Modbus en 1 23

This document describes the configuration of a Modbus DP 1 VISU 23 industrial controller. It lists the register addresses, data types, and descriptions of various sensor and status values stored in the controller's memory blocks, including identification information, operating parameters, error counts, sensor readings, module statuses, and more. The data ranges from 8-bit values like sensor states and counters, to 16-bit values like temperatures and voltages, to 32-bit values like error counts. Module status registers indicate the active, warning, error or other states using bit fields.

Uploaded by

bnx5dkq786
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
38 views

Modbus en 1 23

This document describes the configuration of a Modbus DP 1 VISU 23 industrial controller. It lists the register addresses, data types, and descriptions of various sensor and status values stored in the controller's memory blocks, including identification information, operating parameters, error counts, sensor readings, module statuses, and more. The data ranges from 8-bit values like sensor states and counters, to 16-bit values like temperatures and voltages, to 32-bit values like error counts. Module status registers indicate the active, warning, error or other states using bit fields.

Uploaded by

bnx5dkq786
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

Modbus DP 1 VISU 23

Start End type description

8192 8192 u 16bit High (8bit): Visu-ID, Low (8bit): reserved


---
HHHH HHHH LLLL LLLL

8193 8193 u 16bit High (12bit): part number; Low (4bit):reserviert


---
HHHH HHHH HHHH LLLL

8194 8195 u 32bit Serial number

8196 8196 u 16bit motor sensor ohmic value


1-65535Ω, 0 = not present

8197 8197 u 16bit Discharge sensor ohmic value


1-65535Ω, 0 = not present

8198 8198 u 16bit error Messages


Bit 0: 0 = no error , 1 = at least one error is current appending

8199 8199 u 16bit status messages


Bit 0 - Engine status: 0 = Motor stands still; 1 = motor running
Bit 1&2 - PTC temperature range -> 0=low; 1=increased-; 2=critical; 3=off

8203 8203 s 16bit Discharge gas temperature

8206 8206 u 16bit High (8bit): Major Software Revision Number


Low (8bit): Minor Software Revision Number
Arrangement: HHHH HHHH LLLL LLLL

8210 8210 u 16bit Variants to Articles Main Number


S = number of transferred value
0-9999
P-number = (transmitted value) - 10000
10000-19999

8211 8211 u 16bit voltage key


22=DualVoltage 115-230VAC
31=24VAC
13=24VDC

8212 8213 u 32bit Total error shutdowns


Arrangement: LLLL LLLL LLLL LLLL HHHH HHHH HHHH HHHH
0-327675

8214 8215 u 32bit Total operating shutdowns


Arrangement: LLLL LLLL LLLL LLLL HHHH HHHH HHHH HHHH
0-327675

8216 8216 u 16bit Current hour period in seconds (internal time)


0…3599 seconds

Modbus DP 1 VISU 23 13. Aug. 18 1 / 11


Modbus DP 1 VISU 23

Start End type description

8218 8218 u 8bit State oil differential pressure sensor


0 = not in use
1 = Differential pressure bad
2 = Differential pressure good
3 = Short circuit
4 = Sensor disabled
---------
For future sensors
5 = Open circuit
6 = Wrong sensor
7 = Not screwed in

8220 8220 u 16bit motor voltage L1-L2


0 = not used for motor status = 1
1…65535 motor voltage

8221 8221 u 16bit Motor voltage L2-L3


0 = not used for motor status = 1
1…65535 motor voltage

8222 8222 u 16bit motor voltage L3-L1


0 = not used for motor status = 1
1…65535 motor voltage

8223 8223 u 16bit average frequency (all 3 phases)


0 = not assigned
1 = frequency 0 Hz
2 = wrong phase sequence
3 ... 65535 motor frequency in Hz

8224 8224 u 16bit Actual current value current sensor 1


Current = (transmitted value) / 10
0,1-1310,6A
0 = sensor short circuit
13107 = sensor interruption

8228 8228 u 8bit Number of hours of the current day (internal time)
0-23h

8230 8230 u 8bit Total number of starts of the current day (internal time)
0-255

8232 8232 u 8bit Total number of starts of the last day (current day - 1 day, internal time)
0-255

8233 8233 u 8bit Total number of the starts of the penultimate day (current day - 2 days, internal time)
0-255

8234 8234 u 8bit Total number of starts of the third day (current day - 3 days, internal time)
0-255

8235 8235 u 8bit Total number of starts of the fourth day (current day - 4 days, internal time)
0-255

8236 8236 u 8bit Total number of starts of the fifth last day (current day - 5 days, internal time)
0-255

Modbus DP 1 VISU 23 13. Aug. 18 2 / 11


Modbus DP 1 VISU 23

Start End type description

8237 8237 u 8bit Total number of starts of the sixth day (current day - 6 days, internal time)
0-255

8238 8238 u 8bit Asymmetry value for the 3-phase network


0…100%

8240 8240 u 8bit Switching cycles per hour - current hour


0-255

8241 8241 u 8bit Switching cycles per hour - current day


0-255

8242 8242 u 8bit Maximum of the switching cycles per hour of the last day (current day - 1 day, internal
time)
0-255

8243 8243 u 8bit max. Switching cycles per hour - 48 hours ago
0-255

8244 8244 u 8bit max. Switching cycles per hour - 72 hours ago
0-255

8245 8245 u 8bit max. Switching cycles per hour - 96 hours ago
0-255

8246 8246 u 8bit max. Switching cycles per hour - 120 hours ago
0-255

8247 8247 u 8bit Maximum of the switching cycles per hour of the sixth last day (current day - 6 days,
internal time)
0-255

8248 8248 u 16bit Module state motor temperature monitoring


High Byte: actual status according error list
Low Byte: modul status Bit coded
Bit 0 = Active
Bit 1 = Warning
Bit 2 = Error
Bit 3 = time delay active
Bit 4 = locked out
---
HHHH HHHH LLLL LLLL

8249 8249 u 16bit Module state discharge gas temperature monitoring


High Byte: actual status according error list
Low Byte: modul status Bit coded
Bit 0 = Active
Bit 1 = Warning
Bit 2 = Error
Bit 3 = time delay active
Bit 4 = locked out
---
HHHH HHHH LLLL LLLL

Modbus DP 1 VISU 23 13. Aug. 18 3 / 11


Modbus DP 1 VISU 23

Start End type description

8250 8250 u 16bit Module state motor temperature monitoring dynamic


High Byte: actual status according error list
Low Byte: modul status Bit coded
Bit 0 = Active
Bit 1 = Warning
Bit 2 = Error
Bit 3 = time delay active
Bit 4 = locked out
---
HHHH HHHH LLLL LLLL

8251 8251 u 16bit Module status relay monitoring


High Byte: actual status according error list
Low Byte: modul status Bit coded
Bit 0 = Active
Bit 1 = Warning
Bit 2 = Error
Bit 3 = time delay active
Bit 4 = locked out
---
HHHH HHHH LLLL LLLL

8252 8252 u 16bit Module state switching frequency monitoring


High Byte: actual status according error list
Low Byte: modul status Bit coded
Bit 0 = Active
Bit 1 = Warning
Bit 2 = Error
Bit 3 = time delay active
Bit 4 = locked out
---
HHHH HHHH LLLL LLLL

8254 8254 u 16bit Module state oil differential pressure monitoring


High Byte: actual status according error list
Low Byte: modul status Bit coded
Bit 0 = Active
Bit 1 = Warning
Bit 2 = Error
Bit 3 = time delay active
Bit 4 = locked out
---
HHHH HHHH LLLL LLLL

Modbus DP 1 VISU 23 13. Aug. 18 4 / 11


Modbus DP 1 VISU 23

Start End type description

8255 8255 u 16bit Module state phase monitoring


High Byte: actual status according error list
Low Byte: modul status Bit coded
Bit 0 = Active
Bit 1 = Warning
Bit 2 = Error
Bit 3 = time delay active
Bit 4 = locked out
---
HHHH HHHH LLLL LLLL

8260 8260 u 16bit Module state generaly


High Byte: actual status according error list
Low Byte: modul status Bit coded
Bit 0 = Active
Bit 1 = Warning
Bit 2 = Error
Bit 3 = time delay active
Bit 4 = locked out
---
HHHH HHHH LLLL LLLL

8262 8262 u 16bit Module state supply voltage monitoring


High Byte: actual status according error list
Low Byte: modul status Bit coded
Bit 0 = Active
Bit 1 = Warning
Bit 2 = Error
Bit 3 = time delay active
Bit 4 = locked out
---
HHHH HHHH LLLL LLLL

8264 8264 u 16bit Actual state of modul current sensor 1,


High Byte: actual status according error list
Low Byte: modul status Bit coded
Bit 0 = Active
Bit 1 = Warning
Bit 2 = Error
Bit 3 = time delay active
Bit 4 = locked out
---
HHHH HHHH LLLL LLLL

8268 8269 u 32bit Operating time in the low motor temperature range
Operating time = (transmitted value) * 10
0 - 4,294,967,296
---
LLLL LLLL LLLL LLLL HHHH HHHH HHHH HHHH

Modbus DP 1 VISU 23 13. Aug. 18 5 / 11


Modbus DP 1 VISU 23

Start End type description

8270 8271 u 32bit Operating time in the increased motor temperature range
Operating time = (transmitted value) * 10
0 - 4,294,967,296
---
LLLL LLLL LLLL LLLL HHHH HHHH HHHH HHHH

8272 8273 u 32bit Operating time in the critical motor temperature range
Operating time = (transmitted value) * 10
0 - 4,294,967,296
---
LLLL LLLL LLLL LLLL HHHH HHHH HHHH HHHH

8274 8275 u 32bit standstill time


Operating time = (transmitted value) * 10
0 - 4,294,967,296
---
LLLL LLLL LLLL LLLL HHHH HHHH HHHH HHHH

8276 8276 u 16bit Current term of the compressor


0..65.535 min

8278 8278 u 8bit Number of times <5 min


Number of times to determine of quasi- percentage distribution

8279 8279 u 8bit Number of times 5-9 min


Number of times to determine of quasi- percentage distribution

8280 8280 u 8bit Number of times 10-19 min


Number of times to determine of quasi- percentage distribution

8281 8281 u 8bit Number of times 20-29 min


Number of times to determine of quasi- percentage distribution

8282 8282 u 8bit Number of times 30-59 min


Number of times to determine of quasi- percentage distribution

8283 8283 u 8bit Number of times 60-119 min


Number of times to determine of quasi- percentage distribution

8284 8284 u 8bit Number of times 120-300 min


Number of times to determine of quasi- percentage distribution

8285 8285 u 8bit Number of times> 300 min


Number of times to determine of quasi- percentage distribution

8302 8302 u 16bit Sum of shutdowns due to open circuit alarm

8303 8303 u 16bit Sum of shutdowns due to sensor short circuit alarm

8304 8304 u 16bit Sum of shutdowns due to discharge gas sensor open circuit alarm

8305 8305 u 16bit Sum of shutdowns due to discharge gas sensor short circuit alarm

8306 8306 u 16bit Sum of shutdowns due to motor temp static alarm

8307 8307 u 16bit Sum of shutdowns due to motor temp static lockout

Modbus DP 1 VISU 23 13. Aug. 18 6 / 11


Modbus DP 1 VISU 23

Start End type description

8308 8308 u 16bit Sum of shutdowns due to motor temp dynamic alarm

8309 8309 u 16bit Sum of shutdowns due to motor temp dynamic lockout

8310 8310 u 16bit Sum of shutdowns due to discharge gas sensor static alarm

8311 8311 u 16bit Sum of shutdowns due to discharge gas sensor static lockout

8312 8312 u 16bit Sum of warnings due to oil pressure too low

8313 8313 u 16bit Sum of shutdowns due to low oil pressure too low lockout

8316 8316 u 16bit Sum of shutdowns due to phase loss alarm

8317 8317 u 16bit Sum of lockouts due to phase loss alarm

8318 8318 u 16bit Sum of shutdowns due to switching frequency limit alarm

8319 8319 u 16bit Sum of shutdowns due Relaisueberbrueckung message

8322 8322 u 16bit Sum of shutdowns due to sensor INT250 not screwed

8323 8323 u 16bit Sum of shutdowns due to sensor failure oil differential pressure sensor

8330 8330 u 16bit Sum of shutdowns due to wrong phase sequence alarm

8331 8331 u 16bit Sum of lockouts due to wrong phase sequence alarm

8332 8332 u 16bit Compressor run time without oil pressure (INT250)

8333 8333 u 16bit Compressor run time Deactivated Oil Differential Pressure Sensor (INT250)

8334 8334 u 16bit Residual delay time


0..65533 sec estimated time period until the compressor can be switched on again,
65.535 = locked switch off, 65.534 = indefinite time

8336 8336 u 8bit Time since last error in minutes / hours


in the range 0..120 = value in minutes
in the range 121..238 = 3..120h

8337 8337 u 8bit Time since last error in days


0…246 Tage

8338 8338 u 16bit Compressor run time was during the "Relay bridging" recognized
0..65.535 * 10min

8342 8342 u 16bit Sum of warnings due to phase asymmetry alarm

8344 8344 u 16bit Sum of shutdowns due to phase asymmetry alarm

8345 8345 u 16bit Sum of lockouts due to phase asymmetry alarm

8348 8348 u 16bit Sum of shutdowns due to an internal error

8349 8349 u 16bit Sum of shutdowns due to an internal error

8350 8350 u 16bit Sum of warnings due to module supply undervoltage alarm

8351 8351 u 16bit Sum of shutdowns due to module supply undervoltage

Modbus DP 1 VISU 23 13. Aug. 18 7 / 11


Modbus DP 1 VISU 23

Start End type description

8352 8352 u 8bit Error memory: Error number of the last error

8353 8353 u 8bit Error memory: time difference of the last error to the previous
in the range 0.. .120 = value in minutes
in the 121…238 = value in hours 3..120 h

8356 8356 u 8bit Error-memory: error number index -1

8357 8357 u 8bit Error-memory time difference index - 1


in the range 0.. .120 = value in minutes
in the 121…238 = value in hours 3..120 h

8360 8360 u 8bit Error-memory: error number index -2

8361 8361 u 8bit Error-memory time difference index - 2


in the range 0.. .120 = value in minutes
in the 121…238 = value in hours 3..120 h

8364 8364 u 8bit Error-memory: error number index -3

8365 8365 u 8bit Error-memory time difference index - 3


in the range 0.. .120 = value in minutes
in the 121…238 = value in hours 3..120 h

8368 8368 u 8bit Error-memory: error number index -4

8369 8369 u 8bit Error-memory time difference index - 4


in the range 0.. .120 = value in minutes
in the 121…238 = value in hours 3..120 h

8372 8372 u 8bit Error-memory: error number index -5

8373 8373 u 8bit Error-memory time difference index - 5


in the range 0.. .120 = value in minutes
in the 121…238 = value in hours 3..120 h

8376 8376 u 8bit Error-memory: error number index -6

8377 8377 u 8bit Error-memory time difference index - 6


in the range 0.. .120 = value in minutes
in the 121…238 = value in hours 3..120 h

8380 8380 u 8bit Error-memory: error number index -7

8381 8381 u 8bit Error-memory time difference index - 7


in the range 0.. .120 = value in minutes
in the 121…238 = value in hours 3..120 h

8384 8384 u 8bit Error-memory: error number index -8

8385 8385 u 8bit Error-memory time difference index - 8


in the range 0.. .120 = value in minutes
in the 121…238 = value in hours 3..120 h

8388 8388 u 8bit Error-memory: error number index -9

Modbus DP 1 VISU 23 13. Aug. 18 8 / 11


Modbus DP 1 VISU 23

Start End type description

8389 8389 u 8bit Error-memory time difference index - 9


in the range 0.. .120 = value in minutes
in the 121…238 = value in hours 3..120 h

8392 8392 u 8bit Error-memory: error number index -10

8393 8393 u 8bit Error-memory time difference index - 10


in the range 0.. .120 = value in minutes
in the 121…238 = value in hours 3..120 h

8396 8396 u 8bit Error-memory: error number index -11

8397 8397 u 8bit Error-memory time difference index - 11


in the range 0.. .120 = value in minutes
in the 121…238 = value in hours 3..120 h

8400 8400 u 8bit Error-memory: error number index -12

8401 8401 u 8bit Error-memory time difference index - 12


in the range 0.. .120 = value in minutes
in the 121…238 = value in hours 3..120 h

8404 8404 u 8bit Error-memory: error number index -13

8405 8405 u 8bit Error-memory time difference index - 13


in the range 0.. .120 = value in minutes
in the 121…238 = value in hours 3..120 h

8408 8408 u 8bit Error-memory: error number index -14

8409 8409 u 8bit Error-memory time difference index - 14


in the range 0.. .120 = value in minutes
in the 121…238 = value in hours 3..120 h

8412 8412 u 8bit Error-memory: error number index -15

8413 8413 u 8bit Error-memory time difference index - 15


in the range 0.. .120 = value in minutes
in the 121…238 = value in hours 3..120 h

8416 8416 u 8bit Error-memory: error number index -16

8417 8417 u 8bit Error-memory time difference index - 16


in the range 0.. .120 = value in minutes
in the 121…238 = value in hours 3..120 h

8420 8420 u 8bit Error-memory: error number index -17

8421 8421 u 8bit Error-memory time difference index - 17


in the range 0.. .120 = value in minutes
in the 121…238 = value in hours 3..120 h

8424 8424 u 8bit Error-memory: error number index -18

8425 8425 u 8bit Error-memory time difference index - 18


in the range 0.. .120 = value in minutes
in the 121…238 = value in hours 3..120 h

Modbus DP 1 VISU 23 13. Aug. 18 9 / 11


Modbus DP 1 VISU 23

Start End type description

8428 8428 u 8bit Error-memory: error number index -19

8429 8429 u 8bit Error-memory time difference index - 19


in the range 0.. .120 = value in minutes
in the 121…238 = value in hours 3..120 h

8472 8473 u 32bit Total energy consumption


In 1 Ah grid

8474 8474 u 16bit Energy consumption - current hour internal time


0 ... 6.553,5 Ah in the 0.1 Ah grid

8475 8475 u 16bit Energy consumption - current 24h internal time


0 ... 6.553,5 Ah in the 0.1 Ah grid

8476 8476 u 16bit Energy consumption - before 24-48h internal time


0 … 6.553,5 Ah in the 0.1 Ah grid

8477 8477 u 16bit Energy consumption - before 48-72 h internal clock


0 ... 6.553,5 Ah in the 0.1 Ah grid

8478 8478 u 16bit Energy consumption - before 72-96h internal time


0 ... 6.553,5 Ah in the 0.1 Ah grid

8479 8479 u 16bit Energy consumption - before 96-120 h internal time


0 ... 6.553,5 Ah in the 0.1 Ah grid

8480 8480 u 16bit


Energy consumption - before 120-144h internal time
0 ... 6.553,5 Ah in the 0.1 Ah grid

8481 8481 u 16bit Energy consumption - before 144-168 h internal time


0 ... 6.553,5 Ah in the 0.1 Ah grid

8488 8488 u 16bit Sum of shutdowns due to current sensor 1 trip point 1 shutdown

8489 8489 u 16bit Sum of shutdowns due to current sensor 1 trip point 1 Lockout

8490 8490 u 16bit Sum of shutdowns due to current sensor 1 trip point 2 shutdown

8491 8491 u 16bit Sum of shutdowns due to current sensor 1 trip point 2 Lockout

8492 8492 u 16bit Sum of shutdowns due to current sensor 1 open circuit

8493 8493 u 16bit Sum of shutdowns due to current sensor 1 short circuit

8500 8500 u 16bit Sum of warnings due to line undervoltage alarm

8501 8501 u 16bit Sum of warnings due to line overvoltage alarm

8502 8502 u 16bit Sum of shutdowns due to line undervoltage alarm

8503 8503 u 16bit Sum of lockouts due to line undervoltage alarm

8504 8504 u 16bit Sum of shutdowns due to line overvoltage alarm

8505 8505 u 16bit Sum of lockouts due to line overvoltage alarm

8556 8556 u 16bit Module state phase sequence

Modbus DP 1 VISU 23 13. Aug. 18 10 / 11


Modbus DP 1 VISU 23

Start End type description

8557 8557 u 16bit Module state phase loss

8558 8558 u 16bit Module state phase imbalance

8590 8590 u 16bit Phase voltage L1

8591 8591 u 16bit Phase voltage L2

8592 8592 u 16bit Phase voltage L3

8602 8602 u 16bit Module state line undervoltage

8603 8603 u 16bit Module state line overvoltage