DDSU666 Energy Meter Operation Manual
DDSU666 Energy Meter Operation Manual
1. Brief Introduction
1.1 Main application & applicable range
Type DDSU666 single phase electronic energy meter (din-rail) (hereinafter referred to as the
“instrument”) is designed based on power monitoring and energy metering demands for electric power
system, communication industry, construction industry, etc. as a new generation of intelligent
instrument combining measurement and communication function, mainly applied into the
measurement and display for the electric parameters in the electric circuit including voltage, current,
power, frequency, power factor, active energy, etc. The network can be realized through RS485
communication interface and external device. Adopting the standard DIN35mm din rail mounting and
modular design, it is characterized with small volume, easy installation and easy networking, widely
applied into the internal energy monitoring and assessment for industrial and mining enterprises, hotels,
schools, large public buildings.
Complied standards:
IEC62052-11 《 Electricity metering equipment(AC)-General requirements, tests and test
conditions- Part11:Metering equipment 》;
IEC62053-21《Electricity metering equipment(AC)-Particularrequirements-Part21: Static meters
for active energy(classes 1 and 2)》;
MODUS-RTU protocol.
1.2 Product Features
1) Metering the positive and negative active power;
2) Adopting wide LCD, it has clear vision.
3) RS485 communication function with communication protocol complied with Modbus-RTU;
4) Adopting DIN35mm standard din rail mounting, structural modular design, it is characterized
with small volume, easy installation and easy networking.
DDSU666.004.0006 type single phase electronic energy meter(DIN-Rail) ZTY0.464.1036
Operation manual Page 2, Total 21
5(80)A : ZTY8.067.2729V2、ZTY8.067.2730V2
(Note: the actual plate number is determined according to the actual
sample table)
Current transformer ZTY6.176.301
4. Main functions
4.1 Metering function
1) Accurately metering the positive and negative active power;
2) The storage data of the electric energy meter will not lost after powering off.
4.2 Displayed functions
When the energy meter is in normal working condition (on load state), the positive pulse indicator
should be flashed. If long time for no flashing or light for the indicator, please check whether the
wiring mode of the energy meter is right or not.。
W The unit of the active power, the display data of indicating LCD is
active power
var The unit of the reactive power, the display data of indicating LCD
is reactive power
DDSU666.004.0006 type single phase electronic energy meter(DIN-Rail) ZTY0.464.1036
Operation manual Page 6, Total 21
Keyboard operation: After pressing the button for a long time, the display interface
enters the switching interface of setting 645 protocol and Modbus protocol. Shortly
press can switch the protocol, not the address page (only the ModBus protocol can be
switched to the address page), the address of ModBus can be set by the button, the button
can set the address range 1-99.
0.5mm2 . On wiring arrangement, the communication line shall be away from strong cable or other
strong electric field with the maximum transmission distance to be 1200m. For the typical networking
connection mode, please see the below figure, users can select other suitable connection mode based
on detailed conditions.
DDSU666.004.0006 type single phase electronic energy meter(DIN-Rail) ZTY0.464.1036
Operation manual Page 9, Total 21
Length
Parameter Read&write
Parameter code Instruction of the parameters Type of data of data
address attributes
Word
16-bit with
0000H UCode Programming password codE 1 R/W
symbols
Reserved, actual read is the 16-bit with
0001H REV. 1 R
version number symbols
Electric energy zero clearing 16-bit with
0002H ClrE 1 R/W
CLr.E(1:zero clearing) symbols
DDSU666.004.0006 type single phase electronic energy meter(DIN-Rail) ZTY0.464.1036
Operation manual Page 10, Total 21
16-bit with
0003H RESERVED RESERVED 1
symbols
16-bit with
0004H RESERVED RESERVED 1
symbols
16-bit with
0005H ChangeProtocol Protocol changing-over 1 R/W
symbols
16-bit with
0006H Addr Communication address Addr 1 R/W
symbols
16-bit with
0007H RESERVED 1
Urat symbols
16-bit with
0008H RESERVED 1
Irat symbols
16-bit with
0009H RESERVED RESERVED 1
symbols
16-bit with
000AH RESERVED RESERVED 1
symbols
16-bit with
000BH RESERVED RESERVED 1
symbols
Communication baud rate 16-bit with
000CH BAud 1 R/W
bAud symbols
16-bit with
000DH RESERVED RESERVED 1
symbols
16-bit with
000EH RESERVED RESERVED 1
symbols
16-bit with
000FH RESERVED RESERVED 1
symbols
16-bit with
0010H RESERVED RESERVED 1
symbols
DDSU666.004.0006 type single phase electronic energy meter(DIN-Rail) ZTY0.464.1036
Operation manual Page 11, Total 21
single precision
2008H RESERVED RESERVED 2 R
floating decimal
single precision
200AH PF Conjunction power factor 2 R
floating decimal
single precision
200CH RESERVED RESERVED 2 R
floating decimal
single precision
200EH Freq Frequency 2 R
floating decimal
single precision
2010H RESERVED RESERVED 2 R
floating decimal
Electrical data of the secondary side
single precision
4000H Ep Active in electricity 2 R
floating decimal
ChangeProtocol such as protocol switching, data for 2 for Modbus RTU protocol -, data to 1 for DL/T
645-2007;
The CLr. E power reset write 1 removal of total power;
BAud rate: 1:2400bps; 2:4800bps; 3:9600bps;;
4.4 Outline &Mounting Dimension
Outline dimension: 36mm×98mm×65mm;
DDSU666.004.0006 type single phase electronic energy meter(DIN-Rail) ZTY0.464.1036
Operation manual Page 12, Total 21
Figure 5 Configuration
6. Installation & Operation Instruction
6.1 Inspection
1) Before installation, firstly check whether the model No. and specification of the product on the
package is the same as the object. If not, please contact the supplier.
2) Check whether the product shell in the carton is damaged, if is, please contact the supplier.
6.2 Installation
Directly clip the instrument on the rail and install it on the distribution box.
1)When installing, firstly clip one terminal of the slot and then clip to the rail with power.
2)When disassembling, press the movable card with a screwdriver and take out the instrument.
6.3 Wiring mode
6.3.1 Instruction of wiring terminal
Before powering, you must check whether the wiring mode of the instrument is correct, and the
wiring diagram is shown as below:
DDSU666.004.0006 type single phase electronic energy meter(DIN-Rail) ZTY0.464.1036
Operation manual Page 13, Total 21
safety of human
life.
circumstance of that the users fully comply with this instructions and complete seal after delivery within 18 months.
DDSU666.004.0006 type single phase electronic energy meter(DIN-Rail) ZTY0.464.1036
Operation manual Page 15, Total 21
Function
Definition Operation
code
03H Read register Read one or several register data
Write multichannel
10H Write n 16-bit binary data into n continuous registers
register
A.2.3 Data area
The data field will be different based on different function codes. These data can be numerical
DDSU666.004.0006 type single phase electronic energy meter(DIN-Rail) ZTY0.464.1036
Operation manual Page 17, Total 21
values, reference addresses and so on. For different slave computers, both the address and data
information are different, and the communication information table should be provided.
The host utilizes communicate command (function code 03H and 10H) to read and modify the
data registers of the slave freely. But the data length which is read or write at one time should not be
out of the effective range of the data register’s address.
A.3 Brief introduction of function code
A.3.1 Function code 03H:Read register
For example: The slave address which the host intends to read is 01H, the start register address is two
register data of 0CH, sent by the host:
Table A.3
The host sends Send message
Address code 01H
Function code 03H
High byte 00H
Start register address
low byte 0CH
High byte 00H
Register number
low byte 02H
low byte 04H
CRC 校验码
High byte 08H
If the data of the slave register 0CH, 0DH is 0000H, 1388H, the slave will return:
Table A.4
The slave returns Return message
Address code 01H
code) according to the above steps, the content of the CRC register to be get is: 16-digit CRC check
code.
A.5 Error handling
When the meter detects other errors except the error of CRC check code, the information will be
returned to the host, the highest digit of the function code is 1, i.e. the function code returned to the
host from the slave is adding 128 base on the function code sent from the host. The error returned from
the slave is as follows:
Table A.7
Address Function code(top CRC check code CRC check code
Error code
code digit is 1) low byte High byte
1 byte 1 byte 1 byte 1 byte 1 byte
Dear clients,
Please assist us: when the product life is end, to protect our environment, please recycle the product or
components, while for the materials that cannot be recycled, please also deal with it in a proper way. Really
Zip Code:325603
Telephone:0577-62877777
Fax:0577-62891577
Technical hotline:0577-62919999
Email:ztyb@chint.com
Date of Issue: May, 2019.
No.: ZTY0.464.1224V1