0% found this document useful (0 votes)
6K views24 pages

4188-424 - Xenex 2 Installation and Commissioning

This document provides installation and commissioning guidance for conventional 2, 4, and 8 zone fire panel systems. It covers system design, cable installation, panel installation, terminal connections, indicator controls, power up tests, configuration, programming, fault indications, and specifications. The guidance is intended for installers and commissioning engineers working with the listed conventional fire panel models.

Uploaded by

Rabie Mahmoud
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
6K views24 pages

4188-424 - Xenex 2 Installation and Commissioning

This document provides installation and commissioning guidance for conventional 2, 4, and 8 zone fire panel systems. It covers system design, cable installation, panel installation, terminal connections, indicator controls, power up tests, configuration, programming, fault indications, and specifications. The guidance is intended for installers and commissioning engineers working with the listed conventional fire panel models.

Uploaded by

Rabie Mahmoud
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 24

Data, Installation and Commissioning guide

Fire Control and Repeat panels


(Conventional 2, 4 and 8 Zone panel range)

This manual covers a range of This manual is intended


conventional fire panel and include Content Page
for use by installers and
system design, installation and
configuration information. commissioning engineers. System design · · . . . . . 2
Cables - · · · · · . . . . . 4
The fire panels covered are Notes to installers . . . . . 5
designed in accordance with the A separate Operating Panel fixing· · · · . . . . . 6
requirements of EN54-2: 1997, instructions and Log book Terminals · · · · . . . . . 8
A1:2006, plus the requirements of Controls & indicators . . . . 9
has been supplied along Power up tests · · . . . . . 10
EN54-4: 1997, A1:2002, A2:2006.
This publication covers the with this booklet which Installed system tests . . . 11
Conventional fire alarm panels: must be forwarded on to Config. considerations . . . 11
the End User. Access levels 2 · . . . . . 12
q 2 zone panel:- 13270-02LB and Operating instructions for
75585-02NMB Access level 2 functions . . 12
Programming Options . . . 14
q 4 zone panel:- 13270-04LB and Operating instructions for
75585-04NMB Access level 3 functions . . 14
Operating instructions for
q 8 zone panel:- 13270-08LB and Access level 4 functions . . 15
75585-08NMB Fault indications · . . . . . 16
Fault finding · · · . . . . . 17
q Fire alarm repeat panel: Specification for the
13271-08LB and 75586-08NMB. Control panel· · · . . . . . 20
Specification for the
The panels are supplied without Repeat panel· · · . . . . . 22
batteries. Parts list · · · · · . . . . . 23

4188-424 issue 6_Part 1_06-12


System design Fire Panels
NOTE: Spur wiring is not permitted off zone circuits.
System design
End-of-line Capacitor unit
The fire system design should be or bipolar capacitor Un-used Zone circuits must
be terminated with an
to BS 5839:Part 1:2002 + A2:2008 FIRE DETECTION (ZONE) CIRCUIT
end-of-line Capacitor unit
Code of Practice for system or bipolar capacitor
design installation and servicing. BLACK
Supplemented with customer
requirements. RED
Mains Supply MANUAL
FIRE
DETECTOR CALL
The control panel mains supply POINT
must be via a fused spur unit RED BLACK
rated: A fire detector head may be fitted
5A - 1 & 2 Zone panel/Repeat Z1+ Z1- Z2+ Z2-
to a diode-base for continuity when
panel a detector head is removed and Zone Zone
7A - 4 & 8 Zone panel there can be a maximum of up to Circuit Circuit
20 diode-bases per zone circuit.
Standby Supply Control panel
With the recommended batteries
Figure 1 Zone circuit - used and unused
the control panel will provide a
standby supply under mains
failure conditions. A period of
72 hours followed by 30 minutes Connection to 17800 range of detector bases are shown here.
of alarm load is possible and is Control panel MCP
dependent on the system loading.
Zn+
23 2 3 1234
24V power supply 4 4
1 1
5
IN IN
5
Zone 7
The power supply terminals ‘24+ Circuit
7
OUT OUT
and 0’ may drive external ancillary 6 6

equipment and is designed to be Zn-


used in conjunction with auxiliary Standard base shown. Diode Standard base
contacts and common fire and base connection is identical.

fault outputs. The maximum


currents are 250mA (1 & 2 zone)
and 500mA (4 & 8 zone). The
supply is monitored for faulty 24V NOTE: LED unit is supplied LED unit
with LED module
supply level or fuse blowing. - +
NOTE: End of line unit
NOTE: The use of the 24V is supplied with panel

supply will affect the panel 2


3
2

standby capability. 1
4 3 4 23 4
IN 1 1
IN IN
5 5
7 7 7
OUT 5 OUT OUT
Fire Detection 6 6 6

(Zone Circuits)
Base showing
Each zone circuit can have up to Standard base Base with LED End of Line
connection device fitted
3.0mA load. An end-of-line
capacitor unit or bipolar capacitor Control panel
is required for zone circuit Earth continuity Vision detector wiring

monitoring, which must be fitted Zone Zn+


after the last detector or manual Circuit Zn-

call point on the circuit. All


manual call points used must
have a 470 ohms series resistor.

Where a zone circuit is not being


used, the end-of-line capacitor unit
or bipolar capacitor must be fitted
across its terminals in the panel.
Figure 2 Connection to detectors, cal l points and panel

2 4188-424 issue 6_Part 1_06-12


Fire Panels System design

Alarm (Sounder circuits) End-of-line Resistor


10k Ohms NOTE: Spur wiring is not permitted
To comply with the requirements off alarm sounder circuits.
of BS 5839: Part 1:2002 +
A2:2008, two or more alarm
Alarm sounders
sounder circuits should be used must be polarised
on all installations. and suppressed.
ALARM SOUNDER CIRCUIT

NOTE: All sounder circuits Alarm sounder


must have a
(sectors) will operate together in series blocking Earth
continuity
the event of a fire condition. diode Sounder circuit that is
not used is terminated
with an end-of line resistor
NOTE: Each sounder output is
0.5A maximum protected by Sn+ Sn-
0.75A fuse. S1+ S1- Sn+ Sn-
Sounder
Sounder Sounder

1 & 2 Zone 4 & 8 Zone Control panel Control panel


Panels Panels
1A maximum 1.5A maximum Figure 3 Alarm sounder circuit used and unus ed
Alarm sounder Alarm sounder
load per panel load per panel
Push button switch
The load must be shared between or relay pulsed
the sounder circuits. The alarm at 1 second
sounder circuits are regularly interval (minimum)
pulse monitored for failure. It is for class change 100m max.
application Cable
important that the last alarm distance
sounder is fitted with a 10K Ohm
end-of-line resistor.
CC1 CC2
The sounder outputs are Class change
monitored in alarm for loss of
supply or multiple sounder output Control panel
overloads
Figure 4 Class change circuit
Where a sounder circuit is not
being used, the end-of-line resistor
Contacts rated 1A@24Vdc
must be fitted across its terminals
in the control panel. 100m maximum
NOTE:There is no cable distance
Class Change indication given at the
panel of class change push
A pair of unmonitored terminals button operation.
NC
NC
N0
N0

Contacts
allow only the system alarm Auxiliary
change
sounders to be activated from a over occur
contacts
with a fire
remote position. It is considered that Control panel condition
the major use for these will be for
class change functions in schools Figure 5 Auxiliary contacts
and colleges.

Auxiliary Contacts
These are normally open (NO) and
normally closed (NC) contacts that
change over when the panel goes
into a fire condition. The contacts
are rated at 24V dc 1A for a
resistive load and should not be
used to switch voltages in excess of
50V. The auxiliary circuits should be
powered from an independent
power supply.

4188-424 issue 6_Part 1_06-12 3


Cables Fire Panels

Common Fire and fault


The Indicator and Relay
The common fire output is a shown connected here
are typical examples
normally open electronic switch of external circuit
that closes with a fire condition.

The common fault output is a


normally closed electronic switch, NOTE: The maximum 24V
which opens with a fault condition, relay load is 280mW (Common
Fire) and 500mW (Common Fault).
this is for a fail safe operation. Figure 6 Fire
Use a relay to
fault & 24V provide volt free contacts.
outputs
Each electronic switch is current CFT 24V+ - 24V+ supply
24+ CFR 0V
limited, see specification. CFT - Common fault
CFR - Common fire
Current limited Current limited 0V - 0V supply
Use a relay to provide volt free
contacts.
Normally closed
electronic switch Normally open
The +24V & 0V is a power supply electronic switch
for use with auxiliary contacts, 0V
common fire and common fault Control panel
circuits, see specification.

Repeat Panel Screen must be


connected to panel
A Repeat panel can be connected
in series to the control panel. A Figure 7 Control
repeat panel duplicates fire and to repeat panel
connections
fault indications together with
system controls. R+ R- R+ R-
Control panel Repeat panel

q each core having no less than Power supply cord


Cables
1.5mm2 cross section area The mains supply to the panel
The guidance of (maximum 2.5mm2). should be wired in 0.75mm2 cable
BS5839:Part 1:2002 + A2:2008, with a effective connection to
should be followed. q with an inherent or through building service earth continuity
metal conduit screen for earth conductor.
Generally available electrical continuity in order to produce
installation cable may be used, electrical protection and
providing the cable is: screening.

q to BS6387 q having protection from heat and


mechanical damage.
q with no more than 2 - cores

Length per circuit Type of circuit Recommended cables, also see BS5839:Part 1 guidance
2m Mains power supply cord see power supply cord
1Km Zone circuit
1Km Sounder circuits
See BS5839:Part 1:2002 + A2:2008 for guidance
100m Auxiliary circuit
100m Common fire and fault circuit
100m Class change circuit
500m total circuit Repeat panel link Belden type - screened 2-core twisted pair

4 4188-424 issue 6_Part 1_06-12


Fire Panels Notes to installers
Requirements
Notes to installers NOTE: All these procedures
It is recommended that the
Check installer follow the general assume that the cable, gland,
q The power-up and requirements of: steel box (BESA box) and other
commissioning is done by the related accessories are provided
servicing organisation. q BS5839:Part 1:2002 + A2:2008, by the installer.
which is the code of practice
q The wires between the relating to the fire detection and
As fitted wiring drawings
termination point and terminals alarm systems for buildings.
should be short and straight The installer should acquire:
as possible. q the relevant parts of the
BS 7671 Requirements for q site specific information from
q The cables of the fire detection Electrical Installation. the interested parties, for details
and alarm system and other on the location of products for
Second fix installation
systems should usually be
separated by at least 160mm, To prevent the possibility of
unless dedicated conduit or damage or dirt degrading the q the acquired information
ducting is used. performance or appearance of the together with this guide and the
System products, the installation relevant standards should be
q Do not use any part of building of second fix items should be used to assist the work.
structure for earthing. delayed until all major building
Earth continuity
work in the area is complete.
q The cable length between the To maintain earth continuity, the
Fixtures and fittings cable screen must be continued
Repeat LED unit and respective
fire detector where used, should It is the installers responsibility to through each system device,
not exceed 10m. provide: whether the earth is connected to
a device or not.
q Cable Glands should be used · adequate fixtures and fittings
on the equipment for the mains for the type of construction
supply cable. surface onto which a product NOTE: The cable from the main
is to be installed. panel to repeat panels if fitted
q Unused knockouts on product · as an aid to this decision, the must be a screened cable.
enclosure that have been weight and overall size of Refer to Figure 8.
removed, should not be left each full assembly together
open. with implications on cable
entries and routing should be
taken into consideration.
NOTE: Repeat panel link
cable entries are located
at the opposite end to the
Mains input terminal Zone Cable termination mains cable entries, ie on
block c/w mains fuse the Right Hand Side.
Cable
Mains supply Earth
to panel drain Gland
4-off earth points

13-back
13-top
cable entry points

Electronic assembly
Panel backbox

Figure 8 Panel cable entry and earth points

4188-424 issue 6_Part 1_06-12 5


Panel fixing Fire Panels
Quantity supplied with control Repeat
Panel fixing Description panel panel
For fuse location
a) Remove panel from its carton. see Figure 12 2 zone 4 zone 8 zone
b) Store the front panel (including 10K end-of-line resistor 2 4 8
the electronic assembly) and
the metal plates in a safe place 22uF Capacitor unit 2 4 8
until later. End of line label 4 8 16
c) Check the spare parts supplied Fuse T3.15AH250V 2 2 2 2
ceramic 20 x 5mm
with those listed in Table 1. (mains FS1 & battery FS2)
d) Remove the appropriate Fuse F500mA250V 1 1 1
knock-in on the panel case for 20 x 5mm (24V FS11)
cable entry. Battery link 1 1 1 1
e) Hold the panel on the wall in Zone designation label 1 1 1 1
the desired mounting position
and mark the positions of the M3 screws 8 8 8 8
fixing holes. See Figure 9 for
case fixing details. Table 1 Spare parts supplied with each panel

f) Secure the panel to the wall


using suitable fixings. A top NOTE: Each terminal in a
centre keyhole fixing is CAUTION: DO NOT undertake panel will accept a
provided on the case to allow high voltage insulation tests
the panel to be hooked whilst maximum conductor size of
the bottom two fixing points are
WITH THE CABLES 2.5mm2.
located. CONNECTED to their terminals.
This may damage the electronic
circuitry in the product. NOTE: The installation of
NOTE: For details on flush all outstanding parts is
fixing the panel, see Figure 11. I) Refit the front panel (including the usually carried out during
electronic assembly) into the panel Commissioning of the
g) Connect the mains supply using four M3 screws and connect System.
cable to the panel. The cable: the transformer cable and earth
cable, see Figure 10.
· must be fed through one of
the dedicated mains cable j) Attach the top and bottom metal
entry points into the panel. plates using four M3 screws, see
Figure 11.
· must be via an unswitched
fused spur unit, rated 5A for How to knock-in Knock here to open
the 2 Zone Control and a cable entry point the entry point
Repeat panels and 7A for 4&8
Zone panels. Panel size
· The fused spur isolator cover 395mm wide x 274mm high x 87mm deep
should be red and marked:
FIRE ALARM - DO NOT SWITCH
OFF Dedicated mains
cable entry points 4-off
· The fused spur units must be 89mm 89mm earth points
111mm
fed from a dedicated isolation
switch used for the fire alarm
system only.
h) Wire the system. With the
exception of mains cable, all
other cables should remain
unconnected at the panel. For
197mm

the unconnected cable leave


300mm tail wire length and
mark each core identifying its
final point of connection.
The system wiring can be
tested whilst not connected to
19mm

the respective terminals at Panel Backbox


each system device.
Figure 9 Panel fixings

6 4188-424 issue 6_Part 1_06-12


Fire Panels Panel fixing
Dedicated mains
cable entry points 4-off earth points

To To
Transformer Earth

Transformer
cables
to electronic
assembly
T1A T1B E

Earth connection
to the electronic
assembly P1

Panel Backbox
Fixing points for the
electronic assembly

Electronic assembly

NOTE: The metal plates are to be located


Ribs under the ribs on the front panel and fixed
in place using M3 screws.

Red +ve
Battery connections Bottom Plate (instructions printed on plate)
Black -ve

Figure 10 Refitting electronic assembly

Aperture
60mm deep

cross section of
the wall to which
the panel is to be
flush mounted

245mm high

Control or Repeat Flush


panel shroud

4.5 mm diameter holes 378mm wide


12 holes

Figure 11 Installing a flush shroud

Store all spare parts and loose


components including the
batteries inside the panel carton
and keep in a safe place until
required.

4188-424 issue 6_Part 1_06-12 7


Terminals Fire Panels

Terminals
CAUTION
HAZARDOUS VOLTAGES REMAIN
AFTER OPERATION OF FUSE

Product No: 13270 MAIN PANEL


N L Rated Voltage: 230V A.C.
Rated Current: 0.3A
Rated Frequency: 50Hz
Mains Fuse: FS1 T3.15AH250V
Manufacture date: xx/xx/xx by Honeywell
The shaded terminal blocks
Mains input are not fitted on the Repeat panel.
supply

To Zone and Sounder


Circuits, where `n' signifies
circuit number 1 to 8
Zn- Sn-
Auxiliary contacts Zn+ Sn+
1A at 24Vdc resistive Class change, connect to XEN-FFR
NC NO Common fault,
NC NO P3 to P6 Common Fire
Repeat panel
CC2 CFT
To transformer CC1 24+ CFR 0 R+ R-

T1B
T1A E P7

P1
T1A T1B E T2A T2B NC NC NO NO Z1+ Z1- S1+ S1- Z2+ Z2- S2+ S2- Z3+ Z3- S3+ S3- Z4+ Z4- S4+ S4- Z5+ Z5- S5+ S5- Z6+ Z6- S6+ S6- Z7+ Z7- S7+ S7- Z8+ Z8- S8+ S8- CC1 CC2 24+ CFT CFR 0 R+ R-

CN5 CN6 CN7 CN29 CN30 CN8 CN9 CN10 CN11 CN12 CN13 CN14 CN15 CN16 CN17 CN18 CN19 CN20 CN21 CN22 CN23 CN24 CN25 CN26 CN27 CN28
POWER 1 POWER 2 BATTERIES SECTOR 1 SECTOR 2 SECTOR 3 SECTOR 4 SECTOR 5 SECTOR 6 SECTOR 7 SECTOR 8
F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11

Zones
1 2 3 4 5 6 7 8
FIRE
Faults
1 2 3 Test
1 8
Power
4 5 6

P8
System

Software Power

Earth
Cancel Reset
Buzzer System 7 8 9

v
Delay

Access /
Sounder

version
0 Function
Sound Silence
Disabled Alarms Alarms Display Shift

Panel
label EEPROM
Protection
fitted across
pins 1 and 2
Fuses
SECTOR 1 SECTOR 3 SECTOR 5 SECTOR 7 24V
BATTERIES SECTOR 2 SECTOR 4 SECTOR 6 SECTOR 8
MAINS
Fuse FS1 (SB) FS2 (SB) FS3 FS4 FS5 FS6 FS7 FS8 FS9 FS10 FS11 (QB)

2-Zone panel 3.15A 3.15A 750mA 750mA 500mA

4-Zone panel 3.15A 3.15A 750mA 750mA 750mA 750mA 500mA

8- Zone panel 3.15A 3.15A 750mA 750mA 750mA 750mA 750mA 750mA 750mA 750mA 500mA

Repeat panel 3.15A 3.15A

500mA250V
Fuse marking T3.15AH250V
(SB) - Slow blow
ceramic

All sector outputs have resettable 0.75A fuses which do not


All other fuses, ie FS1, FS2 and FS11 need replacing. The individual outputs will recover after
are 20mm x 5mm diameter removing the fault. The recovery time is 30 seconds minimum
QB - Quick Blow AS - Anti-Surge
SB - Slow Blow (ie Time Delay)
and it is recommended that the sectors be switched off (Silence Alarms).

Figure 12 Panel terminals and fuses

8 4188-424 issue 6_Part 1_06-12


Fire Panels Controls & indicators

Controls & indicators CONTROLS - only available when an access code is entered.
ZONE Fire, Fault or Disablement indications
yellow

Zones
red 1 2 3 4 5 6 7 8 yellow
FIRE
1 2 3 Test
Normally lit
Fault green to indicate
5 6 Power Power supply
System 4
healthy
yellow
Cancel System Delay
Power
Buzzer Reset 7 8 9
Earth yellow yellow
Sounder 0
v Access /
Sound Silence Function
Disabled Alarms Alarms Display Shift
The light is lit when
Numeric the Shift/Function key is pressed
keypad or there is an entry to controls
with coded access
Other Fault Display test
Essential controls Shift or Function
indications key
key
Figure 13 Controls and indications

Numeric keypad. Allows the entry emergency or at other agreed


q Power Fault. When lit or flashing
of numeric data. times, ie for sounder tests etc.
indicates that there is a power
Pressing the sound alarms
supply fault present.
q Shift key. The Shift/Function button does not action the
key gives access to the main auxiliary relay.
q Earth Fault. This indicator when
functions of the panel.
lit or flashing indicates that there
q Silence Alarms. Pressing the
is an Earth Fault on the system.
q Display test key. Pressing the Silence Alarms button after
Display Test key after entering entering access code will
silence the system alarms. q Sounder Fault. When flashing in
access code# will initiate a
Should only be pressed when conjunction with a flashing fault
sequence which illuminates all
the emergency is over. indicator indicates a sounder
the indicators in turn enabling
fault. When lit in conjunction with
them to be checked.
Indicators. the disabled indicator indicates
that the sounders are disabled.
# Coded entry is only
q Fire. When lit indicates that the
required if Cancel Buzzer and
system has detected a fire. q Disabled. Illuminates along with
Display Test functions are
the sounder or the zone
configured for operation at
q Fault. When lit or flashing indicators to show a disabled
Access level 2.
indicates that there is a fault condition.
condition on the system which
q Cancel Buzzer. Pressing the
requires rectification. q Test. When lit indicates that the
Cancel Buzzer button after
panel is in Test mode.
entering access code# will stop
q Zone Fire/Fault/Disablement.
the internal buzzer sounding.
Red indicator illuminates when q Power. When lit indicates that
there is a zone fire, it can be a the panel is powered up.
q System Reset. The system
steady or flashing indication.
reset key when pressed after
For a zone fault the yellow q Delay. When lit it indicates that a
entering access code will return
indicator is flashing. A lit zone delay will be effective after
the system to its normal
yellow indicator along with the detection of a fire before
operating state. If there are
Disabled indicator is used to activation of system alarms.
uncleared fires or faults then
show a disabled zone.
these conditions will re-occur.
q Access/Function. The
q System Fault. This indicator Access/Function lamp will flash
q Sound Alarms. Pressing the
when lit indicates that there is a when the shift key is pressed
Sound Alarms button after
fault in the panel’s processor. and will be lit when the coded
entering access code will sound
all of the system alarms. Should functions are accessed.
only be pressed in an

4188-424 issue 6_Part 1_06-12 9


Power up tests Fire Panels
Initial power up Sounder circuit tests
Power up tests a) Disconnect cables to terminals a) Transfer the end-of-line
Connecting the battery will not of zone, sounder, class resistor unit to the last device
power up the panel, power up will change, auxiliary, common fire on a sounder circuit.
occur after mains is applied. and fault circuits. Ensure each
cable is marked for b) Connect a sounder circuit
reconnection to respective cable to a sounder circuit
The total system should be tested terminals later. terminals.
in accordance with the
commissioning requirements of b) Connect end-of-line capacitor c) Carry out sounder open and
BS5839:Part 1:2002 + A2:2008 or units to zones and end-of-line short circuit tests and check
resistor units to sounder appropriate indications are
other standard specified by the
circuits for initial power up. given.
system purchaser.
c) Check mains connection and d) Repeat the above for other
switch on the mains power to sounder circuits.
NOTE: The commissioning the control panel. EEPROM Protection link
procedures assume that the
system has been installed as d) Now connect the battery
supply, see Figure 14.
per instructions in this booklet. NOTE: Ensure that at the end
e) Check the panel provides a of Commissioning and System
normal healthy indication, with tests the EEPROM protection
Checks before power up
the green light lit.
link is fitted to connector P8,
q Ensure you have 'as fitted Zone circuit tests
drawings' see Figure 14.
a) Transfer the end-of-line
q check the system has been capacitor unit to the last device
(detector or manual call point)
installed to the project on a zone circuit.
requirements.
b) Connect a zone cable to the
q if necessary, action the installer terminals of a zone circuit.
to carry out rectification work.
c) Carry out zone open circuit and
short circuit tests and check
q Remove the EEPROM appropriate indications are
protection link from connector given.
P8, see Figure 14.
d) Repeat the above for other
zone circuits.

a) Open the
lower outer cover Control panel

Instructions + Zone designation

Zones
1 2 3 4 5 6 7 8
FIRE 2 3 Test
1
Faults
Power
System 4 5 6
Day/Night
Power Cancel Reset
Earth
Buzzer System 7 8 9
NOTE: A label is supplied in the spares pack
Sounder

Disabled
Sound Silence
Alarms Alarms Display
0 v
Shift
Access /
Function b) Remove the which can be located on this cover to identify
lower inner plate
zone location
1 8
P8

EEPROM
Protection
c) Fit the batteries and
fitted across
connect the battery cables
pins 1 and 2

- + + -

- +
+ -
Connection for 12V 2.1Ah Batteries Connection for 12V 3.4Ah Batteries
For 1, 2 and 4 zone panels + repeat panel For 8 zone panels
Figure 14 Battery installation and EEPROM protection link

10 4188-424 issue 6_Part 1_06-12


Fire Panels Installed system tests

The operation of the control and Zone designation label


Installed system tests a) Write on to the zone
repeat panels and the system may
The fire detection and alarm be re-configured to site specific designation label the name that
system should be tested to ensure needs. identifies the area protected by
it operates to meet the standards each zone circuit.
and project requirements. To facilitate tests on the fire b) Fix the label over the zone
detection and alarm system the designation part of the lower
Configuration control panel can be set to operate inner plate, see Figure 14.
The control panel is factory set to in a test mode. Note a detector
Log book
the requirements of EN54 Parts 2 that is still full of smoke or heat will
and 4. retrigger into a fire condition until Fill in the system details on the
the smoke or heat in the area is first three pages of the log book.
With Test mode A or B active: a cleared.
On completion
triggered manual call point or fire Sound level test
detector in the test zone will give: Ensure the persons responsible
Sound level tests should be for the system are made aware of:
Test A Fire indication for conducted to standard - system operation
10 seconds duration requirements and to customer - access codes to controls
followed by a system
reset satisfaction. - basic controls
- their responsibility
Test B System alarm sounds for Other equipment tests
the first 2 seconds and - and the need to log system
at the same time a Fire Where external equipment is events in the log book.
indication is given for
10 seconds duration connected to the control panel
followed by a system using auxiliary, common fire and
reset
fault terminals, then these must be
Table 2 Test mode operation tested to project requirements.

Visual indications Signals out


Condition Zone Zone Test - Power - Access/ Aux Relay contacts Common fault - Common fire-
Fire Fault Yellow Green Function Normally de- Normally active Normally deactive
(1-8) (1-8) - - Yellow energised
-Red Yellow
Test A or B On On On On Normal Active Deactive
(Normal)
Test A On On On On Normal Active Deactive
(Fire)
Test B On On On On Normal Active Deactive
(Fire)

Test condition indications

Config. considerations q Illuminate the Common fire and the system by operating the Sound
appropriate zone fire lamps. Alarms button.
Repeat panel config.
q Cause the panels internal False alarm rejection
q The power up procedure for the
buzzer to emit the fire tone.
repeat panel is the same as the q This is an enhanced fire
main panel. alarm rejection algorithm
q Activate the common fire and
designed to give greater
auxiliary outputs.
q The presence of a repeat panel immunity to spurious alarms.
needs to be set up at the main
q Delays the activation of the
panel, see Config. and Test q The Fire alarm rejection
sounders for a configurable
section. algorithm should only be used in
delay of between 1 and 10
conjunction with recommended
minutes in 1 minute steps.
Delay mode detectors to guarantee that the
system will reject spurious events
In the Delay mode there is a delay If the panel is reset during the
but will detect and annunciate
between detecting a fire and delay period, the delay is
real fires within 10 seconds,
sounding the alarms to enable the cancelled. Also if another fire
which is an EN54-part 2
fire to be investigated. The panel occurs in a different zone to the
requirement. When set, the
will upon detection of a fire: first fire, the alarms will activate
algorithm applies to ALL zones
immediately. You can override the
on the panel.
delay and activate all sounders in

4188-424 issue 6_Part 1_06-12 11


Access levels 2 Fire Panels
Access codes
Access levels 2 NOTE: It is important to leave
Factory set codes are:
To configure the system enter the Access level 2 Code : 123 the system in a normal
appropriate access code. operating condition on
Depending on how the system is completion of commissioning.
configured coded entry may be
NOTE: It is only necessary to necessary for test.
enter the access code once, NOTE: The auxiliary contacts do
provided the 2 minute timeout is The factory codes can be not operate in the Test Modes.
not exceeded between button changed at any time after power
presses. up.

Operating Instructions for AL2 functions


How to do a Display test
q Enter the AL2 access code and check that the Access/function lamp is lit.

q Press the shift and display buttons and check that all indicators are lit.

How to set the panel to operate in Test mode A


q Enter the AL2 access code and check that the Access/function lamp is lit.

q Press the shift and 3 buttons followed by the number of the zone to be placed in test mode.
- Check that the Test indicator is On and the zone fault indicator is lit.
- The zone can be tested without an alarm of fire

How to set the panel to operate in Test mode B


q Enter the AL2 access code and check that the Access/function lamp is lit.

q Press the shift and 4 buttons followed by the number of the zone to be placed in test mode.
- Check that the Test indicator is On and the zone fault indicator is lit.
- The zone can be tested with 2 seconds alarm of fire.

How to cancel Test mode A/B


q Enter the AL2 access code and check that the Access/function lamp is lit.

q Press the shift and 5 buttons followed by the number of the zone to have test mode cleared.
- The test mode A or B is cancelled.
How to disable a zone
q Enter the AL2 access code and check that the Access/function lamp is lit.

q Press the shift and 1 buttons followed by the number of the zone to be disabled.
- Check that the appropriate Zone fault indicator and the Disabled indicator are lit.
- A detected fire in the disabled zone will not cause the panel to go into fire condition.

How to enable a zone


q Enter the AL2 access code and check that the Access/function lamp is lit.

q Press the shift and 2 buttons followed by the number of the zone to be re-enabled.
- The previously disabled zone is re-enabled.

12 4188-424 issue 6_Part 1_06-12


Fire Panels Operating Instructions for AL2 functions

How to disable sounders


q Enter the AL2 access code and check that the Access/function lamp is lit.

q Press the shift and 1 buttons followed by 0.


- Check that the Sounder and Disabled indicators are lit.
- The Sounder circuits are disabled.

How to enable sounders


q Enter the AL2 access code and check that the Access/function lamp is lit.

q Press the shift and 2 buttons followed by 0.


- The previously disabled sounders are now re-enabled.

How to change AL2 password


q Enter the AL3 access code and check that the Access/function lamp is lit.

q Press the shift and 9001 buttons in sequence and check that the System LED is flashing

q Input the new AL2 access code.

How to change AL3 password


q Enter the AL3 access code and check that the Access/function lamp is lit.

q Press the shift and 9002 buttons in sequence and check that the System LED is flashing

q Input the new AL3 access code.

How to set and unset the Delay mode


q Enter the AL2 access code and check that the Access/function lamp is lit.

q Press the shift and 6 buttons.


- The Delay mode toggles between Delay and No Delay each time this operation is performed.
When Delay mode is selected the Delay lamp is lit.

How to exit from AL2, AL3 or AL4 to AL1


q Press the shift button followed by 0.
- Check that the Access/function lamp is extinguished.
- The panel is now in access level AL1.

4188-424 issue 6_Part 1_06-12 13


Programming Options Fire Panels
Factory set codes: indicate that the EEPROM
Programming Options
AL3 code is: 321 protection link is removed. If
This is the code on first power-up further changes are required, the
NOTE: There is a 2 minute and it can be changed at any time. sequence shift followed by 9000
timeout on the access levels. If must be re-entered.
this period is exceeded the AL4 code is: 7426 Once the changes have been
code will have to be re-entered. This code is for the use by the made, the panel must be powered
servicing organisation only. down and then powered up again
In order to access the EEPROM, for the changes to take place.
There is a reset code, 2623
the EEPROM protection link
which will reset the AL2 and AL3
needs removing, see Figure 14.
codes to their factory settings. NOTE: After programming is
The default settings of the panel complete the EEPROM
Whilst the EEPROM is protection link must be refitted.
may be changed to suit site
unprotected during programming,
requirements.
the system fault light will flash to
Operating instructions for Access level 3 functions
To allow Cancel buzzer at access level 1 (default setting)
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 000 000

To allow Cancel buzzer at access level 2


q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 000 001

To allow Display test at access level 1


q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 001 001

To allow Display test at access level 2 (default setting)


q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 001 002

To allow Test condition at access level 2 (default setting)


q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 002 002

To allow Test condition at access level 3


q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 002 003

To allow most recent alarm indication as a steady state indication (default setting)
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 003 000

To allow most recent alarm as a pulsing indication


q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 003 001

To allow Auxiliary output to activate in fire and deactivate on reset (default setting)
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 005 000

To allow Auxiliary output to activate in fire and deactivate on reset and silence alarms
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 005 001
To change the Delay mode setting (default setting is 1 minute)
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 006 and data 000 to 010 in
minutes. Note if a value of greater than 10 minutes is entered, it will be truncated to 10 minutes.

14 4188-424 issue 6_Part 1_06-12


Fire Panels Operating instructions for Access level 4 functions
To allow False Alarm Rejection On/Off (default is Off)
q Enter 3 digit AL3 code (default = 321), press shift, Enter 9000 007 followed by 000 to turn the false alarm
rejection algorithm Off.

q Enter 3 digit AL3 code (default = 321), press shift, Enter 9000 007 followed by 001 to turn the false alarm
rejection algorithm On.

To enter number of connected Repeat panels (default setting is 0) - TO BE SET AT MAIN PANEL
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 009 001

Operating instructions for Access level 4 functions

CAUTION: These AL4 functions are for trained engineers only and normally
access to these functions is NOT required.

How to set Non Latching Zone configuration (default setting is all zones are latching)
q A non latching zone fire condition will not action the auxiliary relay.
Enter 4 digit AL4 access code (7426), Press Shift, Enter data 9000 032 and data as follows:
Decimal equivalent of eight bit number where a ‘1’ signifies a latching zone and a ‘0’ signifies a non latching
zone, also bit 0 corresponds to zone 1 and bit 7 corresponds to zone 8.
E.g. Requirement eight bit number data
All Zones non latching 00000000 000
Zone 1 latching, all others non latching 00000001 001
Zones 3,5,6 latching, all others non latching 00110100 052
All Zones latching 11111111 255
How to set Reset Silence Configuration (default silence alarms before reset)
q Enter 4 digit AL4 access code (7426), Press Shift, Enter data 9000 033 followed by 000 for a Reset Silences
and 001 for UK Linking.
How to set Sound/Resound alarms configuration (default is sound alarms at any time)
q Enter 4 digit AL4 access code (7426), Press Shift, Enter data 9000 034 followed by 000 for a Sound Alarms
at any time and 001 for Resound only.
How to set Zone short circuit configuration (default is short circuit seen as fault)
q Enter 4 digit AL4 access code (7426), Press Shift, Enter data 9000 035 data as follows:

Decimal equivalent of eight bit number where a ‘1’ signifies a zone short circuit being seen as a fire and a ‘0’
signifies a zone short circuit being seen as a fault, also the bit 0 corresponds to zone 1 and bit 7 corresponds
to zone 8.
E.g. Requirement eight bit number data
For all Zones - short circuit signifies a fault 00000000 000
Zone 1 - short circuit signifies a fire 00000001 001
Zones 3,5&6 - short circuit signifies a fire 00110100 052
All Zones - short circuit signifies a fire 11111111 255
How to set the number of zones used (default is 8 zone)
q Enter 4 digit AL4 access code (7426), Press Shift, Enter data 9000 036 followed by data as follows:
001 for One zone panel, 002 for Two zone panel, 004 for Four zone panel and 008 for Eight zone panel.
How to change Charger Output level (default is 128)
q Enter 4 digit AL4 access code (7426), Press Shift, Enter data 9000 037 followed by a number between 000
and 255.
How to change the Reset Duration (default is 010)
q Enter 4 digit AL4 access code (7426), Press Shift, Enter data 9000 038 followed by a number between 000
and 100, in tenths of a second.

4188-424 issue 6_Part 1_06-12 15


Fault indications Fire Panels

Fault indications How to silence the fault q Notice the buzzer is silenced
buzzer but visual indications remain
All fault repairs should be active.
q Press the 3 digit code, if
carried out by the required and then press Cancel
servicing organisation. Buzzer. NOTE: The sounder circuits
are pulse monitored for
In a fault condition:
failure.
Faults Cause
· the common Fault light What is a Zone A zone fault occurs when a zone circuit cable is open
is lit fault? circuit or short circuit, or the end-of-line capacitor unit
has been disconnected or a detector has been
removed.
· appropriate Fault light What is a A sounder fault occurs when a sounder circuit cable
is also lit Sounder fault? is open circuit or short circuit, or the end-of-line
resistor unit has been disconnected.
· internal Fault Buzzer sounds
intermittent tone What is a Mains A mains failure occurs when the mains power supply
power fault? to the panel is removed. This can occur on mains
fuse failure or mains supply disconnection.
· Multiple faults are
simultaneously annunciated What is a Battery A battery supply failure occurs when the battery
when this does not cause power fault? supply to the panel has failed (due to aging process)
or battery voltage is too low or is disconnected or the
confusion. battery fuse has failed.
What is an Earth An earth fault occurs when there is an electrical path
fault? for current flow from the system to earth connections.
NOTE: Normally the fault lights
What is a Repeat A Repeat Panel fault occurs when a fault is detected
will be automatically extinguished panel fault? within the Repeat Panel
once the fault condition is What is a Repeat A repeat panel link fault occurs when there is a
rectified. panel link fault? communication failure between the control and
repeat panels or if the link has been removed or
damaged.
NOTE: If the system detects a What is a System A system fault occurs in the event that the
Fault? microprocessor or software fails.
fire during a fault condition the
What is a charger A charger fault occurs when the charger will not
fault indicators may be fault? switch off or will not provide charge when on.
extinguished. What is a power A power fault occurs when there is an incorrect 24V
fault? level or fuse failure. Also occurs if the sounder output
supply is at the incorrect level or overloaded during
alarm condition.
Table 3 Types of faults

ZONE Fire, Fault or Disablement indications


yellow

Zones
red 1 2 3 4 5 6 7 8 yellow
FIRE
1 2 3 Test
Normally lit
Fault green to indicate
5 6 Power Power supply
System 4
healthy
yellow
Cancel System Delay
Power
Buzzer Reset 7 8 9
Earth yellow yellow
Sounder 0
v Access /
Sound Silence Function
Disabled Alarms Alarms Display Shift
The light is lit when
Numeric the Shift/Function key is pressed
keypad or there is an entry to controls
with coded access
Other Fault Display test
Essential controls Shift or Function
indications key
key
Figure 15 Fault indicators

16 4188-424 issue 6_Part 1_06-12


Fire Panels Fault finding

Fault finding

Is the Green
Power Indicator lit steadily Panel is in normal
Yes
and are all other indicators operating condition Refer to Zone/
Are the Zone
extinguished? Sounder
Fault and Disabled Yes
Indications
indicators lit?
table, Page
19

Are the fire/zone Refer to Operating


Yes
fire indicators lit? Instructions

Are the Sounder


Refer to the Test Fault and Disabled Yes
Is the Test indicator lit? Yes indicators lit
mode, see Page 11

Are the Fault


Refer to the PSU Fault
and Power fault indicators lit Yes
Indications table, Page Refer to Specialist help
or flashing?
18

Are the Fault Refer to the Earth


and Earth Fault indicators lit or Yes Fault Indications table,
flashing? Page 18

Are the Fault Refer to the Zone/


and Sounder Fault Yes Sounder Indications
indicators flashing? table, Page 19

Are the Fault


and Zone Fault indicators Yes
flashing?

Are the
Fault and Access/ Refer to the Repeat
Yes
Function indicators Panel Faults table, Page
pulsing? 19

Are the Fault


and System Fault Refer to the System
indicators On and is the Yes Fault (Software) table,
Power On indicator Page 19
On or flashing?

4188-424 issue 6_Part 1_06-12 17


Fault finding Fire Panels

PSU Fault Indications

At Main Panel
Green Power Indicator Power Fault Indicator Meaning
Steady Off No PSU Faults
Slow Flash Slow Flash Mains failed (Common Fault indicator also flashes to save batteries*)
Slow Flash Fast Flash Battery disconnected/Battery fault or Charger fault
Slow Flash Steady Auxiliary supply/sounder output supply fault
* If Access/Function indicator flashes slowly, there is either a comms fault, an earth fault or a PSU fault on the Repeat Panel.

At Repeat Panel
Green Power Indicator Power Fault Indicator Meaning
Steady Off No PSU Fault in either Main Panel or Repeat panel
Steady Slow Flash Mains failed at Main Panel
Steady Fast Flash Battery disconnected/Battery fault/Charger fault at Main Panel
Steady Steady Auxiliary supply/sounder output supply fault at Main Panel
Slow Flash Slow Flash Mains failed at Repeat Panel
Slow Flash Fast Flash Battery disconnected/Battery fault/Charger fault at Repeat Panel
* If Access/Function indicator flashes slowly, there is a comms fault, between the Main Panel and the Repeat Panel.

NOTE: If there is a PSU fault at the Main Panel and the Repeat Panel, then priority is given to the fault at the
Main Panel

Earth Fault Indications

At Main panel

Fault - Earth - Power - Buzzer Auxiliary relay contacts Common fault - Common fire -
Yellow Yellow Green normally de-energised normally active normally deactive
Earth fault Steady Pulse On Pulse Normal Deactive Deactive
indications Slowly Slowly

NOTE: If a Repeat panel is connected, the ACCESS/FUNCTION lamp will pulse slowly as well.

At Repeat Panel
Earth Fault Indicator Off No earth fault at the Repeat Panel or the Main Panel
Steady Indication Earth fault local to the Main Panel

18 4188-424 issue 6_Part 1_06-12


Fire Panels Fault finding

Zone/Sounder Indications

Visual Indications Audible Signals out


Indications
Condition Zone Fault - Sounder Disabled Power - Buzzer Aux Relay Common fault - Common
Fault Yellow - Yellow - Yellow Green contacts Normally active fire-
(1-8) - Normally Normally
Yellow de- deactive
energised
Zone Pulse Steady On Pulse slowly Normal Deactive Deactive
fault slowly
Sounder Steady Pulse On Pulse slowly Normal Deactive Deactive
fault slowly
Disable On On On Normal Active Deactive
zone
Disable On On On Normal Active Deactive
Sounder

Repeat Panel Fault Indications


Visual indications Audible Signals out
indication
Condition Fault - Power - Access/ Buzzer Aux Relay contacts Common fault - Common fire-
Yellow Green Function - Normally de-energised Normally active Normally deactive
Yellow
Repeat Steady On Pulse Pulse Normal Deactive Deactive
Panel Link slowly slowly
Fault

System Fault (Software) Indications

Visual indications Audible Signals out


indication
Condition Fault - System - Power - Buzzer Aux Relay contacts Common fault - Common fire-
Yellow Yellow Green Normally de-energised Normally active Normally deactive
Software On On On (Pulses On Normal Deactive Deactive
system at Repeat
fault panel)

4188-424 issue 6_Part 1_06-12 19


Specification for the Control panel Fire Panels

Specification for the Control panel


Note: Batteries are not supplied with some panels
Number of Zone (detection) circuits 1 - Zone panel 2 - Zone panel 4 - Zone panel 8 - Zone panel
Zone circuit voltage range 19V to 25.5V
Zone circuit load (maximum) Maximum Quiescent current: 3.0mA per zone OR
EN54 compliance limitation: 32 devices OR
Maximum of 20 diode bases per zone
(Short circuit current limited to < 20mA)
Number of Sounder circuits 2 2 4 8
Sounder circuit (shared load) 0.5A per output, 1A max shared load
@ 24V +2V -2V with mains present
(24V +2V -4V battery only)
Sounder circuit fuse 0.75A resettable
End-of-line unit Zone circuit: Capacitor (diode) unit Sounder circuit: 10K ohms resistor
OR Biploar Capacitor
Flush fixing kit 13270-29 (Cut out required 378mm wide x 245mm high x 60mm deep)
Colour Front cover - Grey RAL 7000 (standard)
Assembled panel size (in mm) 395 wide x 274 high x 87 deep
Weight (with batteries) approximate 5.8kg 5.8kg 5.8kg 6.2kg
Operating temperature and humidity 0 - 40oC low to +95% RH non condensing
Storage temperature and humidity -5oC to +50oC low to +95% RH condensing
Standards EN54-2: 1997, A1:2006 plus EN54-4: 1997, A1:2002, A2:2006
Approvals BSI approval acquired
Emission BS EN50081-1:1992: Part 1 Residential, Commercial & Light industry
Class B limits
Immunity BS EN50130-4: 1996: Part 4 Alarm systems : Electromagnetic compatibility
Product family standard: Immunity requirements for components of fire, intruder
and social alarm systems
IP rating (BS5490) IP31 (indoor)
Knock-In cable entry points 13 - top & 13 - back
Terminal size 2.5mm2 maximum
Battery standby with 1mA load per
zone and 1A total sounder alarm load 72hr standby plus 0.5hr with alarm load
Auxiliary contacts Pair of normally closed (NC) and a pair of normally open (NO) contacts rated
(operates with fire) 1A @ 24V dc resistive load (Maximum 100m cable distance)
Common Fault Open collector - normally On (35mA limit)
Common Fire Open collector - normally Off (16mA limit)
Class change Normally open push button, up to 100m cable distance away from the panel
24V Power supply (Monitored) 250mA maximum at 24V dc +2V, -4V 500mA maximum at 24V dc +1.5V, -4V
User access: By means of code entry AL2 Site security 3 digit code - 123
via numeric key pad AL3 Site engineering 3 digit code - 321
(AL1 Authorised user - No code is AL4 Engineers 4 digit code - 7426
required) Reset AL2 & AL3 codes 4 digit code - 2623
Key pad button controls Sound alarm, Silence alarm, System Reset & Cancel buzzer & numeric keypad.
Buzzer for local audible indications Fire & System Fault - continuous sound Fault - intermittent sound
(via piezoelectric buzzer operating at 2 or 2.5KHz 70dB(A) at 1m)
Visual indications FIRE & ZONES-fire (Red LEDs ‘lights’)
ZONES-fault, Fault, System, Power, Earth, Sounder, Disable, Test, Power,
Access/Function (Yellow LEDs ‘lights’)
Power on (Green LED ‘lights’)
Delay ( Yellow LED ‘lights’)
Repeat panel connections via serial port, see also repeat panel specification

20 4188-424 issue 6_Part 1_06-12


Fire Panels Specification for the Control panel

Specification for control panel’s Power supply


The control panel consists of single board containing both the control and indicating equipment and the power
supply. A 50VA mains transformer provides a low voltage (30Vac) supply into the power supply circuits. The on
board power supply circuits produce a regulated 24V dc supply, a 24V sounder supply and a battery charger
output.

Note the control and monitoring of the power supply unit is under direct control of the microprocessor of the
control and indicating equipment.

Mains supply
230V AC +10% -15% 50Hz
Mains Fused at 3.15A Ceramic Time delay
Typical standby power 6W
Maximum alarm power <60W (8 zone panel)

Internal supply
24V supply (Feeds current limited 24V dc +2V -2V (or 24V +2V -4V battery operation)
zone circuit & 24V fused output) current limited
<5% ripple voltage
24V Sounder supply (Feeds fused 24V dc +2V -2V (24V +2V -4V battery operation)
sounder circuit) Current limited
<5% ripple voltage
Battery Charger Float voltage 27.3V +1% -1% @ 20degC
Compensation -36mV/K (nominal)
Current limited @ 400mA +20% -20%
Fused @ 3.15A Ceramic Time delay
Reverse protection

Use the Battery Standby Calculator sheet available from 'www.gentexpert.co.uk' to determine the site specific battery
standby capability of the system.
Battery supply
Approved Batteries 12V, 2.1Ah POWERSONIC
12V 3.4Ah POWERSONIC
Type and capacity Sealed lead acid (value regulated)
2x12V, 2.1Ah min to 3.4Ah* max (1,2&4 zone panels)
2x12V, 3.4Ah*max (8 zone panel)
* max capacity limited by internal panel size
Maximum current 1.6A (no mains present)
Final voltage 21.6V
Installation requirements As per control panel

EN54 Part 4 data I min -> 120uA


I maxa -> 21.6mA
I maxb -> 1.5A
Ri max-> 2W
UVLO -> 18.5V ± 1.5V

4188-424 issue 6_Part 1_06-12 21


Specification for the Repeat panel Fire Panels

Specification for the Repeat panel


Number of Zones 8 - Zone (standard size)
Colour Front cover - Grey RAL 7000
Assembled panel size (in mm) 395 wide x 274 high x 87 deep
Weight (with batteries) approximate 5.8kg (2.1Ah battery) / 6.2Kg (with 3.4Ah battery)
Operating temperature and humidity 0 - 40oC low to +95% RH non condensing
Storage temperature and humidity -5oC to +50oC low to +95% RH condensing
Approvals Not applicable
Emission BS EN50081-1:1992: Part 1 Residential, Commercial & Light industry
Class B limits
Immunity BS EN50130-4: 1996: Part 4 Alarm systems : Electromagnetic compatibility
Product family standard: Immunity requirements for components of fire,
intruder and social alarm systems
IP rating (BS5490) IP31 (indoor)
Flush fixing kit 13270-29 (Cut out required 378mm wide x 245mm high x 60mm deep)
Mains operating voltage 230V ac +10% -15% 50Hz
Knock-In cable entry points Top & back entries
Terminal size 2.5mm2 maximum
Battery supply (sealed lead acid) 2-off12V 2.1Ah - 3.4Ah (See applicable batteries as listed for Control panel
Standby duration 72hr standby
User access: By means of code entry AL2 Site security 3 digit code - 123
via numeric key pad AL3 Site engineering 3 digit code - 321
(AL1 Authorised user - No code is AL4 Engineers 4 digit code - 7426
required) Reset AL2 & AL3 codes 4 digit code - 2623
NOTE: Only a limited number of functions are accessible at the repeat panel.
Key pad button controls Sound alarm, Silence alarm, System Reset & Cancel buzzer & numeric
keypad.
Buzzer for local audible indications Fire & System Fault - continuous sound Fault - intermittent sound
(via piezoelectric buzzer operating at 2 or 2.5KHz 70dB(A) at 1m)
Visual indications FIRE & ZONES-fire (Red LEDs ‘lights’)
ZONES-fault, Fault, System, Power, Earth, Sounder, Disable, Test, Power,
Access/Function (Yellow LEDs ‘lights’)
Power on (Green LED ‘lights’)
Delay (LED ‘lights’)
Repeat panel (standard 8 zone) A maximum of 1 repeat panel can be connected in series with the control
panel
Repeat panel connections via serial port

22 4188-424 issue 6_Part 1_06-12


Fire Panels Parts list

Parts list Manual call points (MCP)


Part number Description
Panels
XENS-850 or Flush MCP 470 Ohms Glass
Part number Description MCP1A-R470FG-01
# - less batteries
13270-02LB 2 Zone control panel # XENS-805 or Surface MCP 470 Ohms Re-settable
75585-02NMB 2 Zone control panel # MCP1A-R470SF-01

13270-04LB 4 Zone control panel # XENS-829 or Weatherproof MCP 470 Ohms resistor
75585-04NMB 4 Zone control panel # MWCP1A-R470SG-01 Glass

13270-08LB 8 Zone control panel # XENS-807 Key Operated, Surface Mounted c/w
75585-08NMB 8 Zone control panel # backbox

13271-08LB Repeat panel # XENS-891 Spare Glasses for MCP XENS-800


75586-08NMB Repeat panel # (Pack of 10)
XENS-890 Resettable element for XENS-800
13270-29 Panel flush fixing kit and XENS-805 (pack of 10)
XENS-892 Hinged protective cover for use on
Automatic Fire Detectors XENS-800 range (pack of 10)
XENS-895 Surface Backbox for XENS-800 range
Part number Description
of MCP (pack of 10)
178xx range
XENS-893 Replacement keys for XENS-807
17840-01 Optical Smoke Detector
K/S MCP (pack of 10)
17850-01 Fixed Temperature (58oC) Heat
XENS-899 Pack of test keys (pack of 10)
17860-01 Rate of Rise Heat Detector
17870-01 High Temperature Detector
71150-62NM MCP red surface mounted for
17800-01 Base (without diode)
NO and NC connections
17801-01 Base (with diode)
17800-02 Low profile base (without diode)
24Vdc Alarm signals
17801-02 Low profile base (with diode)
Part number Description
07011-40 Optical Beam reflective 12141-04 Electronic bell (red) IP40
` 50m to 100m 02601-31 Squashni Sounder 24Vdc 18mA
IP54 93dBA @ 1m

NOTE: The beam detector should be powered from 02519-52 Bedhead Sounder 24Vdc 18mA
an external 24V power supply. This arrangement (white) 97dBA @ 1m
requires a reset switch in series with the supply.
C3IP-SN-R IP65 Electronic Sounder
Red (100dBA)
Vision range C3IP-SN-W IP65 Electronic Sounder
Part number Description White (100dBA)
2020P Optical Smoke detector C3-SN-R IP31 Electronic Sounder
2020PT Optical Heat detector Red (100dBA)
2020F Fixed Temp Heat detector C3-SN-W IP31 Electronic Sounder
2020HF High Temp Heat detector White (100dBA)
2020R Rate of Rise Heat Detector C3IP-SN-ST-RR IP65 Electronic Sounder/Strobe
Red (100dBA)
2020B Standard Detector Base C3IP-SN-ST-WR IP65 Electronic Sounder/Strobe
2020BSD Standard Det. Base with diode White (100dBA)
2020DB Deep Detector Base C3-SN-ST-RR IP31Electronic Sounder/Strobe
2020DBSB Deep Detector Base with diode Red (100dBA)
C3-SN-ST-WR IP31 Electronic Sounder/Strobe
72499-24NM Circular remote LED White (100dBA)
ZF18 Square remote LED C3-VP-ST-RR IP31Voice sounder/Strobe
17899-44 Repeat Relay Red (100dBA)
C3-VP-ST-WR IP31 Voice sounder/Strobe
White (100dBA)
C2IP-ST-RR IP65 Ultra Low current Strobe
(5mA) red body/red lens

4188-424 issue 6_Part 1_06-12 23


Parts list Fire panels

24Vdc Alarm signals


Part number Description
CONV-IP-SN-R IP55 Electronic Sounder
Red 100 dBA
CONV-SN-R IP31 Electronic Sounder
Red 100dBA
CONV-SN-ST-RR IP55 Electronic Sounder Strobe
Red body Red lens 100 dBA
CONV-IP-ST-RR IP55 Ultra low current Strobe
Red body Red lens
CONV-IP-VP-R IP55 Voice Enhanced Electronic
Sounder Red (100 dBA)

CONV-IP-VP-ST-RR IP55 Voice Enhanced


Electronic Sounder and Strobe
Red Body Red Lens (100 dBA)

74451-24NM Multitone Low Profile Sounder,


Red with shallow base
74452-24NM Multitone Low Profile Sounder,
Red with deep base
74456-24NM Sounder base, White 3 tone
74455-24NM Bedhead Sounder
74456-61NM Sounder base cover plate
74430-88NM 6" Electronic bell 24V dc
Red IP40
74432-88NM 6" Electronic bell, weather
resistant Electronic bell,
24V dc Red IP55
0086
Panel Accessories Gent by Honeywell
Hamilton Industrial Park, 140 Waterside Road, Leicester LE5 1TN, UK
Part number Description
0086-CPD-553764
XENS-BATT-12 2 x 12V 2.1Ah battery
Xenex
(for 1, 2 & 4 zone
panel plus repeat panel) EN54-2: 1997, A1:2006
Control and Indicating equipment for fire detection and fire alarm systems
in buildings
XENS-BATT-48 2 x 12V 3.4Ah battery
(for 8 zone panel) 7.8 Output to Fire alarm device(s)
7.10 Test Conditions
7.11 Delays to action outputs
XEN-FFR Fire fault relay unit
EN54-4: 1997, A1:2002, A2:2006
Power supply equipment for fire detection and fire alarm systems in
buildings.

Other technical data: see documents in project file 6304, held by the
manufacturer.

WEEE Directive:
At the end of their useful life, the packaging, At the end of their useful life, the packaging,
product and batteries should be disposed of product and batteries should be
disposed of via a suitable recycling centre.
via a suitable recycling centre and in Do not dispose of with your normal household waste.
accordance with national or local legislation. Do not burn.

Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the
content hereof without obligation to notify any person of such revisions of changes.

Hamilton Industrial Park, Waterside Road, Leicester LE5 1TN, UK Website: www.gent.co.uk

by Honeywell
Telephone: +44 (0) 116 246 2000 Tech. Support: www.gentexpert.co.uk Fax (UK): +44 (0)116 246 2300

4188-424 issue 6_Part 1_06-12

You might also like