Diesel Generator Set
MTU 12V1600 DS650
590 kVA/50 Hz/Prime (Exhaust-Optimized)/380 - 415V
Reference MTU 12V1600 DS650 (650 kVA Fuel-Optimized)
for Standby Rating Technical Data
System ratings **
  Voltage (L-L)                          380V                           400V                                 415V
  Phase                                  3                              3                                    3
  PF                                     0.8                            0.8                                  0.8
  Hz                                     50                             50                                   50
  kW                                     472                            472                                  472
  kVA                                    590                            590                                  590
  Amps                                   896                            852                                  821
  skVA@30% voltage dip                   1,050                          1,200                                1,750
  Generator model                        573RSL4033                     573RSL4033                           573RSL4035
  Temp rise                              125 °C/40 °C                   125 °C/40 °C                         125 °C/40 °C
  Connection                             4 LEAD WYE                     4 LEAD WYE                           4 LEAD WYE
** Prime technical data is for an exhaust-optimized prime unit.
Certifications and standards
—— Emissions                                                                 —— Performance Assurance Certification (PAC)
   • TA-Luft certified                                                          • Generator set tested to ISO 8528-5 for transient response
—— Generator set is designed and manufactured in facilities certified           • Verified product design, quality, and performance integrity
   to standards ISO 9001:2008 and ISO 14001:2004                                • All engine systems are prototype and factory tested
—— Seismic certification – optional                                          —— Power rating
   • IBC certification                                                         • Accepts rated load in one step per NFPA 110
   • OSHPD pre-approval                                                         • Permissible average power output during 24 hours of operation
                                                                                  is approved up to 75%.
Standard features *
—— MTU is a single source supplier                                                       —— Generator
—— Global product support                                                                   • Brushless, rotating field generator
—— 2 year standard warranty                                                                 • 2/3 pitch windings
—— 12V1600 diesel engine                                                                    • PMG (Permanent Magnet Generator) supply to regulator
   • 21.0 Liter displacement                                                                • 300% short circuit capability
   • Common rail fuel injection                                                          —— Digital control panel(s)
   • 4-cycle                                                                                • UL recognized, CSA certified, NFPA 110
—— Engine-generator resilient mounted                                                       • Complete system metering
—— Complete range of accessories                                                            • LCD display
—— Cooling system
   • Integral set-mounted
   • Engine-driven fan
Standard equipment *
Engine                                                                                    Digital control panel(s)
—— Air cleaners                                                                           —— Digital metering
—— Oil pump                                                                               —— Engine parameters
—— Oil drain extension and S/O valve                                                      —— Generator protection functions
—— Full flow oil filters                                                                  —— Engine protection
—— Closed crankcase ventilation                                                           —— CANBus ECU communications
—— Jacket water pump                                                                      —— Windows®-based software
—— Thermostats                                                                            —— Multilingual capability
—— Blower fan and fan drive                                                               —— Remote communications to RDP-110 remote annunciator
—— Radiator - unit mounted                                                                —— Programmable input and output contacts
—— Electric starting motor - 24V                                                          —— UL recognized, CSA certified, CE approved
—— Governor – electronic isochronous                                                      —— Event recording
—— Base - formed steel                                                                    —— IP 54 front panel rating with integrated gasket
—— SAE flywheel and bell housing                                                          —— NFPA 110 compatible
—— Charging alternator - 24V
—— Battery box and cables
—— Flexible fuel connectors
—— Flexible exhaust connection
—— TA-Luft compliant engine
Generator
—— NEMA MG1, IEEE, and ANSI standards compliance for temperature
   rise and motor starting
—— Sustained short circuit current of up to 300% of the rated current
   for up to 10 seconds
—— Self-ventilated
—— Superior voltage waveform
—— Digital, solid state, volts-per-hertz regulator
—— No load to full load regulation
—— Brushless alternator with brushless pilot exciter
—— 4 pole, rotating field
—— 105 °C maximum prime temperature rise
—— 1-bearing, sealed
—— Flexible coupling
—— Full amortisseur windings
—— 125% rotor balancing
—— 3-phase voltage sensing
—— ±0.25% voltage regulation
—— 100% of rated load - one step
—— 5% maximum total harmonic distortion
* Represents standard product only. Consult the factory/MTU Distributor for additional configurations.        MTU 12V1600 DS650 (590 kVA) - Prime - Exhaust Opt / 02
Application data
Engine                                                                              Fuel consumption **
Manufacturer		                                        MTU                           At 100% of power rating: L/hr (gal/hr)		                                126 (33.4)
Model **		 12V1600G10F                                                              At 75% of power rating: L/hr (gal/hr)		                                  95 (25.1)
Type		                                             4-cycle                          At 50% of power rating: L/hr (gal/hr)		                                   65 (17.2)
Arrangement		                                          12-V
Displacement: L (cu in)		                         21 (1,281)                        Cooling - radiator system **
Bore: cm (in) 		                                  12 (4.72)                         Ambient capacity of radiator: °C (°F)		                                   50 (122)
Stroke: cm (in) 		                                15 (5.91)                         Maximum restriction of cooling air:
Compression ratio		                                   17.5:1                        intake and discharge side of radiator: kPa (in. H20)		                   0.2 (0.8)
Rated rpm		                                          1,500                          Water pump capacity: L/min (gpm)		                                       433 (115)
Engine governor             electronic isochronous (ADEC)                           Heat rejection to coolant: kW (BTUM)		                               225 (12,795)
Maximum power: kWm (bhp) **		                    524 (703)                          Heat rejection to after cooler: kW (BTUM)		                            121 (6,881)
Speed regulation		                                ± 0.25%                           Heat radiated to ambient: kW (BTUM)		                                52.5 (2,985)
Air cleaner		                                           dry                         Fan power: kW (hp)		                                                    25.4 (34)
Liquid capacity (Lubrication)                                                       Air requirements **
Total oil system: L (gal)				                                           73 (19.3)   Aspirating: *m3/min (SCFM)		                                            36 (1,271)
Engine jacket water capacity: L (gal)			                                65 (17.2)   Air flow required for radiator
System coolant capacity: L (gal)		                                     106 (28.1)   cooled unit: *m3/min (SCFM)		                                       803 (28,350)
                                                                                    Remote cooled applications; air flow required for
Electrical                                                                          dissipation of radiated generator set heat for a
Electric volts DC                                                             24    maximum of 25 °F rise: *m3/min (SCFM)		                                191 (6,733)
Cold cranking amps under -17.8 °C (0 °F)                                   1,050
                                                                                    * Air density = 1.184 kg/m3 (0.0739 lbm/ft3)
Fuel system
Fuel supply connection size                                  -10 JIC 37° female     Exhaust system **
                                               M20 x 1.5 male adapter provided      Gas temp. (stack): °C (°F)		                                           466 (871)
Fuel return connection size                                   -6 JIC 37° female     Gas volume at stack temp: m3/min (CFM)		                              96 (3,390)
                                               M14 x 1.5 male adapter provided      Maximum allowable back pressure at
Maximum fuel lift: m (ft)                                                  5 (16)   outlet of engine, before piping: kPa (in. H20)		                        8.5 (34.1)
Recommended fuel                                                      diesel #2
Total fuel flow: L/hr (gal/hr)                                      341.8 (90.3)
** Prime technical data is for an exhaust-optimized prime unit.                                                  MTU 12V1600 DS650 (590 kVA) - Prime - Exhaust Opt / 03
Weights and dimensions
Drawing above for illustration purposes only, based on standard open power 400 volt generator set. Lengths may vary with other voltages. Do not use for installation design.
See website for unit specific template drawings.
  System                                      Dimensions (L x W x H)                                              Weight (dry/less tank)
  Open power unit (OPU)                       3,737 x 1,899 x 2,137 mm (147.1 x 74.8 x 84.1 in)                   5,249 kg (11,572 lb)
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.
Sound data
  Unit type                                   Prime full load
  Level 0:
                                              C/F
  Open power unit: dB(A)
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust.
Emissions data                                                                             Rating definitions and conditions
  NOx + NMHC                                  CO                     PM                    —— Prime power ratings apply to installations where utility power is
                                                                                              unavailable or unreliable. At varying load, the number of generator
  C/F                                         C/F                    C/F
                                                                                              set operating hours is unlimited. A 10% overload capacity is
                                                                                              available for one hour in twelve. Ratings are in accordance with
                                                                                              ISO 8528-1, ISO 3046-1, BS 5514, and AS 2789. Average load factor:
                                                                                              ≤ 75%.
                                                                                           —— Consult your local MTU Distributor for derating information.
                                                                                                                                                                                 Subject to change. | 23568 | 2020-02
C/F = Consult Factory/MTU Distributor
N/A = Not Available
Rolls-Royce Group