3-WAY ECO-i SYSTEM
1. Simple Settings Function Remote Controller Functions
• This allows the filter lifetime, operating mode [Remote Controller Functions Section]
priority change, central control address, and other
settings to be made for an individual or group- 2
control indoor unit to which the remote controller
used for simple settings is connected.
When simple settings mode is engaged, operation
stops at the individual or group-control indoor unit
to which the remote controller for simple settings is
connected.
<Procedure>
Fig. 7-1 3
➀ Press and hold the and buttons
simultaneously for 4 seconds or longer.
➁ “ ,” unit No. “ ” (or “ ” in the case of 7
group control), item code “ ,” and settings data
“ ” are displayed blinking on the remote
4
controller LCD display (Fig. 1). At this time, the
indoor unit fan (or all indoor unit fans in the case of
group control) begins operating.
1 6 5 RCS-TM80BG
➂ If group control is in effect, press the
button and select the address (unit No.) of the
Fig. 1
indoor unit to set. At this time, the fan at the indoor
unit begins operating.
* If unit No. “ ” is displayed, the same setting
4 will be made for all indoor units.
➃ Press the temperature setting /
buttons to select the item code to change.
➄ Press the timer time / buttons to select the
desired setting data.
* For item codes and setting data, refer to the
following page.
➅ Press the button. (The display stops blinking
and remains lit, and setting is completed.)
➆ Press the button to return to normal remote
controller display.
4-2
SM830171-00.indb 2 2008/11/12 18:09:01
3-WAY ECO-i SYSTEM
1. Simple Settings Function Remote Controller Functions
List of Simple Setting Items
Setting data
Item code Item
No. Description
0000 Not displayed
0001 150 hours
Filter sign ON time 0002 2,500 hours
(fitlter life time) 0003 5,000 hours
0004 10,000 hours
0005 Use the filter clogging sensor.
0000 Standard (setting at time of shipping)
Degree of filter fouling Highly fouled
0001
(Filter sign ON time is reduced to one-half the set time.)
0001 Central control address 1
0002 Central control address 2
0003 Central control address 3
Central control
address
0064 Central control address 64
0099 No central control address set (setting at time of shipping)
Operating mode 0000 Normal (setting at time of shipping)
priority change 0001 Priority
Compressor ON Compressor OFF
0000 MED 1 min., LO 3 min. LO
Fan speed when 0001 MED LO
heating thermostat is 0002 LO LO
OFF 0004 MED 1 min., LO 3 min. MED
0005 MED MED
0006 LO MED
0000 No shift 4
0001 Shifts intake temperature 1°C down.
0002 Shifts intake temperature 2°C down.
Heating intake 0003 Shifts intake temperature 3°C down.
temperature shift
0004 Shifts intake temperature 4°C down.
0005 Shifts intake temperature 5°C down.
0006 Shifts intake temperature 6°C down.
Electric heater 0000 No heater
installation 0001 Heater installed
Humidifying when 0000 No (setting at time of shipping)
heater thermostat is
OFF 0001 Yes
Permit/prohibit 0000 Permit
automatic
heating/cooling 0001 Prohibit
0000 Normal
Cool-only
0001 Cool only (Set “1” for item code OD.)
NOTE
• In order to avoid water leakage and damage to the fan, do not set for humidifying when the thermostat is OFF unless a
vaporizing humidifier is used.
• Consider the device purpose and type when changing the settings. Incorrect settings may result in malfunction.
• Do not change any setting data that does not appear in this list.
4-3