100%(1)100% found this document useful (1 vote) 701 views23 pagesNFPA - Concepts of Egress Design
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
SECTION 4
Concepts of Egress Design
James K, Lathrop
cans of egress and their design should be based on an evaluation ofa building's total fire pro-
{ection system and an analysis ofthe population characteristics and hazards (othe occupants
of that building. The means of egress design should be treated as an integral part ofthe total system
that provides reasonable lite safety from fire
‘This chapter covers the fundamental concepts of good egress design that are the basis for
NEPA 101°, Life Safety Code®, and NFPA S00, Building Construction and Safety Code®. NFPA
101 governs good practices to provide life safety features in existing buildings and structures and.
features that can be designed as integral parts of new construction to provide reasonable safety to
‘occupants in fires. NFPA 5000 adresses new construction only, but covers life safety from many
hhazards in addition to fire. The components of good means of egress are discussed in some det
‘with their functions and relationships in the total concept of proper egress design, Computer model-
ing and simulation to assist the egress design process also ae discussed
Sec also Section 4, Chapter I, “Human Behavior and Fite”; Section 4, Chapter 2, “Caleulation
“Methods for Bgress Prediction”; Section 4, Chapter 5, “Strategies for Occupant Evacuation During
Emergencies"; and Section 20, Chapter 1, “Assessing Life Safety in Buildings
FUNDAMENTALS OF DESIGN
‘The approach to designing means of egress frst requires a familiarity with the reactions of people
infie emergencies. These reactions can differ widely, depending onthe physical and mental capa-
bites and conditions of building occupants. The psychological and physiological factors alfecting
the use of exits during emergencies are being identified and measured in esearch studies. Dr. Tohn
L, Bryan discusses in detail behavioral response to fire and smoke in Section 4, Chapter I of this
book!
Patterns of movement of people, singly and in crowded conditions, must also be understood,
In buildings used as schools or theaters howsing highly mobile occupants, for example, there are
certain reproducible flow characteristics from persons exiting te buildings. These predictable low
characteristics have fostered computer simulation and modeling to aid the egress design process.
However, no number of practical exit facilities can prevent injury or loss of life if the occupant
gress flow is inhibited or prevented by the bulng itself, by personel, or by fire and smoke con-
ditions. An in-depth review of movement of people by Proulx can be found in Section 3. Chapter
13 of the SEPE Handbook of Fire Protection Engincering” as well a in “Emergency Movement”
by Nelson and Mowrer in Section 3, Chapter 14, ofthe same document
Human Factors
‘The design and capacity of doors, passageways, stairways, and other components in the total means
‘of egress ate related tothe physical dimensions of the buman body. The tendency of people to avoid
bodily contact with others should be recognized as a major factor in determining the number of
ames K, Lathrop, FSFPE, ss vice-president ofthe frm Koifel Associates of Elkridge, Maryland, and Niantic,
‘Connecticut. He i+ member of the Technical Committees on Fundamentals, Boaré and Care Occupancies,
Residential Oeeupances, and NEPA'S Unyorm Fire Code™, He is also a alternate on the Techies! Com
nite on Furmshings and Contents andthe Technicel Commitee on Fire Tess, He i chair of the Technicel
(Consnitte oa Means of Egress andthe Technical Committe on Pyrotechnics
4-694-70 SECTION 4 | Human Factors in Emergencies
persons who will occupy a given space at any given time. Given
a choice, people usually automaticaly establish “territories” to
avoid bodily contact with others.
Studies have shown that most adult men measure less than
20.7 in. (520 mm) across at the shoulder, with no allowance for
‘ditional thicknesses of clothing.* A “body ellipse” concept
is used to develop the design of pedestrian systems. The major
axis of the body ellipse measures 24 in. (609 mm), whereas
the minor axis is 18 in. (457 mm). This ellipse equals 2.3 £¢
(0.21 m?), which is assumed to help determine the maximums
practical standing capacity of a space.
‘The movement of persons results in a swaying action that
varies from male to female and, depending on the type of mo-
tion, varies with movement on stairs, on level surfaces, or in
dense crowds. Body sway has been observed to range 1% in.
(@8 mm) left and right during normal free movement. Where
‘movement is reduced to shuffling in dense crowds and to move-
iment on stairs, a total sway range of almost 4 in, (101 mm) has
been observed. In theory, this indicates that a total width of
30 in. (762 mm) would be required to accommodate a single
file of pedestrians traveling up or down stairs.>
Crowding people into spaces where less than 31° (0.28 m?)
of space per person is available under nonemergency conditions
‘may creates hazard. When the average area occupied per person
is reduced to 2% ft (0.25 m) or less, contact will be unavoid-
able, Needless to say, under the psychological stesses imposed
during a fire, such crowding and contact could contribute to
crowd pressures, resulting in injuries, When a queue occurs be-
cause of an artificial temporary situation or because of some
[permanent design feature, crowd control becomes difficult, and
the well-being of individuals is threatened,
Factors Affecting Movement of People
‘There are several factors that determine how quickly people
may passthrough the means of egress
In level walkways an average walking speed of 250 fin
(1.26 msec) is attained under free-flow conditions, with 25 £2
(2.3 m?) of space available per person, Speeds below 145 fi
min (0.73 msec) show shuffling, which restricts motion, Fig-
ure 4.3.1, adapted from Research Report No. 95 of the London
“Transport Board, shows the rate of speed reduction for space
concentrations of ess than 7 (0.65 me) per person, Speeds of
Jess than 145 fein (0.73 m/sec) resultin shuffling, and, finally
1 jam point is reached with one person every 2 ft2(0.18 m). The
possibilty of a significant nonadaptive behavior exists when-
ever egress movement is restricted, and the problem becomes
urgent under fre exposure conditions, especially when there is
more than one person every 3 (0.28 m?)
Calculations of flow rates using velocity (/min [mlsec))
and density (persoas/f® [m¢) will reveal flow (persons/minit
[persons/sec/m] of width), which increases as the pedestrian
ea decreases, The flow inereases will continue until forward
‘movement becomes restricted tothe point that the flow begins
to dtop. Interestingly, observations of flow rates in one study
noted the same flow rate sometimes accurred even though walk-
ing speeds of people were significantly different, Investigation
revealed that te rate of decrease in speed, accompanied by an
‘Speed
{emp om)
4782)
(rin) oon)
069 64
NTE
Flow imagined tobe
ey (1
Shing bteongers
toa stop <=‘
Y
om \
48
(63) 132
en
sam pois
{reaeieg)” ~~,
020 W780 a8 a28 20
Concantatin per person)
FIGURE 4.3.1 Speed in Level Passageways (SI nits:
41min = 0305 m/min; 1 £2 = 0.093 m!)
increase in densily, results in uniform flow rales over a wide
range of conditions.
‘A study of passageways indicates that for passageways
over 4 ft (1.2 m) wide, flow rates are directly proportional to
width, The London Transport Board Research Report No, 95°
determined the flow rate in level passages to be 27 persons!
rin/ft (1.5 persons/see/m) of width, Travel down stairways was
determined at 21 persons/ming/ft (1.2 persons/secim) of width,
whereas upward travel was reduced (0 19 persons/minift (1.1
ppersons/seclm) of width, Where the width of a footway is less
than 4 ft (12 m), the flow rate depends upon the number of pos-
sible traffic lanes, Absolute maximum flow rates occur when
approximately 3 £2 (0.28 m?) is occupied per person, which is
applicable to both level walkways and stairs, In observed and
‘measured evacuations, however, it has been empirically deter-
rined that the maximum flow sates down staits in high-tise
buildings occur when from 4 to $ fof space (0.37 to 0.46 m*)
is occupied per person, as shown in Figure 4,3,2.° When flow in
‘opposite directions takes place in a passageway up to the point
where the two flows are of equal magnitude, chet is no signifi
cant reduction in toll flow below that which would be predicted
fn the basis of unidirectional flow in the same passageway.
Further, flow can be 50 percent greater in short passage-
ways less than 10 ft (3.05 m) long than through along passage-
‘way ofthe same width, Minor obstructions within a passageway
do not appear to have a significant effect on flow. Within a 6-f
(.82-m) wide passageway, there is no effect on flow rates when
1 ££ (0.35 m) projection is introduced. A 2 f (0.61 m) projec-
tion resulting in a 33 percent reduction in width reduces the flow
rate by approximately 10 percent. A major obstruction, though,
such as that which occurs ata ticket booth or turnstile, may in-
terrupt the movement of people and reduce flow rates.
Corners, bends, and slight grades up to 6 percent are appar-
enlly not factors in determining flow rates. A slight reduction in
speed does occur, bt the flow rate is maintained by an increased
conceattation of persons.CHAPTER 3 Concepts of Egress Design 4-71
80
B «0 4
Es
g:% 4
se
RB a 4
PB
3 10 4
°
‘oor oe 0s
Mean density stairway, persontt®
FIGURE 4.3.2 Eifect of Density on Flow Down Exit
Stairways in Evacvations of High-Rise Oftice Buildings
(0.093 m?)
Accenter handrail or mullion, which may divide a passage:
‘way into narrower sections, can further zeduce the capacity of
the passageway. The observed capacity of a 6-f¢(1.82-m) wide
stairway reveals a reduction from 130 to 105 persons/min after
installation of a center handrail
‘Except forthe very young and the very old, age does not ap-
pear to bea significant factor in determining travel speed. Studies
hhave shown a significant reduction in walking speeds for per
sons over 65 yeats of age. Studies have further revealed that 40
percent increase is possible in the normal walking speed, which
tends to discount this factor as a major influence on flow rates:*
For additional information see Section 3, Chapter 13, ofthe
SEPE Handbook of Fire Protection Engineering?
Methods of Calculating Egress
‘Two major principles ate used to determine the necessary egress
‘width. They are based on anticipated population characteristics
identified with a specifi occupancy.
‘The Flow Method. This method uses the theory of evacuating a
building within a specified meximam period of time. Flow rates
‘were traditionally set at 60 persons per 22 in, (559 mm) width!
‘min through level passageways and doorways. In older editions
fof NFPA 10/ this 22 in, (559 mm) width was referred to as 1
“unit” of exit width. Credit was given only for whole or half
‘units, aalf unt being 12 in, (0.3 m). The unt of exit width is no
longer being used in most model codes. The flow method most
‘commonly used today is based on so much width of an egrese
clement per person served. For example 0.2 in, (0.5 em) per per
son for a door or other level egress component is what is used by
the Life Safety Code and the International Building Code, Table
43:1 provides the capacity factors used by the Life Safety Code.
TABLE 4.3.1. Capacity Factors
Stairways Level Components
OWieth pee and Ramps
Person) (Width per Person)
Area in mm in mm
Board andcare Od 10002 5
Health ear, 03. 18 02 5
sprinkered
Healthcare, os 1500s 13
nonsprinklered
High-hazard 07 180 od 10
All others 03 18 02 5
‘Source Table 7.31, NFPA 101, 2006 esion
Paul's” effective stair width concept advocates the consid
eration of only the portion of the stair used in effective move-
‘ment by the occupants, as observed in Functional and practice
evacuations, This Width is established with 6 in, (150 mm) clear
ance from each side wall of the stat, Figure 4.3.3 illusteares
the flow time in seconds relative tothe effective stair width per
person and the units of width,
[-7.0in, (180 mm so, 1 i, (280 mm) reas
i. (165 is, 18 (090mm ead
\e 2. (19 mn ie, 10,25 mn rae
“eh
Joao
raster eapactyreternca
7 wo uns of ent wea 20 person
z 7
:, ozs 2
as ‘width/150 persons q g
§ §
Lg z
3 ors &
i? i
a . o10
¢ g
32 i :
3 oas
et
° 0
© 108200 206400500 ao
Flow time (ee)
FIGURE 4.3.3 Relationship between Eifecive Sais Width
and Units of Exit Width per Person and Flow Time for Three
Stair Geometries”A-T2 SECTION 4 | Human Factors in Emergencies
The Capacity Method. This methods based on the theory that
sufficient numbers of stairways should be provided in a build-
ing to adequately house all occupants of the building without
‘requiring any movement, or flow, out of the stairways. In theory,
assuming a stairwell provides a safe and protected area for all
‘occupants within the protective barrier rested by the slairway
enclosure, evacuation ofthe building may then be more leisurely,
Permitting people to travel at arate within their physical ability
‘The capacity method recognizes that evacuation from high-rise
buildings is physically very demanding. Purther, evacuation of
health care facility is likely to be slow. Thus, design criteria
ate established to pesmit holding occupants within exits or areas
of refuge. The capacity method is not recognized in most model
codes. However, codes do recognize areas of refuge. For ex-
anple, the Life Safety Code does mandate that most health care
occupancies have smoke compartments into which patients can
bbe moved without having to evacuate the building
Application
‘The capacity and flow methods may both be applied to efficient
egress design, depending on specific circumstances. Where
People are expected to be physically or mentally sick. aged,
asleep, or incapacitated in any way, evacuation and use of the
flow method can be augmented with the capacity method.
less using a performance-based design, most model codes do
not recognize the use of the eapacity method alone.
‘There is litle time between an alert and the use of an exit
in assembly occupancies, and maximum flow rates that cause
reductions inthe area used by each person may result in reduced
lwaffc lows, On the other hand, the staff supervision of childzen
in an educational setting, coupled with their familiarity with the
surroundings, their presumed high physical capabilites, and
their experience with a program of drills should allow rapid
evacuation times. Pauls has reviewed the historical and current
iterature relative to the principles of people movement, exit
width determination, and the design of the means of egress.»
Design of Means of Egress
‘Designing a means of egress involves more than numbers, flow
rates, and densities, Safe exit from a building requires a safe
path of egress from the fire environment. The path is atranged
for ready use in case of emergency and should be sufficient to
‘permit all occupants to reach a safe place before they are en-
angered by fire, smoke, or heat, Proper egress design permits
everyone to leave the fire-endangered areas inthe shortest pos-
sible time with efficient exit use, Ifa fire is discovered in its
incipient stage and the occupants are alerted promptly, effective
evacuation may take place,
‘Maximum permited evacuation travel distances are related
to the occupant characteristics, occupant alertness, and building
fire protection, The less capable people are to move, the less
alert they are (such as sleeping), and the less protected a build-
ing is (such as no sutomatie sprinkler protection, the shorter the
‘permissible travel distance.
Depending on the physical environment of the structure,
the characteristics of the occupants, andthe fire detection and
alarm facilities, fie or smoke may prevent the use of one means
of egress. Therefore at least one alternative means of egress re-
rote from the firs is essential, Provision of two separale means
of egress is a fundamental safeguard, except where 2 building
or room is small and arranged so that a second exit would not
provide an appreciable increase in safety. There are fewer or no
advantages to separate means of egress if there is travel through
‘common space or use of common structural features tht result
in the loss ofthe two distinct and physically separate means of
egress.
‘One example of “common” stricture is a multistory build-
ing where scissors stairs are used. These are two stats enclosed
Within a common shaft, separated by a partition common to both
stairs, Scissors stare are sometimes used to provide the required
exit capacity while minimizing th loss of valuable floorspace.
‘Where a set of scistons stats is the only means of egress when
two remote exits are required, the fundameatal principle of two
separate means of egress design may be violated. Ifthe common
partision between the stars fils, it Would result in the simulane-
fous lose of both exits during a fit, leaving no alternative means
of egress. With scissors stairs, the validity of the two separate
means of egress, therefore, depencis on the design characteristics
and construction ofthe common partition (Figure 43.4).
In some proposed egress designs, all the exite discharge
‘rough a single lobby at street level, eventhough this procedure
results in egress travel through a common space. This design
philosophy presumes that the lobby may be considered a sale
trea forall future egress needs during the life of the building.
Where two remote means of egress are requited, this type af
egress design is not permitted by the Life Safety Code ot by most
model building codes.
NFPA 0] limits openings in exit enclosures to those neces-
sary for access tothe enclosure from normally occupied spaces
and for egress from the enclosure, Penetration of enclosures by
ducts or other wilities constitutes a point of weakness and may
result in contamination of the enclosure during a fire and should
not be permitted, Furthermore, itis not good practice to use exit
enclosures for any purpose that could interfere with their value
as exits, For example, ent stair enclosures should nat be used
for storage or any other use not associated with egress or areas
of vefuge for mobility impuired persons
Provisions for handicapped persons is an important con-
sideration in the design of an emergency means of egress from
building. A 32 in, (813 mm) doorway is considered the mini-
‘mum width (o accommodate a person in a wheelchair. Since
handicapped employees or vistors may be found in all types of
buildings, special life safety considerations are indicated. NFPA
201 contains several additional provisions to protect moblity-
impaired individuals. I lso must be noted thal mobiliy handi-
caps are not the only type of handicap needing to be addressed.
Hearing and sight impairments, along with certain mental dis-
abilities, must be considered
LIFE SAFETY CODE®
[NFPA 10i, introduced in 1927 and revited and seissued in suc-
cessive editions, is developed by several committees under theCHAPTER 3 Concepts of Egress Design 4-73
FIGURE 4.3.4 Advantages and Disadvantages of Scissors
‘Staie versus Conventional Stairs. This sot of scissore
salts provides the same degree of remote exit doors asthe
circled stirs shown by dotted lines—travel distance fr ll
fcecupants isthe same, even if the doted exit stairs were
located at opposite comers as denoted by the cross marks
Space is saved; however, the integrity ofthe separation of the
‘so scissors stat isin question
oversight of the Technical Correlating Committee on Safety
to Life. a representative group dedicated to safety of life from
ize, NFPA J01 is primarily concerned withthe contzol of con-
ditions that threaten the lives of individals in building fires.
‘This objective is different from fire protection provisions in
building codes, which are concezned with the preservation of
property in addition to the preservation of life. In 2000, NFPA.
Announced its intent to write a building code. The first edition
of NFPA $000®, Building Construction and Safety Code®, was
published in 2003. The provisions for means of egress in NFPA
5000 are written by the same committes that write NFPA 10
Because of this, the discussion here will address NEPA 101.
is equally applicable to NFPA 5000 when dealing with new
‘Adequate means of egress alone are nota guarantee of life
safety from fire. They do not protect an individual whose own
carelessness causes a threat to life, such as setting his or her
‘own clothes on fire. Neither do sufficient means of egress alone
provide adequate protection in occupancies such a8 hospitals,
nursing homes, prisons, assisted living facilities, and mental
institutions, where occupants are confined or are physically or
‘mentally unable to escape without effective and immediate as-
sislance, NFPA [0] does recognize such situations and provides
life safety measures, including low-flame-spread and reduced-
smoke-producing materials for interior finish. In addition, aute-
‘atic sprinkler and smoke management systems called for by
NEPA [0] are designed to restzicl the spread of fire and smoke
and thus help to defend the occupants within an area of refuge
until they are able to use the exits or until the fire has been
extinguished,
In general, saving building occupants from a fire requires
the following, all of which are identified in NFPA 10/:
1, Sulficient aumber of properly designed, unobstructed
means of egress of adequate capacity and arrangement
2, Provision of alternative means of egress for use if one
‘means of egress is blocked by fir, heat or smoke
5, Protection of the means of egress against fire, heat, and
smoke during the egress time determined by the occupant
load, avel distanes, and exit capacity
4, Subdivision of areas by proper construction to provide
areas of refuge in those occupancies where total vacua
tion is nota primary consideration
5. Protection of vertical openings to limit the operation of fire
protection equipment to a single floor
6, Provision of detection or slarm systems to alert occupants
and notify the fire department in case offre
7. Adequate illumination of the means of egress
8, Proper marking of the means of egress and the indication
of directions
9. Protection of equipment or areas of unusual hazard that
‘could produce a fire capable of endangering the egressing
occupants
10, Initiation, organization, and practice of effective dill
procedures
11, Provision of instructional materials and verbal alarm sys-
tems in high-density and high-life-hazard occupancies to
facilitate adaptive behavior
12, Use of interior finish materials that prevent a high flame
spread or dense smoke production that could endanger
‘egressing occupants
igure 4.3.5 illustrates some of the principles of exit
safety
NFPA 101 recognizes that fll reliance cannot be placed
fon any single safeguard, because any single protective feature
‘may not function due to mechanical or human failure, For this
reason, redundant safeguards, any one of which will result in a
reasonable level of life safety, should be provided. NFPA 101
also recommends the special protection of hazardous areas and
specifies where automatic sprinkler, detection, and other protec-
tive systems are required.
NFPA 101 is used widely as a guide to good practice and
as a basis for local laws or regulations I differs from building
codes since it generally provides ite distinction among the dif
ferent classes of building construction. However, where totalA-TA SECTION 4 Human Factors in Emergencies
Atleast wo
rave out
rete rom
lezen ote
Evacuation sie wel plannes
frequen practn
—— a
oo)
‘Aadtional ena according to rarer
‘Stpersons and eater danger
Et avalable in tesconabl travel tance
Esa pas marks
Uiodetructed wel ighted
Ke
‘|
FIGURE 4.3.5 Principles of Exit Safety
evacuation of a building is not practical, duc either to the oc-
cupant characteristics or the building environment, the con-
struction type becomes an important variable and should be
considered,
NFPA 101 also recognizes that all habitable buildings con-
lain sufficient quantities of combustible contents to produce
lethal quantities of smoke and heat! In addition, caswalty
studies have established that the toxic properties of smoke axe
the principal hazard to life," and this hazard is recognized in
NEPA 10/.
NFPA 101 is intended to be applied to both new and exist-
ing buildings and is designed to provide a reasonable level of
if safety from fire in both types of buildings, The authority
having jurisdiction is given considerable latitude in achieving
conformance with existing buildings. Each existing building
represents a special situation that requires individual tention
for the most effective and economical method of achieving &
reasonable level of life safer.
‘The claim that buildings constructed many years ago ac-
cording to all the legal requirements are sufficiently safe now
should not necessarily be accepted. Ifthe cost of reasonable life
safely is judged to be prohibitive the occupancy or the structure
should be changed or prohibited because there is no justification
for subjecting building occupants to an unreasonable level of
peti from a fir.
‘There may be a variety of differing opinions as to what
constitutes reasonable life safety from a fire in any given ase.
11s not possible to guarantee occupants 100 percent life safety
from a fire; beyond certain conditions, a building becomes haz-
ardous tothe life safety ofthe occupants in a fire. How should
the authority having jurisdiction establish the minimum con~
ditions? NFPA 10/ provides guidance for such decisions with
the help of studies of major-loss-of life ftes," fire devel-
opment research," personnel evacuation, '*
behavior
NEPA 101 examines the various occupancy popula-
tions according co their perceived life safety hazard, which ine
cludes psychological and sociological variables in addition to
the physiological and environmental factors. These occupancy
classifications are assembly, educational, day care, health cate,
ambulatory health care, detention/corectional, residential, resi-
dential board and care, mercantile, business, industrial, and stor-
age. Additional provisions for special-purpose and high-rise
structures are also included
Separate and distinct means of egress provisions are made
for each occupancy classification, with the various occupancy
subgroups included. These classifications. based on the pet~
ceived hazard to life safely from a fre, often difer from older
building code occupancy classifications. For example, mer
cantile and office occupancies were often grouped together in
previous editions of building codes. However, there appears to
be an increased hazard to life in mercantile properties, resull-
ing from the displays of combustible merchandise, the greater
density ofthe population, and the transient character of most of
the occupants. These factors are not usually found in office and
educational buildings, which have a relatively low combustiil-
ity content, & lower population density, and normally alert oc-
pants who are inthe building daily and presumably have the
opportunity to familiarize themselves with the means of egress
through functional use and evacuation drills
and human
INFLUENCES ON EGRESS
Influence of Hazard of Contents
‘An evaluation of the hazard of the building contents must take
into account the relaive probability of the ignition of combus-
tibles, the spread of flames and heat, the probable smoke and
gases expected tobe generated by the fire, and the possibilty of|
a fire-related explosion or other structural failure endangering
‘ecupants. The degree of hazard is usually determined by the
flammability or toxicity ofthe contents and by the processes or
operations conducted in the building. Most NFPA 101 require
rents are based on the exposure created by contents with an or-
dinary hazard, Special requirements for areas with high-bazard
contents usually consist of special protection systems, isolation
of the havard area via fire-rated construction, reduced travel dis-
tances, and additional means of egress
‘To assist in evaluating the contents hazards, NFPA 101 es-
lablishes three classifications of contents: (1) low, (2) ondinary-
and (3) high-hazard. They are discussed next. These should not
be confused with the classifications established by NEPA 10,
‘Standard for Portable Fire Extinguishers, or NFPA 13, StandardCHAPTER 3 Concepts of Egress Design 4-75.
for the Installation of Sprinkler Systems, nor with those estab-
lished by some model building codes,
Low-Hazard Contents. These are contents of such low com
Dustibility that no self-propagating fize can occur in them,
Consequently, the only probable danger requiring the use of
‘emergency exits will be from smoke or from fie from some ex
femal source. These are extremely unusual. The storage of sheet
‘metal without combustible packing is one example.
‘Ordinary-Hazard Contents. These are contents that ae liable
to bum with moderate rapidity and to give off a considerable
volume of smoke. This class includes most buildings and is the
‘bass fr the general requirements of NEPA 101.
High-Hazard Contents. These are contents that are liable to
‘burn with extreme rapidity or from which explosions are to be
feared in the event of fire, Examples are occupancies in which
‘lamanmable liquids o gases are handled, used, o¢ stored; in which,
‘combustible dust explosion hazards exist; in which hazardous
chemicals or explosives are stored; in which combustible fibers
are processed or handled in a manner that produces combustible
Alyings; and similar situations
Influence of Building Construction
and Design
A building of ire-resstance-rated construction is designed to
permit a burnout of contents without structural collapse, Fire-
resistance-rated design does not ensure the life safety of the
‘ecupants of such buildings. 2"¥ However. the ability of a struc
tural frame to maintain building rigidity under fire exposure is
{important tothe maintenance ofthe fte resistance protection of
exit enclosures. Where a 2-hour fireated exit enclosure is re-
quired, a fir-resistance-rated structural frame capable of withe
standing stresses impased by fire for a similar period is also
necessary. Iti inconsistent to provide a 2 hour ext enclosure in
building with a structural frame rated at less than 1 hour, for
example, unless special construction precautions ae taken 10
prevent structural failure ofthe building from adversely affect
ing the protective construction of the exit enclosures
‘The protection of vertical openings is one of the most
significant factors in the design of multistory buildings, from
the standpoint of life safety and exit design. Because of the
natural tendency of fte to spread upward in a building, careful
attention to detsils of design and construction are required to
‘minimize this effect. One of the arcatest hazards to life safety
zesults from fires that start below the occupants and the means
of egress, such asin basements or onthe level of exit discharge.
‘Similarly, fires in mulistory buildings may result sn smoke
spread into enclosed exits before evacuation 121" Conversely
escape {rom fires that occur above the occupants is relatively
simple, provide sufficient warning is given and adequate means
of egress are available.
‘The influence on the life safety of the occupants by the
raterials used in building construction depends primarily on
‘whether the materials will propagate flame, support combus-
tion, or create dense amounts of smoke when exposed toa fire
initially involving the building contents. Some materials used
as insulation, for example, could contuibute to rapid flame de-
velopment and dense smoke production spread. Masonry walls
enclosing a wood-frame interior provide no increased occupant
life safety compared with a total wood-frame structure.
Exit requirements are based on buildings of conventional
design, Unusual buildings, such as those without windows or
‘those with unopenable windows, call for special consideration,
Windows provide a number of advantages in a fire. Windows
allow occupants to see rescue operations in progress and allow
‘occupants to communicate visually with rescue personnel, They
also provide a means of access tothe building by fixe department
personnel for rescue and fie fighting. Operable windows pro-
vide the addtional advantage of access to fresh air, the potential
ability o communicate orally with rescue personnel, and poten-
tial use for escape. Although it might be possible to break fixed
windows to provide those same advantages, this poses several
problems. First, falling glass presents « hazard to fire fighters
‘outside; next, ifthe broken window permits smoke to enter, it
cannot be closed as an operable window can; and last, depending
fn the type of glass and its thickness the window may be very
difficult to break. Automatic sprinklers are considered a primary
requirement for life safety in windowless buildings, buildings
‘with unopenable windows, and underground structures.
Influence of Interior Finish,
Furnishings, and Decorations
‘The rapid spread of flame over the surface of walls, ceilings,
or floor coverings may prevent eccupant use of the means of
egress, In general, NFPA J0/ limits the Name-spread index cla
sification of interior finish materials on walls and ceilings to
a maximum of 200, based on the results of tests conducted in
accordance with NFPA 255, Standard Method of Test of Surface
Burning Characteristics of Building Materials, also known as
ASTM E84, Lower ratings are prescribed forthe interior finish
materials used in exits and in exit access corridors, Materials
classified as having a lower lame-spread index are also requized
{in certain areas in individual occupancies. A fire-retardant coa
ing may be used on existing interior finish materials to reduce
the rate of lame spread. In aeas protected with automatic sprine
Iker, the use of materials with higher flame-spread index ela
sifications sometimes is permitted. Table 4.3.2 summarizes the
interior finish requirements contained in NFPA 101 forthe vari
‘ous occupancy classifications, NFPA 10/ also recognizes NFPA.
286, Standard Methods of Fire Tests for Evaluating Contribu
sion of Wall ana Ceiling Interior Finish to Room Fire Growth
‘Any material that passes this tet, based on the pass-fal eriteria
Contained in NFPA 10/, can be used anywhere ina building.
Floor coverings are evaluated by NEPA /0/, through the
use of NEPA 253, Standard Method of Test for Critical Radiant
Flux of Floor Covering Systems Using a Radiant Heat Energy
Source, also known as ASTM E648, Two classes of floor cover
ings are established: Class I finishes, with a minimum critical
radiant fux of 0.45 Wlem?, and Class TI finishes, with a mini-
‘mum critical radiant flax of 0.22 Wien
Fumishings and decorations—particularly furnishings—
play an increasingly important role in loss of life by fie.Interior Finish Classification Limitations
Occupancy Exity But Access Corridors Other Spaces
‘Assembly-—new
‘300 Occupant load A AorB Aork
Lor Tor ll
<<300 Occupant load A AoB ABorc
Tort Tort
Assembly—existing
800 Occupant load A AoB Ack
300 Occupant load A AaB ABorc
Educational—new A AoB AorB;
Tort Tort Con Low paritions*
Educational—eristing A AcrB A.B.orC
Day-care centers—new A A Ack
Tort Tort
Day-care centers existing AoB AB Ao’
Day-care homes—new AoB AoB A.B.or€
Tor
Day-care homes—existing AaB A,B, or ABore
Health eare—new A A A
NA Bon lower portion 2 in small individual
of corridor wall rooms
Tort Tort
Health cate—esisting AoB AB Ao’
Detention and eorrectional—new Aok ArB A.B.orc
(sprinklers mandatory) Tor I Tor Ir
Detention and corectional—existing AaB AorB ABore
Tor Tor I
‘One- and two-family dwellings and lodging ABor€ ABor€ ABorc
forrooming houses
Hotels and dormitories new A AcrB ABorc
Tor Tort
Hotels and dormitories existing Aok AorB A.B.orc
Toe it Toe it?
Apartment buildings—new A AaB ABorc
orl Tor It
Apartment buildings —existing AorB AcrB ABorc
Tor I* Tor I*
Residential board and care—
(See Chapters 32 and 33 of NEPA 101.)
Mercantile—now AoE AoE Ack
Tort
Mereantile—existing
‘Class A or Class B stores Aok AorB Ceilings A or B; walls—A. B, or C
Class C stores A.B,or® A.B,orC A.B,orC
Business and ambulatory health eare—new ‘ork Aok ABlorc
Torll
Business and ambulatory bealth care—existing AaB AaB A.Bor
Industrial AoE A.B, or€ ALBlorC
Tort Tort
Storage AorB A.B, or€ ABore
Tor
Nove
[Clas A otesior wall and ceiling finish—lame spread 0-25, new aplication) stoke developed 0-450
2 Class terior walla eling Gnsh flame spread 26-75, (se applicaons) smoke develuped 0-150
5. Class Ctrior wal an eelingKinish—ilame spread 76-200, (ge applications) smoke developed 0-150
4s Lntenoe or fneh-—eniel radiant ae no less than 0.48 Wem
5 Cle interior oor Gnih—crtieal raat fat. ot more tha 0.22 Wem? bat ese than 0.48 Wien
6: Automate spinlers—wheve a complete standard system of automate speakers is stale, interior wal and cling
‘ish with lame spreadating not exceeding Class Cis permited ioe used in any location where Class B ssequied
and witharatingof Cars Biman ioeation were Class As requte: smal, Class llrior oor Snish's permed
tore used in any loeaion where Claes Ti equte, and no erica aan rang se reqied where Cass I
required These provisions o at apply to new detention and eorectional occupancies.
7 Baposed portion of stuetral members complying wih Ue reguzenens fr heavy mbes constuction are permite
*Seocatesponding ebaptess of NFPA 10! for details.
Source Tile A.1022. NEPA 101, 2006 edition,CHAPTER 3 Concepts of Egress Design 4-77
Decorations can be treated with a flame retardant. Furnishings
oon the other hand, are difficult control and regulate asa fire
hazard, since they are not attached to, of par of, the building
construction or ofthe interior finish materials, Furnishings are
moved, refurbished, and replaced, However, there are now test
procedures for measuring the combusibilty of upholstered fur
niture and is suscepubility to ignition." Two NEPA standards
address fumitute combustibiity: NFPA 260, Standard Methods
of Test and Classification System for Cigarete Ignition Resis:
tance of Components of Upholstered Furniture; and NFPA 261,
Standard Method of Test for Determining Resistance of Mock
Up Upholstered Furniture Material Assemblies to Ignition by
Smoldering Cigarettes. ASTM E1590, Standard Method for
Fire Testing Mattresses, assesses heat release of mattresses and
bedding. Ifthe Life Saery Code regulates upholstered furniture
for mattresses, the restriction will be found in the appropriate
‘ecupancy chapter. Few occupancies have such regulations, and
even those occupancies limit the restriction to new upholstered
furniture and mattresses. The U.S. Consumer Products Safety
‘Commission (CPSC) also basa standard fr evaluating the ignite
ability of mattesses A number of fires have been documented
in which severe conditions resulted from fire involvement of
only a few furnishing items $194
Influence of Psychological and
Physiological Factors on Egress
“The psychological and physiological conditions ofthe occupants
must be considered, in addition to the physical configuration
factors of the building in planning means of egress. Studies ine
dicate people usually behave adaptively and often altuistcally
inthe stess of afte 2122 A heterogeneous collection of persons
under the influence of alcohol or drugs, as may be present in
‘an assembly occupancy, may pose a greater probability of non
adaptive group behavior, with a competitive fight, panic-type
‘behavior the likely result. Historically this type of nonadaptive
‘behavior has been documented, although studies indicate that
the phenomenon is rare and depends on unigue, predetermined
conditions involving both the population and the physical envi-
ronment ofthe structure 2-2
In some cases, evacuation procedures and the cteation of
areas of refuge within high-rise buildings encourage occupant
movement upward within the buikling. The effectiveness of
this concept has not been completely validated in actual fires
Because ofthe orientation of some people toward total evacue
ation and escape from the building tis possible that they may
attempt to evacuate @ building in the conventional “down and
‘out” approach despite instruction to the contrary This i even
more problematic since the September 11, 2001 World Trade
Center disaster.
Evacuation procedures in federal high-rise office buildings,
as directed by vocal alarm systems, have continually obtained
the selective movement of personnel in both upward and down
‘ward directions. In two serious highctse office building fires
in Sto Paulo, Brazil, he occupants moved upward to the root
‘when their downward movement was inhibited by smoke and
hneat! Inthe MGM Grand Hotel fire in Las Vegas, Nevada. in
November 1980, there also was upward movement inthe stat
‘ways tothe roof and to rooms on upper floors when downward
twavel was made untenable by smoke and heat.!"2! It should be
noted that rarely have successful helicopter rescues from the
roof been performed, Roof-mounted structures, antennas, and
Similar items make close approach difficult. In a significant
fire, thermal updafls make approaching the building hazard-
‘us, Buildings propery built and maintained in accordance with
codes such a the Life Safery Code should not need such drastic
Allexits need tobe conspicuously marked, because people
sae likely to be unfamiliar with the various exits ftom an area
‘under fre conditions and thus neglect alt
Its also important that the means of egress from a building
be used as a matter of daily routine, so the occupants will be
familiar with their location and operation. NFPA 101 requires
that the main ext of assembly occupancies, which also serves
asthe entrance, be sized to handle at least half of the total occu
pant load ofthe building Some assembly occupancies are now
equited to have a main exit hat can accommodate two-thirds of
the occupant load. This is a esul of the Station nightelub fire in
West Warwick, Rhode Island, where 100 people died
‘There are three critical parameters in the effective use of
the zoned evacuation of personnel to areas of refuge within a
building:**
1. Proper construction to provide compartmented areas that
are protected from the effects offre and smoke
2. An effective verbal alarm system giving clear and com-
prehensive instructions, with provision for originating on-
Scene instructions from the fire department®>
3, Effective evacuation drills to familiarize the oceupants with
‘the way the system function
thas been advocated that occupants in fte-esistant, com-
partmented buildings wsed as hotels, motels, apartments, dormic
tories, hospitals, and other health car facilities should stay in
their rooms rather than evacuate, because the 1ooms are the most
adequate area of refuge Tn general this method has not been
adopted by NFPA 10/ or by model building codes. However,
the concept of areas of refuge is used by NFPA 101 extensively
in occupancies suchas health care as well as detention and cor-
rectional facilities and also to protect occupants with mobility
impairments in all occupancies. In occupancies such as health
care, ambulatory health care, and detention and correctional
‘occupancies, NFPA J01 has mandatory provisions for smoke
compartmentation to limit the need to move occupants off the
story of fire origin. In new construction of any occupancy, build.
ings that are not protected by automatic sprinklers are required
to provide “accessible means of egress” which in mulistoried
buildings usually means areas of rofuge, NFPA 101 provides
various ways of providing areas of refuge. The two most come
mon areas of refuge are oversized ext sti landings or subdivie
sion of the story by horizontal exits or smoke barriers
Influence of Fire Protection Equipment
It is unsuitable to rely totally on manual or automatic fire-
extinguishing systems in place of adequate means of egress, be-
cause fireextinguishing systems are subject to both human andA-T8. SECTION 4 © Human Factors in Emergencies
‘mechanical failure. In addition, building areas may become un-
tenable for human occupancy before the fie-extinguishing sys-
tems are effective, Under no congition can manual or automatic
fire suppression be accepted as a substitute forthe provision and
‘maintenance of proper means of egress. However, NFPA JO]
does provide significant alternative methods of compliance for
buildings protected by automatic sprinkler systems. In addition,
automatic sprinkler systems and various automatic detection
systems are often installed in existing buildings to compensate
for problems with the means of egress
‘Where a complete standard system is installed, automatic
sprinklers are sufficiently reliable to have a major influence on
Life safety. In addition to providing an automatic alarm of fire,
they quickly discharge water on the fre before smoke has spread
dangerously, Alwhough automatic sprinklers should never be
used in place of adequate means of egress, they ate recognized
in various ways by NFPA 10/. When total automatic sprinkler
protection is provided, NEPA 101 permits increased travel dis-
tance to exits, the use of interior finish of greater combustibilty
reductions in corridor requirements, and, in some occupancies,
the use of combustible construction in situations where it would
otherwise be prohibited. Provisions for areas of refuge axe sig-
‘nificantly easier to comply with in buildings protected through-
cout by automate sprinklers, Sprinklers are particularly valuable
in dealing with problems in existing buildings.
‘Automatic fte detection, or fre alarm, systems are valu-
able in notifying building occupants of a fire go they may evacu-
ate promptly. Automatic fire detection systems only provide a
warning of fire and do nothing themselves to suppress or limit
the spread of fire and smoke. An automatic fice detection system
is nol a substitute for adequate means of egress
‘Smoke detection systems can be useful to help mitigate
problems in existing buildings. They can be especially useful
Where earlier egress may help selve problems, such a exist-
ing excessive common paths of travel, dead ends, and travel
distance
DEFINITION OF THE TERM.
“MEANS OF EGRESS’
NEPA 10/ and most of the U.S. model building codes use the
term “means of egress” A means of egress isa continuous path
of travel from any point ina building or structare toa public way
that isin the open air outside at ground level. Egress consists of
three separate and distinet parts:
1. Bvit access, Portion of a means of egress that leads to the
entrance of an exit
2. Exit. Portion of a means of egress that is separated ftom
the area of the building from which escape is to be made
by walls, floors, doors, or other means that provide the
protected path necessary for the occupants to proceed
with reasonable safely to the exterior of the building. An
exit may comprise vertical and horizontal means of travel,
such as exterior doors, protected stairways, ramps, and exit
passageways.
3. Bxit discharge. Portion of a means of egress between the
termination ofthe exit and a public way
Figure 4.36 illustrates the relationship among these three
parts of an exit in a building
The Exit Access
‘The exit access may be a comtidor, aise, balcony, gallery, room,
‘porch, or tof. The length of the exit acess establishes the travel
distance to an exit, an extremely important feature of a means of
egress, because an occupant might be exposed to fire or smoke
dlusing the time it takes to reach an exit. The average recom-
mended maximum travel distance i200 f¢ (61 m), but this dis-
tance varies with the occupancy, depending on the fire hazard
and the physical ability and alertness of the occupants (Table
43.3), The travel distance must be measured from the most re
rote point in a room of floor area to an exit,
In most cases, the travel distance can be increased if the
building is completely protected with a standard supervised au-
tomatic sprinkler system,
{A dead end isan extension of a corridor beyond an exit oF
fan access to exits that forms a pocket in which occupants may
bbe rapped. Since thee is only one direction of travel to an exit
from a dead end, a fire in a dead end between the exit and an
‘secupant prevents the occupant from reaching the exit. Another
problem with dead ends is that while taveling foward an exit
in a smoky almosphere, an occupant may pass by the exit and
‘walk into the dead end. This requires return travel, which adds
distance, and therefore time, co reach the exit In good egress
FIGURE 4.3.6 Examples of Exit Access, Exit and Exit
Discharge. To the occupant of the building an this level, the
doors at A;,A,,E;,and E, are exis. To the person emerging
rom the exit enclosures doors D, and D, are exit discharge
doors, Exit access i denoted by dashed lines. Exit discharge is
denoted by dotted lines. Solid lines are within the ext(CHAPTER 3
Concepts of Egress Design 4-79
TABLE 4.3.3 Common Path, 1d, and Travel Distance Limits (by Occupancy) )
Common Path Limit Dead-End “Travel Distance
Unsprinklered —Sprinklered —Unsprnklered —_Sprinklered —Unsprinklered—_Sprinklered
Type of Occupancy Sem) Sim) Stim) sem) Sit) Stim)
‘Assembly
New 20ns 2ons 20¢6) 26.1 200625070)
(rsp (a3
Bristing 20075 20n15 206.1 2066.0 20066" 25076)
(ose (ours
Educational
New 753) 10030) 2066.1) 50.13) 15045) 200.61)
Existing 75.023) 10030) 2066.1) 5015) 15045) 200,61)
Day Care
New 7523) 1000) 206611) 50.15) 104s 200,601
Existing 753) 10030) 2066.1) 5013) 1505} 200,60
Health Care
New NR NR 3000.) 300.) NA 200 61
Euisting NR NR NR NR isos 200,68
Ambulatory Health Care
New aaa" 100G0" 206.1) s0(is) 15045} 200 ¢61»¢
Enisting 7523" 1030" 5045), 50.15) 15045} 200,61}
Detention and
Correctional
New—use condition 505) 100 30) 5005) 50.8) 1504s} 200,601
11m, 1V
New—use condition V 5013) 1000) 2066.1) 206.) 150s} 200601
isting —ese condition 5015) 100 30 NR NR 15045 200,601
WALV.Y
Residential
One- and wo-faily NR NR NR NR NR NR
dwvelings
‘Lodging or ooming houses NR NR NR NR NR NR
Hotels and dormitories,
New 3sdo7e® —sosye® 35,107) 50.15) 175.638 325 09)8
Eisting 35078 SOLIS 5005) 50(15) 175.5388 325 (09)8
Apartments
New ssuome — Souse 3510.7) 50.19) 175.638 325 09)
Existing 350.7% ——S0(I5 5015) 505) 175,58 525 09)
Board and cate
Small, new and existing NR NR NR NR NR
Large, new NA 135 G8)" NA 50015) NA 325 (99)
Large, existing 11083) 16049) 505) 5015) 175,53) 325 09}
‘Mercantile
Chass A,B,C
New 753) 10030) 20,61) 5015) 150 (45) 250.6)
Enisting 7503) 100 30) 505) 50.5) 15045) 250,76)
Open air NR NR 00) 00) NR NR
Mall
New 7503) 10000) 2066.1) 5015) 15045) 4001203!
Existing 753) 100 G0) 5015) 5015) 150145) 490120)!
(continued)4-80 SECTION 4 © Human Factors in Emergencies
TABLE4.3.3 Continued )
‘Common Path Lin ‘Dead-End Limit
Unsprinklered —Sprinklered —Unsprinklered — Sprinlered —Unsprinklered _Sprinklered
Type of Occupancy film) film) film) Simm) Sim) a)
Business
New 753 100 G30) 2066.1) 50.5) 200 (61) 300,01)
Existing 7523) 100 30) sous) 505) 200 (61) 300,81)
5015) 100.30) 5015) sus) 200 (61)! 2005"
50 (15) 100 (30) 50.5) 50.15) 300(91) 400 (122),
High hazard 0 0) 0) 0) 00) 75003)
Aircraft servicing hangars, 50 (15)8 100.30" sous sous . .
‘ground floor
Aireratt servicing hangars, sous 7503" 50,15)" sos)" 75003) 7503)
‘mezzanine floor
Storage
Low hazard NR NR NR NR NR NR
Ordinary hazard sous) 100.30) sous) 100.30) 200 (61) 400 (122)
High hazard 00) 00) 00) 00) 75,03) 100 (30)
Parking stuctures, open 50415) 5013) sous) 5015) 300(91) 400 (122)
Parking structures, enclosed 50 (15) 5015) 5013) 5013) 150 (45) 200 (60)
Aiseraft storage hangars, sos 100.307" soci. sous . .
‘ground floor
Aircraft storage hangars, sous sas Sos sous 7503) 75003)
mezzanine floor
Underground spaces in sous 1030" sos 100 (30)" 200(61) 400 (122)
‘rain elevators
‘News
‘NA=Not applicable
NBs No requiem
‘or common path sring > 50
rons 2016.1 m): for common path serving 50 persons, 75 1 23 m),
SDeadend emits of 20 (6.1m) permited: dead-end asies of 20 (6.1 m) permed
«See Chaps [2 and 13 of NFPA 11 for special consieions for aokt-proeted sserbly eating in ana ad ala,
‘his dimension i for the (otal wae dstanee,asuming ineremental portions have fully uuize thee permed
‘maximums Fr ave! stance win the oom, and Irom te oom ext acces dor Io the ei, ee the appropriate
occupancy chapter of NFPA TOI
See basnes ceupances, Chapers 38 and 39 of NFPA J01
‘ce Chater 2 of NFPA 10] fr special considerations for existing common pats
‘This dession stom he oonceridr or sutelcoride ext acces oot othe ex thsi applies to comider common,
pat
'ste the appropiate occupancy chaper of NFPA 101 fr requirement for second exit acest based on room area
'See appropriate occupancy chaps of NFPA 10] fr special wael distance considerations fo exterior Ways of ext ccs,
See 3644and 374.8 of NFPA 01 for socal uvel distance considerations in covered mull considered o Be pedetian
ways,
‘See Chapters 38 and 39 of NEPA 01 fr special common pal considerations fr single tenant space.
'See Chapers 40 ana 2 of NFPA 10! fr special reuiemns on sparing of doors nara Rahat
"See Chaper 40 of NFPA 107 for industrial occupaey special ave distance considerations,
"See Chapers 40 and 42 of NFPA [01 for special equrements it high-haratd conditions eit.
Source Table A.78, NFPA 10, 2006 eon,
designs, dead-en corridors are not used, However, NFPA 101
permits dead ends in most occupancies, within reasonable limits
(Gee Table 4.3.3). Two examples of dead-end corridors are il-
Justrated in Figure 4.3.7.
‘The width of an ext access should be at least sufficient for
the number of persons it must accommodate, In some occupan-
cies, the width of the access is governed by the character of
sctivity in the occupancy. One example is a new hospital, where
patients may be moved in beds or in gumeys. The corridors in
the patient areas of the hospital must be 8 ft 2.4 m) wide to
allow for a bed to be wheeled out of room and turned 90"
‘A fundamental principle of ext access is the provision of
a free and unobstructed way to the exits. Ifthe access passes
‘rough a room that can be locked or through an area containing
a fire hazard more severe than is typical of the occupancy, the
principles of fee and unobstructed exit access are violated.CHAPTER 3 Concepts of Egress Design 4-81
HI
LI mal
FIGURE 4.3.7 Two Examples of Dead-End Corridors
‘A shows an elevator lobby that has no exit atthe far end,
thereby forming adead-end corridor. B is a “classic” dead.
end corridor.
a |
‘The floor of an exit access should be level. If this isnot pos-
sible, small differences in elevation may be overcome by a ramp
and large differences by stairs. Whete only one or two steps axe
necessary to overcome differences in level in an exit aveess, a
xamp is preferred, because people may trip in a crowded cor
rior and fall on the staits if they do not see the steps or notice
‘that those in front of them have stepped up or down,
The Exit
‘The types of permissible exits are doors leading dtectly outside
at ground level or through a protected passageway tothe outside
at ground level, smokeproaf enclosures, protected interior and
‘outside stairs, exit passageways, enclosed ramps, and in existing
par
fee
pee
&s
fof —o%
e
Enetoses Horizontal
‘sane onto
FIGURE 4.3.8. Plan Views of Types of Exits. Stair enclosure
prevents ie on any floc for tapping the persons above. A
smokepeoof tower is better as it opens to the ait at each floor,
largely preventing the chance of stoke inthe stairway. A hori-
zontal eit provides a quick refuge and lestens the need fora
hasty ight down stats, Fie-rated doors must be arranged to
be self-closing or automatic-closing by smoke detection,
buildings, enclosed escalators or moving walkways. Elevators
are nol accepted as exits; however, they can be used to provide
‘a way of removing mobility-impaired individuals from areas of
refuge, NEPA [01 also recognizes elevators for very limited use
as a second exit for limited-access towers such as FAA control
towers, Research is currently being conducted in an altempt to
make elevators more usable for egress purposes. See Figures
4.3.8 and 4.39 for illustrations of some common types of exit
arrangements.
‘The specific placement of exits is a matter of design judg-
‘ment, given the specifications of travel distance, allowable dead.
ends, common path of wavel, and exit capacity, NFPA 10/ states
|< hea neal
1oniam
Notes than tpt
veinstonr Sina spnng
we eee open,
gm door Ahr door
‘door Meche ‘Wehr door
13
Seen Guard ie
May i 18
oom
Pian A pune
ane wat | ran
mrechanel
vention
20min dor
nn so
Min 72
- Wehr door (183. em)
tt
open —_
}___] outsise chee
Tinfan nto
issent Sm
linc Pino
FIGURE 4.3.9 Fou: Variations of Smokeproof Enclosures.
Plan A has an open-air vestibule opening fom a corridor
Plan B shows an entrance by way of an outside balcony.
Plan C could provide a stair entrance common to two areas,
In Plan D, smoke and geses entering the vestibule would be
exhausted by a natural or induced draft in the open air shal.
Teach case, a double entrance to the stat tower with at
least one side open or vented is characteristic ofthis type of,
construction, Pressurizalion ofthe slat ower inthe event of
fire provides an attractive alternate for tll buldings and isa
sieans of eliminating the entrance vesubule4-82 SECTION 4 | Human Factors in Emergencies
that exits must be remote from each other, thus providing two
separate means of egress so located that occupants ean travel in
either of two opposite directions to reach an exit. This concept
is important when itis necessary for occupants to leave fre or
smoke-contaminated area and move toward an exit. F occupants
have no choice bul to enter the fre area to reach an exit, itis
doubtful whether they will beable or willing to do so,
The Exit Discharge
Ideally, all exits in a building should discharge directly to the
outside or through a fire-resistance-rated passageway to the
outside of the building. NFPA 10/ permits a maximum of SO
‘percent ofthe exit stats to discharge onto the street floor. The
obvious disadvantage ofthis arrangement i that if a fire occurs
on the street-level floor, it is possible for people using the exit
staizs discharging there to be discharged into the fite area, I any
exits discharge to the street floor, NFPA 101 therefore requires
that such exits discharge to a free and unobstructed way to the
outside of the building, thatthe street floor be protected by au-
tomatic sprinklers, and thatthe street floor be separated from
any floors below by construction having a 2 hour fie resistance
rating
Discharging an exit to the outside is not necessasily dis-
charging to a safe place. I the exit discharges into a courtyard,
an exit passageway must be provided from the courtyard through
the building so thatthe occupants can get away from the build-
ing. Ifthe ext discharges into a fenced yard, the occupants must
be able to get out of the yard to get away from the building, If
the exit discharges into an alley, the alley must be of sufficient
width to accommodate the capacity ofall the exits discharging
into it, and any openings in the building walls bordering the
alley should he protected to prevent fre exposure to the occt-
pants proceeding through the alley.
‘When exit stairs from floors above the street floor continue
fn to floors below the street floor, occupants evacuating the
building may miss the exit discharge door tothe street level,
continue down the stairway, and enter a floor below the level of
exit discharge. Therefore, NEPA J0/ requires a physical barier
or other effective means atthe street floor landing to prevent
evacuees from passing the level of exit discharge
‘CAPACITY OF MEANS OF EGRESS
‘The capacity of exits is calculated using a capacity factor pro-
vided in NFPA 10/. This capacity factor is given as in.person
(canfperson) and varies with the occupancy (see Table 4.3.1), The
{otal ext capacity for each component of the means of egress
such as doors, stare, ramps, cozidors, and so on, is calculated
bso on its clear wid. For example, one 34 in, (86 em) clear
width door in an office occupancy would have an exit capacity
of 170 persons (34 in. 0.2 in person = 170 persons [86 em
(05 emiperson = 172 persons)). The reason for these variations
in exit capacity factors isto establish a consistent total evacus-
\uon time in different occupancies, based on the physical ability,
‘mental aleriness, age, and sociological roles of the occupants
In occupancies where people are housed for care, the time taken
to reach exits will be greater than in some other occupancies,
and so the exits must be sufficiently wide to allow nonambula-
tory occupants to egress and to prevent any waiting fo get into
the exit,
‘Occupant Load
Occupant load, or the number of people to he expected in &
building or an area within a building at anytime for whom exits
‘ust be provided, is determined by the actual anticipated oc-
cupant load but not less than that number obtained by dividing
the gross area ofthe story or the net area of a specific portion
ofthe building by the area inf? (a2 projected foreach person,
‘The amount of floor area projected for each person varies with
the occupancy (Table 4.3.4) These figures are based on actual
counts of people in buildings and on reviews of architectural
plans. Tn some situations, the maximum number of people in a
building ahove the caleulated occupant load can be determined
atthe design stage, in which case tis number shouldbe used in
the design of the exits. Atypical example is an assembly occu-
pancy in which fixed seating is installed. Counting the number
of seats provided, and calculating the standing or waiting areas
by the occupant load factor, would obviously give a more ac-
curate figure than multiplying a f (m?)fperson figure by the
net floor area
‘Computing Required Egress Width
‘To compute the minimum required egress widths from the indi-
vidual floors of a building, the following steps are nevessary
1, Calculate the floor area, either net or gross, whichever is
applicable,
2. Determine from NFPA. 0/ the estimated number of fe?
(os?/person, or occupant load factor
3. Divide the number of ft (ax?)person (occupant load factor)
into the floor area to determine the minimum number of
people for whom exits must be provided for that floor; use
this calculated occupant load or the actual occupant load,
Whichever is higher.
4. Measure the clear width of each component in the means of
egress
5. Determine the capacity factor from NFPA 101 for each exit
‘componeat forthe appropriate occupancy.
6, Divide the clear width of each exit component by the
capacity factor to determine the egress capacity for each
component.
7. Determine the most restrictive component in each egress
system,
8. Determine the total egress capacity for the story.
9. Ensure that the total egress capacity equals or exceeds the
total occupant load,
In mulistory buildings, the egress capacity foreach story is
calculated separately. In other words, the capacity ofthe stairs
need only be wide enough to serve each floor, but it must not
be less than the minimum width required by NFPA 01. It must
also be noted that the requized egress capacity cannot be de-
creased in the direction of egress travel.
Street-floor exits may Fequire special treatment, depending
on the occupancy. Some occupancies require that street-floorTABLE 43.4 Occupant Load Factor )
tie per Perso per Perso Ue 1 per Persons per Peso
‘Assembly Use Detention ad me Ti
Concentrated use, ‘Tet 0.65 net ‘Correctional Use
iho fined seating Residential Use
Less concentrated se, ae Leet Hotels nd dormitories 200 86
thou ined seating ‘Apartentbuings 200 186
Beach-type ceding IpenowI8— I peronéSS———Boud anne, ag 200 86
Tinea newrmm =~ yeauaan ne
Fed seating Nomberef None et Conatantaghtacas 100 os
redseas Bred seats scr an
ating spaces seei2i72 seei2i72
ere fodiyi72 andi ing Secabmumorindusrat NA *
(EPA Jon NEPA 10H
Kitchens 100 93 Storage Use .
He aw ‘oe 2 Tastorage ocupacies xa Na
Library reading rooms sOnet 46 net nen “oo 78
Swimming poo SO(ewersric) Ascuaterauice) NPS soo es
‘Swimming pool decks 30 28 and mercantile
Byercite rooms with so 4s cecupences,
eauipment Mercantile Use
Breriserooms witout 15 M4 Suceson sect 0 as
vipat ea
sige Ison net Sues ea on 0 er “0 a7
Lighingandacescut 100 et 93 net moe set Hews
walks, galleries, gridirons ‘Sales area on floor below 30, 28
Casino aed sia nu 1 sect Dea
mig aes Sales aeacn lorsabove 60 so
stating inks so 4s Seet Dou?
dvcational Use Poorsorporions of See Business See Busnes
Cuseone ovat 19 et floes weedonlyfor Use Ue
‘Shops, laboratories, 50 net 46 net offices
vovatona rors oor o potions of 300 ne
Day-Care Use 35 net 3.3 net ‘floors used only for
HealthCare Use feoge occ and
Tapaticatweetet x0 23 eee
departments ‘Mall buildings* Per factors Per factors
Steping depress 0 ha Tete
Ambulatory beathcae 100 93 ectspace! — Geatspace
oer
[NA Not applicable. The occupant load is the maximum probable numberof oecupats present a ny time
‘all facto ate expressed in gross area unless marked “nel
"Yor the purpose of determining ocupant loud in mercantile ocupancice wher, duo difecaces in grade of eects on
different ides, wo or more floors decly accessible from sects (nt including alleys or vital back els) ert,
‘ach such lor is permed oe considered» sree loo The eceupant lod facior iv ane pron fr each 40 (=
(6.7 1m) of goss lor ares of sales space
‘or the porose of determining occupant loadin mercantile oecypancies wih no street floor, at defined in 3.3239 of
[NEPA UOI. but with atces diced fom the steet by slats of escalates, the Hoot at he point af exance tothe
rmereantle occupancy is considered the suet floor
oF an food cout or other assembly Ue areas lesen the mal hat re notinclued aa potion ofthe gros esable
‘rea ofthe mall bling, te occupant loud sclelated hazed onthe occupant lad factor (or hla a spied
‘Tle 71.2 of NFPA 10] The remaining mal aea isnot equed tobe asigned an occupant load
‘The porions ofthe mall that ar considered a pedestrian Way and ol usd as goss Ieasabe are ate not equte 0 be
‘seed an ocupant load based on Table 7412 of NFPA TOI. However, means of egress rom ama pedestian way
ite required to be provided fran occupant load determined by dividing the gros lesable rea of the ral building
(oot inclaing anchor ores) by ie appropriate lowent whole nmberaccupant [oa actor Irom Figure 731 2(8) oF
Figure 73.120) of NPPA 10!
‘Bach individual ena spac is required to have means of egress to the outside oro the mall based on occupant Loads
“aeulated by using the apropeise occupant oe fate fom Table 7.3.1.2 of NFPA T01
vidal anche totes requed Yo ave means of eget independent of te al,
73.12, NFPA 101 206 eon.
4-834-84 SECTION 4 Human Factors in Emergencies
exits be sized to handle not only the occupant load ofthe street
floor but also the occupant load of the exits discharging to the
street floor from floors above and below. In addition, in those
‘ecupancies where floors above andor below the street floor are
permitted to have unenclosed stats and escalators connecting
them withthe street loor, the exits must be suflicient to provide
simultaneously forall the occupants of all communicating levels
and areas. In other words, all comyunicating levels in the same
fire area are considered a single floor area for the purposes of
determining the required egress capacity. This unified fre arca
factor can have a considerable effect on the sizing of the street-
oor exits
Should two or more exits converge into a common exit,
the common exit should never be narrower than the stm of the
widths ofthe exits converging into it,
Generally, the minimuim number of exits is two In certain
limited situations, however, one exit may be permitted in some
‘occupancies if there isa very low occupant load, low fire hazard,
and a limited travel distance,
EGRESS FACILITIES
AND ARRANGEMENTS:
‘The following egress facilities are covered in NFPA 101
Doors
Doors should be side-hinged or pivoted swinging type and
should swing in the direction of egress travel, except in small
rooms. Horizontal sliding, vertical, ot rolling doors are recog-
nized for use as means of egress in some occupancies. In assem-
bly occupancies, day-care centers, and schools, panic hardware
should be installed on all egress doors equipped with latches
that serve areas with an occupant load of 100 or more.
Where doots protect exit facilities, as in stairway enclo-
sures and horizontal exits, they normally must be kept closed to
limit the spread of smoke. If open, they must be closed imme-
diately in case of fre. Although ordinary, fusible-link-operated
devices to close doors in case of fire are designed to close in
time to stop the spread of fie, they do not operate soon enough
to stop the spread of smoke and are not permitted by NEPA 10/
Atrelatively low temperatures, smoke accumulation cauld con
tinue and could reach untenable levels long before the fusible
ink melts, allowing the door to close
Sometimes, people keep self-closing doors open with hooks
or with wedges under the door, Doors also can be blocked open
to provide ventilation, for the convenience of building mainte-
nance personnel, of to avoid the accident hazard of swinging
doors, The following measures have been provided in the NEPA
101 to alleviate this undesirable situation:
1. Doors that are normally Kept open can be equipped with
door closers and automatic hold-open devices that release
the door and allow them to close when smoke detectors
operate
2. Doors that are normally closed can be equipped to open
electrically or pneumatically when a person approaches the
door, as long as smoke detectors are used to prevent the
door from automatically opening when there is smoke in
the area
3. Doors that normally are closed can be opened and held
‘open manually by monitors, as in schools,
Qualifications and limitations are applicable to each of
these measures. One i that, in the event of electrical failure, the
door must close and remain closed unless itis opened manually
for egress purposes.
‘Another major maintenance difficulty with exit doors isthe
exterior door that is locked to prevent unauthorized access or
for other reasons, NFPA 101 specifies that when the building
is ovcupied, all doors must be Kept unlocked in the direction
of egress.
NFPA 10/ allows a delayed releasing device on some
egress doors, provided ths is permitted by the requirements of
the occupancy in question. Where the devices are allowed, the
following provisions apply’
1. The building must be protected throughout by an approved
and supervised automatic fire detection system ot aulo-
atic sprinkler system,
‘The release devices are installed only in low- or ordinaty-
hazard areas.
[3 The devices must unlock when the fire detection system or
automatic sprinkler system operates.
4. The devices must unlock on loss of power
5. The devices must initiate an ireversible process that will
free the latch within 15 seconds whenever a force of not
more than 15 1b (6.8 kg) is applied to the releasing device,
and the door must aot relock automatically. Operation of
the releasing device must actuate & signal near the door,
6. Asignmasthe placed adjacent to the door that reads: PUSH
UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN
15 SECONDS!
7. Emergency lighting must be provided atthe door, Refer to
NFPA 10/ for mote details and restrictions. Some of the
‘occupancy chapters have further linitations.
[NFPA 0] also provides “Access Controlled Egress Doors:
‘The code spells out several imitations for these. One ofthe limi
tations included is that when an aecupant approaches the door
from the egress side, a sensor must unlock it
Locks on a door that let people exit but not enter are sat-
isfactory, but even this type of lock may not be satisfactory for
security purposes. Possible measures to prevent unauthorized
"use of exit doors include the following’
1. An automatic alarm that rings when the door is opened
2. Visual supervision such as wired-glass panels, closed-
circuit television, and mirrors, which may be used where
appropriate
3. Automatic photographic devices to provide pictures of
So-called exit locks, with a break-glass unit actuated by
stuiking ahandle with the hand, are not permitted by NFPA 107
‘unless installed in conjunction with panic bars. Otzerwise, they
«do not comply withthe NFPA 101 provision that reads: “A late
or other fastening device on a door shall be provided with are-CHAPTER 3 Concepts of Egress Design 4-85.
leasing device having an obvious method of operation and that
is readily operated under all lighting conditions
Other types of break-glass locks and electrical controls
for releasing exits from a central point are not pertted by
NFPA 101. The exception is an occupancy where controls may
be necessary, at in health care or detention and correctional
‘occupancies
A single door in a doorway should not be Less than 32 in,
(813 mm) wide in new buildings and 28 in. (711 mm) in exist
ing buildings. To prevent tripping, the floor on both sides of
the door should have the same elevation for the full swing of
the door,
Panic Hardware
gress doors in assembly, day-care, and educational occupa
cies, such as schools or movie theaters, normally are equipped
with panic hardware, Basically, panic hardware devices are de
signed to facilitate the xlease ofthe latching device oa the door
‘when a pressure not to exceed 15 lb (6.8 ke) is applied in the
direction of ext travel, Such releasing devices are bars or panels
extending not less than one-half of the width of the door and
placed at a height not less than 30 in, (762 mm) of more than
Ain. (1.1 m) above the floor.
Panic hardware that has been tested and listed for use on
fire-protection-rated doors is termed “fire exit hardware” If
panic hardware is needed on fire-protection-rated doors, only
fire exit hardware i to be used,
Panic hardware is available for use on single and double
doors, with Vatitions for rim-mounted hardware and mortise ot
vertical rod devices.
Horizontal Exits
A horizontal ext is a means of egress from one building to an
area of refuge in another building on approximately the same
level, ora means of egress through a 2 hour fire barrier ‘oan area
of refuge at approximately the same level in the same building
that affords safety from fire and smoke. With a horizontal exit, it
is obvious that space must be provided in the ares or building of
refuge forthe people entering the refuge area, NFPA 10/ recom
‘ends 3 1€ (0.28 m*) of space per person, with the exception of,
healthcare or detention and correctional occupancies, where 6
to 30 ft (0.56 to 2.79 m) of space is recommended, Horizontal
exits cannot comprise more than one-half te total required exit
capacity, except in healthcare facilites, where horizontal exits
‘may comprise two-thirds ofthe total required exit capacity, and
in detention and correctional facilities, where horizontal exits
‘ean comprise 100 percent of the total exit capacity, Horizon.
tal exits have been applied universally in health care facilities
‘where the evacuation of patients over stairs is slower and more
difficult than taking them through a horizontal exit toa safe area
of refuge. A horizontal ext arrangement within a single building
and belween two buildings is illustrated in Figure 4.3.10,
AA swinging door ina fie wall provides a horizontal exit in
‘one direction only. Two openings, each with a door swinging in
the direction of ext wavel, are needed to provide horizontal exits
{rom both sides ofthe wall. Where property protection requires
Fine
TWwoowayhorzora extn
anoperston sulaeg
Serrebsing ve door
requred fre separation
FIGURE 4.3.10 Types of Horizontal Exits
Sling At bung. Sactoeng
br aulomale-clsing ve dors ana
Protected passage reaurea
fire doors on hoth ses ofthe wall, a normally open, automatic,
fusibleclink-operated, horizontally sliding fire door may be used
(on one side, wi a swinging fie door oa the other.
Stairs
[Exit stars are arranged (0 minimize the danger of falling, be-
‘cause one person falling on a stairway may result in the eom-
plete blockage of an exit, Stairs must be wide enough for (wo
persons to desvend side by side, thus maintaining a reasonable
rate of evacuation, even though aged or mobility-impaired per
sons may slow the tavel on one side, There must beno decrease
in the width ofthe stair along the path of travel, since this may
create congestion
Steep stairs are dangerous, Stair treads must be deep
enough to give good footing. NEPA 10/ specifies a minimum
11 i, (279 mm) tread and a maximum 7 in. (178 mm) riser for
new stairs. Landings should be provided to break up any exces-
sively long individual flight, Continuous railings are now rec-
‘ommended for new stairs, New stairs more than 60 in, (1.5 m)
wide should have one or more center rails. Beginning with
the 2006 edition of NFPA 101, new very tall buildings will be
required to have wider stairs, Ifa stair serves a total of more
‘than 2000 people there are mote stringent width requirements
to accommodate better flow (allowing for easier passing and
{or easier movement of mobilily-impaired persons) as well as
counter flow (allowing fixe fighters with equipment up while
‘occupants are evacuating).
Prior to 2006, to classes of stairs were permitted in NFPA
10] for existing buildings, with single clas of stairs for new
staits, There were Class A and Class B stars for existing build-
ings. Stating with the 2006 edition the provisions for Class A.
sits were deleted from the code and now there is one set of
requirements for new and one for existing, The requirements
are given in Table 43.5,
Stairs can serve as exit access, exit, or exit discharge. When
used as an exit, they must be in an enclosure that meets exit
enclosure requirements or outside the building and properly
protected, Exit access sais that comsect two or mote stories axe
vertical openings and must be protected as vertical opening.
Stairways may be inside the building where NFPA 101 gen-
cally specifies protective enclosures, They also may be outside4-86 SECTION 4 © Human Factors in Emergencies
TABLE 4.3.5 Requirements for New and Existing Bulling Stairs )
Nev Siaire Existing Stairs
‘Minimum with clear of all 44in. 12m) 36 in (0.91 m)
obstructions except projections 36in. (091 m) 36 n. (0.91 m)
not exceeding 3¥+ in. (0-89 mm) Where total occupant load
at and below handsail height on ofall floors served by
each side stairways i less than 50
‘Maximum eight of rises Tin. (178 mm) Sin. (203 mm)
‘Minimum height of risers 4 in, (102 mm) _
Mininvam tread depth in, 279 mm) in, (229 mm)
‘Minimum headroom 68in 2.03 m) 618in 2.03 m)
‘Maximum height between landings 2RG7m) 126G.7m)
Minimum dimension of landinge
in direction of tavel,
Stairways and intermediate landings shall continue with no decrease in width along
the direction of exit iavel In new buildings every landing shall have a dimension,
measured in direction of travel, equa tthe width ofthe sta Such dimension need
not exceed 4 f (1.22 m) when the stair has a straight run.
Doors opening immediatly on stat, No
without landing a least width of
door
No
if they comply withthe requirements for exterior stairs and are
arranged so that persons who fear heights will not be reluctant
‘o.use them, aze not exposed to fre conditions originating i the
‘building, and, where necestary, are shielded from snow and ice
Exterior stairs should not be confused with fire escape stairs
Figure 4.3.11), Exterior stairs as shown in the figure can be
used in many types of occupancies, such as schools, motels,
small professional buildings, and so on. Note that there are wo
_means of egress, emote from each other, from the second-story
balcony.
Construction details of star enclosures i
lve the princi-
piles of limiting fie and smoke spread, Doors on openings from
each story are essential to prevent the stairway from serving as a
‘Aue. In general, stairway enclosures should include not only the
Ordinary glee
nao
ooouYy
cool!
FIGURE 4.3.11 Outside Stairs Providing Direct Exits to
the Outside for All Rooms in a Mulistory Building, There
are no interior corridors through which smoke and flame
could spread,
stair, but also the path of travel from the bottom of the stairs to
the exit discharge, so that occupants have a protected, enclosed:
passageway all the way out ofthe building. The stair enclosure
should be of | hour construction when connecting three or fewer
floors and of 2 hour construction when connecting four or more
floors
Smokeproof Enclosures
‘Smokeproot enclosures provide the highest protected type of
stair enclosure recommended by NFPA 101. Access tothe stair
is only by balvonies open to the outside air, vented vestibules,
‘or mechanically pressurized vestibues, so that smoke, heat, and
‘lame will nt spread readily into the tower even if the doors are
accidentally left open (see Figure 4 3.9).
Ramps
Ramps, enclosed and otherwise arranged like stairways, are
sometimes used instead of slairways where there are large
crowds and to provide both access and egress for nonambula-
tory persons. To be considered safe, exits ramps must have &
very gradual slope.
Exit Passageways
Anhallway, corridor, passage, tunnel, or underfloor or overhead
passageway may be designated an exit passageway, providing
‘is separated and arranged according to the requirements for
exits
‘The use of a hallway or corridor as an exit passageway in-
leoduces some unique considerations. The use of these spaces
for purposes other than exiting may violate fundamental design
considerations. In an industrial situation, for example, the use
‘of a gasoline-powered forklift in a corridor designated as an
‘exit passageway would violate the principles of exit design,CHAPTER 3 Concepts of Egress Design 4-87
NFPA 101 specifies that an exit enclosure should not be used
for any purpose that could interfere with its value as an exit and
is strictly limited by the code. Furthermore, penetration of the
enclosure by ducts and other tities may violate the protective
enclosuze
Each opening in an exit enclosure introduces a point of
‘weakness that could allow fire contaminants to spread into the
exit and prevent its use. The typical comridar used as an exit with
numerous door openings could result in fire contamination of
the enclosure if a door fails to close and latch, The door open-
ings in exit enclosures should be limited to those necessary for
access to the enclosure from normally occupied spaces. There
Tore, doors and other openings to spaces such as boiler rooms,
storage spaces, trash rooms, and maintenance closets are not
allowed into an exit passageway
‘An exit passageway should not be confused with an exit
access corridor. Exit access corridors do not have as stringent
construction protection requirements as do exit passageways,
because they provide access to an exit rather than being an ex-
tension and component of the exit. In Figure 4.3.6 the passage
between B, and Dy is an exit passageway.
Fire Escape Stairs
Fire escapes are, at best, a poor substitute for standard interior
‘or exterior stairs. NEPA 101 only permits existing fire escapes
inexisting buildings: for some occupancies they aze not allowed
even for existing buildings. Existing fire escape stairs can be
rebuilt, but new fire escapes cannat be installed on an existing
building unless specifically approved by the authority having
jurisdiction
‘The same principles of design apply to fire escapes that
apply to interior stairs, though requitements for width, pitch,
and other dimensions are generally less strict. NFPA 101 gives
{he following eriteria for fire escape stair design.
Fire escape stairs ideally extend tothe stret or to ground
level, When sidewalks would be obstructed by permanent
sats, swinging stair sections designed to swing down under
the weight of a person may be used for the lowest flight of the
fire escape stairs. The area below the swinging section must be
kept unobstructed so the swinging section ean reach the ground,
‘A counterweight ofthe type that balances on a pivot should be
provided for swinging stars; cables should not be used. Fire
‘escapes that end on balconies above the ground level and pro-
Vide no way to reach the ground, except by portable ladders or
jumping, are unsafe,
“Many persons who fear heights are reluctant to use fire es
capes. As far as possible, design should provide a sense of secu.
sity aswell as suitable railings and other details actually needed
{or safety, Fire escapes must be well anchored to building walls
and kept painted to prevent rust,
Preferred access lo fire escapes is through doors leading
{rom the main building area or from corridors, never through
rooms that may have locked doors except where every room
‘or apartment has separate access to a fire escape. Although
preferred access to fire escapes is by doors, windows may be
"used, in which case sills should not be toa high above the floor.
Windows should be of ample size, and, if insect screens are
installed, they should be of a type that can be opened or re-
moved quickly and easily. Decorative grilles or security bars
should not be installed over windows that provide access to
fire escapes
Fire escapes can create a severe fire exposure to people
if flames come out windows beneath them (Figure 4.3.12)
‘The best location for fie escapes is on exterior masonry walls
without exposing windows, with access t fire escape balconies
by exterior fire doors. Where window openings expose fire e3-
capes, fixed wired glass in metal sashes should be used. Where
there is a complete standard automatic sprinkler system in the
‘building, the fie exposure hazard to personnel on fire escapes
is minimized.
Innorthem climates, outside
by snow and ice
1c escapes may be obstructed,
Escalators, Moving Walkways,
and Elevators
In some occupancies, escalators may be recognized as egress in
ceisting buildings. However, they are seldom installed in such
a way that they would qualify as exits, and itis common to find
escalator installations with unprotected floor openings. Escala.
{os are nol recognized as an acceplable component in a means
of egress in new construction in any occupancy and in existing
conditions in many occupancies.
‘Moving walkways also may be used as existing means of
egress if they conform to the general requirements for ramps, if
inclined, and for passageways, if level,
Elevators ate not recognized as exits, However, elevators axe
permitted tobe used, under limited conditions, (o serve ateas of
refuge for the mobility impaired, The Life Safety Code also rec-
‘ognizes elevators, under very limited conditions, asthe second
exit from limited-aocess towers such as FAA control towers. As
‘mentioned earlier, there is significant research being conducted
in an attempt to develop ways to use elevators for egress
my
ya
FIGURE 4.3.12 The Makeshift, Often Dangerous Aspect
of Fire Escapes. Fire may make fire escapes useless as this
picture, drawn from a photograph ofan actual fire, shows.4-88 SECTION 4 © Human Factors in Emergencies
Areas of Refuge
Since 1991, NFPA 101 as listed “areas of refuge” as a spe-
cific means of egress element, Although they are beneficial 1o
all people, their primary purpose is for people with difficulty
using stairs. All new buildings must address the issue of “aeces-
sible means of egress." In most new nonsprinklered mulistory
buildings, this will require some form of area of refuge. Figures
43.13 and 4.3.14 illustrate two methods for providing areas of
‘refuge in nonsprinklered buildings.
Ropes and Ladders
Ropes and ladders generally are not recognized in codes as @
substitute for standard exits [som a building. This is proper since
there is no excuse for permiing their use except possibly in
existing one- and two-family dwellings where itis economically
{impractical to add a secondary means of esvape. In this case, a
tuilable rope or chain ladder or a folding metal ladder may be
suitable, However, the homeowner should recognize that aged,
infirm, very young, and physically handicapped persons cannot
FIGURE 4.3.13 Exi
tar Used as an Area of Refuge,
‘When stair landings are used as an area of refuge, the stairs
are requited toe 48 in, (122m) between handrails to
accommodate carrying persons in wheelchairs.
LJ
FIGURE 4.3.
Areas of Refuge in Nonsprinklered New
‘Construction. In this case the story is subdivided by either a
horizoatal exit ora I hour fice resistance rated stoke hati,
Each sie ofthe barrier isan area of refuge forthe other
side. Ifthe smoke bait is used the stairs are required (o be
48 in. (122 em) between handrails to acommodate carying
persons in wheelchairs.
use ladders and that, ifthe ladder passes near or over a window
in alower floor, flames from the window can prevent the use of
the ladder
Windows
Windows are not exits, They may be used as access to fire ¢s-
capes in existing buildings if they meet certain criteria concern-
ing the sizeof window opening and the height ofthe sill from
the floor. Windows may be considered a means of escape from
certain residential occupancies.
Windows are required in school rooms subject to student
cccupancy, unless the building is equipped with a standard au-
tomatic sprinkler system, and in bedrooms and living areas in
fone- and two-family dwellings that do not have two separate
means of escape. These windows are for rescue and ventilation
and must meet the criteria for size of opening, method of opera-
tion, and height from the floor.
EGRESS LIGHTING AND EXIT SIGNS
Egress Lighting
‘In buildings where artificial lighting is provided for normal use,
the illumination of the means of egress is required to ensure
that occupants can evacuate the building quickly, The intensity
of the illumination of the means of egress should be not less
than 1 footcandle (10.77 lu's*) measured at the floor. Itis desit-
able that such floor illumination be provided by light recessed
i the wall and located approximately 1 ft (30.5 cm) above the
‘loor because such lights are then unlikely to be obscured by
the smoke that might occur during a fre, In auditoriums and
other places of assembly where mavies or other projections are
shown, NFPA 10/ permits a reduetion in this illumination for
the period of the projection to values of not less than 4 foot-
candle (2.2 lwim?)
Emergency Lighting
NEPA 101 requites emergency power for illuminating the
‘means of egress in many occupancies. For exatmple, emergency
lighting is required in assembly occupancies; in most educa-
tional buildings; in health care facilities; in detention and cor-
rectional facilities; in most hotels and apartinent buildings: in
Class A and B mercantiles; in business buildings based on oceu-
‘pant load and number of stories: in most industrial and storage
buildings: and in underground or windowless structures subject
to occupancy by more than 100 persons.
Well-designed emergency lighting using « source of power
independent from the normal building service automatically
provides the necessary illumination in the event of an interup-
tion of power to normal lighting. The flute of the pubic uiity
or other outside electric power supply, the opening of a circuit
breaker or fuse, or any manual at, including accidental opening
of switch controlling normal lighting facilities, should result in
the automatic operstion of the emergency lighting system,
Reliability of the exit illumination is most important
NFPA 70, National Electrical Code®, details requirementsCHAPTER 3 Concepts of Egress Design 4-89
{or the installation of emergency lighting equipment. Battery
operated electric lights and portable lights normally are not
used for primary exit illumination, but they may be used as
‘an emergency source under the restrictions imposed by NEPA.
101, Luminescent, uorescent, of other reflective materials aze
nota Substitute for required illumination, because they are not
normally sufficiently intense to justify recognition as exit floor
illumination, However, such items aze being used to supple-
‘ment emergency lighting. And, a is discussed under exit signs
below, code-compliant luminescent exit signs are now being
‘manufactured,
‘Where electric battery-operated emergency lights ae used,
suitable facilities are needed to keep the batteries properly
charged. Automobile-type lead storage batteries are not si
able because of their relatively shor life when not subject 10
Frequent recharge, Likewise, dey batteries have a limited life,
and there ie a danger that they may not be replaced when they
hhave deteriorated,
If normal building lighting fails, well-eranged emergency
lighting provides necessary floor illumination automatically,
with no appreciable interruption of illumination during the
changeover. Where a generator is provided, a delay of up to
10 seconds is considered tolerable, The norntal procedure is
to provide such emergency lighting for « minimum period of
hours, Most health care occupancies have self-contsined
clectrie generating plants for emergency power supplies, not
‘aly for exit lighting but also for use inthe event of failure of
the public utility, Where such emergency electric facilites are
provided, they may supply power for emergency exit lighting,
as well as other critical azeas of such buildings.
Exit Signs
All requized exits and access ways must be identified by readily
visible signs where the exit or the way to teach itis not imme-
diately visible to the occupants, Directional “EXIT” signs are
required in locations where the direction of travel to the near
cst exil is nol immediately apparent, The character of the accu:
ancy will determin the actual need for such signs. In assembly
‘occupancies, hotels, department stores, and other buildings with
‘wansient populations, the need for signs will be greater than in
‘building with permanent or semipermanent populations. Even
in permanent residental-occupancy buildings, signs are needed.
to identify exit facilites, such as stats, that ate not used regu:
larly during the normal occupancy of the building. Itis just as
‘important that doors, passageways, or stirs that are not exits but
are so located or arranged that they may be mistaken for exits be
identified by signs with the words “NO EXIT”
Signs should be so located and of such size, color, and de
sign as to be readily visible, Care should be taken not to ob-
scure the visibility of these signs with decorations, furnishings,
(or other building equipment, NFPA J0/ does not make any spe-
cific requirement for sign color bat requires that signs be of a
distinctive color. Some local codes do specify exit sign color
NFPA 10/ specifies the size of the sign, the dimensions of the
Jeers, and the levels of illumination for externally illuminated
signs, For internally ilhuminsted signs, the code mandates com:
pliance with UL 924, Standard for Emergency Lighting and
Power Equipment, This performance-ated standard provides
rods to ealate deren pes of ext ins nluing Iv
Improvement in the physical matkng of exis in an office
cecupancy wih peine-soure, redo green sucbe gh as been
Suggested Placing coor luninaion on the wall close ote
oor o provide etetve illumination under snoke conditions
ase the practice in Japan ia ecniqu worthy of research
ALARM SYSTEMS
Fire alarm systems to alert occupants to leave the building are
normally operated manually. The alarm-sounding devices them-
selves should be distinctive in pitch and tone quality from all
other sounding devices, and the use of these devices should be
restricted to evacuation notification. Vocal alarm systems have
been developed and installed in many high-rise buildings."
NFPA 10] mandates voice alarm and communication systems
in high-rise buildings. I is, of course, very important that ll
alarm system devices be distributed throughout a building so
as tobe heard effectively in every room above all other sounds.
Visible, as well as audible, alarm devices are sometimes used
in buildings. NEPA 101 permits flashing the exit signs with the
activation of the fre alarm system. In new construction, vis-
ible alarms must be provided in addition to sudible alarms in
‘most instances. Advances in alarm technology, such as direc-
tional sounders, are now being used to assist people in finding
the exits
‘The proper maintenance of alarm systems is most impor:
tant, Alarm systems should be supervised by a responsible per-
son Who will make the proper tests a specified intervals and will
take charge of all alterations and additions tothe systems.
EMERGENCY EGRESS
AND RELOCATION DRILLS
Emergency exit and relocation drills are essential in schools
and are desirable in every type of occupancy to ensure familiar
ity with the exits and their operation. In occupancies such as
bospitals, nursing homes, hotels, and department stores, drills
are usually imited to employee participation, without alarming
patients, guests, or customers. Drills should be planned to get
everyone out of the building orto an area of refuge in an orderly
‘manner, as promplly as possible. Fire fighting is always second-
ary to life safety, and, in general, firefighting operations should
not be started until the evacuation is completed, except in cases
‘here trained fire departments conduct rescue and fire-fighting
‘operations simultaneously.
Drills should be held at least once a month or more often,
but not at regularly scheduled periods. Drills should occur on
all shifts in an occupancy operated 24 hours a day, They should
simulate typical fire conditions for the occupancy. Drills, both
with and without warning, are beneficial
School emergency egress and relocation drills are an exer-
cise in discipline, not speed, though reasonably prompt evacu-
ation of a building is important. Students and staff should not
be permitted to stop to put on coats. No individuals should be4-90 SECTION 4 © Human Factors in Emergencies
Permitted to remain in the building, and no one should be ex-
cused {rom participating in the drill. The drill should include a
roll call by class at designated assembly areas outside the build-
ing to make sure that no one has been left behind
‘There also should be an established routine for a complete
check of the entire building, including toilets, to make sure that
no one has been left behind, All exits should be used in drill,
‘but routes should be varied from dill to drill. Occasional drills
should be eld that simulate conditions of an ext blocked by fire
cor smoke, Al drills should simulate the fre department notitica-
tion procedure. For a more detailed discussion of fre exit drill,
see Chapter 1 ofthis section.
MAINTENANCE OF THE.
MEANS OF EGRESS.
‘The provision of a standard means of egress with adequate
capacity does not guarantee the safety of the occupants in the
event of an evaevation of any building. Means of egress that are
‘not properly maintained can mean loss of life in afte. Property
managers usually asign definite responsibility for maintenance
‘of mechanical and electrical equipment but may fail to do the
same for the means of egress. Asa result inspection authorities
ray find olherwite safe stairways used as storage for materials
during peak sales or manufacturing periods. In apartment build-
ings, rubbish, baby carriages, and other obstructions are often
found in stairway enclosures. Exit doors may be found locked
or hardware in need of repair. Doors blocked open or removed
from openings into stairway enclosures may permit rapid spread
of smoke or hot gases throughout the building. Loose handrails
and loose or slippery stair treads offer the dangerous probability
that persons evacuating a building will fallin the path of others
seeking escape. Maintaining the exit discharge free ofthe accu-
‘mulation of ice and snow in climates subject to such weather is
very critical. Maintaining the means of egress in safe operating
condition at all times is 3s important tothe prevention of loss of.
life as the proper construction ofthe building and the elimins-
tion of fie hazards
SUMMARY
Providing adequate means of egress is «key fire safety issue in
both new buildings and existing facilities. NFPA 101 provides
indepth coverage for providing adequate means of egress. For
new constriction, many ofthe issues are also covered i build
ing codes, including NFPA 5000. This chapter only introduces
the subject. To more completely understand the subject, both the
NEPA Life Sfety Code® Handbook an the SEPE Handbook of
Fire Protection Engineering should be consulted.
BIBLIOGRAPHY
References Cited
1. Bryan, 1.B., "Behavioral Response to Fite and Smoke,” SFPE
Handbook of Fire Protection Engineering, Nationa Fie Protec-
{on Assocation, Quiney, MA, 2002.
20.
2
Proulx, G,, "Movement of People: The Evacuation Timing,
SEPE Handbook of Fire Protection Engincerng, National Fre
Protection Association, Qiney, MA, 2002
Nelson, HE. and Moore, F W,, "Emergency Movement
SEE Handbook of Fre Protection Engineering, National Pte
Protection Asorition, Quincy, MA. 2002.
ruin J.J. Pedesirian Planning and Design, Metropolitan As-
seciaton of Urban Desigers and Eavironmeatal Planners ne,
New York, 1977
Pauls, 1, "Movement of People in Building Bvacuations
Human Response o Tall Buildings, Down, Hutchinson and
Ross, Ine. Stroudsburg, PA, 1977
‘Second Report ofthe Operational Research Team onthe Capac
ity of Footways” Research Report No. 85, London Transport
Board, London, UK, 1958
Pesls, JL, "Calculating Evacuation Times for Tall Buildings
Fire Safery Journal, 1981, pp. 113-235,
Pauls, FL, "The Movement of People in Buildings and Design
Solutions for Means of ress,” Fire Technology, Vol 20, No
1986, pp. 27-47.
Abbot I. C, "Fire Involving Upholstery Materials
nat Vol. 65, No.4, 1971, p88,
Lhcep, JK. eta, "In Osceola: A Mater of Contents" Fire
Tournal, No. 68, No 3, 1975, pp. 20-26.
Hall J.., Burns, Toxte Gases, ad Orher Hazards Associated
ith Fires! National Fire Protection Assocation, Fite Analysis
tnd Research Division, Quincy. MA. 1996,
‘Shary, A. “South Ameriea Burning." Fire Journel, Vo. 68,
Nov, 1974 pp. 23-33,
Best, R, and Demers, .P, "Fite atthe MGM Grand” Fire
Tournal Nol 75, No, 1982, pp. 19-37
Powers, W.R, “New York Otic Building Fite,” Fire Journal
Vol. 65, Ne. 11971, pp. 18-23, 87
Keating, IP, etal, Am Evaluation ofthe Federal High Rise
Emergency Evacuation Procedures, Deparment of Psychology,
University of Washington, Seattle, 1978.
Peale, JL, "Evacuation and Other Fite Safety Measures in
High-Rise Buldings” Research Paper No. 648, National Re
secarch Council of Canada, Division of Building Research, Ot-
tawa, 1975,
Pauls, JL, "Management and Movement of Building Occupants
in Emergencies,” Research Paper No. 748, National Research
Council of Canada, Division of Building Research, Otawa,
1978,
Philips, AW, "You and the High-Rise Building Fie” Tel:
ony Report 741, Society of Fire Protection Enginests, Boson,
1978,
Krasny, JF, etal, "Development ofa Candidate Tes Method
for the Measuremeat of te Propensity of Cigarettes to Cause
Smoldering Ignition of Upholstered Furiture and Mattvesss,”
[NBSIR 81-2363, Center for Fite Reseach, National Bureau of
Standards, Washington, DC, 1981
(CER Par 1623, Standard for the Flammability of Matresses and
-Manirees Pads, FF=8-72, 40 FR 59940, US. Consumer Product,
Safety Commision, Washington, DC, 1972,
Bejan J-L-, "Human Behavir in the MGM Grand Hotel Fite”
Fire Journal, Nol. 16, No.2, 1982, pp. 37-81, 44-8,
Keating, JP, and Lofter, EE, “The Logic of Fire Besape,"Pay=
chology Today, 1981, pp. 14-19.
Keating, 1B, “The Myth of Panic” Fire Journal, Vol. 76, No.3,
1982, pp. 57-51, 147,
Shaty, A. "Real-Wodld Problems with Zoned Evacuation’
Fire Journal Vol. 71, No.2, 1983, pp. 32-33, 55.
Macdonald, J N.,Non-Bvacuation in Comparmmented Fie
Recieve Buildings Can Save Lives and Mater Sense, 8th
NFPA Annual Mecting, New Orleans, LA, May 28,1984
Cohn, B.M., Study of Human Engincering Considerations in
Emergency Eutng from Secure Spaces, Gage Babcock & Asso~
ciation, Ine, Chicago, 1978
Fire Jour:CHAPTER 3 Concepts of Egress Design 4-91
[NFPA Codes, Standards, and Recommended Practices
Reference tothe following NEPA codes, standards, and recommended
‘practices will prove further information on concepts of egres design
‘iscusred i thi chapter (See the latert version of The NFPA Catalog
Jor avallabilty of current editions of he following documents.)
NEPA 1, Uniform Fire Code
NEPA 13, Standard for Installation of Sprinkler Systeme
[NEPA 10, Navional Electrical Code™
NEPA 80, Standard or Fire Doors and Other Opening Protectves
NEPA 107°, Life Safety Code®
NEPA IOLA, Guide om Alteative Approaches to Life Safery
NEPA 253, Standard Method of Tet for Critical Radiant Flu of
Floor Covering Systems Using a Radiant Heat Energy Source
[BPA 255, Standard Method of Test of Surface Burning Characters.
His of Building Materials
[NEPA 260, Standard Methods of Tests and Clasifiation System for
CCigareste Ignition Resistance of Components of Uphalatered
Parniture
[NEPA 261, Standard Method of Tet for Determining Resistance of
‘Mock Up Upholstered Furniture Material Assemblies to Ignition
dy Smoldering Cigareter
[NFPA 286, Standard Methods of Fee Tests for Evaluating Contrib
sion of Wall and Ceiling Interior Finish to Room Fire Grovah
[NEPA 914, Code for Fire Protection of Historic Sractures
[NEPA 3000, Bulding Construction and Safry Code™
References
“Design and Construction of Building Exits” Miscellaneous Publica
tion MSI, 1935, National Bure of Standards, Washington, DC,
pp 30-87 (Out af pint)
UL9DA, Standard for Emergency Lighting and Power Equipment