CONTENTS
1. INTRODUCTION ............................................................................................................. 1
2. FUNCTION ...................................................................................................................... 3
4. INSTALLATION ............................................................................................................. 13
operations. The Uninterruptible Power System is designed to meet the user‘s need of
equipment of industrial automation that make the UPS more compact and less noisy.
2. SPWM Technology.
3. Intelligent Design.
9. The UPS has its own internal power source (batteries), the batteries charges
To be sure that the UPS will be operated correctly, the following items should be
1
noticed:
9. In case of fire, do not use fluid extinguisher so as to avoid electric shock accident,
2
2. FUNCTION
② Bypass LED (orange): This indicates the output outlet is supplied via bypass.
③ Output LED (green): This means the UPS power is from its inverter to the load.
④ Battery Capacity LED (orange): The batteries are almost exhausted out.
⑤ Overload LED (orange): This indicates the UPS is connected with overload.
–UPS STATUS
–INPUT VOLTAGE
–OUTPUT VOLTAGE
3
–INPUT FREQUENCY
–OUTPUT FREQUENCY
–BATTERY VOLTAGE
–OUTPUT POWER
⑧ MENU Key : This switch is pressed to select the UPS status on LCD Display.
UP&DOWN keys have additional shortcut function , the specific use of the table
below:
Note: After pressing UP & DOWN shortcut function for 1 second , can realize a
continuous press function at 180 ms (5.55Hz). The MENU Key does not have
4
2.2 The Appearance of UPS
5
2.2.3 4KVA~6KVA (Tower)
6
2.2.5 8KVA~15KVA (Tower)
7
2.2.7 20KVA~40KVA (Tower)
○
10 AC Input Breaker (SW1): To control the AC input power.
Bypass Input Breaker (SW2): To supply AC input power into Bypass output.
AC Output Breaker (SW5): To control the AC output power. Don’t disconnect the
Maintenance Bypass Breaker (SW6): Only when the UPS need to be repaired or
maintained, the maintenance bypass breaker can be closed. Don’t close the
○
11 Power Distribution Terminals: Input/output power and batteries power
distribution terminals.
8
○
12 Dry Contacts Port: To supply dry contacts signal.
○
13 Computer Interface: Communication port between the UPS and computer.
○
14 Ventilation Holes: Please keep the ventilation holes free.
○
15 Power Cords Holes: Input/output power cords and batteries power cords channel.
○
16 PARALLEL INTERFACE.
○
17 Dial Switch: To set up ON , which means UPS is working under single system.
○
18 Port Detecting (OF-OUT): To detect the trip of output breaker.
9
3. SITE & ENVIRONMENT CONSIDERATION
3.1 Unpacking
1. Carefully take off all the packaging material of the UPS, and carefully locate the UPS
2. Check visually the appearance and mechanical structure to find whether any
physical damage was made during the transport. If any damage is found, notify the
dealer immediately.
3.2 Transporting
3.3 Positioning
2. Allow a minimum distance of 10 cm in the rear and two sides of the UPS for
ventilation. (Fig.3-2)
10
Figure 3-2
4. Keep the UPS far away from heat emitting sources. (Fig.3-5)
11
Figure 3-7
12
4. INSTALLATION
1. Please connect the suitable power for UPS of nearest electric power distribution
2. Operation notice
(3). If the voltage between the neutral line and the ground line is higher than 5V,
please check the grounding system and install the grounding system again.
3. Terminals schematic diagram refer to the following figure, the specific kind prevail.
All the input and output distribution terminals must be connected firmly.
Warning: If the bypass input and AC input are the same power, please connect the
short wires between INPUT terminal and BYPASS terminal. (Only for 1KVA~15KVA)
4.1.1 1KVA~3KVA
N L G + - N L G N L
13
4.1.2 4KVA~6KVA
A. Single phase Power Input, Single phase Power Output (Rack, DC220V and DC192V)
N G L + - N L N G L
B. Single phase Power Input, Single phase Power Output (Tower, DC220V and
DC192V)
N L + - N L N L
C. Single phase Power Input, Single phase Power Output (Rack and Tower, DC110V)
N L + + - - N L N L
D. Three phase Power Input, Single phase Power Output (Rack, DC220V and DC192V)
N L + - N L N T S R
14
E. Three phase Power Input, Single phase Power Output (Rack, DC110V)
N L + + - - N L N L S R
4.1.3 8KVA~15KVA
A. Single phase Power Input, Single phase Power Output, Rack and Tower, DC220V
and DC192V
N L + - N L N L
B. Single phase Power Input, Single phase Power Output, Rack and Tower, DC110V
N L N L N L + -
C. Three phase Power Input, Single phase Power Output, Rack and Tower, DC220V and
DC192V
N L + - N L N T S R
15
D. Three phase Power Input, Single phase Power Output, Rack, DC110V (8KVA and
10KVA).
N L N L N T S R + -
E. Three phase Power Input, Single phase Power Output, Tower, DC110V (15KVA).
N L + - N L N T S R
4.1.4 20KVA~40KVA
Three phase Power Input, Single phase Power Output, Tower, DC220V and DC 192V.
N L + - N L N T S R
Statement: The terminals arrangement should be mainly in kind.
16
4.2 Input and Output Wire
1. The current and the diameter of power wire reference to the ’Input Current and
Input Power Wire table’ and ‘Output Current and Output Power Wire table’.
2. The power wires and the terminals must be qualified products. The used goods and
4. The power wires use high quality terminals crimping and must not be engirded on
the terminals.
6. Please turn off AC supply to prevent the electric shock while connecting wires. Live
7. When connecting with the AC source, please avoid sharing the breaker with the
other equipments. The UPS should be connected with the AC source directly.
8. After all the power wires having been fixed, please check to confirm that the
conductors are unable to contact with the case or other conductive material to
9. Improper use of the grounding plug can result in a risk of electric shock. Consult a
understood.
10. Please use the nearest connecting point of earth bar or AC source for GROUND
line.
17
12. Ensure the connected load doesn‘t exceed the capacity of the UPS.
2KVA 1-1 13A 11A 4mm2 2.5mm2 Φ3.5-5 Φ2-5 DC192 11A 2.5mm2 Φ2-5
DC110 19A 4mm2 Φ3.5-5
DC220 14A 4mm2 Φ3.5-5
3KVA 1-1 20A 17A 4mm2 4mm2 Φ3.5-5 Φ3.5-5 DC192 16A 4mm2 Φ3.5-5
DC110 28A 6mm2 Φ5.5-5
18
DC220 32A 6mm2 Φ5.5-5
3-1 12A 34A 2.5mm2 10mm2 Φ2-5 Φ8-6 DC192 37A 10mm2 Φ8-6
DC110 64A 6mm2*2 Φ5.5-5
6KVA
DC220 32A 6mm2 Φ5.5-5
1-1 46A 34A 10mm2 10mm2 Φ8-6 Φ8-6 DC192 37A 10mm2 Φ8-6
DC110 64A 6mm2*2 Φ5.5-5
DC220 37A 10 mm2 Φ8-6
3-1 14A 45A 4 mm2 10 mm2 Φ3.5-5 Φ8-6 DC192 49A 10 mm2 Φ8-6
DC110 75A 16 mm2 Φ14-6
8KVA
DC220 37A 10 mm2 Φ8-6
1-1 53A 45A 10 mm2 10 mm2 Φ8-6 Φ8-6 DC192 49A 10 mm2 Φ8-6
DC110 75A 16 mm2 Φ14-6
DC220 47A 10 mm2 Φ8-6
3-1 17A 57A 4 mm2 10 mm2 Φ3.5-5 Φ8-6 DC192 61A 16 mm2 Φ14-6
DC110 94A 25 mm2 Φ22-8
10KVA
DC220 47A 10 mm2 Φ8-6
1-1 67A 57A 16 mm2 10 mm2 Φ14-6 Φ8-6 DC192 61A 16 mm2 Φ14-6
DC110 94A 25 mm2 Φ22-8
20KVA 3-1 35A 114A 10 mm2 35 mm2 Φ8-6 Φ38-8 DC192 107 35 mm2 Φ38-8
DC110 187A 50 mm2 Φ60- 8
DC220 140 35 mm2 Φ38-8
30KVA 3-1 52A 170A 16 mm2 50 mm2 Φ14-6 Φ60- 8
DC192 160 50 mm2 Φ60- 8
DC220 187 50 mm2 Φ60- 8
40KVA 3-1 70A 227A 25 mm2 60 mm2 Φ22- 8 Φ70- 8
DC192 215 60 mm2 Φ70- 8
19
Warning: The Voltage of AC source should satisfy the input voltage range of UPS
Item
The Diameter of
Max. Output
Output Power Terminal Spec.
Current
Wire
Capacity
Warning: Please turn to professional personnel for help or contact us if you can’t
20
5. OPERATION
1) Make sure the main breakers and “PUSH ON-OFF switch “are in the OFF.
1. Close the AC Output Breaker, DC Input Breaker, Bypass Input Breaker, and AC Input
Breaker of each UPS. Press “PUSH ON-OFF switch” (SW4) to the position “ON”. The
LED of “Input LED ” and “Bypass LED ” should light up simultaneously. “LCD
Figure 5-1
21
2. About 3 seconds later, “LCD Display” shall indicate the AC utility power and
batteries are normal. And the output outlet is supplied via bypass.
Figure 5-2
3. About 20 seconds later, “Output LED ” will also illuminate and “Bypass LED ”
fade out at the same time, indicating UPS is operating correctly. The UPS power is
Figure 5-3
4. Disconnect AC input of UPS for blackout simulation, the “Input LED ” will
extinguish and UPS beeps every 4 seconds to remind the user AC failure. This
22
Figure 5-4
5. Re-supply AC utility power, “Input LED ” will light up again, then the initial start
up procedure is completed.
6. After connecting the load to UPS, press the LCD display control switch to transfer
to the load percent display. If the value is over 100%, it means that the UPS is
overload. Please reduce the load capacity to the display load percent value is below
90%.
Figure 5-5
23
5.2 The Operation of the Maintenance Bypass Breaker (SW6)
Only for the UPS who matching the maintenance bypass breaker.
Only when the UPS need to be repaired or maintained, the Maintenance Bypass
breaker can be closed. Please follow the operation procedure listed below.
1. Press “PUSH ON-OFF Switch (SW4)” to turn off the inverter, then the load is
Now the electric power doesn’t exist in the UPS except the terminals, the maintenance
can be carried out safely. When the UPS maintenance is complete, then the load
resumes power via inverter. Please follow the operation procedure listed below.
6. Press “PUSH ON-OFF Switch (SW4)” to turn on the inverter, then the load is
Warning: Don’t close the Maintenance Bypass Breaker when UPS is normal operating.
24
5.3 Maintenance
1. If the users interrupting one UPS unit of parallel redundant system for maintenance,
without stopping the power supply to the load, please follow the steps below.
① Under the Normal Operation Mode, Press “PUSH ON-OFF Switch” of each UPS to
④ Remove the input cable, output cable, battery cable, ground connection and DB9
Now the user can carry out the safe maintenance work.
Warning: It's strictly forbidden to parallel the units without DB9 communication
cable connected.
2. After finishing the maintenance work, the parallel redundant system can resume
running under the normal operation mode without interrupting the AC output by
① Connect the input cable, output cable, battery cable, ground connection and DB9
② Close AC Output Breaker, DC Input Breaker, Bypass Input Breaker and AC Input
25
③ Set each UPS units in parallel position.
④ Press “PUSH ON-OFF Switch” of each UPS to set the parallel redundant system
26
6. OPERATION MODES OF THE UPS
Under the normal operation mode, the AC output power comes from AC utility input
and passes through AC/DC rectifier; DC/AC inverter and static transfer switch to supply
27
6.2.2 Static Bypass Mode
When the inverter is under the abnormal conditions, such as over temperature, short
circuit or overloaded and exceed the inverter’s limit, the UPS will automatically switch
to bypass mode. The load is supplied by standby source via bypass without any
interruption.
When the AC utility power or the rectifier fails, the battery system immediately feed the
inverter instead of the rectifier. During this course, the output will continue to supply
the load without any interruption. Therefore, the load connected to the output is
protected.
28
6.2.4 Maintenance Bypass Mode
Only for the UPS who matching the maintenance bypass breaker.
During the maintenance and repair work, the user can switch the UPS to operate under
the “Maintenance Bypass Mode”. The AC output will not be interrupted during the
switch procedure. And the maintenance bypass loop can insure the continuously power
A hot-standby UPS system basically consists of two (or more) single UPS units which
operate independently of each other. Any one unit can be feeding the load at any time.
All units are continuously in operation; but only one is supplying the load, but only
In case of a failure in the unit currently supplying the load, another unit is ready to
take over the load without an interruption on the output side. The load is still
The load is supplied by the static bypass, only if there is no inverter ready in the
29
Figure 6-6: Hot-Standby System Mode
30
6.4 Parallel Redundant System (Option)
N + X is the most reliable power supply structure, N on behalf of the total UPS load
minimum required number, X represents the number of redundant UPS, that is, the
system can withstand the failure at the same time the number of UPS. N + X is the best
way to the use of high reliability for the occasion. This ensures clean and conditioned
power supply to the connected load even during the failure of any one UPS unit. The
electronic parallel operation device integrated in each individual standard unit ensures
uniform distribution of the connected load to the individual units at any time and
Parallel redundant system uses the advanced mode, and has more reliability and
stability
Two host units will be distributed 50% of the connected load under the normal
operation mode.
The users can first start-up any one of the two units without any complicated
The UPS has intelligence procedure; therefore any operational mistake made by the
31
Figure 6-7: Parallel Redundant System Mode
32
7. TROUBLE SHOOTING GUIDE
1) LCD Status:
Figure 7-1
UPS STATUS:
AC utility power is normal and the UPS is running normally with full load.
Action:
No.
33
2) LCD Status:
Figure 7-2
UPS STATUS:
Action:
No.
3) LCD Status:
Figure 7-3
UPS STATUS:
AC utility power is normal, but the DC input voltage is under voltage. And the buzzer
34
beeps once every second.
Action:
Check whether the DC Input Breaker (SW3) is closed. If it’s closed, check whether the
battery system fails. If the battery system fails, please contact the professional technical
4) LCD Status:
Figure 7-4
UPS STATUS:
The AC utility power is normal and the load is fed only by the bypass of UPS.
Action:
Press “PUSH ON-OFF Switch (SW4)” to turn on the inverter, the UPS will switch to the
normal operation mode to feed the load by inverter. If turn on no response, please find
35
5) LCD Status:
Figure 7-5
UPS STATUS:
AC utility power is normal but UPS is overloaded. “Overload LED” lights up and buzzer
beeps continuously.
Action:
Please reduce the critical load to (%) <100% rated capacity of UPS. If the situation
6) LCD Status:
Figure 7-6
36
UPS STATUS:
AC utility power is normal, but UPS is abnormal. The load is supplied by AC utility
Action:
Press “PUSH ON-OFF Switch (SW4)” to turn off the inverter, and then turn on the UPS
again, if the UPS is still abnormal; please contact our customer service center.
7) LCD Status:
Figure 7-7
UPS STATUS:
AC utility power fails. The inverter is supplied by the battery input power. The UPS is
connected with full load. Buzzer alarm sounds every 4 seconds, after 1 minute to stop
beep.
Action:
If AC utility power fails, reduce the less critical load in order to extend the backup time.
37
8) LCD Status:
Figure 7-8
UPS STATUS:
AC utility power fails. The inverter is supplied by the battery input power. But the
Action:
9) LCD Status:
Figure 7-9
UPS STATUS:
38
AC utility power fails and battery runs out. UPS has shut down automatically.
Action:
UPS will restart up when AC utility power is restored. If AC utility power failure is more
than 6 hours, please follow daily operation procedure to turn off the UPS.
39
8. DAILY MAINTENANCE GUIDANCE
1. Please strictly observe the right correctly turn on and shutdown to operate.
4. It’s unsafe to turn on the UPS with heavy load connected. Turn off the load before
8.2 Maintenance
1. The environment in which the UPS is located must be kept dry and relatively dust
free.
3. All power connections at the AC input, DC input, output terminals and main
4. Please check the fans of the UPS inside every month, ensure heat dissipation of the
UPS normal.
5. Please keep the ventilation holes free. Preventing the ventilation holes from being
blocked is must.
40
9. COMMUNICATION INSTRUCTION
UPS equipment with RS485 or RS232 interface for the user to choose and use. The
requirements in the field. Generally, RS-485 is for long distance transmission and
PIN1~5: NC
PIN7: GND
Figure 9-1: RS-232 Female Connector
PIN8: NC
PIN1: D-/B
PIN2: D+/A
PIN3~4: NC
Figure 9-2: RS-485 Male Connector
PIN5: GND
PIN6~9: NC
41
9.2 Dry Contacts Port
1. DC Fault (Battery Low): Short when the battery input voltage is too high
or too low.
2. AC Fault: Short when the main AC input fails or the reserve AC input fails.
4. Inverter Fault: Short when UPS encounters one or more following fault
conditions: UPS output voltage is too high / low; fuse break; short in
Statement:
42
10. TECHNICAL DATA
AC Voltage AC220V±25%
Frequency 50Hz±10%
Voltage AC220V±1%
Frequency 50Hz±0.5%
Wave Form Sinusoid, Distortion Linear Load <3% 0-100% Linear Load
Efficiency ≥90%
43
Input LED (Green), Output LED(Green), Battery Capacity LED
LED
(Orange), Bypass LED (Orange), Fault LED (Red), Overload (Orange)
Overload Continuously
Net Weight
40(Electricity) 45(Electricity) 50(Electricity)
Appeara 24(Industry) 27(Industry) 30(Industry)
(Kg)
nce
Dimension
Rack:426*455*180 (W*D*H) Tower:180*455*435 (W*D*H)
(mm)
Operation
-5℃~40℃
Temperature
Environm
Relative
Humidity 0-95% (Non Condensing)
ent
Audible Noise
Level < 50dB ( At 1 Meter )
Note: All the specifications mentioned above are subjected to change without prior notice.
44
10.2 4KVA~6KVA Technical Data
45
Operation
-5℃~40℃
Temperature
Environme
Relative Humidity 0-95% (Non Condensing)
nt
Audible Noise
< 50dB ( At 1 Meter )
Level
Note: All the specifications mentioned above are subjected to change without prior notice.
46
10.3 8KVA~15KVA Technical Data
47
Operation
-5℃~40℃
Temperature
Environme
Relative Humidity 0-95% (Non Condensing)
nt
Audible Noise
< 55dB ( At 1 Meter )
Level
Note: All the specifications mentioned above are subjected to change without prior notice.
48
10.4 20KVA~40KVA Technical Data
AC Voltage AC380V±25%
Input DC Voltage DC220V / DC192V / DC110V
Frequency 50Hz±10%
Voltage AC220V±1%
Frequency 50Hz±0.5%
Wave Form Sinusoid, Distortion Linear Load <3% 0-100% Linear Load
Overload 120%~150% for 60s Transfer to Bypass,
Output Protection ≥150% for 1s Transfer to Bypass
Power Factor 0.7-1.0 lag
Crest Factor 3:1
Efficiency ≥90%
Transfer Time 0ms
Battery Power off
Overload ≥120% 1min; ≥150 1s
Protect Short Circuit Transfer to bypass
Fault Transfer to bypass ,alarm
EMC GB 7260.2 Approved
English Display, UPS Status, Input/Output Voltage, Input/Output
LCD
Frequency, Battery Voltage, Output Load, and Historical Event
Display
Input LED (Green), Output LED(Green), Battery Capacity LED
LED
(Orange), Bypass LED (Orange), Fault LED (Red), Overload (Orange)
AC Fault Every 4 Seconds
Bat Power Off Every Second
Alarms Bat Low Every Second
Overload Continuously
System Fault Continuously
Communi RS-232(Option) UPSilon 2000 software
cation RS-485 UPSilon 2000 software/ Modbus protocol (option)
Interface Dry Contacts Five groups
Net Weight 280(Electricity) 345(Electricity) 410(Electricity)
Appearan (Kg) 245(Industry) 300(Industry) 360(Industry)
ce Dimension
720*480*1392 (W*D*H)
(mm)
49
Operation
-5℃~40℃
Temperature
Environme
Relative Humidity 0-95% (Non Condensing)
nt
Audible Noise
< 60dB ( At 1 Meter )
Level
Note: All the specifications mentioned above are subjected to change without prior notice.
50
11. PARALLEL REDUNDANT SYSTEM
1. The DB9 communication cable must be connected firmly, please do not use
non-configured cable.
4. Please refer to Figure for wiring connections of parallel redundant system, and
Both the static bypass and maintenance bypass of all UPS should gain their power
If the bypass input and AC input are the same power, please connect the short
wires between INPUT terminal and BYPASS terminal. (Only for 1KVA~15KVA)
11.2.1 1KVA~3KVA
51
11.2.2 4KVA~6KVA
A. Single phase Power Input Single phase Power Output (Rack, DC220V and
DC192V)
52
B. Single phase Power Input Single phase Power Output (Tower, DC220V and
DC192V)
53
C. Single phase Power Input Single phase Power Output (Rack and Tower,
DC110V)
D. Three phase Power Input Single phase Power Output (Rack, DC220V and
DC192V)
54
E. Three phase Power Input Single phase Power Output (Rack, DC110V)
11.2.3 8KVA~15KVA
A. Single phase Power Input Single phase Power Output, Rack and Tower, DC220V
and DC192V
55
B. Single phase Power Input Single phase Power Output, Rack and Tower, DC110V
C. Three phase Power Input Single phase Power Output, Rack and Tower, DC220V
and DC192V
56
D. Three phase Power Input Single phase Power Output, Rack, DC110V (8KVA and
10KVA)
E. Three phase Power Input Single phase Power Output, Tower, DC110V (15KVA)
57
11.2.4 20KVA~40KVA
58