Motor temperature, Dynamic switch- Error Temperature increase in the motor winding was
3
off unusually quick
Motor temperature, Dynamic switch- Error Temperature increase in the motor winding was
4
off unusually quick
Motor temperature, short circuit Error Sensor input motor temperature has detected a
8
short circuit
Sensor input Motor temperature has Error Sensor input Motor temperature has detected an
10
detected an open circuit open circuit
Sensor input discharge gas Error Sensor input discharge gas temperature has
13
temperature has detected a short detected a short circuit
circuit
Sensor input discharge gas Error Sensor input discharge gas temperature has
14
temperature has detected a open detected a open circuit
circuit
Motor temperature too high after Error After a mains reset, the resistance value of the
15
reset motor sensor is above the reset limit
time stamp can be shifted from here on.
Discharge gas temperature too high Error After a mains reset, the resistance value of the
16
after mains reset hot gas sensor is above the reset limit
time stamp can be shifted from here on.
Sensor screwed in wrong Error The oil differential pressure sensor does not
18
provide the correct signal, either it is not screwed
in correctly or there is a defect.
Oil differential pressure too low Error The compressor is running and the oil differential
19
pressure sensor reports a differential pressure to
the oil pump that is too low.
Sensor input oil differential pressure Error Sensor input oil differential pressure has detected
20
has detected a short circuit a short circuit
Sensor input Oil differential pressure Error Sensor input Oil differential pressure has detected
35
has detected an open circuit interruption
Current from sensor 1 has exceeded Error Current from sensor 1 has exceeded limit 2
49
trip point 2
Sensor input current monitoring 1 has Error Sensor input current monitoring 1 has detected a
51
detected a short circuit short circuit
Sensor input current monitoring 1 has Error Sensor input current monitoring 1 has detected an
53
detected an open circuit interruption
Dynamic warning; temperature Warning Temperature increase in the motor winding was
120
increase in the motor winding was unusually quick
unusually quick
Dynamic warning; temperature Warning Temperature increase in the motor winding was
121
increase in the motor winding was unusually quick
unusually quick