ضبط أنفرتر 1213

This document provides instructions for configuring the parameters of a drive motor. It lists 5 steps: 1) Put the drive in commissioning mode and configure motor parameters like voltage, current, power, etc. 2) End commissioning mode. 3) Set access level, supply voltage, overload reaction, and other parameters. 4) Configure multi-operator panel, reference values, ramp times, and digital and analog inputs/outputs. 5) Acknowledge any faults. It provides the parameter number, value, and description for many of the key settings.

Uploaded by

Anas Hafez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
44 views2 pages

ضبط أنفرتر 1213

This document provides instructions for configuring the parameters of a drive motor. It lists 5 steps: 1) Put the drive in commissioning mode and configure motor parameters like voltage, current, power, etc. 2) End commissioning mode. 3) Set access level, supply voltage, overload reaction, and other parameters. 4) Configure multi-operator panel, reference values, ramp times, and digital and analog inputs/outputs. 5) Acknowledge any faults. It provides the parameter number, value, and description for many of the key settings.

Uploaded by

Anas Hafez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Road 286, No.

14 Algeria Square
NEW MAADI – CAIRO - EGYPT
Phone: +20-2-25167821
FAX: +20-2-27538150
Email: [email protected]
Web Site: www.intelsoft-eg.com

PROCESS AUTOMATION - OFFICE AUTOMATION - LOCAL AREA NETWORKS – COMPUTER GRAPHICS

For configuring the drive follow the following steps.

1‐ To configure the motor parameters you must put the drive in commissioning mode:

P0010 = 1

2‐ Change the motor parameters:‐

P0304 = 400 V (Motor Voltage)

P0305 = 25 A (Motor Current)

P0307 = 22 KW (Motor Power)

P0308 = 0.78 (Motor P.F)

P0310 = 50 HZ (Motor Frequency)

P0311= 3000 r.p.m (Motor Speed)

3‐ End of Quick commissioning mode

P3900=1

4‐ Set the parameter as the following

Para. Value discription


P0003 3 Access Level
P0004 0 Parameters range
P0210 400 Inverter supply Voltage
P0290 3 OverLoad Reaction
P0640 150 Over current Ratio
P0700.0 2 Control (DI)
P0700.1 6 Control (Profibus)
P0701.0 1 ON/OFF1
P0701.1 0
P0704.0 99 BICO
P0704.1 0
P0705.0 99 BICO
P0705.1 0
P0706.0 99 BICO
P0706.1 99 BICO
P0731.0 52.2 Running
P0731.1 52.2 Running
P0732.0 52.3 Fault
P0732.1 52.3 Fault
P0810 722.5 Local(0) / remote(1)
P0840 722.0 ON/OFF1
P0844 1 OFF2
P0845 1 OFF2
P0848 1 OFF3
P0849 1 OFF3
P0852 1 Pulse enable
P0918 63 Profibus address
P0927 00000000 Lock Change Parameter
P0927 00001111 Change Parameters available
P1000.0 1 MOP
P1000.1 6 Profibus
P1031 0 MOP SP will not be stored
P1032 1 Innhibit negative SP.
P1035 722.3 MOP Up
P1036 722.4 MOP Down
P1040 20 Starting SP for MOP
P1080 0 Min. frequency
P1082 50 Max. frequency
P1120 5 Ramp Up time
P1121 5 Ramp down time
P2000 50 Reference frequency
P2001 400 Reference Voltage
P2002 25 Reference Current
P2040 0 CB monitoring time
P2041.0 3 PZD to CB
P2041.1 0 PZD to CB
P2041.2 1 PZD to CB
P2041.3 0 PZD to CB
P2051.0 r52 CB to PZD
P2051.1 r21 CB to PZD
P2051.2 r27 CB to PZD
P2051.3 r53 CB to PZD

5‐ To acknowledge any fault

P2103 = 1