6FM100/12Volt 100Ah
General Series VRLA batteries are designed with AGM(Absorbent
Glass Mat) technology,High performance plates and electrolyte togive
extra power output for common power backup system. General Series
Batteries are the general purpose batteries with 10 years floating design
life at 25℃.
Emergency Power System Power tools
Communication equipment Alarm system
Telecommunication systems Marine equipment
Uninterruptible power supplies Medical equipment
Electric toy car and wheelchairs, etc Fire and Security System
Heavy Duty Grid Positive........Lead dioxide Negative........Lead
Mechanized assembly Electrolyte........Sulfuric acid Safety Valve........EPDR
Non-spillable construction Separator........Fiber glass Terminal........Copper
High Reliability and Stability Container........ABS(UL94-HB) / Flame Retardant ABS (UL94-V0)
Sealed and Maintenance-free
Long Life and low self-discharge design
Nominal Voltage 12V
Battery Model Rated capacity (10Hour rate) 100Ah
Cells Per battery 6
Length Width Height Total Height
Dimension
331mm 173mm 213mm 218mm
Approx Weight 28.00Kg
Internal Resistance Full charged at 25℃(77℉): Approx 5mΩ
Max.discharge current 800A(5s)
Floating design life @ 25℃ (77℉) 10 years
10Hour rate(10A/10.8V) 5Hour rate(14.45A/10.5V) 3Hour rate(18.75A/10.5V) 1Hour rate(38.5A/10.5V)
Capacity @ 25℃ (77℉)
100Ah 72.25Ah 56.25Ah 38.5Ah
40℃ (104℉) 25℃ (77℉) 0℃ (32℉) -15℃(5℉)
Capacity affected by Temp(10 HR)
102% 100% 85% 65%
After 3 months storage After 6 months storage After 12 months storage
Self Discharge @ 25℃ (77℉)
93% 84% 65%
Cycle Use 14.5-14.9V (Initial charging current less than 30A)
Charge method @ 25℃ (77℉)
Float Use 13.6-13.8V
3
6FM100 12Volt 100Ah
8.5
218
213
18
9
20
Constant voltage charge (25℃)
-Cycle use: 14.50-14.90V
-Standby use: 13.60-13.80V
-Max. charge current: 30.00A
M6
331 173 17.5
F.V / TIME 5min 10min 15min 30min 1h 2h 3h 4h 5h 8h 10h 20h
A 360.00 220.00 175.00 115.00 60.00 35.00 26.00 21.00 17.54 11.58 11.00 5.70
9.60V
W 3816.00 2336.40 1872.50 1242.00 654.00 381.50 286.00 231.00 192.96 128.57 122.10 64.13
A 330.00 220.83 160.83 109.17 62.00 33.58 25.50 20.00 17.21 11.40 10.50 5.60
10.20V
W 3597.00 2451.25 1793.29 1228.13 697.50 379.49 288.15 227.00 195.31 129.39 119.18 63.56
A 306.04 211.00 150.00 105.83 60.00 32.92 25.00 19.00 17.00 11.25 10.30 5.53
10.50V
W 3366.46 2373.75 1695.00 1206.50 684.00 376.90 286.25 218.50 195.50 129.38 118.45 63.60
A 278.67 201.67 140.00 101.00 58.00 32.08 24.50 18.67 16.25 10.96 10.00 5.46
10.80V
W 3065.33 2299.00 1603.00 1166.55 669.90 370.56 284.20 217.47 189.31 127.66 116.50 63.61
A 241.00 190.00 130.00 94.00 55.00 31.25 23.50 18.33 15.54 10.67 9.75 5.40
11.10V
W 2723.30 2194.50 1508.00 1099.80 643.50 365.63 276.13 216.33 183.39 125.87 115.05 63.72
Note: The above datas are average values. (Edition 2017-11) www.championpower.cn
Page 1 of 2
6FM100/12Volt 100Ah
120
2.16/6.48/13.0 100
Voltage (V)
1.85/5.55/11.1 80
1.80/5.40/10.8
Capacity(%)
0.25C 0.20C 0.17C 0.12C 0.1C 60
1.75/5.25/10.5 100%DOD 50%DOD 30%DOD
0.05C
0.55C 0.40C
1.70/5.10/10.2 40
1.65/4.95/9.90
3C 2C 1C 20
1.60/4.80/9.60
0
7min 15min 27min 1h 2h 3h 4h 5h 8h 10h 20h 200 400 600 800 1000 1200 1400
Number of cycles (cycles)
Discharge time
Charged
( V / 12V )
Volume
Current
Voltage
( V / CE )
( V / 8V )
( V / 6V )
( V / 4V )
(%) (XCA) (V)
140
15.6 10.4 7.8 5.2 2.6
120 0.25
15.0 Charged Volume
15.0 10.0 7.5 5.0 2.5 Cyc 100
le U 0.20
se 14.0 Charge Voltage
14.4 9.6 7.2 4.8 2.4 80
0.15
13.0
Stand
by Use 60
13.8 9.2 6.9 4.6 2.3
0.10
40 12.0
13.2 8.8 6.6 4.4 2.2
20 0.05
11.0
Charging Current
-10 0 10 20 30 40 50 60 0 0
0 2 4 6 8 10 12 14 16 18 20
Ambient temperature(℃) Charging time (hours)
11 0
100
2.30V/Cell
5 90
Life (years)
Capacity (%)
80
1
70
60
40℃ 30℃ 20℃
50
0 40
10 20 30 40 50
0 2 4 6 8 10 12 14 16 18 20
Temperatura(℃) Storage time: months
120 15 7.5 5.0 120 0.24
Charge Volume
100 14 7.0 4.7 100 0.20
Charge Voltage
Charge Voltage (V)
Charge Currient (CA)
80 13 6.5 4.3 80 0.16
Charge Volume (%)
① Discharge
Capacity (%)
100% (0.05 CA*20h)
50% (0.05 CA*10h)
12 6.0 4.0 ② Charge 60 0.12
60 Charge Voltaje 2.275V /cell
Testing conditions: floating voltage: 2.27 to 2.30V /cell Charge Current 0.1 CA
③ Temperature 25℃
Ambient temperature: 25 ℃ (℉) 11 5.5 3.7 40 0.08
40
10 5.0 3.3 20 0.04
20 Charge Current
9 4.5 3.0 0 0
0 0 2 4 6 8 10 12 14 16 18 20 24 28
1 2 3
Charge Time (h)
Life (years)
Note: The above datas are average values. (Edition 2017-11) www.championpower.cn