800xa Outline - IO MTUs - S800 IO
800xa Outline - IO MTUs - S800 IO
DATA SHEET
DATA SHEET I/O MTUs - S800 I/O | 2023-08-25 | Copyright © 2023 ABB 1
Specific feature ¹ TU805K01 TU810V1 TU811V1 TU812V1
General info
Article number 3BSE035990R1 3BSE013230R1 3BSE013231R1 3BSE013232R1
Connection Terminal block 25 pin D-sub
Channels 16 8 16
Voltage 50 V 250 V 50 V
AI810, AI815, AI820, AI830, AI810, AI815, AI820, AI830,
AI830A, AI835, AI835A, AI845, AI830A, AI835, AI835A, AI845,
AO810, AO810V2, AO815, AO810, AO810V2, AO815,
Use with I/O DI801, DO801 AO820, AO845, AO845A, DI820, DI821, DO820, and AO820, AO845, AO845A,
DI810, DI811, DI814, DI830, DO821 DI810, DI811, DI814, DI830,
DI831, DI840, DI880, DI885, DI831, DI840, DI880, DI885,
DO810, DO814, DO815, DO810, DO814, DO840,
DO840, DO880, DP820, DP840 DO880, DP820 and DP840
2 x 2 Process power terminals 2 x 2 Process power, 5 x 2 25 pin (male) D-Sub connector
Process connections 2 x 16 Process power Process power (0 V) up to 16 I/O signals
distribution terminals
Type Compact
Mounting Both directions
Mounting detail Horizontal 55 ºC (131 °F) Horizontal 55 Cº (131 °F) Horizontal 55 ºC (131 °F)
Vertical 40 ºC (104 °F) Vertical 40 ºC (104 °F) Vertical 40 ºC (104 °F)
Single/redundant I/O Single
Dimensions
64 mm (2.52 in.) including
Width 86.1 mm connector, 64 mm (2.52 in.) including connector, 58.5 mm (2.3 in.) edge to
58.5 mm (2.3 in.) edge to edge installed
edge installed
Depth 40.5 mm 64 mm (2.52 in.) including 64 mm (2.52 in.), including terminals
terminals
Height 40.5 mm 170 mm (6.7 in.) including latch 170 mm (6.7 in.), including
latch
Weight 0.3 kg 0.17 kg (0.37 lbs)
Environment and certification
RoHS compliance EN 50581:2012
WEEE compliance DIRECTIVE/2012/19/EU
¹ For detailed information on each module, please visit: 800xahardwareselector.com
2 DATA SHEET I/O MTUs - S800 I/O | 2023-08-25 | Copyright © 2023 ABB
Specific feature ¹ TU813 TU814V1 TU818 TU819
General info
Article number 3BSE036714R1 3BSE013233R1 3BSE069209R1 3BSE068891R1
Connection Crimp Snap-in connector Terminal block 25 pin D-sub
Channels 8 16 32
Voltage 250 V 50 V
AI810, AI815, AI820, AI830,
AI835A, AI835, AI845, AO810,
AO810V2, AO815, AO820, AI810, AI815, AI835A, AI843,
Use with I/O DI820, DI821, DI825, DO820, AO845, AO845A, DI810, DI811, AI845, AI880A, DI810, DI811, DI818 and DO818
DO821 and AI825 DI814, DI830, DI831, DI840, DI818, DI830, DI831, DI840,
DI880, DI885, DO810, DO814, DI880, DI885, DO818, DP840
DO815, DO840, DO880,
DP820 and DP840
30 Two D-sub connectors 25 pin
Process connections 16 up to 16 I/O channels 40 pole screw terminal (male)
2 x 2 Process power up to 32 I/O signals
2 x 5 Process power (0 V)
Type Compact
Mounting Both directions
Mounting detail Horizontal 55 ºC (131 °F)
Vertical 40 ºC (104 °F)
Single/redundant I/O Single Single
Dimensions
Width 64 mm (2.52 in.) including connector, 58.5 mm (2.3 in.) edge to edge installed
Depth 64 mm (2.52 in.), including terminals
Height 170 mm (6.7 in.) including latch
Weight 0.17 kg (0.37 lbs)
Environment and certification
RoHS compliance EN 50581:2012
WEEE compliance DIRECTIVE/2012/19/EU
¹ For detailed information on each module, please visit: 800xahardwareselector.com
DATA SHEET I/O MTUs - S800 I/O | 2023-08-25 | Copyright © 2023 ABB 3
Specific feature ¹ TU830V1 TU831V1 TU833 TU834
General info
Article number 3BSE013234R1 3BSE013235R1 3BSE038726R1 3BSE040364R1
Connection Terminal block Crimp Snap-in connector Terminal block
Channels 16 8 16 8
Voltage 50 V 250 V 50 V
AI810, AI815, AI820, AI830, AI810, AI815, AI820, AI830,
AI830A, AI835, AI835A, AI843, AI830A, AI835, AI835A, AI843,
AI845, AO810, AO810V2, AI845, AO810, AO810V2,
AO815, AO820, AO845, DI820, DI821, DO820, and AO815, AO820, AO845,
Use with I/O AO845A, DI810, DI811, DI814, DO821 AO845A, DI810, DI811, DI814, AI880 and AI880A
DI818, DI830, DI831, DI840, DI830, DI831, DI840, DI880,
DI880, DI885, DO810, DO814, DI885, DO810, DO814, DO815,
DO815, DO818, DO840, DO840, DO880, DP820 and
DO880, DP820 and DP840 DP840
56 40
16 up to 16 I/O channels (2 up to 8 I/O channels (2
Process connections 56 up to 8 I/O channels terminals per channel) terminals per channel)
(2 terminals per channel) 4 Process power 6.3 A 4 Process power
10 x 2 Process power (0 V) 20 Process power (0 V)
Type Extended
Mounting Both directions
Mounting detail 55 ºC (131 °F)
Single/redundant I/O Single
Dimensions
126 mm (5 in.) including 126 mm (5 in.) including 126 mm (5 in.) including 126 mm (5.0 in.) including
Width connector, 120.5 mm (4.74 in.) connector, connector, 120.5 mm (4.74 in.) connector, 120.5 mm (4.74 in.)
edge to edge installed 120.5 mm (4.74 in.) edge to edge to edge installed edge to edge installed
edge installed
Depth 64 mm (2.52 in.) including terminals
Height 110 mm (4.3 in.) 105 mm (4.1 in.) 110 mm (4.3 in.) including
locking device
Weight 0.28 kg (0.6 lbs) 0.22 kg (0.48 lbs) 0.28 kg (0.6 lbs)
Environment and certification
RoHS compliance EN 50581:2012
WEEE compliance DIRECTIVE/2012/19/EU
¹ For detailed information on each module, please visit: 800xahardwareselector.com
4 DATA SHEET I/O MTUs - S800 I/O | 2023-08-25 | Copyright © 2023 ABB
Specific feature ¹ TU835V1 TU836V1 TU837V1 TU838
General info
Article number 3BSE013236R1 3BSE013237R1 3BSE013238R1 3BSE008572R1
Connection Terminal block
Channels 8 16
Voltage 50 V 250 V 50 V
AI810, AI815, AI845, DI810,
Use with I/O AI810, AI815 and AI845 DO820, and DO821 DI811, DI814, DI830, DI831,
DI840 and DO814
16 28 40
up to 8 I/O channels up to 8 I/O channels up to 16 I/O channels
Process connections (2 terminals per channel) (2 terminals per channel) 8 fused sensor power outlets
4 Process power 2 x 6 power common 4 Process power
4 Process power (0V) terminals 12 Process power (0 V)
Type Extended
Mounting Both directions
Mounting detail 55 ºC (131 °F)
Single/redundant I/O Single
Dimensions
Width 126 mm (5 in.) including connector, 120.5 mm (4.74 in.) edge to edge installed
Depth 64 mm (2.52 in.) including terminals
Height 110 mm (4.3 in.)
Weight 0.26 kg (0.57 lbs)
Environment and certification
RoHS compliance EN 50581:2012
WEEE compliance DIRECTIVE/2012/19/EU
¹ For detailed information on each module, please visit: 800xahardwareselector.com
DATA SHEET I/O MTUs - S800 I/O | 2023-08-25 | Copyright © 2023 ABB 5
Specific feature ¹ TU839 TU842 TU843 TU844
General info
Article number 3BSE046966R1 3BSE020850R1 3BSE021443R1 3BSE021445R1
Connection Terminal block
Channels 8 16 8
Voltage 250 V 50 V
Use with I/O DI820, DI821and DI825 AI843, AO845, AO845A, DI840, DI880, DO840, DO880 and AI845, AI880, AI880A and
DP840 DP840
28 56 up to 16 I/O channels (2 56 up to 16 I/O channels (2 40 up to 8 I/O channels (2
up to 8 I/O channels terminals per channel), 4 terminals per channel) terminals per channel)
Process connections (2 terminals per channel) Process power, 20 Process 4 Process power 4 Process power
2x6 Process Power terminals power (0 V) 20 Process power (0 V) 20 Process power (0 V)
0.2 A
Type Extended Redundant
Mounting Both directions Horizontal Vertical Horizontal
Mounting detail 55 ºC (131 °F) 55 º (131 °F)
Single/redundant I/O Single Redundant
Dimensions
126 mm (5 in.) including 131 mm (5.16”) including
Width connector, 120.5 mm (4.74 in.) connector, 131 mm (5.16”) including connector, 124 mm (4.88”) edge to
edge to edge installed. 124 mm (4.88”) edge to edge edge installed
installed
Depth 64 mm (2.52 in.) including 64 mm (2.52”) including terminals
terminals
Height 110 mm (4.3 in.) 186.5 mm (7.34”) including locking device
Weight 0.28 kg (0.6 lbs) 0.6 kg (1.3 lbs.)
Environment and certification
RoHS compliance EN 50581:2012
WEEE compliance DIRECTIVE/2012/19/EU
¹ For detailed information on each module, please visit: 800xahardwareselector.com
6 DATA SHEET I/O MTUs - S800 I/O | 2023-08-25 | Copyright © 2023 ABB
Specific feature ¹ TU845 TU850 TU851 TU852
General info
Article number 3BSE021447R1 3BSE050930R1 3BSE068782R1 3BSE069964R1
Connection Terminal block 25 pin D-sub
Channels 8 16
Voltage 50 V 250 V 50 V
Use with I/O AI845, AI880, AI880A and AI810, DI810, DI811,DI830, DI820, DI821, DI825, DI828, AI843, AO845A, DI840, DI880,
DP840 DI831 DO820, DO821, and DO828 DO840, DO880 and DP840
40 up to 16 I/O channels
40 up to 8 I/O channels (2 16 current limited 16 up to 16 I/O channels (2
Process connections terminals per channel) sensor/transmitter power 32 up to 16 I/O channels terminals per channel), Two
4 Process power outlets D-sub connectors 25 pin
20 Process power (0 V) D-sub connectors 25 pin (male)
(male)
Type Redundant Extended Redundant
Mounting Vertical Both directions Horizontal
Mounting detail 55 º (131 °F)
Single/redundant I/O Redundant Single Redundant
Dimensions
131 mm (5.16”) including 126 mm (5 in.) including connector, 120.5 mm (4.74 in.) edge to 131 mm (5.16 in.) including
Width connector, 124 mm (4.88”) edge installed connector, 124 mm (4.88 in.)
edge to edge installed edge to edge installed
Depth 64 mm (2.52”) including 64 mm (2.52 in.) including terminals
terminals
Height 186.5 mm (7.34”) including 110 mm (4.3 in.) 186.5 mm (7.34 in.) including
locking device locking device
Weight 0.6 kg (1.3 lbs.) 0.26 kg (0.57 lbs) 0.22 kg (0.48 lbs) 0.55 kg (1.2 lbs)
Environment and certification
RoHS compliance EN 50581:2012
WEEE compliance DIRECTIVE/2012/19/EU
¹ For detailed information on each module, please visit: 800xahardwareselector.com
DATA SHEET I/O MTUs - S800 I/O | 2023-08-25 | Copyright © 2023 ABB 7
Specific feature ¹ TU854 TU890 TU891
General info
Article number 3BSE069966R1 3BSC690075R1 3BSC840157R1
Connection 25 pin D-sub Terminal block
Channels 16 8
Voltage 50 V 24 V
Use with I/O AI845, AI880A and DP840 AI890, AI893, AI895, AO890, AO895, DI890, DO890
up to 8 I/O channels (2 terminals per
Process connections channel) 27 blue terminals 27 gray terminals
D-sub connector 25 pin (male)
Type Redundant Compact
Mounting Horizontal
Mounting detail 55 ºC (131 °F) 55 º (131 °F) 55 ºC (131 °F)
Single/redundant I/O Redundant Single
Dimensions
131 mm (5.16 in.) including connector,
Width 124 mm (4.88 in.) edge to edge 64 mm (1.77 in.) including connector, 58.5 mm (2.3 in.) edge to edge installed
installed
Depth 64 mm (2.52 in.) including terminals 58 mm (2.28 in.), 106 mm (4.2 in.) including terminals
Height 186.5 mm (7.34 in.) including locking 194 mm (7.6 in.) including latch
device
Weight 260 g (9.17 oz) 0.17 kg (0.37 lbs.) 0.17 kg (0.37 lbs)
Environment and certification
RoHS compliance EN 50581:2012
WEEE compliance DIRECTIVE/2012/19/EU
¹ For detailed information on each module, please visit: 800xahardwareselector.com
8 DATA SHEET I/O MTUs - S800 I/O | 2023-08-25 | Copyright © 2023 ABB
— —
solutions.abb/800xA 800xA and Symphony Plus is a We reserve all rights to this
solutions.abb/controlsystems registered trademark of ABB. All document and the items and images
rights to other trademarks reside it contains. The reproduction,
with their respective owners. disclosure to third parties or the use
of the content of this document –
We reserve the right to make including parts thereof – are
technical changes to the products or prohibited without ABB’s prior
modify the contents of this written permission.
document without prior notice. With
regard to purchase orders, the Copyright© 2023 ABB All rights
agreed particulars shall prevail. ABB reserved
does not assume any responsibility
for any errors or incomplete
information in this document.