Preventive Maintenance Motor Summary

The document outlines a preventative maintenance schedule for an electric motor over various time intervals: daily/weekly, monthly, three-monthly, six-monthly, annually, five years, and 15 years. It includes checking measurements like temperature, vibration and insulation levels, performing visual inspections, cleaning, testing, and replacing components like bearings, seals, and insulation. The goal is to monitor the motor's performance and condition over time through scheduled inspections and maintenance.

Uploaded by

alnaggar.amro
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
135 views10 pages

Preventive Maintenance Motor Summary

The document outlines a preventative maintenance schedule for an electric motor over various time intervals: daily/weekly, monthly, three-monthly, six-monthly, annually, five years, and 15 years. It includes checking measurements like temperature, vibration and insulation levels, performing visual inspections, cleaning, testing, and replacing components like bearings, seals, and insulation. The goal is to monitor the motor's performance and condition over time through scheduled inspections and maintenance.

Uploaded by

alnaggar.amro
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

Preventive maintenance Schedule for electric motor

Daily / Weekly PM
DATE / / 2021 Motor Tag: PM-7001A Location: UNITY FPF

• Electrical Measurement recording (or use recording measurement device)

Recommended
I 1 I 2 I 3 Unbalance ratio Comment
value

10 %

Recommended
V 1 V 2 V 3 Unbalance ratio Comment
value

2%

Power factor Frequency Power Comment

• Temperature measurement recording (or use recording measurement device)

Drive end bearing Non-Drive end Motor frame Ambient


Comment
temperature bearing temperature temperature temperature

First Phase Second Phase Third Phase


Insulation class Comment
Wdg Temp. Wdg Temp. Wdg Temp.

• Vibration measurement recording (or use recording measurement device)

Motor overall Recommended Bearing drive end Bearing non drive Recommende
Comment
vibration value vibration end vibration d value

4.45 mm/sec 4 gE
• Visual Inspection

Points to inspect Checked (√) Comment

Rust / corrosion parts

Missing bolts

Earthing cable connection

ventilation fan

Abnormal sound
Preventive maintenance Schedule for electric motor
Monthly PM

DATE / / 2021 Motor Tag: PM-7001A Location: UNITY FPF

Points to inspect Checked (√) Comment

Cleaning motor enclosure

Thermal image recording

Online Partial discharge test


Preventive maintenance Schedule for electric motor
Three Monthly PM

DATE / / 2021 Motor Tag: PM-7001A Location: UNITY FPF

Points to inspect Checked (√) Comment

Greasing motor bearing

Motor Alignment check

Coupling connection

Check on Earthing cable


connection tighten and
greasing

Preventive maintenance Schedule for electric motor


Six Monthly PM

DATE / / 2021 Motor Tag: PM-7001A Location: UNITY FPF

Points to inspect Checked (√) Comment

Bearing vibration testing

Preventive maintenance Schedule for electric motor


Annual PM
DATE / / 2021 Motor Tag: PM-7001A Location: UNITY FPF

• Insulation evaluation testing

DAR Test Recommendation value Comment

Greater than 1.4

PI Test Recommendation value Comment

Greater than 4

DD Test Recommendation value Comment

Smaller than 2

Tan δ test Recommendation value Comment

0 to 0.005

HI-POT Test Recommendation value Comment

MΩ or GΩ
(100 mA Max.)

Surge Test Recommendation value Comment

LL EAR <10%
PP EAR <5%
Inductance test Recommendation value Comment

Trend values over time

Cu winding test Recommendation value Comment


Unbalance Smaller
than 3%

Capacitance test Recommendation value Comment

Trend values over time

• Tasks Inside switchgear and motor Junction box

Points to inspect Checked (√) Comment

Cleaning the MCC

Check on circuit breaker, fuses,


contactor mechanism and coil,
overload
Don’t use WD40 for electrical
contact Only mechanism
lubrication)
Earthing connection inside
switchgear

Revise protection setting

Tighten all control and power wiring

Make function check

Check on Junction box sealing


(gasket) and gland connection,
Earthing point
Check on any auxiliary circuit for
motor as RTD for bearing or
winding temperature, Vibration
sensor , space heater , internal
thermistor

Tighten power cable to motor


terminals
Check on sealing between Junction
box Terminals and motor enclosure
(Opening for wiring through)
Check on fan connection tighten and
fan blades for any damage or loose

Tighten motor mounting base , and


also check for coupling tighten , also
IP seal for motor shaft

• Insulation resistance test IR for Cable and motor from switchgear side

IR test Recommendation value Comment

MΩ or GΩ
Preventive maintenance Schedule for electric motor
Five years Overhaul

DATE / / 2021 Motor Tag: PM-7001A Location: UNITY FPF

Points to inspect Checked (√) Comment

Replace the shaft bearing

Replace Bearing inner and


outer seal

Replace Front and End shield


sealing

Replace Junction box sealing

Replace inner sealing between


junction and motor body
(internal Wiring opening)
Check on uniformity for Stator
core slots and lamination, and
perform Lamination core test

Check on rotor balancing

Check for aluminum bar


continuity

Check for any deformation for


bearing housing

Replace Ventilation fan and it


is sealing
Preventive maintenance Schedule for electric motor
15 years Overhaul

DATE / / 2021 Motor Tag: PM-7001A Location: UNITY FPF

Points to inspect Checked (√) Comment

Sandblasting process

painting for motor frame

Cleaning and washing stator


winding using pressure steam
or electrical solvent to remove
any contamination or dirties

Dryness stator winding using


hot furnace

Increase Insulation of stator


winding

Replace all connection bolts