TECHNICAL SPECIFICATION - LV POWER CABLE - Hyundai Engineering - WP-1 LINE Project - LSAG - 20Mar2023.Rev.5

1. The document provides technical specifications for several types of low voltage power cables to be used in the WP-1 LINE Project for Hyundai Engineering. 2. The cables covered include armored and unarmored cables with copper conductors, XLPE insulation, and PVC sheathing for voltages up to 1.2kV. Specialty cables for variable speed drives and fire resistance are also specified. 3. The document outlines the construction requirements for conductors, insulation, screens, armor, and sheathing as well as testing, marking, packing, and documentation requirements to be followed for the cable supply.

Uploaded by

nn
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
167 views36 pages

TECHNICAL SPECIFICATION - LV POWER CABLE - Hyundai Engineering - WP-1 LINE Project - LSAG - 20Mar2023.Rev.5

1. The document provides technical specifications for several types of low voltage power cables to be used in the WP-1 LINE Project for Hyundai Engineering. 2. The cables covered include armored and unarmored cables with copper conductors, XLPE insulation, and PVC sheathing for voltages up to 1.2kV. Specialty cables for variable speed drives and fire resistance are also specified. 3. The document outlines the construction requirements for conductors, insulation, screens, armor, and sheathing as well as testing, marking, packing, and documentation requirements to be followed for the cable supply.

Uploaded by

nn
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 36

REQ No. : Ref. No.

: LSAG-22-PD2204020
User / Customer : Hyundai Engineering Page No. : 1 of 35
Title : WP-1 LINE Project
Manufacture : LSAG Cable Indonesia
Document Title :

Technical Specification For


LV Power Cable
Low Voltage Power Cable – Armoured
N2XR(Al)Y - 0.6/1(1.2)kV
(Cu/XLPE/AWA/PVC-FR) - 0.6/1(1.2)kV
N2XRY - 0.6/1(1.2)kV
(Cu/XLPE/SWA/PVC-FR) - 0.6/1(1.2)kV

Low Voltage Power Cable - Un Armoured


N2XY - 0.6/1(1.2)kV
(Cu/XLPE/PVC-FR) - 0.6/1(1.2)kV

Low Voltage Power Cable for VSD Cable


N2XSRY - 0.6/1(1.2)kV
(Cu/XLPE/CTS/SWA/PVC-FR) ) - 0.6/1(1.2)kV
N2XCRY - 0.6/1(1.2)kV
(Cu/XLPE/CWS/CTS/SWA/PVC-FR) - 0.6/1(1.2)kV

Low Voltage Power Cable for EBV


N2XRY-FRC - 0.6/1(1.2)kV
(Cu/MICA/XLPE/SWA/PVC-FR) - 0.6/1(1.2)kV

Additional Item (N2XR(AL)Y 1 x 95


5 20, Mar. 2023 sqmm, N2XCRY 3 x 16 sqmm)
Reza S. M. Yanuar R. Teguh S.

4 09, Feb. 2023 Additional Item (N2XSRY, N2XCRY) Reza S. M. Yanuar R. Teguh S.
2
3 31, Jan. 2023 Additional Item N2XRY-FRC 3x70 mm Reza S. M. Yanuar R. Teguh S.
2 10, Jan. 2023 Construction Issue Reza S. M. Yanuar R. Teguh S.
1 28, Nov. 2022 Technical Data Issue Reza S. M. Yanuar R. Teguh S.
0 30, May. 2022 Original Issue Yanuar R. Teguh S. W.Y. Jung
Rev. No. Date Descriptions Prepared By Reviewed By Approved By
1. SCOPE

1.1. This specification covers 0.6/1 (1.2) kV copper conductor, cross-linked polyethylene
insulated (XLPE) and PVC over sheathed armoured and non armoured power, VSD,
and fire resistance (EBV) cable generally in accordance with SNI IEC 60502-1 unless
otherwise specified in this specification.
1.2. The types of power cable included in this specification :

Cable description Cable type

0.6/1(1.2)kV Copper conductor, XLPE insulated, Cu/XLPE/AWA/PVC FR Cat.C


Aluminum Wire armour, PVC over sheathed cables (N2XR(Al)Y) - 0.6/1(1.2)kV
Flame Retardant Cat. C

0.6/1(1.2)kV Copper conductor, XLPE insulated,


Cu/XLPE/SWA/PVC FR Cat.C
Steel Wire armour, PVC over sheathed cables
(N2XRY) - 0.6/1(1.2)kV
Flame Retardant Cat. C

0.6/1(1.2)kV Copper conductor, XLPE insulated, Cu/XLPE/PVC FR Cat.C


PVC over sheathed cables Flame Retardant Cat. C (N2XY) - 0.6/1(1.2)kV

0.6/1(1.2)kV Copper conductor, XLPE insulated,


Cu/XLPE/CTS/SWA/PVC FR Cat.C
Copper Tape screen, Steel Wire armour, PVC over
(N2XSRY) - 0.6/1(1.2)kV
sheathed cables Flame Retardant Cat. C

0.6/1(1.2)kV Copper conductor, XLPE insulated,


Cu/XLPE/CWS/CTS/SWA/PVC FR Cat.C
Copper Wire screen, Steel Wire armour, PVC over
(N2XCRY) - 0.6/1(1.2)kV
sheathed cables Flame Retardant Cat. C

0.6/1(1.2) kV Fire Resistance Power Cable


Copper conductor, XLPE Insulation, Steel Wire Cu/MICA/XLPE/SWA/PVC FR
armour, PVC over sheathed cables Flame (N2XRY-FRC) - 0.6/1(1.2)kV
Retardant Cat. C

2. REFERENCE STANDARDS

IEC 60228 : Conductors of insulated cables


SNI IEC 60502-1 : Power cables with extruded insulation and their accessories for rated
voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables
for rated voltages from 1 kV (Um = 1,2 kV) up to 3 kV (Um = 3,6 kV)
IEC 60811 : Common test methods for insulating and sheathing materials of electric
cables
IEC 60332-3-24 : Test on electric and optical fibre cables under fire conditions (Cat.C)
IEC 60331-21 : Tests for electric cables under fire conditions - Circuit integrity - Part 21:
Procedures and requirements - Cables of rated voltage up to and including
0,6/1,0 kV
SNI 0225 : 2011 : Persyaratan Umum Instalasi Listrik 2011

TECHNICAL SPECIFICATION_LV POWER CABLE 2 of 35


3. CONSTRUCTION AND MATERIAL

3.1. Conductor
The conductor shall be the plain annealed copper conductor complying with IEC 60228
(Class 2). The shape of conductor shall be round stranded for size under 16 sqmm,
compacted circular stranded for size 16 sqmm and above.
3.2. Fire Proof Layer (for EBV cable)
The fireproof layer shall be consisted of mica/glass tape or mica laminated plastic film
tape. The layer shall be applied between the conductor and insulation.
3.3. Insulation
The insulation shall be extruded layer of cross-linked polyethylene (XLPE) compound
complying with SNI IEC 60502-1.
The minimum thickness at any point shall not fall below 90% of the nominal value by
more than 0.1 mm.
3.4. Assembly and fillers (for multi-cores cable only).
The cores shall be laid up together and suitable direction. Where necessary, non-
hygroscopic filler may be used to give the completed cable substantially circular cross-
section with suitable binder tape.
3.5. Inner sheath / Separation Sheath (for armour type)
The inner sheath shall be an extruded layer of black PVC complying with SNI IEC 60502-
1.
The minimum thickness at any point shall not fall below the value given in the attached 1
till 5. by more than 20% + 0.2mm.
3.6. Metallic Screen (for VSD cable N2XSRY or N2XCRY)
The metallic screen shall consist of one or more copper tapes or combination of copper
wire and copper tape(s).
3.7. Armoured
The armoured type of cable covered use aluminum round wire (AWA) for single core
cable and galvanized steel round wire armour (SWA) for multicore cable.
3.8. Over sheath
The over sheath shall be an extruded layer of black PVC/ST2 compound for flame
retardant and orange PVC/ST2 compound for fire resistance with water penetration
resistant comply to SNI IEC 60502-1.
The minimum thickness at any point shall not fall below the value given in the attached
table 1. by more than 20% + 0.2mm.

4. CORE IDENTIFICATION

Each core of cable shall be identified by color :


- 1 cores : Black
- 2 cores : Brown – Black
- 2 cores with Ground (1P+N+G) : Brown – Black – Yellow w/ Green Stripe
- 3 cores : Brown – Black – Grey
- 3 cores with Ground (3P+G) : Brown – Black – Grey – Yellow w/ Green Stripe
- 3 cores with Ground (3P+3G) : Brown – Yellow w/ Green Stripe (1) – Black – Yellow w/
Green Stripe (2) – Grey – Yellow w/ Green Stripe (3)
- 4 cores (3P+N) : Brown – Black – Grey – Blue
- 4 cores with Ground (3P+G+N) : Brown – Black – Grey – Yellow w/ Green Stripe – Blue

TECHNICAL SPECIFICATION_LV POWER CABLE 3 of 35


5. TEST

The test shall be carried out in accordance with SNI IEC 60502-1 & IEC 60332-3-24 for Flame
Retardant and accordance with SNI IEC 60502-1 & IEC 60331-21 for Fire Resistance. For
detail test will be inform in Inspection Test Plan (ITP) document.

6. MARKING

6.1. Cable Marking


The following legend shall be printed on the surface of over sheath throughout the length
of cable. Maximum interval between marking should not exceed 550 mm.
− Ref. standard no. : SNI IEC 60502-1
− Brand name : LSAG
− Cable type : Cu/XLPE/SWA/PVC
− Flame retardant grade : FR Cat. C
− Common Indonesian cable type : (N2XRY)
− Nos. of core & Conductor size
− Rated voltage : 0.6/1(1.2)kV
− Year of manufacture
− Length marking per meter

ex) SNI IEC 60502-1 LSAG Cu/XLPE/SWA/PVC FR Cat.C (N2XRY-FR) 3x150㎟ 0.6/1(1.2)kV 2022
0001M
ex) SNI IEC 60502-1 LSAG Cu/MICA/XLPE/SWA/PVC FRC 750 (N2XRY-FRC) 3x6㎟ 0.6/1(1.2)kV
2022 0001M

6.2. Drum Marking


The Following information shall be marked.
− Rated voltage and cable type
− Nos. of core and conductor size
− Cable length
− Net weight
− Gross weight
− Direction of rotation
− End position of cable
− Manufacturer’s name
− Year of manufacture
− Drum Number

7. PACKING

The completed cables shall be supplied a non-returnable wooden or steel drum to prevent
from damage during the transportations.
The end of cable shall be sealed to prevent the ingress of moisture.
The diameter of wooden drum shall be complied manufacturer’s standard.

TECHNICAL SPECIFICATION_LV POWER CABLE 4 of 35


Attached table 1. : DESIGN PARTICULAR

A. Armoured Cable

A.1 Cu/XLPE/AWA/PVC FR Cat.C (N2XR(Al)Y) - 0.6/1 (1.2) kV Single Core

Overall Current-Carrying
Conductor Insulation Diameter of Thickness DC Short
Nominal Weight Capacity
Inner Sheath of Overall Resistance circuit
Cross- of Impedance
Over Diameter at current
sectional Outside (Bedding Cable
No. of Outside Thickness Sheath 20oC in air at 1 sec
Area Wire Diameter Diameter Layer) in ground
at 300C at 200C
(min) (Approx.) (nom.) (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.)
2
mm - mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

95 15 11.5 1.1 13.8 15.8 1.8 21.5 1,300 0.193 0.267 269 226 13.59

120 18 13.0 1.2 15.5 17.5 1.8 22.5 1,575 0.153 0.220 312 257 17.16

150 18 14.5 1.4 17.4 19.4 1.8 24.5 1,881 0.124 0.187 342 287 21.45

185 18 16.0 1.6 19.3 21.3 1.9 26.0 2,284 0.0991 0.160 384 324 26.46

240 30 18.5 1.7 22.0 23.9 2.0 28.5 2,884 0.0754 0.135 450 375 34.32

300 34 20.5 1.8 24.2 26.2 2.1 31.0 3,622 0.0601 0.121 514 419 42.90

400 34 23.5 2.0 27.6 29.8 2.2 34.5 4,541 0.047 0.110 648 513 57.20

500 53 26.5 2.2 31.0 33.4 2.3 38.0 5,638 0.0366 0.102 747 570 71.50

630 53 30.5 2.4 35.3 38.0 2.5 42.0 7,237 0.0283 0.098 864 638 90.09

TECHNICAL SPECIFICATION_LV POWER CABLE 5 of 35


A.2 Cu/XLPE/SWA/PVC FR Cat.C (N2XRY) - 0.6/1 (1.2) kV Two Core

Current-Carrying
Conductor Insulation Overall DC Short
Thickness Weight Capacity
Nominal Diameter of Overall Resistance circuit
Cross- of of Impedance
Inner Sheath Diameter at current
sectional Outside Over Sheath Cable in air in
No. of Outside Thickness (Bedding Layer) 20oC at 1 sec
Area Wire Diameter Diameter at ground
300C at 200C
(min) (Approx.) (nom.) (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.)
2
mm - mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

4 7 2.5 0.7 4.1 10.2 1.8 15.5 567 4.61 5.879 45 43 0.57

6 7 3.5 0.7 4.9 11.3 1.8 17.5 653 3.08 3.928 58 53 0.86

10 7 4.0 0.7 5.5 13.1 1.8 19.0 802 1.83 2.335 69 80 1.43

16 6 5.0 0.7 6.4 14.6 1.8 20.5 954 1.15 1.469 91 107 2.29

25 6 6.0 0.9 7.9 17.8 1.8 24.5 1,419 0.727 0.930 119 138 3.58

35 6 7.0 0.9 8.9 19.8 1.8 26.5 1,676 0.524 0.672 148 171 5.01

50 6 8.5 1.0 10.5 23.2 1.9 29.5 2,058 0.387 0.499 175 209 7.15

70 12 10.0 1.1 12.2 27.0 2.1 34.5 2,921 0.268 0.349 269 213 10.01

95 15 11.5 1.1 13.8 30.6 2.2 38.0 3,622 0.193 0.256 328 252 13.59

120 18 13.0 1.2 15.5 34.0 2.3 42.0 4,288 0.153 0.208 382 271 17.16

150 18 14.5 1.4 17.4 38.2 2.5 47.0 5,519 0.124 0.173 441 306 21.45

185 30 16.0 1.6 19.3 42.0 2.7 51.5 6,530 0.0991 0.146 506 343 26.46

240 34 18.5 1.7 21.9 47.2 2.8 57.0 7,996 0.0754 0.120 599 395 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 6 of 35


A.3 Cu/XLPE/SWA/PVC FR Cat.C (N2XRY) - 0.6/1 (1.2) kV Two Core with One Ground (1P+N+G)

Short
Overall Overall DC Resistance Current-Carrying circuit
Conductor
Thickness Diameter Diameter Thickness at 20oC Capacity current
Nominal Weight
of of of Inner of Overall at 1 sec
Cross-sectional of Impedance
Insulation Insulation Sheath Over Diameter
Area Cable in
(nom.) (Bedding Sheath
No. of Wire Outside Diameter in air ground Phase
Phase Layer) Phase Ground
(min.) (approx.) at at
300C 200C
Phase Ground Phase Ground Phase Ground Phase Ground (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.) (Max).
2 2
mm mm min. min. mm mm mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (Ω/km) (A) (A) (kA)

4 4 7 7 2.5 2.5 0.7 0.7 4.1 10.8 1.8 17.5 644 5.879 4.61 4.61 40 36 0.57

6 6 7 7 3.5 3.5 0.7 0.7 4.9 12.0 1.8 18.5 738 3.928 3.08 3.08 52 44 0.86

10 10 7 7 4.0 4.0 0.7 0.7 5.5 14.0 1.8 20.5 939 2.335 1.83 1.83 71 58 1.43

16 16 6 6 5.0 5.0 0.7 0.7 6.4 15.6 1.8 23.0 1,287 1.469 1.15 1.15 96 75 2.29

25 25 6 6 6.0 6.0 0.9 0.9 7.9 19.0 1.8 26.0 1,711 0.930 0.727 0.727 119 96 3.58

35 25 6 6 7.0 6.0 0.9 0.9 8.9 21.2 1.9 28.45 2,002 0.672 0.524 0.727 147 115 5.01

50 25 6 6 8.5 6.0 1.0 0.9 10.5 24.8 2.0 32.0 2,389 0.499 0.387 0.727 179 135 7.15

70 35 12 6 10.0 7.0 1.1 0.9 12.2 29.3 2.2 37.5 3,411 0.349 0.268 0.524 229 167 10.01

95 50 15 6 11.5 8.5 1.1 1.0 13.8 32.7 2.3 41.5 4,199 0.256 0.193 0.387 278 197 13.59

120 70 18 12 13.0 10.0 1.2 1.1 15.5 36.4 2.4 46.0 5,495 0.208 0.153 0.268 322 223 17.16

150 95 18 15 14.5 11.5 1.4 1.1 17.4 40.9 2.6 51.0 6,627 0.173 0.124 0.193 371 251 21.45

185 95 30 15 16.0 11.5 1.6 1.1 19.3 45.0 2.7 55.5 7,645 0.146 0.0991 0.193 424 281 26.46

240 120 34 18 18.5 13.0 1.7 1.2 21.9 51.0 2.9 62.0 9,402 0.120 0.0754 0.153 500 324 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 7 of 35


A.4 Cu/XLPE/SWA/PVC FR Cat.C (N2XRY) - 0.6/1 (1.2) kV Three Core

Overall Current-Carrying
Conductor Insulation DC
Nominal Diameter of Thickness Weight Capacity Short
Overall Resistance
Cross- Inner Sheath of of Impedance circuit current
Diameter at
sectional Outside (Bedding Over Sheath Cable in at 1 sec
No. of Outside Thickness 20oC in air
Area Layer) ground
Wire Diameter Diameter
at 300C at 200C
(min) (Approx.) (nom.) (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.)
mm2 - mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

4 7 2.5 0.7 4.1 10.9 1.8 17.5 644 4.61 5.879 40 36 0.57

6 7 3.5 0.7 4.9 12.0 1.8 18.5 738 3.08 3.928 52 44 0.86

10 7 4.0 0.7 5.5 14.0 1.8 20.5 939 1.83 2.335 71 58 1.43

16 6 5.0 0.7 6.4 16.0 1.8 23.0 1,287 1.15 1.469 96 75 2.29

25 6 6.0 0.9 7.9 19.0 1.8 26.0 1,711 0.727 0.930 119 96 3.58

35 6 7.0 0.9 8.9 21.2 1.9 28.5 2,088 0.524 0.672 147 115 5.01

50 6 8.5 1.0 10.5 24.8 2.0 32.0 2,590 0.387 0.499 179 135 7.15

70 12 10.0 1.1 12.2 29.3 2.2 37.5 3,716 0.268 0.349 229 167 10.01

95 15 11.5 1.1 13.8 32.7 2.3 41.5 4,616 0.193 0.256 278 197 13.59

120 18 13.0 1.2 15.5 36.4 2.4 46.0 5,943 0.153 0.208 322 223 17.16

150 18 14.5 1.4 17.4 40.9 2.6 51.0 7,103 0.124 0.173 371 251 21.45

185 30 16.0 1.6 19.3 45.0 2.7 55.5 8,464 0.0991 0.146 424 281 26.46

240 34 18.5 1.7 21.9 51.0 2.9 62.0 10,517 0.0754 0.120 500 324 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 8 of 35


A.5 Cu/XLPE/SWA/PVC FR Cat.C (N2XRY) - 0.6/1 (1.2) kV Three Core with One Ground (3P+G)

Overall
Short
Overall Diameter
DC Resistance Current-Carrying circuit
Conductor Thickness Diameter of Inner Thickness
Nominal Weight at 20oC Capacity current
of of Sheath of Overall
Cross-sectional of Impedance at 1 sec
Insulation Insulation (Bedding Over Diameter
Area Cable
(Approx.) Layer) Sheath
in air in
No. of Wire Outside Diameter
Phase Phase Ground at ground Phase
(min.) (Approx.)
300C at 200C
Phase Ground Phase Ground Phase Ground Phase Ground (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.) (Max.)

mm2 mm2 min. min. Mm mm mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (Ω/km) (A) (A) (kA)

4 4 7 7 2.5 2.5 0.7 0.7 4.1 11.9 1.8 18.5 725 5.879 4.61 4.61 40 36 0.57

6 6 7 7 3.5 3.5 0.7 0.7 4.9 13.2 1.8 19.5 851 3.928 3.08 3.08 52 44 0.86

10 10 7 7 4.0 4.0 0.7 0.7 5.5 15.4 1.8 22.5 1,225 2.335 1.83 1.83 71 58 1.43

16 16 6 6 5.0 5.0 0.7 0.7 6.4 17.2 1.8 24.5 1,514 1.469 1.15 1.15 96 75 2.29

25 25 6 6 6.0 6.0 0.9 0.9 7.9 21.1 1.9 28.5 2,047 0.930 0.727 0.727 119 96 3.58

35 25 6 6 7.0 6.0 0.9 0.9 8.9 23.5 1.9 31.0 2,431 0.672 0.524 0.727 147 115 5.01

50 25 6 6 8.5 6.0 1.0 0.9 10.5 27.9 2.1 35.5 3,223 0.499 0.387 0.727 179 135 7.15

70 35 12 6 10.0 7.0 1.1 0.9 12.2 32.4 2.3 41.0 4,233 0.349 0.268 0.524 229 167 10.01

95 50 15 6 11.5 8.5 1.1 1.0 13.8 36.3 2.4 46.0 5,714 0.256 0.193 0.387 278 197 13.59

120 70 18 12 13.0 10.0 1.2 1.1 15.5 40.8 2.6 51.0 6,961 0.208 0.153 0.268 322 223 17.16

150 95 18 15 14.5 11.5 1.4 1.1 17.4 45.4 2.8 56.0 8,331 0.173 0.124 0.193 371 251 21.45

185 95 30 15 16.0 11.5 1.6 1.1 19.3 50.4 2.9 61.0 9,810 0.146 0.0991 0.193 424 281 26.46

240 120 34 18 18.5 13.0 1.7 1.2 21.9 56.7 3.1 68.0 12,111 0.120 0.0754 0.153 500 324 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 9 of 35


A.6 Cu/XLPE/SWA/PVC FR Cat.C (N2XRY) - 0.6/1 (1.2) kV Four Core (3P+N)

Overall Current-Carrying
Conductor Insulation Diameter of DC
Nominal Thickness Weight Impedance Capacity Short
Inner Sheath Overall Resistance
Cross- of of circuit current
(Bedding Layer) Diameter at
sectional Outside Over Sheath Cable in at 1 sec
No. of Outside Thickness 20oC in air
Area Wire Diameter Diameter ground
at 300C at 200C
(min) (Approx.) (nom.) (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.)
2
mm - mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

4 7 2.5 0.7 4.1 11.9 1.8 18.5 725 4.61 5.879 40 36 0.57

6 7 3.5 0.7 4.9 13.2 1.8 19.5 851 3.08 3.928 52 44 0.86

10 7 4.0 0.7 5.5 15.4 1.8 22.5 1,225 1.83 2.335 71 58 1.43

16 6 5.0 0.7 6.4 17.2 1.8 24.5 1,514 1.15 1.469 96 75 2.29

25 6 6.0 0.9 7.9 21.1 1.9 28.5 2,047 0.727 0.930 119 96 3.58

35 6 7.0 0.9 8.9 23.5 1.9 31.0 2,516 0.524 0.672 147 115 5.01

50 6 8.5 1.0 10.5 27.9 2.1 35.5 3,424 0.387 0.499 179 135 7.15

70 12 10.0 1.1 12.2 32.4 2.3 41.0 4,538 0.268 0.349 229 167 10.01

95 15 11.5 1.1 13.8 36.3 2.4 46.0 6,131 0.193 0.256 278 197 13.59

120 18 13.0 1.2 15.5 40.8 2.6 51.0 7,409 0.153 0.208 322 223 17.16

150 18 14.5 1.4 17.4 45.4 2.8 56.0 8,807 0.124 0.173 371 251 21.45

185 30 16.0 1.6 19.3 50.4 2.9 61.0 10,629 0.0991 0.146 424 281 26.46

240 34 18.5 1.7 21.9 56.7 3.1 68.0 13,226 0.0754 0.120 500 324 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 10 of 35


A.7 Cu/XLPE/SWA/PVC FR Cat.C (N2XRY) - 0.6/1 (1.2) kV Four Core with One Ground (3P+G+N)

Overall Short
Overall Diameter DC Resistance Current-Carrying circuit
Conductor Diameter of Inner
Thickness Thickness at 20oC Capacity current
Nominal of Sheath Weight
of of Overall at 1 sec
Cross-sectional Insulation (Bedding of Impedance
Insulation Over Diameter
Area Layer) Cable
(Approx.) Sheath in
No. of Wire Outside Diameter Phase in air ground
Phase Ground Phase
(min.) (Approx.) at at
300C 200C
Phase Ground Phase Ground Phase Ground Phase Ground (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.) (Max.)

mm2 mm2 min. min. Mm mm mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (Ω/km) (A) (A) (kA)

4 4 7 7 2.5 2.5 0.7 0.7 4.1 13.1 1.8 19.5 820 5.879 4.61 4.61 40 36 0.57

6 6 7 7 3.5 3.5 0.7 0.7 4.9 14.6 1.8 21.0 967 3.928 3.08 3.08 52 44 0.86

10 10 7 7 4.0 4.0 0.7 0.7 5.5 17.0 1.8 24.0 1,405 2.335 1.83 1.83 71 58 1.43

16 16 6 6 5.0 5.0 0.7 0.7 6.4 19.0 1.8 26.0 1,743 1.469 1.15 1.15 96 75 2.29

25 25 6 6 6.0 6.0 0.9 0.9 7.9 23.3 1.9 30.5 2,393 0.930 0.727 0.727 119 96 3.58

35 25 6 6 7.0 6.0 0.9 0.9 8.9 26.0 2.1 34.4 3,154 0.672 0.524 0.727 147 115 5.01

50 25 6 6 8.5 6.0 1.0 0.9 10.5 30.2 2.2 39.0 3,902 0.499 0.387 0.727 179 135 7.15

70 35 12 6 10.0 7.0 1.1 0.9 12.2 35.3 2.4 45.5 5,498 0.349 0.268 0.524 229 167 10.01

95 50 15 6 11.5 8.5 1.1 1.0 13.8 40.1 2.6 51.0 6,96 0.256 0.193 0.387 278 197 13.59

120 70 18 12 13.0 10.0 1.2 1.1 15.5 44.6 2.7 55.5 8,379 0.208 0.153 0.268 322 223 17.16

150 95 18 15 14.5 11.5 1.4 1.1 17.4 50.2 2.9 61.5 10,131 0.173 0.124 0.193 371 251 21.45

185 95 30 15 16.0 11.5 1.6 1.1 19.3 55.3 3.1 67.0 11,951 0.146 0.0991 0.193 424 281 26.46

240 120 34 18 18.5 13.0 1.7 1.2 21.9 62.3 3.4 76.0 15,778 0.120 0.0754 0.153 500 324 34.32

- Cable outside diameter tolerance 20% upto 20mm, 15% upto 30mm, 10% above 35mm
- Minimum Bending Radius :
- Installed :
a. 12 x OD (For Multi Core)
b. 15 x OD (For Single Core)

TECHNICAL SPECIFICATION_LV POWER CABLE 11 of 35


B. Un-Armoured Cable

B.1. Cu/XLPE/PVC FR Cat.C (N2XY) - 0.6/1 (1.2) kV Single Core

Thickness Overall Current-Carrying


Conductor Of Diameter DC
Nominal Thickness of Weight Impedance Capacity Short
Insulation Before Over Overall Resistance
Cross- Over of circuit current
Sheath Diameter At
sectional Outside Sheath Cable at 1 sec
No. of Outside (Without Inner 20oC in air
Area Wire Diameter Diameter in ground
Sheath)
at 300C at 200C
(min) (Approx.) (nom.) (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.)
2
mm - mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

120 15 13.0 1.2 15.5 15.5 1.5 18.5 1,211 0.153 0.212 312 257 17.16

150 18 14.5 1.4 17.5 17.4 1.6 21.0 1,492 0.124 0.179 342 287 21.45

240 30 18.5 1.7 22.0 21.9 1.8 25.5 2,415 0.0754 0.126 450 375 34.32

300 34 20.5 1.8 24.5 24.2 1.8 28.0 2,986 0.0601 0.111 514 419 42.90

400 34 23.5 2.0 27.5 27.4 2.0 32.0 3,824 0.047 0.100 648 513 57.20

500 53 26.5 2.2 31.0 31.0 2.1 35.0 4,847 0.0366 0.092 747 570 71.50

630 53 30.5 2.4 35.5 35.2 2.2 39.0 6,196 0.0283 0.086 864 638 90.09

TECHNICAL SPECIFICATION_LV POWER CABLE 12 of 35


B.2. Cu/XLPE/PVC FR Cat.C (N2XY) - 0.6/1 (1.2) kV Two Core

Overall Current-Carrying
Conductor Insulation Diameter DC
Nominal Thickness Weight Impedance Capacity Short
Before Over Overall Resistance
Cross- of of circuit current
Sheath Diameter at
sectional Outside Over Sheath Cable at 1 sec
No. of Outside Thickness (Without Inner 20oC in air
Area Wire Diameter Diameter in ground
Sheath)
at 300C at 200C
(min) (Approx.) (nom.) (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.)
2
mm - mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

4 7 2.5 0.7 4.1 8.2 1.8 12.0 187 4.61 5.879 45 43 0.57

6 7 3.5 0.7 4.9 9.3 1.8 13.0 235 3.08 3.928 58 53 0.86

10 7 4.0 0.7 5.5 11.1 1.8 15.0 330 1.83 2.335 69 80 1.43

16 6 5.0 0.7 6.4 12.6 1.8 16.5 440 1.15 1.469 91 107 2.29

25 6 6.0 0.9 7.9 15.8 1.8 19.5 647 0.727 0.930 119 138 3.58

35 6 7.0 0.9 8.9 17.8 1.8 21.5 838 0.524 0.672 148 171 5.01

50 6 8.5 1.0 10.5 21.2 1.8 24.5 1,114 0.387 0.499 175 209 7.15

70 12 10.0 1.1 12.2 25.0 1.9 28.5 1,551 0.268 0.349 269 213 10.01

95 15 11.5 1.1 13.8 28.2 2.0 32.0 2,058 0.193 0.256 328 252 13.59

120 18 13.0 1.2 15.5 31.6 2.1 35.5 2,559 0.153 0.208 382 271 17.16

150 18 14.5 1.4 17.4 35.4 2.2 39.5 3,139 0.124 0.173 441 306 21.45

185 30 16.0 1.6 19.3 39.2 2.4 44.0 3,920 0.0991 0.146 506 343 26.46

240 34 18.5 1.7 21.9 44.4 2.5 49.0 5,054 0.0754 0.120 599 395 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 13 of 35


B.3. Cu/XLPE/PVC FR Cat.C (N2XY) - 0.6/1 (1.2) kV Two Core with One Ground (1P+N+G)

Overall Short
Overall Diameter DC Resistance Current-Carrying circuit
Conductor
Thickness Diameter Before Thickness at 20oC Capacity current
Nominal Weight at 1 sec
of of Over of Overall
Cross-sectional of Impedance
Insulation Insulation Sheath Over Diameter
Area Cable
(Approx.) (Without Sheath in
No. of Wire Outside Diameter Phase Inner in air ground
Sheath) Phase Ground Phase
(min.) (Approx.) at at
300C 200C
Phase Ground Phase Ground Phase Ground Phase Ground (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.) (Max.)

mm2 mm2 min. min. mm mm mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (Ω/km) (A) (A) (kA)

4 4 7 7 2.5 2.5 0.7 0.7 4.1 8.9 1.8 12.5 238 5.879 4.61 4.61 40 36 0.57

6 6 7 7 3.5 3.5 0.7 0.7 4.9 10.0 1.8 14.0 304 3.928 3.08 3.08 52 44 0.86

10 10 7 7 4.0 4.0 0.7 0.7 5.5 12.0 1.8 16.0 440 2.335 1.83 1.83 71 58 1.43

16 16 6 6 5.0 5.0 0.7 0.7 6.4 13.6 1.8 17.5 599 1.469 1.15 1.15 96 75 2.29

25 25 6 6 6.0 6.0 0.9 0.9 7.9 17.0 1.8 21.0 896 0.930 0.727 0.727 119 96 3.58

35 25 6 6 7.0 6.0 0.9 0.9 8.9 19.2 1.8 23.0 1,101 0.672 0.524 0.727 147 115 5.01

50 25 6 6 8.5 6.0 1.0 0.9 10.5 22.8 1.8 26.0 1,361 0.499 0.387 0.727 179 135 7.15

70 35 12 6 10.0 7.0 1.1 0.9 12.2 26.9 1.9 30.5 1,886 0.349 0.268 0.524 229 167 10.01

95 50 15 6 11.5 8.5 1.1 1.0 13.8 30.3 2.0 34.0 2,510 0.256 0.193 0.387 278 197 13.59

120 70 18 12 13.0 10.0 1.2 1.1 15.5 34.0 2.2 38.5 3,224 0.208 0.153 0.268 322 223 17.16

150 95 18 15 14.5 11.5 1.4 1.1 17.4 38.1 2.3 42.5 4,034 0.173 0.124 0.193 371 251 21.45

185 95 30 15 16.0 11.5 1.6 1.1 19.3 42.2 2.6 50.0 5,174 0.146 0.0991 0.193 424 281 26.46

240 120 34 18 18.5 13.0 1.7 1.2 21.9 47.8 2.7 53.0 6,208 0.120 0.0754 0.153 500 324 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 14 of 35


B.4. Cu/XLPE/PVC FR Cat.C (N2XY) - 0.6/1 (1.2) kV Three Core

Thickness
Overall Current-Carrying
Conductor of DC
Nominal Diameter Before Thickness Weight Capacity Short
Insulation Overall Resistance
Cross- Over Sheath of of Impedance circuit current
Diameter at
sectional Outside (Without Inner Over Sheath Cable in at 1 sec
No. of Outside 20oC in air
Area Diameter Sheath) ground
Wire Diameter
at 300C at 200C
(min) (Approx.) (nom.) (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.)
mm2 - mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

4 7 2.5 0.7 4.1 8.9 1.8 12.5 238 4.61 5.879 40 36 0.57

6 7 3.5 0.7 4.9 10.0 1.8 14.0 304 3.08 3.928 52 44 0.86

10 7 4.0 0.7 5.5 12.0 1.8 16.0 440 1.83 2.335 71 58 1.43

16 6 5.0 0.7 6.4 13.6 1.8 17.5 599 1.15 1.469 96 75 2.29

25 6 6.0 0.9 7.9 17.0 1.8 21.0 896 0.727 0.930 119 96 3.58

35 6 7.0 0.9 8.9 19.2 1.8 23.0 1,174 0.524 0.672 147 115 5.01

50 6 8.5 1.0 10.5 22.8 1.8 26.0 1,562 0.387 0.499 179 135 7.15

70 12 10.0 1.1 12.2 26.9 1.9 30.5 2,192 0.268 0.349 229 167 10.01

95 15 11.5 1.1 13.8 30.3 2.0 34.0 2,928 0.193 0.256 278 197 13.59

120 18 13.0 1.2 15.5 34.0 2.2 38.5 3,672 0.153 0.208 322 223 17.16

150 18 14.5 1.4 17.4 38.1 2.3 42.5 4,511 0.124 0.173 371 251 21.45

185 30 16.0 1.6 19.3 42.2 2.5 47.0 5,640 0.0991 0.146 424 281 26.46

240 34 18.5 1.7 21.9 47.8 2.7 53.0 7,323 0.0754 0.120 500 324 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 15 of 35


B.5. Cu/XLPE/PVC FR Cat.C (N2XY) - 0.6/1 (1.2) kV Three Core with One Ground (3P+1G)

Thickness Overall Short


of Overall Diameter DC Resistance Current-Carrying circuit
Conductor
Insulation Diameter Before Thickness at 20oC Capacity current
Nominal (Approx.) Weight at 1 sec
of Over of Overall
Cross-sectional of Impedance
Insulation Sheath Over Diameter
Area Cable
(Without Sheath in
No. of Wire Outside Diameter Phase Inner in air ground
Sheath) Phase Ground Phase
(min.) (Approx.) at at
300C 200C
Phase Ground Phase Ground Phase Ground Phase Ground (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.) (Max.)
2 2
mm mm min. min. mm mm mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (Ω/km) (A) (A) (kA)

2.5 2.5 7 7 2.0 2.0 0.7 0.7 3.5 8.7 1.8 12.5 224 9.449 7.41 7.41 30 28 0.36

4 4 7 7 2.5 2.5 0.7 0.7 4.1 10.0 1.8 13.5 295 5.879 4.61 4.61 40 36 0.57

6 6 7 7 3.5 3.5 0.7 0.7 4.9 11.3 1.8 15.0 383 3.928 3.08 3.08 52 44 0.86

10 10 6 6 4.0 4.0 0.7 0.7 5.5 13.5 1.8 17.0 561 2.335 1.83 1.83 71 58 1.43

16 16 6 6 5.0 5.0 0.7 0.7 6.4 15.2 1.8 19.0 771 1.469 1.15 1.15 96 75 2.29

25 25 6 6 6.0 6.0 0.9 0.9 7.9 19.2 1.8 23.0 1,164 0.930 0.727 0.727 119 96 3.58

35 25 6 6 7.0 6.0 0.9 0.9 8.9 21.5 1.8 25.0 1,463 0.672 0.524 0.727 147 115 5.01

50 25 6 6 8.5 6.0 1.0 0.9 10.5 25.5 1.9 29.0 1,863 0.499 0.387 0.727 179 135 7.15

70 35 12 6 10.0 7.0 1.1 0.9 12.2 30.1 2.0 34.0 2,596 0.349 0.268 0.524 229 167 10.01

95 50 15 6 11.5 8.5 1.1 1.0 13.8 34.0 2.2 38.0 3,484 0.256 0.193 0.387 278 197 13.59

120 70 18 12 13.0 10.0 1.2 1.1 15.5 38.0 2.3 42.5 4,420 0.208 0.153 0.268 322 223 17.16

150 95 18 15 14.5 11.5 1.4 1.1 17.4 42.6 2.5 47.5 5,535 0.173 0.124 0.193 371 251 21.45

185 95 30 15 16.0 11.5 1.6 1.1 19.3 47.2 2.6 52.0 6,667 0.146 0.0991 0.193 424 281 26.46

240 120 34 18 18.5 13.0 1.7 1.2 21.9 53.5 2.9 59.0 8,642 0.120 0.0754 0.153 500 324 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 16 of 35


B.6. Cu/XLPE/PVC FR Cat.C (N2XY) - 0.6/1 (1.2) kV Four Core (3P+N)

Overall Current-Carrying
Conductor Insulation Diameter DC
Nominal Thickness Weight Capacity Short
Before Over Overall Resistance
Cross- of of Impedance circuit current
Sheath Diameter at
sectional Outside Over Sheath Cable at 1 sec
No. of Outside Thickness (Without Inner 20oC in air
Area Wire Diameter Diameter in ground
Sheath)
at 300C at 200C
(min) (Approx.) (nom.) (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.)
mm2 - mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

4 7 2.5 0.7 4.1 10.0 1.8 13.5 295 4.61 5.879 40 36 0.57

6 7 3.5 0.7 4.9 11.3 1.8 15.0 383 3.08 3.928 52 44 0.86

10 7 4.0 0.7 5.5 13.5 1.8 17.0 561 1.83 2.335 71 58 1.43

16 6 5.0 0.7 6.4 15.2 1.8 19.0 771 1.15 1.469 96 75 2.29

25 6 6.0 0.9 7.9 19.1 1.8 23.0 1,164 0.727 0.930 119 96 3.58

35 6 7.0 0.9 8.9 21.5 1.8 25.0 1,534 0.524 0.672 147 115 5.01

50 6 8.5 1.0 10.5 25.5 1.9 29.0 2,064 0.387 0.499 179 135 7.15

70 12 10.0 1.1 12.2 30.1 2.0 34.0 2,902 0.268 0.349 229 167 10.01

95 15 11.5 1.1 13.8 34.0 2.2 38.0 3,902 0.193 0.256 278 197 13.59

120 18 13.0 1.2 15.5 38.0 2.3 42.5 4,868 0.153 0.208 322 223 17.16

150 18 14.5 1.4 17.4 42.6 2.5 47.5 6,011 0.124 0.173 371 251 21.45

185 30 16.0 1.6 19.3 47.2 2.6 52.0 7,487 0.0991 0.146 424 281 26.46

240 34 18.5 1.7 21.9 53.5 2.9 59.0 9,758 0.0754 0.120 500 324 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 17 of 35


B.7. Cu/XLPE/PVC FR Cat.C (N2XY) - 0.6/1 (1.2) kV Four Core with One Ground (3P+G+N)

Thickness Overall Thickness Short


Weight
of Overall Diameter of Overall DC Resistance Current-Carrying circuit
Conductor of Impedance
Insulation Diameter Before Over Diameter at 20oC Capacity current
Nominal Cable
(Approx.) of Over Sheath at 1 sec
Cross-sectional
Insulation Sheath
Area
(Without in
No. of Wire Outside Diameter Phase Inner in air ground
Sheath) Phase Ground Phase
(min.) (Approx.) at at
300C 200C
Phase Ground Phase Ground Phase Ground Phase Ground (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.) (Max.)

mm2 mm2 min. min. mm mm mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (Ω/km) (A) (A) (kA)

4 4 7 7 2.5 2.5 0.7 0.7 4.1 11.1 1.8 15.0 358 5.879 4.61 4.61 40 36 0.57

6 6 7 7 3.5 3.5 0.7 0.7 4.9 12.6 1.8 16.5 466 3.928 3.08 3.08 52 44 0.86

10 10 7 7 4.0 4.0 0.7 0.7 5.5 15.0 1.8 19.0 774 2.335 1.83 1.83 71 58 1.43

16 16 6 6 5.0 5.0 0.7 0.7 6.4 17.0 1.8 20.5 952 1.469 1.15 1.15 96 75 2.29

25 25 6 6 6.0 6.0 0.9 0.9 7.9 21.3 1.8 25.5 1,547 0.930 0.727 0.727 119 96 3.58

35 25 6 6 7.0 6.0 0.9 0.9 8.9 24.0 1.8 28.0 1,844 0.672 0.524 0.727 147 115 5.01

50 25 6 6 8.5 6.0 1.0 0.9 10.5 27.8 2.0 32.0 2,392 0.499 0.387 0.727 179 135 7.15

70 35 12 6 10.0 7.0 1.1 0.9 12.2 32.9 2.2 37.5 3,362 0.349 0.268 0.524 229 167 10.01

95 50 15 6 11.5 8.5 1.1 1.0 13.8 37.3 2.3 42.0 4,485 0.256 0.193 0.387 278 197 13.59

120 70 18 12 13.0 10.0 1.2 1.1 15.5 41.9 2.5 47.0 5,697 0.208 0.153 0.268 322 223 17.16

150 95 18 15 14.5 11.5 1.4 1.1 17.4 47.0 2.6 52.5 7,082 0.173 0.124 0.193 371 251 21.45

185 95 30 15 16.0 11.5 1.6 1.1 19.3 52.1 2.8 58.0 8,630 0.146 0.0991 0.193 424 281 26.46

240 120 34 18 18.5 13.0 1.7 1.2 21.9 59.1 3.1 65.5 11,192 0.120 0.0754 0.153 500 324 34.32

- Cable outside diameter tolerance 20% upto 20mm, 15% upto 30mm, 10% above 35mm
- Minimum Bending Radius :
- Installed :
a. 12 x OD (For Multi Core)
b. 15 x OD (For Single Core)

TECHNICAL SPECIFICATION_LV POWER CABLE 18 of 35


C. VSD Cable

C.1 Cu/XLPE/CTS/SWA/PVC FR Cat.C (N2XSRY) - 0.6/1 (1.2) kV Two Core

Overall Current-Carrying
Conductor Insulation Diameter of Overall Thickness DC
Nominal Weight Capacity Short
Inner Diameter of of Overall Resistance
Cross- of Impedance circuit current
Sheath Separation Over Diameter at
sectional Outside Cable in at 1 sec
No. of Outside Thickness (Bedding Sheath Sheath 20oC in air
Area Wire Diameter Diameter ground
Layer)
at 300C at 200C
(min) (Approx.) (nom.) (Approx.) (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.)
mm2 - mm mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

4 7 2.5 0.7 4.1 10.2 13.1 1.8 19.5 633 4.61 5.879 37 39 0.57

6 7 3.5 0.7 4.9 11.3 14.2 1.8 20.5 707 3.08 3.928 48 49 0.86

10 7 4.0 0.7 5.5 13.1 16.0 1.8 23.0 974 1.83 2.335 66 65 1.43

25 6 6.0 0.9 7.9 17.8 20.7 1.8 28.0 1,462 0.727 0.930 117 107 2.29

35 6 7.0 0.9 8.9 19.8 22.7 1.9 30.0 1,728 0.524 0.672 144 128 3.58

C.2 Cu/XLPE/CTS/SWA/PVC FR Cat.C (N2XSRY) - 0.6/1 (1.2) kV Three Core

Overall Current-Carrying
Conductor Insulation Diameter of Overall Thickness DC
Nominal Weight Capacity Short
Inner Diameter of of Overall Resistance
Cross- of Impedance circuit current
Sheath Separation Over Diameter at
sectional Outside Cable in at 1 sec
No. of Outside Thickness (Bedding Sheath Sheath 20oC in air
Area Wire Diameter Diameter ground
Layer)
at 300C at 200C
(min) (Approx.) (nom.) (Approx.) (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.)
2
mm - mm mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

2.5 7 2.0 0.7 3.5 9.8 12.6 1.8 19.0 618 7.41 9.449 30 28 0.36

4 7 2.5 0.7 4.1 11.0 13.7 1.8 20.0 698 4.61 5.879 40 36 0.57

6 7 3.5 0.7 4.9 12.0 14.9 1.8 21.5 799 3.08 3.928 52 44 0.86

10 7 4.0 0.7 5.5 14.0 16.9 1.8 24.0 1,121 1.83 2.335 71 58 1.43

TECHNICAL SPECIFICATION_LV POWER CABLE 19 of 35


C.2 Cu/XLPE/CTS/SWA/PVC FR Cat.C (N2XSRY) - 0.6/1 (1.2) kV Three Core (Cont.)

Overall Short
Current-Carrying
Conductor Insulation Diameter of Overall Thickness DC circuit current
Nominal Weight Capacity
Inner Diameter of of Overall Resistance at 1 sec
Cross- of Impedance
Sheath Separation Over Diameter at
sectional Outside Cable in
No. of Outside Thickness (Bedding Sheath Sheath 20oC in air
Area Wire Diameter Diameter ground
Layer)
at 300C at 200C
(min) (Approx.) (nom.) (Approx.) (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.)
2
mm - mm mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

16 6 5.0 0.7 6.4 15.6 18.4 1.8 25.5 1,337 1.15 1.469 96 75 2.29

25 6 6.0 0.9 7.9 19.0 21.9 1.9 29.0 1,764 0.727 0.930 119 96 3.58

35 6 7.0 0.9 8.9 21.2 24.0 2.0 31.5 2,136 0.524 0.672 147 115 5.01

50 6 8.5 1.0 10.5 24.8 27.7 2.1 36.0 2,876 0.387 0.499 179 135 7.15

70 12 10.0 1.1 12.2 29.3 32.1 2.3 40.5 3,740 0.268 0.349 229 167 10.01

95 15 11.5 1.1 13.8 32.7 35.8 2.4 45.5 5,002 0.193 0.256 278 197 13.59

120 18 13.0 1.2 15.5 36.4 39.5 2.5 49.5 5,921 0.153 0.208 322 223 17.16

150 18 14.5 1.4 17.4 40.9 44.2 2.7 54.5 7,105 0.124 0.173 371 251 21.45

185 30 16.0 1.6 19.3 45.0 48.4 2.9 59.0 8,482 0.0991 0.146 424 281 26.46

240 34 18.5 1.7 21.9 51.0 54.6 3.1 66.0 10,556 0.0754 0.120 500 324 34.32

C.3 Cu/XLPE/CTS/SWA/PVC FR Cat.C (N2XSRY) - 0.6/1 (1.2) kV Three Core with One Ground (3P+G)

Short
Overall circuit
Overall DC Resistance Current-Carrying
Conductor Overall Diameter current
Thickness Diameter Thickness at 20oC Capacity
Diameter of Inner at 1
Nominal of Weight Impedance
of of Sheath of Overall sec
Cross-sectional Separation of
Insulation Insulation (Bedding Over Diameter
Area Sheath Cable
(Approx.) Layer) Sheath
No. of Wire Outside Diameter in
Phase Ground Phase
(min.) (Approx.) Phase in air ground
at 300C at 200C
Phase Ground Phase Ground Phase Ground Phase Ground (Approx.) (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.) (Max.)
2 2
mm mm min. min. mm mm mm mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (Ω/km) (A) (A) (kA)

4 4 7 7 2.5 2.5 0.7 0.7 4.1 12.0 14.8 1.8 21.5 927 5.879 4.61 4.61 40 36 0.57

TECHNICAL SPECIFICATION_LV POWER CABLE 20 of 35


C.3 Cu/XLPE/CTS/SWA/PVC FR Cat.C (N2XSRY) - 0.6/1 (1.2) kV Three Core with One Ground (3P+G). (Cont.)

Short
Overall circuit
Overall DC Resistance Current-Carrying
Conductor Overall Diameter current
Diameter at 20oC Capacity
Thickness Diameter of Inner Thickness at 1
Nominal of Weight Impedance
of of Sheath of Overall sec
Cross-sectional Separation of
Insulation Insulation (Bedding Over Diameter
Area Sheath Cable
(Approx.) Layer) Sheath
No. of Wire Outside Diameter in
Phase Ground Phase
(min.) (Approx.) Phase in air ground
at 300C at 200C
Phase Ground Phase Ground Phase Ground Phase Ground (Approx.) (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.) (Max.)
2 2
mm mm min. min. mm mm mm mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (Ω/km) (A) (A) (kA)

6 6 7 7 3.5 3.5 0.7 0.7 4.9 13.2 16.1 1.8 23.5 1,195 3.928 3.08 3.08 52 44 0.86

10 10 7 7 4.0 4.0 0.7 0.7 5.5 15.5 18.3 1.8 25.5 1,491 2.335 1.83 1.83 71 58 1.43

16 16 6 6 5.0 5.0 0.7 0.7 6.4 17.2 20.1 1.8 27.5 1,806 1.468 1.15 1.15 96 75 2.29

25 16 6 6 6.0 5.0 0.9 0.7 7.9 21.1 24.0 2.0 31.5 2,360 0.930 0.727 0.727 119 96 3.58

240 120 34 18 18.5 13.0 1.7 1.2 21.9 56.7 60.5 3.2 71.5 11,289 0.120 0.0754 0.153 500 324 34.32

C.4 Cu/XLPE/CTS/SWA/PVC FR Cat.C (N2XSRY) - 0.6/1 (1.2) kV Three Core with Three Ground (3P+3G)

Overall Short
Overall DC Resistance Current-Carrying circuit
Conductor Overall Diameter
Thickness Diameter Thickness at 20oC Capacity current
Diameter of Inner
Nominal of Weight Impedance at 1 sec
of of Sheath of Overall
Cross-sectional Separation of
Insulation Insulation (Bedding Over Diameter
Area Sheath Cable
(Approx.) Layer) Sheath
No. of Wire Outside Diameter in
Phase Ground Phase
(min.) (Approx.) Phase in air ground
at 300C at 200C
Phase Ground Phase Ground Phase Ground Phase Ground (Approx.) (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.) (Max.)
2 2
mm mm min. min. mm mm mm mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (Ω/km) (A) (A) (kA)

240 50 34 6 18.5 8.5 1.7 1.0 21.9 50.7 54.5 3.0 65.0 11,340 0.120 0.0754 0.387 500 324 34.32

TECHNICAL SPECIFICATION_LV POWER CABLE 21 of 35


C.5 Cu/XLPE/CWS/CTS/SWA/PVC FR Cat.C (N2XCRY) - 0.6/1 (1.2) kV Three Core

Overall Current-Carrying
Conductor Insulation Diameter of Overall Thickness DC Short
Nominal Weight Capacity
Inner Diameter of of Overall Resistance circuit
Cross- of Impedance
Sheath Separation Over Diameter at current
sectional Outside Cable in
No. of Outside Thickness (Bedding Sheath Sheath 20oC in air at 1 sec
Area Wire Diameter Diameter ground
Layer)
at 300C at 200C
(min) (Approx.) (nom.) (Approx.) (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.)
2
mm - mm mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

4 7 2.5 0.7 4.1 11.0 14.8 1.8 21.5 888 4.61 5.879 40 36 0.57

6 7 3.5 0.7 4.9 12.0 16.0 1.8 23.5 1,150 3.08 3.928 52 44 0.86

10 7 4.0 0.7 5.5 14.0 17.9 1.8 25.5 1,427 1.83 2.335 71 58 1.43

16 6 5.0 0.7 6.4 16.0 20.0 1.8 27.5 1,745 1.15 1.468 96 75 2.29

25 6 6.0 0.9 7.9 19.0 23.4 1.9 31.0 2,245 0.727 0.930 119 96 3.58

240 34 18.5 1.7 21.9 50.1 57.3 3.1 68.0 10,925 0.0754 0.120 500 324 34.32

C.6 Cu/XLPE/CWS/CTS/SWA/PVC FR Cat.C (N2XCRY) - 0.6/1 (1.2) kV Four Core (3P+N)

Overall Current-Carrying
Conductor Insulation Diameter of Overall Thickness DC Short
Nominal Weight Capacity
Inner Diameter of of Overall Resistance circuit
Cross- of Impedance
Sheath Separation Over Diameter at current
sectional Outside Cable in
No. of Outside Thickness (Bedding Sheath Sheath 20oC in air at 1 sec
Area Wire Diameter Diameter ground
Layer)
at 300C at 200C
(min) (Approx.) (nom.) (Approx.) (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.)
2
mm - mm mm mm Mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

6 7 3.5 0.7 4.9 13.3 17.5 1.8 24.5 1,270 3.08 3.928 52 44 0.86

- Cable outside diameter tolerance 20% upto 20mm, 15% upto 30mm, 10% above 35mm
- Minimum Bending Radius :
- Installed :
a. 12 x OD (For Multi Core)
b. 15 x OD (For Single Core)

TECHNICAL SPECIFICATION_LV POWER CABLE 22 of 35


D. EBV Cable (Fire Resistance Cable)

D.1 Cu/MICA/XLPE/SWA/PVC-FR (N2XRY-FRC) - 0.6/1(1.2) kV Two Core

Overall Current-Carrying
Conductor Insulation Thickness DC Short
Nominal Diameter of Weight Capacity
of Overall Resistance circuit
Cross- Inner Sheath of Impedance
Over Diameter at current
sectional Outside (Bedding Cable in
No. of Outside
Thickness Sheath 20oC in air at 1 sec
Area Layer) ground
Wire Diameter Diameter
at 300C at 200C
(min) (Approx.) (nom.) (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.)
mm2 - mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

4 7 2.5 0.7 5.0 12.0 1.8 19.0 655 4.61 5.879 45 43 0.57

6 7 3.0 0.7 5.5 13.1 1.8 20.0 752 3.08 3.928 58 53 0.86

10 7 4.0 0.7 6.5 14.9 1.8 22.0 924 1.83 2.335 69 80 1.43

25 6 6.0 0.9 8.8 19.6 1.8 27.5 1,619 0.727 0.930 119 138 3.58

35 6 7.0 0.9 9.8 21.6 1.8 30.0 1,933 0.524 0.672 148 171 5.01

D.2 Cu/MICA/XLPE/SWA/PVC-FR (N2XRY-FRC) - 0.6/1(1.2) kV Three Core

Overall Current-Carrying
Conductor Insulation Thickness DC Short
Nominal Diameter of Weight Capacity
of Overall Resistance circuit
Cross- Inner Sheath of Impedance
Over Diameter at current
sectional Outside (Bedding Cable in
No. of Outside
Thickness Sheath 20oC in air at 1 sec
Area Layer) ground
Wire Diameter Diameter
at 300C at 200C
(min) (Approx.) (nom.) (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.)
mm2 - mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

2.5 7 2.0 0.7 4.5 11.6 1.8 19.0 645 7.41 9.449 30 28 0.36

4 7 2.5 0.7 5.0 12.8 1.8 20.0 748 4.61 5.879 40 36 0.57

6 7 3.0 0.7 5.5 13.9 1.8 21.5 853 3.08 3.928 52 44 0.86

TECHNICAL SPECIFICATION_LV POWER CABLE 22 of 35


D.2 Cu/MICA/XLPE/SWA/PVC-FR (N2XRY-FRC) - 0.6/1(1.2) kV Three Core (Cont.)

Overall Current-Carrying
Conductor Insulation Thickness DC Short
Nominal Diameter of Weight Capacity
of Overall Resistance circuit
Cross- Inner Sheath of Impedance
Over Diameter at current
sectional Outside (Bedding Cable in
No. of Outside
Thickness Sheath 20oC in air at 1 sec
Area Layer) ground
Wire Diameter Diameter
at 300C at 200C
(min) (Approx.) (nom.) (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.)
2
mm - mm mm mm mm mm mm kg/km (Ω/km) (Ω/km) (A) (A) (kA)

10 7 4.0 0.7 6.5 15.9 1.8 22.5 995 1.83 2.335 71 58 1.43

16 6 5.0 0.7 7.2 17.5 1.8 24.0 1,330 1.15 1.469 96 75 2.29

25 6 6.0 0.9 8.8 20.9 1.8 27.5 1,769 0.727 0.930 119 96 3.58

35 6 7.0 0.9 9.8 23.0 1.8 30.0 2,171 0.524 0.672 147 115 5.01

50 6 8.5 1.0 11.2 26.7 2.1 35.5 3,064 0.387 0.500 179 135 7.15

70 12 10.0 1.1 13.1 31.2 2.2 40.0 3,976 0.268 0.350 229 167 10.01

TECHNICAL SPECIFICATION_LV POWER CABLE 23 of 35


D.3 Cu/MICA/XLPE/SWA/PVC-FR (N2XRY-FRC) 0.6/1(1.2) kV Two Core with One Ground (1P+N+G)

Short
Overall DC Resistance Current-Carrying circuit
Conductor Overall
Thickness Diameter Thickness at 20oC Capacity current
Nominal Diameter of Weight
of of Inner of Overall at 1 sec
Cross-sectional Insulation of Impedance
Insulation Sheath Over Diameter
Area Cable in
(Approx.) (Bedding Sheath
No. of Wire Outside Diameter Phase in air ground
Layer) Phase Ground Phase
(min.) (Approx.) at at
300C 200C
Phase Ground Phase Ground Phase Ground Phase Ground (Approx.) (Approx.) (nom.) (Approx.) (Approx.) (Max.) (Max.) (Max.) (Max.) (Max.) (Max.)

mm2 mm2 min. min. mm mm mm mm mm Mm mm mm kg/km (Ω/km) (Ω/km) (Ω/km) (A) (A) (kA)

4 4 7 7 2.5 2.5 0.7 0.7 5.0 12.8 1.8 20.0 747 5.879 4.61 4.61 40 36 0.57

6 6 7 7 3.5 3.5 0.7 0.7 5.5 13.9 1.8 21.5 852 3.928 3.08 3.08 52 44 0.86

35 25 6 6 7.0 6.0 0.9 0.9 9.8 23.1 1.9 32.0 2,244 0.672 0.524 0.727 147 115 5.01

- Cable outside diameter tolerance 20% upto 20mm, 15% upto 30mm, 10% above 35mm
- Minimum Bending Radius :
- Installed :
a. 12 x OD (For Multi Core)
b. 15 x OD (For Single Core)

TECHNICAL SPECIFICATION_LV POWER CABLE 24 of 35


Attached table 2. : DRAWING for SUBMITTAL

VOLTAGE 0.6/1 (1.2)kV NO. OF CORE 1 CONDUCTOR SIZE 95 – 630 sqmm

Cable type : Cu/XLPE/AWA/PVC FR Cat.C (N2XR(AL)Y)

4
5

ITEM DESCRIPTION DETAILS

1 Conductor Annealed copper stranded conductor

2 Insulation Extruded XLPE compound

3 Inner Sheath Extruded Black PVC compound

4 Armour Aluminium round wire

*5 Binder Non metallic tape

6 Over Sheath Extruded Black PVC FR Cat. C compound

REMARK : - Suitable non metallic tape may be applied on armour as a binder

TECHNICAL SPECIFICATION_LV POWER CABLE 25 of 35


VOLTAGE 0.6/1 (1.2)kV NO. OF CORE 2-4 CONDUCTOR SIZE 4 – 240 sqmm

Cable type : Cu/XLPE/SWA/PVC FR Cat.C (N2XRY)

2
3
4
5
6

ITEM DESCRIPTION DETAILS

1 Conductor Annealed copper stranded conductor

2 Insulation Extruded XLPE compound

*3 Filler Non Hygroscopic Filler

*4 Binder Non Hygroscopic Tape

5 Inner Sheath Extruded Black PVC compound

6 Armour Galvanized steel round wire

*7 Binder Non metallic tape

8 Over Sheath Extruded Black PVC FR Cat. C compound

REMARK : * - Suitable non hygroscopic filler and tape may be applied on laying up cores

- Suitable non metallic tape may be applied on armour as a binder

TECHNICAL SPECIFICATION_LV POWER CABLE 26 of 35


2P+1G CONDUCTOR
VOLTAGE 0.6/1 (1.2)kV NO. OF CORE 3P+1G 4 – 240 sqmm
SIZE
4P+1G
Cable type : Cu/XLPE/SWA/PVC FR Cat.C (N2XRY)

1
2
3
4
5
6
7
8

ITEM DESCRIPTION DETAILS

1 Phase Conductor Annealed copper stranded conductor

2 Earth Conductor Annealed copper stranded conductor

3 Insulation Extruded XLPE compound

*4 Filler Non Hygroscopic Filler

*5 Binder Non Hygroscopic Tape

6 Inner Sheath Extruded Black PVC compound

7 Armour Galvanized steel round wire

*8 Binder Non metallic tape

9 Over Sheath Extruded Black PVC FR Cat. C compound

REMARK : * - Suitable non hygroscopic filler and tape may be applied on laying up cores

- Suitable non metallic tape may be applied on armour as a binder

TECHNICAL SPECIFICATION_LV POWER CABLE 27 of 35


VOLTAGE 0.6/1 (1.2)kV NO. OF CORE 1 CONDUCTOR SIZE 120 – 630 sqmm

Cable type : Cu/XLPE/PVC FR Cat.C (N2XY)

ITEM DESCRIPTION DETAILS

1 Conductor Annealed copper stranded conductor

2 Insulation Extruded XLPE compound

3 Over Sheath Extruded Black PVC FR Cat. C compound

REMARK : * - Suitable non hygroscopic filler and tape may be applied on laying up cores

TECHNICAL SPECIFICATION_LV POWER CABLE 28 of 35


VOLTAGE 0.6/1 (1.2)kV NO. OF CORE 2-4 CONDUCTOR SIZE 4 – 240 sqmm

Cable type : Cu/XLPE/PVC FR Cat.C (N2XY)

2
3
4

ITEM DESCRIPTION DETAILS

1 Conductor Annealed copper stranded conductor

2 Insulation Extruded XLPE compound

*3 Filler Non Hygroscopic Filler

*4 Binder Non Hygroscopic Tape

5 Over Sheath Extruded Black PVC FR Cat. C compound

REMARK : * - Suitable non hygroscopic filler and tape may be applied on laying up cores

TECHNICAL SPECIFICATION_LV POWER CABLE 29 of 35


2P+1G CONDUCTOR
VOLTAGE 0.6/1 (1.2)kV NO. OF CORE 3P+1G 4 – 240 sqmm
SIZE
4P+1G
Cable type : Cu/XLPE/PVC FR Cat.C (N2XY)

2
3
4
5

ITEM DESCRIPTION DETAILS

1 Phase Conductor Annealed copper stranded conductor

2 Earth Conductor Annealed copper stranded conductor

3 Insulation Extruded XLPE compound

*4 Filler Non-Hygroscopic Filler

*5 Binder Non-Hygroscopic Tape

6 Over Sheath Extruded Black PVC FR Cat. C compound

REMARK : * - Suitable non hygroscopic filler and tape may be applied on laying up cores

TECHNICAL SPECIFICATION_LV POWER CABLE 30 of 35


CONDUCTOR
VOLTAGE 0.6/1 (1.2)kV NO. OF CORE 2-3 2.5 – 240 sqmm
SIZE
Cable type : Cu/XLPE/CTS/SWA/PVC FR Cat.C (N2XSRY)

1
2

3
4
5
6
7
8
9

10

ITEM DESCRIPTION DETAILS

1 Conductor Annealed copper stranded conductor

2 Insulation Extruded XLPE compound

*3 Filler Non Hygroscopic Filler

*4 Binder Non Hygroscopic Tape

5 Inner Sheath Extruded Black PVC compound

6 Screen Copper Tape

7 Separation Sheath Extruded Black PVC compound

8 Armour Galvanized steel round wire

*9 Binder Non metallic tape

10 Over Sheath Extruded Black PVC FR Cat. C compound

REMARK : * - Suitable non hygroscopic filler and tape may be applied on laying up cores

- Suitable non metallic tape may be applied on armour as a binder

TECHNICAL SPECIFICATION_LV POWER CABLE 31 of 35


CONDUCTOR
VOLTAGE 0.6/1 (1.2)kV NO. OF CORE 3P+G 4 – 240 sqmm
SIZE
Cable type : Cu/XLPE/CTS/SWA/PVC FR Cat.C (N2XSRY)

1
2
3

4
5
6
7
8
9
10

11

ITEM DESCRIPTION DETAILS

1 Phase Conductor Annealed copper stranded conductor

2 Earth Conductor Annealed copper stranded conductor

3 Insulation Extruded XLPE compound

*4 Filler Non Hygroscopic Filler

*5 Binder Non Hygroscopic Tape

6 Inner Sheath Extruded Black PVC compound

7 Screen Copper Tape

8 Separation Sheath Extruded Black PVC compound

9 Armour Galvanized steel round wire

*10 Binder Non metallic tape

11 Over Sheath Extruded Black PVC FR Cat. C compound

REMARK : * - Suitable non hygroscopic filler and tape may be applied on laying up cores
- Suitable non metallic tape may be applied on armour as a binder

TECHNICAL SPECIFICATION_LV POWER CABLE 32 of 35


3x240 + 3x50
VOLTAGE 0.6/1 (1.2)kV NO. OF CORE 3P+3G CONDUCTOR SIZE
sqmm
Cable type : Cu/XLPE/CTS/SWA/PVC FR Cat.C (N2XSRY)

2
3
4
5
6
7
8
9
10

11

ITEM DESCRIPTION DETAILS

1 Phase Conductor Annealed copper stranded conductor

2 Earth Conductor Annealed copper stranded conductor

3 Insulation Extruded XLPE compound

*4 Filler Non Hygroscopic Filler

*5 Binder Non Hygroscopic Tape

6 Inner Sheath Extruded Black PVC compound

7 Screen Copper Tape

8 Separation Sheath Extruded Black PVC compound

9 Armour Galvanized steel round wire

*10 Binder Non metallic tape

11 Over Sheath Extruded Black PVC FR Cat. C compound

REMARK : * - Suitable non hygroscopic filler and tape may be applied on laying up cores
- Suitable non metallic tape may be applied on armour as a binder

TECHNICAL SPECIFICATION_LV POWER CABLE 33 of 35


VOLTAGE 0.6/1 (1.2)kV NO. OF CORE 3 CONDUCTOR SIZE 4 – 240 sqmm

Cable type : Cu/XLPE/CWS/CTS/SWA/PVC FR Cat.C (N2XCRY)

2
3
4
5
6
7
8
9
10
11

12

ITEM DESCRIPTION DETAILS

1 Conductor Annealed copper stranded conductor

2 Insulation Extruded XLPE compound

*3 Filler Non Hygroscopic Filler

*4 Binder Non Hygroscopic Tape

5 Inner Sheath Extruded Black PVC compound

6&7 Screen Copper Round Wire + Copper Tape

*8 Binder Non Metallic Tape

9 Separation Sheath Extruded Black PVC compound

10 Armour Galvanized steel round wire

*11 Binder Non metallic tape

12 Over Sheath Extruded Black PVC FR Cat. C compound

REMARK : * - Suitable non hygroscopic filler and tape may be applied on laying up cores
- Suitable non metallic tape may be applied on screen or armour as a binder

TECHNICAL SPECIFICATION_LV POWER CABLE 34 of 35


NO. OF 2 - 3 Cores, CONDUCTOR
VOLTAGE 0.6/1(1.2)kV 2.5 – 70 sqmm
CORE 2P+1G SIZE

Cable type : Cu/MICA/XLPE/SWA/PVC-FR (N2XRY-FRC)

ITEM DESCRIPTION DETAILS

1 Conductor Annealed copper stranded conductor

2 Conductor Wrapping Mica Tape

3 Insulation Extruded XLPE compound

4 Inner Sheath Extruded Black PVC compound

5 Armour Galvanized steel round wire

*6 Binder Non metallic tape

7 Over Sheath Extruded Orange PVC FR Cat. C compound

REMARK : * - Suitable non metallic tape may be applied on armour as a binder