ELKM3 Digital Controller Manual
ELKM3 Digital Controller Manual
1 Mounting requirements
Engineering Manual When the maximum front protection (IP65) is desired, the
optional gasket must be monted.
Code : ISTR-MKR1-3ENG03 - Vr. 3.0 (ENG)
EL.CO. S.r.l. 2.2 General notes about wiring
Via Lago di Molveno, 20 - 36015 Schio (VI) • ITALY 1. Do not run input wires together with power cables.
Tel.: +39 0445 661722 - Fax: +39 0445 661792 2. External components (like zener barriers, etc.) connected
www.elco-italy.com between sensor and input terminals may cause errors in
e-mail: [email protected] measurement due to excessive and/or not balanced line
resistance or possible leakage currents.
1. Outline dimensions (mm)
3. When a shielded cable is used, it should be connected at
Instrument with non removable terminals one point only.
4. Pay attention to the line resistance; a high line resistance
may cause measurement errors.
78 5 64 14
2.3 Inputs
2.3.1 Termocouple Input
35
PV
AT
1 2
2. Connection diagram
+ -
Passive TX,
2 wires, Relay Out 1: 4 (4) A/250 VAC
4... 20 mA Relay Out 2, 3: 2 (1) A/250 VAC (*) External resistance: 100Ω max., maximum error 25 mV.
SSR Out 1, 2 , 3: 10 VDC/15 mA
0/12... 60 mV,
Out1: 4... 20 mA (KR3 only)
Cold junction: automatic compensation between 0... 50°C.
0/1... 5V,
0/2... 10V + SSR Out4: 12 VDC/20 mA Cold junction accuracy: 0.05°C/°C after a warm-up of
* KR3 servodrive models: both Out2 and Out3
4... 20 mA are to be selected as “M” in Configuration code;
20 minutes.
(active) +
Out2: open, Out3: close Input impedance: > 1 MΩ.
Pt1000
Pt100 DI2 DI1 Calibration: According to EN 60584-1.
RS485
TC + Note: For TC wiring use proper compensating cable
D- D+ preferable shielded.
+ - Out1
Out4
Out3 Out2
C NO C NO C NC NO
Power
Supply
4...20 mA
2 wires
Transmitter
- +
1 2
+ -
External resistance: not relevant.
Cold junction: automatic compensation between 0... 50°C.
1 2 3 4
Cold junction accuracy: 0.05°C/°C.
Input impedance: > 1 MΩ. Input impedance: < 53Ω.
Internal auxiliary PWS: 12 VDC (±10%), 20 mA max..
2.3.3 RTD Pt 100 Input
0/4... 20 mA input wiring for passive transmitter
using an external pws
RTD
0/4...20 mA
passive
transmitter
- +
1 2 3 +
External
Input circuit: Current injection (150 µA).
PWS
Line resistance: Automatic compensation up to 20Ω/wire
with maximum error ±0.1% of the input span.
Calibration: According to EN 60751/A2. -
Note: The resistance of the 3 wires must be the same.
0/4... 20 mA
active
transmitter
2 3
+ -
1 2
+ -
Input impedance: > 1 MΩ for mV Input
500 kΩ for Volt Input.
2.4 Outputs C NO
Safety notes: OP1 contact rating: - 2 A /250 V cosj = 1
- 1 A /250 V cosj = 0.4
––To avoid electrical shocks, connect power line at last.
Operation: 1 x 105
––For supply connections use No. 16 AWG or larger wires
rated for at last 75°C. SSR Output
––Use copper conductors only. SSR
––SSR outputs are not isolated. A reinforced isolation must + -
be assured by the external solid state relays. 17 18
––For SSR, mA and V outputs if the line length is longer than
30 m use a shielded wire. + -
WARNING! Before connecting the output actuators, Logic level 0: Vout < 0.5 VDC
we recommend to configure the parameters to Logic level 1: 12 V ± 20%, 15 mA max.
suit your application (e.g.: input type, Control
strategy, alarms, etc.). 2.4.3 Output 3 (OP3)
2.4.1 Output 1 (OP1) Relay Output
Relay Output
15 16
22 23 24
C NO
+ -
Neutral Line
Logic level 0: Vout < 0.5 VDC
Logic level 1: 12 V ± 20%, 15 mA max. Supply Voltage: - 24 VAC/DC (±10%)
- 100... 240 VAC (-15... +10%)
2.4.4 Output 2 and Output 3 Servomotor Drive Notes: 1. Before connecting the instrument to the power
Close Open line, make sure that line voltage is equal to the
voltage shown on the identification label;
C NO C NO
2. The polarity of the power supply has no importance;
15 16 17 18
3. The power supply input is NOT fuse protected.
Please, provide a T type 1A, 250 V fuse externally.
Out3 Out2
4. When the instrument is powered by the A01 key,
OP2/3 contact rating: - 2 A /250 V cosj = 1; the outputs are NOT supplied and the instrument
- 1 A /250 V cosj = 0.4. can show the ouLd (Out 4 Overload) indication.
Operation: 1 x 105.
3. Technical characteristics
2.4.5 Output 4 (OP4) Case: Plastic, self-extinguishing degree: V-0 according to UL 94;
SSR Output Front protection: IP 65 (when the optional panel gasket is
+ - mounted) for indoor locations according to EN 60070-1;
Terminals protection: IP 20 according to EN 60070-1;
Installation: Panel mounting;
4 11
+ - Terminal block:24 M3 screw terminals, for cables from
0.25... 2.5 mm2 (AWG 22... AWG 14) with connection
SSR
diagrams;
Logic level 0: Vout < 0.5 VDC; Dimensions: 78 x 35 depth 69.5 mm (3.07 x 1.37 depth 2.73 in.)
Logic level 1: 12 V ± 20%, 20 mA max..
Panel cutout: 71(+0.6) x 29(+0.6) mm [2.79(+0.023) x 1.14+(+0.023) in.]
Note: Overload protected. 71 x 29 (-0... +0.5 mm)
Weight: 180 g max..
2.5 Serial Interface
Power supply: • 24 VAC/DC (±10% of the nominal value);
RS485 D+ • 100... 240 VAC (-15... +10% of the
nominal value);
C
Power consumption: 5 VA max.;
D-
Insulation voltage: 2300 V rms according to EN 61010-1;
D+ Display updating time: 500 ms;
8 9 10 D- Sampling time: 130 ms;
D- D+ Resolution: 30000 counts;
TC S -58... 3200°F 1 9
Auxiliary functions activation S
TC R -58... +3200°F 2 0
None 0
TC T -94... +752°F 2 1
Wattmeter (instantaneous power expressed in W) 1
Infrared J -58... +1445°F 2 2
Wattmeter (energy expressed in Wh) 2
Infrared K -58... +1445°F 2 3
Absolute worked time (expressed in days) 3
PT 100/PTC KTY81-121 -328... +1562°F/-67... +302°F 2 4
Absolute worked time (expressed in hours) 4
PT 1000/NTC 103-AT2 -328... +1562°F/-58... +230°F 2 5
7. Push the button.
c%d1: L MN O If the just entered codes are accepted, the upper display
shows code flashing while the lower display shows good.
Control mode OP1 OP2 OP3 OP4 N O
8. Push the button to save the configuration code and
H AL1 AL2 AL3 0 0
ON/OFF heating = H exit the Code configuration procedure.
NU AL1 AL2 H 0 1
C AL1 AL2 AL3 0 2 Note: After using the “Code configuration” method, it will
ON/OFF cooling = C
NU AL1 AL2 C 0 3 always be possible to modify the parameters using the
H C AL2 AL3 0 4 “Complete configuration” method. If the value of a
H AL1 AL2 C 0 5 parameter among those included in the configuration
ON/OFF with neutral C H AL2 AL3 0 6 codes (cod1 - cod2) gets modified, the instrument
zone (H/C) NU H AL2 C 0 7 will acquire the change while maintaining all the other
C AL1 AL2 H 0 8 parameters.
NU C AL2 H 0 9
H AL1 AL2 AL3 1 0
Attention! After a parameter change made as described in the
PID heating = H previous “Note”, when retrieving the configuration
NU AL1 AL2 H 1 1
C AL1 AL2 AL3 1 2 codes (cod1 - cod2), the lower display will
PID cooling = C show “oFF” to alert the operator that one of the
NU AL1 AL2 C 1 3
H C AL2 AL3 1 4 parameters has been changed.
H AL1 AL2 C 1 5
C H AL2 AL3 1 6
PID double action (H/C)
NU H AL2 C 1 7
C AL1 AL2 H 1 8
NU C AL2 H 1 9
]tin group - Timer function parameters Notes: 1. The instrument can receive the start, hold and
reset commands by button, by logic inputs
Five timer types are available: and/or by serial link.
Delayed start with a delay time and a “end of cycle” time. 2. An HOLD command can suspend the time count.
Tr.t1 Tr.t2 [82] tr.F= Independent timer function
Start
Available: Always.
OUT off ON off
Range: nonE = Timer not used
i.d.A = Delayed start timer
––Setting tr.t2 = Inf the timer out remains in ON condition
i.uP.d = Delayed start at power up
until a reset command is detected.
i.d.d = Feed-through timer
Tr.t1 Tr.t2 = inF i.P.L = Asymmetrical oscillator with start in OFF
Start i.L.P = Asymmetrical oscillator with start in ON
off ON off [83] tr.u - Engineering unit of the time
OUT
Available: When [82] tr.F is different form nonE.
Reset Range: hh.nn = Hours and minutes
nn.SS = Minutes and seconds
SSS.d = Seconds and tenth of seconds
Note: When the timer is running, you can see the value of
this parameter but you can NOT modify it.
[84] tr.t1 - Time 1
Available: When [82] tr.F is different form nonE.
Range: When [83] tr.u = hh.nn = 00.01... 99.59
When [83] tr.u = nn.SS = 00.01... 99.59
When [83] tr.u = SSS.d = 000.1... 995.9
[85] tr.t2 - Time 2
Available: When [82] tr.F is different form nonE
Range: When [83] tr.u = hh.nn = 00.01... 99.59 + inF
When [83] tr.u = nn.SS = 00.01... 99.59 + inF
When [83] tr.u = SSS.d= 000... 995.9 + inF.
Note: Setting [85] tr.t2 = inF, the second time can be stopped
by a reset command only.
When manual control is selected, the instrument will start to 3. If no error is detected, send the instrument to your
operate with the same power output as the last one supplied supplier to be checked.
by automatic mode and can be modified using the and
buttons.
7.2 List of possible errors
ErAT Fast Auto-tune cannot start. The measure value is too
In case of ON/OFF control, 0% corresponds to the close to the set point.
deactivated output while any value different from 0 Push the button in order to delete the error message.
corresponds to the activated output. ouLd Overload on the out 4
As in the case of visualization, the programmable values The messages shows that a short circuit is present on
range from H100 (100% output power with reverse action) to the Out 4 when it is used as output or as a transmitter
C100 (100% output power with direct action). power suply. When the short circuit disappears the
Notes: 1. During manual mode, the alarms are operative. output restart to operate.
NoAt Auto-tune not finished within 12 hours.
2. If you set manual modes during self-tune
ErEP Possible problem of the instrument memory.
execution, the self- tune function will be aborted.
The messages disappears automatically.
3. During manual mode, all functions not related When the error continues, send the instrument to your
with the control (wattmeter, independent timer, supplier.
“worked time”, etc) continue to operate normally. RonE Possible problem of the firmware memory.
When this error is detected, send the instrument to
6.6 Stand by mode your supplier.
This operative mode also deactivates the automatic control Errt Possible problem of the calibration memory.
but forces the control output to zero. When this error is detected, send the instrument to
In this mode the instrument operates as an indicator. your supplier.
When the instrument is in stand by mode the upper display 8. GENERAL NOTES
will show the measured value while the lower display will
show alternately the set point and the message “St.bY”. 8.1 Proper use
Notes: 1. During stand by mode, the relative alarms are Every possible use not described in this manual must be
disabled while the absolute alarms are operative consider as a improper use.
or not according to the ALxo (Alarm x enabling
This instrument is in compliance with EN 61010-1 “Safety
during Stand-by mode) parameter setting.
requirements for electrical equipment for measurement,
2. If you set stand by mode during self-tune control and laboratory use”; for this reason it coud not be
execution, the self- tune function will be aborted. used as a safety equipment.
3. During stand by mode, all functions not related Whenever a failure or a malfunction of the control device
8.2 Warranty
This product is under warranty against manufacturing
defects or faulty materials that are found within 18 months
from delivery date. The warranty is limited to repairs or to the
replacement of the instrument.
The tampering of the instrument or an improper use of the
product will bring about the immediate withdrawal of the
warranty’s effects.
In the event of a faulty instrument, either within the period
of warranty, or further to its expiry, please contact our
sales department to obtain authorisation for sending the
instrument to our company.
The faulty product must be shipped to EL.CO. with a detailed
description of the faults found, without any fees or charge for
EL.CO., except in the event of alternative agreements.
8.3 Maintenance
This instrument does not requires periodical recalibration
and it have no consumable parts so that no particular
maintenance is required.
Some times, a cleaning action is suggestible.
1. SWITCH THE EQUIPMENT OFF (power supply, relay
out, etc.).
2. Take the instrument out of its case.
3. Using a vacuum cleaner or a compressed air jet (max. 3
kg/cm2) remove all deposits of dust and dirt which may
be present on the case and on the internal circuits being
careful not to damage the electronic components.
4. To clean external plastic or rubber parts use only a cloth
moistened with:
• Ethyl Alcohol (pure or denatured) [C2H5OH] or
• Isopropyl Alcohol (pure or denatured) [(CH3)2CHOH]
or
• Water (H2O).
5. Make sure that there are no loose terminals.
6. Before putting the instrument back in its case, make sure
that it is perfectly dry.
7. Put the instrument back and turn it ON.
8.4 Accessories
The instrument has a lateral socket into which a special
tool can be inserted. This tool, named KEYA01, allows:
––To memorize a complete instrument configuration and to
use it for other instruments.
––To transfer a complete instrument configuration to a PC or
from a PC to an instrument
––To transfer from a PC to an instrument a complete
instrument configuration
––To transfer a configuration from an KEYA01 to another one.
––To test serial interface of the instruments and to help the
]]
inP GROUP - Main and auxiliary input configuration
Dec.
no. Param. Description Values Default
Point
Sensor selection (according to the HW)
J = TC J,
crAL = TC K,
S = TC S,
r = TC R,
t = TC T,
ir.J = IRS J,
ir.cA = IRS K,
Pt1 = RTD Pt100,
Model C Pt10 = RTD Pt1000,
0.60 = 0... 60 mV,
12.60 = 12... 60 mV,
0.20 = 0... 20 mA,
4.20 = 4... 20 mA,
0.5 = 0... 5 V,
1.5 = 1... 5 V,
0.10 = 0... 10 V,
1 SEnS 2.10 = 2... 10 V
0 J
J = TC J,
crAL = TC K,
S = TC S,
r = TC R,
t = TC T,
ir.J = IRS J,
ir.cA = IRS K,
Ptc = TC KTY81-121,
Model E ntc = NTC 103-AT2,
0.60 = 0... 60 mV,
12.60 = 12... 60 mV,
0.20 = 0... 20 mA,
4.20 = 4... 20 mA,
0.5 = 0... 5 V,
1.5 = 1... 5 V,
0.10 = 0... 10 V,
2.10 = 2... 10 V
Decimal Point Position (linear inputs) 0... 3
2 dp 0 0
Decimal Point Position (different than linear inputs) 0/1
3 SSC Initial scale read-out for linear inputs dp -1999... 9999 0
4 FSc Full Scale Readout for linear inputs dp -1999... 9999 1000
5 unit Engineer unit °C/°F °C
6 Fil Digital filter on the measured value 1 0 (= OFF)... 20.0 s 1.0
Sensor error used to enable the safety output or = Over range
7 inE ou = Under range our
value our = Over and under range
8 oPE Safety output value (% of the output) -100... 100 0
on = Output used as PWS for TX,
out4 = Output 4 (digital output 4),
9 IO4.F I/O 4 function out4
dG2c = Digital input 2 driven by contact,
dG2U = Digital input 2 driven by voltage
oFF = Not used,
1 = Alarm reset,
2 = Alarm acknowledge (ACK),
3 = Hold of the measured value,
4 = Stand by mode,
5 = Manual mode,
6 = HEAt with SP1 and CooL with SP2,
7 = Timer RUN/Hold/Reset,
10 diF1 Digital Input 1 function 8 = Timer Run, oFF
9 = Timer Reset,
10 = Timer Run/Hold,
11 = Timer Run/Reset,
12 = Timer Run/Reset with lock,
18 = Sequential SP selection,
19 = SP1 - SP2 selection,
20 = SP1... SP4 binary selection,
21 = Digital inputs in parallel to and keys
]]
Out group
Dec.
no. Param. Description Values Default
Point
NonE = Output not used
H.rEG = Heating output
c.rEG = Cooling output
Out 1 function (when Out 1 is a linear output) 0 r.inP = Measure retransmission
r.Err = Error (sp - PV) retransmission
r.SP = Set point retransmission
r.SEr = Serial value retransmission
NonE = Output not used
H.rEG = Heating output
12 o1F c.rEG = Cooling output H.reG
AL = Alarm output
t.out = Timer output
t.HoF = Timer out -OFF in hold
Out 1 function (when Out1 is a digital output) 0 or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator
bo.PF = Out-of-range, burn out and Power failure indicator
St.bY = Stand by status indicator
diF.1 = The output repeats the digital input 1 status
diF.2 = The output repeats the digital input 2 status
on = Out 1 always ON
0... 63
+1 = Alarm 1
+2 = Alarm 2
13 o1AL Alarms linked up with the out 1 0 +4 = Alarm 3 AL1
+8 = Loop break alarm
+16 = Sensor Break
+32 = Overload on output 4
dir = Direct action
rEU = Reverse action
14 o1Ac Out 1 action 0 dir
dir.r = Direct with reversed LED
ReU.r = Reverse with reversed LED
NonE = Output not used
H.rEG = Heating output
c.rEG = Cooling output
AL = Alarm output
t.out = Timer output
t.HoF = Timer out -OFF in hold
15 o2F Out 2 function 0 or.bo = Out-of-range or burn out indicator AL
P.FAL = Power failure indicator
bo.PF = Out-of-range, burn out and Power failure indicator
St.bY = Stand by status indicator
diF.1 = The output repeats the digital input 1 status
diF.2 = The output repeats the digital input 2 status
on = Out 2 always ON
0... 63
+1 = Alarm 1
+2 = Alarm 2
16 o2AL Alarms linked up with the out 2 0 +4 = Alarm 3 AL1
+8 = Loop break alarm
+16 = Sensor Break
+32 = Overload on output 4
]]
AL1 group
Dec.
no. Param. Description Values Default
Point
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAo = Windows alarm in alarm outside the windows
LHAI = Windows alarm in alarm inside the windows
24 AL1t Alarm 1 type 0 HiAb
SE.br = Sensor Break
LodE = Deviation low alarm (relative)
HidE = Deviation high alarm (relative)
LHdo = Relative band alarm in alarm out of the band
LHdi = Relative band alarm in alarm inside the band
0... 15
+1 = Not active at power up
25 Ab1 Alarm 1 function 0 +2 = Latched alarm (manual reset) 0
+4 = Acknowledgeable alarm
+8 = Relative alarm not active at set point change
-- For High and low alarms, it is the low limit
26 AL1L of the AL1 threshold; dp From -1999 to AL1H (E.U.) -1999
-- For band alarm, it is low alarm threshold
]]
AL2 group
Dec.
no. Param. Description Values Default
Point
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAo = Windows alarm in alarm outside the windows
LHAI = Windows alarm in alarm inside the windows
32 AL2t Alarm 2 type 0 Loab
SE.br = Sensor Break
LodE = Deviation low alarm (relative)
HidE = Deviation high alarm (relative)
LHdo = Relative band alarm in alarm out of the band
LHdi = Relative band alarm in alarm inside the band
0... 15
+1 = Not active at power up
33 Ab2 Alarm 2 function 0 +2 = Latched alarm (manual reset) 0
+4 = Acknowledgeable alarm
+8 = Relative alarm not active at set point change
-- For High and low alarms, it is the low limit
34 AL2L of the AL2 threshold; dp From -1999 to AL2H (E.U.) -1999
-- For band alarm, it is low alarm threshold
-- For High and low alarms, it is the high
35 AL2H limit of the AL2 threshold; dp From AL2L to 9999 (E.U.) 9999
-- For band alarm, it is high alarm threshold
36 AL2 AL2 threshold dp From AL2L to AL2H (E.U.) 0
37 HAL2 AL2 hysteresis dp 1... 9999 (E.U.) 1
38 AL2d AL2 delay 0 From 0 (oFF) to 9999 (s) oFF
0 = Alarm 2 disabled during Stand by and out of range
Alarm 2 enabling during Stand-by mode and 1 = Alarm 2 enabled in stand by mode
39 AL2o 0 2 = Alarm 2 enabled in out of range condition 0
out of range conditions 3 = Alarm 2 enabled in stand by mode and in overrange
condition
]]
AL3 group
Dec.
no. Param. Description Values Default
Point
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAo = Windows alarm in alarm outside the windows
LHAI = Windows alarm in alarm inside the windows
40 AL3t Alarm 3 type 0 nonE
SE.br = Sensor Break
LodE = Deviation low alarm (relative)
HidE = Deviation high alarm (relative)
LHdo = Relative band alarm in alarm out of the band
LHdi = Relative band alarm in alarm inside the band
0... 15
+1 = Not active at power up
41 Ab3 Alarm 3 function 0 +2 = Latched alarm (manual reset) 0
+4 = Acknowledgeable alarm
+8 = Relative alarm not active at set point change
-- For High and low alarms, it is the low limit
42 AL3L of the AL3 threshold; dp From -1999 to AL3H (E.U.) -1999
-- For band alarm, it is low alarm threshold
]]
LBA group - Loop Break Alarm Parameters
Dec.
no. Param. Description Values Default
Point
48 LbAt LBA time 0 From 0 (oFF) to 9999 (s) oFF
49 LbSt Delta measure used by LBA during Soft start dP From 0 (oFF) to 9999 (E.U.) 10
50 LbAS Delta measure used by LBA dP 1...9999 (E.U.) 20
uP = Active when Pout = 100%
51 LbcA Condition for LBA enabling 0 dn = Active when Pout = -100% both
both = Active in both cases
]]
rEG group - Control Parameters
Dec.
no. Param. Description Values Default
Point
Pid = PID (heat and/or)
On.FA = ON/OFF asymmetric hysteresis
52 cont Control type 0 On.FS = ON/OFF symmetric hysteresis Pid
nr = Heat/Cool ON/OFF control with neutral zone
3Pt = Servomotor control
-4 = Oscillating auto-tune with automaticrestart at power up
and after all point change
-3 = Oscillating auto-tune with manual start
-2 = Oscillating -tune with auto-matic start at the first power up only
-1 = Oscillating auto-tune with auto-matic restart at every power up
0 = Not used
1 = Fast auto tuning with automatic restart at every power up
2 = Fast auto-tune with automatic start the first power up only
53 Auto Autotuning selection 0 7
3 = FAST auto-tune with manual start
4 = FAST auto-tune with automatic restart at power up and after
a set point change
5 = SmartTune with automatic restart at every power up
6 = SmartTune with automatic start the first power up only
7 = SmartTune with manual start
8 = SmartTune with automatic restart at power up and after a
set point change
oFF = Not active
54 Aut.r Manual start of the Autotuning 0 oFF
on = Active
no = The instrument does not perform the self-tuning
55 SELF Self tuning enabling 0 no
YES = The instrument is performing the self-tuning
56 HSEt Hysteresis of the ON/OFF control dP 0... 9999 (E.U.) 1
57 cPdt Time for compressor protection 0 From 0 (oFF) to 9999 (s) oFF
58 Pb Proportional band dP 1... 9999 (E.U.) 50
59 ti Integral time 0 From 0 (oFF) to 9999 (s) 200
60 td Derivative time 0 From 0 (oFF) to 9999 (s) 50
61 Fuoc Fuzzy overshoot control 2 0.00... 2.00 0.50
62 tcH Heating output cycle time 1 0.1... 130.0 (s) 20.0
Power ratio between heating and
63 rcG 2 0.01... 99.99 1.00
cooling action
64 tcc Cooling output cycle time 1 0.1... 130.0 (s) 20.0
65 rS Manual reset (Integral pre-load) 1 -100.0... +100.0 (%) 0.0
66 od Delay at power up 2 From 0.00 (oFF) to 99.59 (hh.mm) oFF
Maximum power output used during
67 St.P 0 -100... 100 (%) 0
soft start
]]
SP group - Set point parameters
Dec.
no. Param. Description Values Default
Point
70 nSP Number of used set points 0 1... 4 1
71 SPLL Minimum set point value dP From -1999 to SPHL -1999
72 SPHL Maximum set point value dP From SPLL to 9999 9999
73 SP Set point 1 dP From SPLL to SPLH 0
74 SP 2 Set point 2 dP From SPLL to SPLH 0
75 SP 3 Set point 3 dP From SPLL to SPLH 0
76 SP 4 Set point 4 dP From SPLL to SPLH 0
77 A.SP Selection of the active set point 0 From 1 (SP 1) to nSP 1
RSP = The value coming from serial link is used as remote
set point
trin = The value will be added to the local set point selected
78 SP.rt Remote set point type 0 trin
by A.SP and the sum becomes the operative set point
PErc = The value will be scaled on the input range and this
value will be used as remote SP
Loc = local
79 SPLr Local/remote set point selection 0 Loc
rEn = remote
Rate of rise for POSITIVE set point
80 SP.u 2 0.01... 99.99 (inF) Eng. units per minute inF
change (ramp UP)
Rate of rise for NEGATIVE set point
81 SP.d 2 0.01... 99.99 (inF) Eng. units per minute inF
change (ramp DOWN)
]]
TIN group - Timer function parameters
Dec.
no. Param. Description Values Default
Point
NonE = Timer not used
i.d.A = Delayed start timer
i.uP.d = Delayed start at power up
82 tr.F Independent timer function 0 nonE
i.d.d = Feed-through timer
i.P.L = Asymmetrical oscillator with start OFF
i.L.P = Asymmetrical oscillator with start ON
hh.nn = Hours and minutes
83 tr.u Timer unit 0 nn.SS = Minutes and seconds nn.SS
SSS.d = Second and tenth of seconds
2 When tr.u < 20: 0.01... 99.59
84 tr.t1 Time 1 1.00
1 When tr.u = 200: 0.1... 995.9
2 When tr.u < 2: From 00.00 (oFF) to 99.59 (inF)
85 tr.t2 Time 2 1.00
1 When tr.u = 2: From 000.0 (oFF) to 995.9 (inF)
rES = Timer reset
86 tr.St Timer status 0 run = Timer run rES
HoLd = Timer hold
]]
PAn group - Operator HMI parameters
Dec.
no. Param. Description Values Default
Point
Level 2 password (limited -- oFF (Level 2 not protected by password)
87 PAS2 0 20
access level) -- 1... 200
Level 3 password (com-
88 PAS3 0 3... 200 30
plete configuration level)
Level 4 password (CODE
89 PAS4 0 201... 400 300
configuration level)
]]
Ser group - Serial link parameters
Dec.
no. Param. Description Values Default
Point
-- oFF
99 Add Instrument address 1
-- 1... 254
1200 = 1200 baud
2400 = 2400 baud
100 bAud baud rate 9600 = 9600 baud 9600
19.2 = 19200 baud
38.4 = 38400 baud
nonE = Retransmission not used (the instrument is a slave)
Selection of the value to be rSP = The instrument becomes a Master and retransmits the operati-
101 trSP ve set point nonE
retransmitted (Master) PErc = The instrument become a Master and it retransmits the power
output
]]
CAl group - User calibration parameters
Dec.
no. Param. Description Values Default
Point
107 AL.P Adjust Low Point From -1999 to (AH.P - 10) in engineering units 0
108 AL.o Adjust Low Offset -300... +300 (E.U.) 0
109 AH.P Adjust High Point From (AL.P + 10) to 9999 engineering units 9999
110 AH.o Adjust High Offset -300... +300 0