
execution, the self- tune function will be aborted. used as a safety equipment.
3. During stand by mode, all functions not related Whenever a failure or a malfunction of the control device

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 25


may cause dangerous situations for persons, thing or OEM during machine start up.
animals, please remember that the plant has to be equipped Note: When the instrument is powered by the KEYA01, the
with additional safety devices. outputs are NOT supplied and the instrument can
EL.CO. S.r.l. and its legal representatives do not assume any show the “ouLd” (Out 4 Overload) indication.
responsibility for any damage to people, things or animals
deriving from violation, wrong or improper use or in any case
not in compliance with the instrument’s features.

8.2 Warranty
This product is under warranty against manufacturing
defects or faulty materials that are found within 18 months
from delivery date. The warranty is limited to repairs or to the
replacement of the instrument.
The tampering of the instrument or an improper use of the
product will bring about the immediate withdrawal of the
warranty’s effects.
In the event of a faulty instrument, either within the period
of warranty, or further to its expiry, please contact our
sales department to obtain authorisation for sending the
instrument to our company.
The faulty product must be shipped to EL.CO. with a detailed
description of the faults found, without any fees or charge for
EL.CO., except in the event of alternative agreements.

8.3 Maintenance
This instrument does not requires periodical recalibration
and it have no consumable parts so that no particular
maintenance is required.
Some times, a cleaning action is suggestible.
1. SWITCH THE EQUIPMENT OFF (power supply, relay
out, etc.).
2. Take the instrument out of its case.
3. Using a vacuum cleaner or a compressed air jet (max. 3
kg/cm2) remove all deposits of dust and dirt which may
be present on the case and on the internal circuits being
careful not to damage the electronic components.
4. To clean external plastic or rubber parts use only a cloth
moistened with:
• Ethyl Alcohol (pure or denatured) [C2H5OH] or
• Isopropyl Alcohol (pure or denatured) [(CH3)2CHOH]
or
• Water (H2O).
5. Make sure that there are no loose terminals.
6. Before putting the instrument back in its case, make sure
that it is perfectly dry.
7. Put the instrument back and turn it ON.

8.4 Accessories
The instrument has a lateral socket into which a special
tool can be inserted. This tool, named KEYA01, allows:
––To memorize a complete instrument configuration and to
use it for other instruments.
––To transfer a complete instrument configuration to a PC or
from a PC to an instrument
––To transfer from a PC to an instrument a complete
instrument configuration
––To transfer a configuration from an KEYA01 to another one.
––To test serial interface of the instruments and to help the

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 26


Appendix A

]]
inP GROUP - Main and auxiliary input configuration
Dec.
no. Param. Description Values Default
Point
Sensor selection (according to the HW)
J = TC J,
crAL = TC K,
S = TC S,
r = TC R,
t = TC T,
ir.J = IRS J,
ir.cA = IRS K,
Pt1 = RTD Pt100,
Model C Pt10 = RTD Pt1000,
0.60 = 0... 60 mV,
12.60 = 12... 60 mV,
0.20 = 0... 20 mA,
4.20 = 4... 20 mA,
0.5 = 0... 5 V,
1.5 = 1... 5 V,
0.10 = 0... 10 V,
1 SEnS 2.10 = 2... 10 V
0 J
J = TC J,
crAL = TC K,
S = TC S,
r = TC R,
t = TC T,
ir.J = IRS J,
ir.cA = IRS K,
Ptc = TC KTY81-121,
Model E ntc = NTC 103-AT2,
0.60 = 0... 60 mV,
12.60 = 12... 60 mV,
0.20 = 0... 20 mA,
4.20 = 4... 20 mA,
0.5 = 0... 5 V,
1.5 = 1... 5 V,
0.10 = 0... 10 V,
2.10 = 2... 10 V
Decimal Point Position (linear inputs) 0... 3
2 dp 0 0
Decimal Point Position (different than linear inputs) 0/1
3 SSC Initial scale read-out for linear inputs dp -1999... 9999 0
4 FSc Full Scale Readout for linear inputs dp -1999... 9999 1000
5 unit Engineer unit °C/°F °C
6 Fil Digital filter on the measured value 1 0 (= OFF)... 20.0 s 1.0
Sensor error used to enable the safety output or = Over range
7 inE ou = Under range our
value our = Over and under range
8 oPE Safety output value (% of the output) -100... 100 0
on = Output used as PWS for TX,
out4 = Output 4 (digital output 4),
9 IO4.F I/O 4 function out4
dG2c = Digital input 2 driven by contact,
dG2U = Digital input 2 driven by voltage
oFF = Not used,
1 = Alarm reset,
2 = Alarm acknowledge (ACK),
3 = Hold of the measured value,
4 = Stand by mode,
5 = Manual mode,
6 = HEAt with SP1 and CooL with SP2,
7 = Timer RUN/Hold/Reset,
10 diF1 Digital Input 1 function 8 = Timer Run, oFF
9 = Timer Reset,
10 = Timer Run/Hold,
11 = Timer Run/Reset,
12 = Timer Run/Reset with lock,
18 = Sequential SP selection,
19 = SP1 - SP2 selection,
20 = SP1... SP4 binary selection,
21 = Digital inputs in parallel to and keys

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 27


Dec.
no. Param. Description Values Default
Point
oFF = Not used,
1 = Alarm reset,
2 = Alarm acknowledge (ACK),
3 = Hold of the measured value,
4 = Stand by mode,
5 = Manual mode,
6 = HEAt with SP1 and CooL with SP2,
7 = Timer RUN/Hold/Reset,
11 diF2 Digital Input 2 function 8 = Timer Run, oFF
9 = Timer Reset,
10 = Timer Run/Hold,
11 = Timer Run/Reset,
12 = Timer Run/Reset with lock,
18 = Sequential SP selection,
19 = SP1 - SP2 selection,
20 = SP1... SP4 selection,
21 = Digital inputs in parallel to and keys

]]
Out group
Dec.
no. Param. Description Values Default
Point
NonE = Output not used
H.rEG = Heating output
c.rEG = Cooling output
Out 1 function (when Out 1 is a linear output) 0 r.inP = Measure retransmission
r.Err = Error (sp - PV) retransmission
r.SP = Set point retransmission
r.SEr = Serial value retransmission
NonE = Output not used
H.rEG = Heating output
12 o1F c.rEG = Cooling output H.reG
AL = Alarm output
t.out = Timer output
t.HoF = Timer out -OFF in hold
Out 1 function (when Out1 is a digital output) 0 or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator
bo.PF = Out-of-range, burn out and Power failure indicator
St.bY = Stand by status indicator
diF.1 = The output repeats the digital input 1 status
diF.2 = The output repeats the digital input 2 status
on = Out 1 always ON
0... 63
+1 = Alarm 1
+2 = Alarm 2
13 o1AL Alarms linked up with the out 1 0 +4 = Alarm 3 AL1
+8 = Loop break alarm
+16 = Sensor Break
+32 = Overload on output 4
dir = Direct action
rEU = Reverse action
14 o1Ac Out 1 action 0 dir
dir.r = Direct with reversed LED
ReU.r = Reverse with reversed LED
NonE = Output not used
H.rEG = Heating output
c.rEG = Cooling output
AL = Alarm output
t.out = Timer output
t.HoF = Timer out -OFF in hold
15 o2F Out 2 function 0 or.bo = Out-of-range or burn out indicator AL
P.FAL = Power failure indicator
bo.PF = Out-of-range, burn out and Power failure indicator
St.bY = Stand by status indicator
diF.1 = The output repeats the digital input 1 status
diF.2 = The output repeats the digital input 2 status
on = Out 2 always ON
0... 63
+1 = Alarm 1
+2 = Alarm 2
16 o2AL Alarms linked up with the out 2 0 +4 = Alarm 3 AL1
+8 = Loop break alarm
+16 = Sensor Break
+32 = Overload on output 4

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 28


Dec.
no. Param. Description Values Default
Point
dir = Direct action
rEU = Reverse action
17 o2Ac Out 2 action 0 dir
dir.r = Direct with reversed LED
ReU.r = Reverse with reversed LED
NonE = Output not used
H.rEG = Heating output
c.rEG = Cooling output
AL = Alarm output
t.out = Timer output
t.HoF = Timer out -OFF in hold
18 o3F Out 3 function 0 or.bo = Out-of-range or burn out indicator AL
P.FAL = Power failure indicator
bo.PF = Out-of-range, burn out and Power failure indicator
St.bY = Stand by status indicator
diF.1 = The output repeats the digital input 1 status
diF.2 = The output repeats the digital input 2 status
on = Out 3 always ON
0... 63
+1 = Alarm 1
+2 = Alarm 2
19 o3AL Alarms linked up with the out 3 0 +4 = Alarm 3 AL2
+8 = Loop break alarm
+16 = Sensor Break
+32 = Overload on output 4
dir = Direct action
rEU = Reverse action
20 o3Ac Out 3 action 0 dir
dir.r = Direct with reversed LED
ReU.r = Reverse with reversed LED
NonE = Output not used
H.rEG = Heating output
c.rEG = Cooling output
AL = Alarm output
t.out = Timer output
21 o4F Out 4 function 0 AL
t.HoF = Timer out -OFF in hold
or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator
bo.PF = Out-of-range, burn out and Power failure indicator
St.bY = Stand by status indicator
0... 63
+1 = Alarm 1
+2 = Alarm 2
AL1 +
22 o4AL Alarms linked up with the out 4 0 +4 = Alarm 3
AL2
+8 = Loop break alarm
+16 = Sensor Break
+32 = Overload on output 4
dir = Direct action
rEU = Reverse action
23 o4Ac Out 4 action 0 dir
dir.r = Direct with reversed LED
ReU.r = Reverse with reversed LED

]]
AL1 group
Dec.
no. Param. Description Values Default
Point
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAo = Windows alarm in alarm outside the windows
LHAI = Windows alarm in alarm inside the windows
24 AL1t Alarm 1 type 0 HiAb
SE.br = Sensor Break
LodE = Deviation low alarm (relative)
HidE = Deviation high alarm (relative)
LHdo = Relative band alarm in alarm out of the band
LHdi = Relative band alarm in alarm inside the band
0... 15
+1 = Not active at power up
25 Ab1 Alarm 1 function 0 +2 = Latched alarm (manual reset) 0
+4 = Acknowledgeable alarm
+8 = Relative alarm not active at set point change
-- For High and low alarms, it is the low limit
26 AL1L of the AL1 threshold; dp From -1999 to AL1H (E.U.) -1999
-- For band alarm, it is low alarm threshold

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 29


Dec.
no. Param. Description Values Default
Point
-- For High and low alarms, it is the high
27 AL1H limit of the AL1 threshold; dp From AL1L to 9999 (E.U.) 9999
-- For band alarm, it is high alarm threshold
28 AL1 AL1 threshold dp From AL1L to AL1H (E.U.) 0
29 HAL1 AL1 hysteresis dp 1... 9999 (E.U.) 1
30 AL1d AL1 delay 0 From 0 (oFF) to 9999 (s) oFF
0 = Alarm 1 disabled during Stand by and out of range
Alarm 1 enabling during Stand-by mode and 1 = Alarm 1 enabled in stand by mode
31 AL1o 0 2 = Alarm 1 enabled in out of range condition 0
out of range conditions 3 = Alarm 1 enabled in stand by mode and in overrange
condition

]]
AL2 group
Dec.
no. Param. Description Values Default
Point
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAo = Windows alarm in alarm outside the windows
LHAI = Windows alarm in alarm inside the windows
32 AL2t Alarm 2 type 0 Loab
SE.br = Sensor Break
LodE = Deviation low alarm (relative)
HidE = Deviation high alarm (relative)
LHdo = Relative band alarm in alarm out of the band
LHdi = Relative band alarm in alarm inside the band
0... 15
+1 = Not active at power up
33 Ab2 Alarm 2 function 0 +2 = Latched alarm (manual reset) 0
+4 = Acknowledgeable alarm
+8 = Relative alarm not active at set point change
-- For High and low alarms, it is the low limit
34 AL2L of the AL2 threshold; dp From -1999 to AL2H (E.U.) -1999
-- For band alarm, it is low alarm threshold
-- For High and low alarms, it is the high
35 AL2H limit of the AL2 threshold; dp From AL2L to 9999 (E.U.) 9999
-- For band alarm, it is high alarm threshold
36 AL2 AL2 threshold dp From AL2L to AL2H (E.U.) 0
37 HAL2 AL2 hysteresis dp 1... 9999 (E.U.) 1
38 AL2d AL2 delay 0 From 0 (oFF) to 9999 (s) oFF
0 = Alarm 2 disabled during Stand by and out of range
Alarm 2 enabling during Stand-by mode and 1 = Alarm 2 enabled in stand by mode
39 AL2o 0 2 = Alarm 2 enabled in out of range condition 0
out of range conditions 3 = Alarm 2 enabled in stand by mode and in overrange
condition

]]
AL3 group
Dec.
no. Param. Description Values Default
Point
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAo = Windows alarm in alarm outside the windows
LHAI = Windows alarm in alarm inside the windows
40 AL3t Alarm 3 type 0 nonE
SE.br = Sensor Break
LodE = Deviation low alarm (relative)
HidE = Deviation high alarm (relative)
LHdo = Relative band alarm in alarm out of the band
LHdi = Relative band alarm in alarm inside the band
0... 15
+1 = Not active at power up
41 Ab3 Alarm 3 function 0 +2 = Latched alarm (manual reset) 0
+4 = Acknowledgeable alarm
+8 = Relative alarm not active at set point change
-- For High and low alarms, it is the low limit
42 AL3L of the AL3 threshold; dp From -1999 to AL3H (E.U.) -1999
-- For band alarm, it is low alarm threshold

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 30


Dec.
no. Param. Description Values Default
Point
-- For High and low alarms, it is the high
43 AL3H limit of the AL3 threshold; dp From AL3L to 9999 (E.U.) 9999
-- For band alarm, it is high alarm threshold
44 AL3 AL3 threshold dp From AL3L to AL3H (E.U.) 0
45 HAL3 AL3 hysteresis dp 1... 9999 (E.U.) 1
46 AL3d AL3 delay 0 From 0 (oFF) to 9999 (s) oFF
0 = Alarm 3 disabled during Stand by and out of range
Alarm 3 enabling during Stand-by mode and 1 = Alarm 3 enabled in stand by mode
47 AL3o 0 2 = Alarm 3 enabled in out of range condition 0
out of range conditions 3 = Alarm 3 enabled in stand by mode and in overrange
condition

]]
LBA group - Loop Break Alarm Parameters
Dec.
no. Param. Description Values Default
Point
48 LbAt LBA time 0 From 0 (oFF) to 9999 (s) oFF
49 LbSt Delta measure used by LBA during Soft start dP From 0 (oFF) to 9999 (E.U.) 10
50 LbAS Delta measure used by LBA dP 1...9999 (E.U.) 20
uP = Active when Pout = 100%
51 LbcA Condition for LBA enabling 0 dn = Active when Pout = -100% both
both = Active in both cases

]]
rEG group - Control Parameters
Dec.
no. Param. Description Values Default
Point
Pid = PID (heat and/or)
On.FA = ON/OFF asymmetric hysteresis
52 cont Control type 0 On.FS = ON/OFF symmetric hysteresis Pid
nr = Heat/Cool ON/OFF control with neutral zone
3Pt = Servomotor control
-4 = Oscillating auto-tune with automaticrestart at power up
and after all point change
-3 = Oscillating auto-tune with manual start
-2 = Oscillating -tune with auto-matic start at the first power up only
-1 = Oscillating auto-tune with auto-matic restart at every power up
0 = Not used
1 = Fast auto tuning with automatic restart at every power up
2 = Fast auto-tune with automatic start the first power up only
53 Auto Autotuning selection 0 7
3 = FAST auto-tune with manual start
4 = FAST auto-tune with automatic restart at power up and after
a set point change
5 = SmartTune with automatic restart at every power up
6 = SmartTune with automatic start the first power up only
7 = SmartTune with manual start
8 = SmartTune with automatic restart at power up and after a
set point change
oFF = Not active
54 Aut.r Manual start of the Autotuning 0 oFF
on = Active
no = The instrument does not perform the self-tuning
55 SELF Self tuning enabling 0 no
YES = The instrument is performing the self-tuning
56 HSEt Hysteresis of the ON/OFF control dP 0... 9999 (E.U.) 1
57 cPdt Time for compressor protection 0 From 0 (oFF) to 9999 (s) oFF
58 Pb Proportional band dP 1... 9999 (E.U.) 50
59 ti Integral time 0 From 0 (oFF) to 9999 (s) 200
60 td Derivative time 0 From 0 (oFF) to 9999 (s) 50
61 Fuoc Fuzzy overshoot control 2 0.00... 2.00 0.50
62 tcH Heating output cycle time 1 0.1... 130.0 (s) 20.0
Power ratio between heating and
63 rcG 2 0.01... 99.99 1.00
cooling action
64 tcc Cooling output cycle time 1 0.1... 130.0 (s) 20.0
65 rS Manual reset (Integral pre-load) 1 -100.0... +100.0 (%) 0.0
66 od Delay at power up 2 From 0.00 (oFF) to 99.59 (hh.mm) oFF
Maximum power output used during
67 St.P 0 -100... 100 (%) 0
soft start

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 31


Dec.
no. Param. Description Values Default
Point
-- 0.00 (oFF)
68 SSt Soft start time 2 -- 0.01... 7.59 (hh.mm) oFF
-- inF (always ON)
69 SS.tH Threshold for soft start disabling dP -1999... +9999 (E.U.) 9999

]]
SP group - Set point parameters
Dec.
no. Param. Description Values Default
Point
70 nSP Number of used set points 0 1... 4 1
71 SPLL Minimum set point value dP From -1999 to SPHL -1999
72 SPHL Maximum set point value dP From SPLL to 9999 9999
73 SP Set point 1 dP From SPLL to SPLH 0
74 SP 2 Set point 2 dP From SPLL to SPLH 0
75 SP 3 Set point 3 dP From SPLL to SPLH 0
76 SP 4 Set point 4 dP From SPLL to SPLH 0
77 A.SP Selection of the active set point 0 From 1 (SP 1) to nSP 1
RSP = The value coming from serial link is used as remote
set point
trin = The value will be added to the local set point selected
78 SP.rt Remote set point type 0 trin
by A.SP and the sum becomes the operative set point
PErc = The value will be scaled on the input range and this
value will be used as remote SP
Loc = local
79 SPLr Local/remote set point selection 0 Loc
rEn = remote
Rate of rise for POSITIVE set point
80 SP.u 2 0.01... 99.99 (inF) Eng. units per minute inF
change (ramp UP)
Rate of rise for NEGATIVE set point
81 SP.d 2 0.01... 99.99 (inF) Eng. units per minute inF
change (ramp DOWN)

]]
TIN group - Timer function parameters
Dec.
no. Param. Description Values Default
Point
NonE = Timer not used
i.d.A = Delayed start timer
i.uP.d = Delayed start at power up
82 tr.F Independent timer function 0 nonE
i.d.d = Feed-through timer
i.P.L = Asymmetrical oscillator with start OFF
i.L.P = Asymmetrical oscillator with start ON
hh.nn = Hours and minutes
83 tr.u Timer unit 0 nn.SS = Minutes and seconds nn.SS
SSS.d = Second and tenth of seconds
2 When tr.u < 20: 0.01... 99.59
84 tr.t1 Time 1 1.00
1 When tr.u = 200: 0.1... 995.9
2 When tr.u < 2: From 00.00 (oFF) to 99.59 (inF)
85 tr.t2 Time 2 1.00
1 When tr.u = 2: From 000.0 (oFF) to 995.9 (inF)
rES = Timer reset
86 tr.St Timer status 0 run = Timer run rES
HoLd = Timer hold

]]
PAn group - Operator HMI parameters
Dec.
no. Param. Description Values Default
Point
Level 2 password (limited -- oFF (Level 2 not protected by password)
87 PAS2 0 20
access level) -- 1... 200
Level 3 password (com-
88 PAS3 0 3... 200 30
plete configuration level)
Level 4 password (CODE
89 PAS4 0 201... 400 300
configuration level)

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 32


Dec.
no. Param. Description Values Default
Point
nonE = No function
tunE = Auto-tune/self-tune enabling. A single press (longer than 1 se-
cond) starts the auto-tune
oPLo = Manual mode. The first pressure puts the instrument in manual
mode (OPLO) while a second one puts the instrument in Auto mode
90 uSrb button function during AAc = Alarm reset tunE
RUN TIME ASi = Alarm acknowledge
chSP = Sequential set point selection
St.by = Stand by mode. The first press puts the instrument in stand by
mode while a second one puts the instrument in Auto mode.
Str.t = Timer run/hold/reset
nonE = Standard display
Pou = Power output
SPF = Final set point
Spo = Operative set point
AL1 = Alarm 1 threshold
AL2 = Alarm 2 threshold
AL3 = Alarm 3 threshold
ti.uP = When the timer is running, the display shows the timer counting
91 diSP Display management 0
up. At the end of the counting, the instrument shows “t.End”
messages alternately with the measured value.
ti.du = When the timer is running, the display shows the timer counting
down. At the end of the counting, the instrument shows “t.End”
messages alternately with the measured value.
PErc = Percent of the power output used during soft start (when the soft
start time is equal to infinite, the limit is ever active and it can be
used also when ON/OFF control is selected)
0 = The display colour is used to show the actual deviation (PV - SP)
1 = Display red (fix)
92 di.cL Display colour 0
2 = Display green (fix)
3 = Display orange (fix)
Deviation for display colour
93 AdE 1... 999 (E.U.) 5
management
-- oFF (display always ON)
94 di.St Display Timeout 2 oFF
-- 0.1... 99.59 (mm.ss)
Filter on the displayed -- oFF (filter disabled)
95 fiLd 1 oFF
value -- From 0.0 (oFF) to 20.0 (E.U.)
AS.Pr = Starts in the same way it was prior to the power down
Instrument status at power Auto = Starts in Auto mode
96 dSPu AS.Pr
ON oP.0 = Starts in manual mode with a power output equal to zero
St.bY = Starts in stand-by mode
ALL = All modes will be selectable by the next parameter
Au.oP = Auto and manual (OPLO) mode only will be selectable by the next
97 oPr.E Operative modes enabling ALL
parameter
Au.Sb = Auto and Stand-by modes only will be selectable by the next parameter
If oPr.E = ALL: - Auto = Auto mode
- oPLo = Manual mode
- St.bY = Stand by mode
98 oPEr Operative mode selection If oPr.E = Au.oP: - Auto = Auto mode Auto
- oPLo = Manual mode
If oPr.E = Au.Sb: - Auto = Auto mode
- St.bY = Stand by mode

]]
Ser group - Serial link parameters
Dec.
no. Param. Description Values Default
Point
-- oFF
99 Add Instrument address 1
-- 1... 254
1200 = 1200 baud
2400 = 2400 baud
100 bAud baud rate 9600 = 9600 baud 9600
19.2 = 19200 baud
38.4 = 38400 baud
nonE = Retransmission not used (the instrument is a slave)
Selection of the value to be rSP = The instrument becomes a Master and retransmits the operati-
101 trSP ve set point nonE
retransmitted (Master) PErc = The instrument become a Master and it retransmits the power
output

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 33


]]
COn group - Consumption parameters
Dec.
no. Param. Description Values Default
Point
oFF = Not used
1= Instantaneous power (kW)
2= Power consumption (kW/h)
102 Co.tY Measurement type 4= Total worked days with threshold. It is the number of hours oFF
that the instrument is turned ON divided for 24
5= Total worked hours with threshold. It is the number of hours
that the instrument is turned ON
103 UoLt Nominal Voltage of the load 1... 9999 (V) 230
104 cur Nominal current of the load 1... 999 (A) 10
Threshold of the working oFF = threshold not used
105 h.Job 0... 9999 days (when cotY = 4) 0
period 0... 9999 hours (when cotY = 5)
106 t.Job Worked time (not resettable) 0... 9999 days

]]
CAl group - User calibration parameters
Dec.
no. Param. Description Values Default
Point
107 AL.P Adjust Low Point From -1999 to (AH.P - 10) in engineering units 0
108 AL.o Adjust Low Offset -300... +300 (E.U.) 0
109 AH.P Adjust High Point From (AL.P + 10) to 9999 engineering units 9999
110 AH.o Adjust High Offset -300... +300 0

EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 34


EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 35
EL.CO. - ELKM3 - MANUALE INGEGNERISTICO - Vr. 01 (ITA) PAG. 36

You might also like