For configuring the drive follow the following steps.
1‐ To configure the motor parameters you must put the drive in commissioning mode:
P0010 = 1
2‐ Change the motor parameters:‐
P0304 = 400 V (Motor Voltage)
P0305 = 25 A (Motor Current)
P0307 = 22 KW (Motor Power)
P0308 = 0.78 (Motor P.F)
P0310 = 50 HZ (Motor Frequency)
P0311= 3000 r.p.m (Motor Speed)
3‐ End of Quick commissioning mode
P3900=1
4‐ Set the parameter as the following
Para. Value discription
P0003 3 Access Level
P0004 0 Parameters range
P0210 400 Inverter supply Voltage
P0290 3 OverLoad Reaction
P0640 150 Over current Ratio
P0700.0 2 Control (DI)
P0700.1 6 Control (Profibus)
P0701.0 1 ON/OFF1
P0701.1 0
P0704.0 99 BICO
P0704.1 0
P0705.0 99 BICO
P0705.1 0
P0706.0 99 BICO
P0706.1 99 BICO
P0731.0 52.2 Running
P0731.1 52.2 Running
P0732.0 52.3 Fault
P0732.1 52.3 Fault
P0810 722.5 Local(0) / remote(1)
P0840 722.0 ON/OFF1
P0844 1 OFF2
P0845 1 OFF2
P0848 1 OFF3
P0849 1 OFF3
P0852 1 Pulse enable
P0918 63 Profibus address
P0927 00000000 Lock Change Parameter
P0927 00001111 Change Parameters available
P1000.0 1 MOP
P1000.1 6 Profibus
P1031 0 MOP SP will not be stored
P1032 1 Innhibit negative SP.
P1035 722.3 MOP Up
P1036 722.4 MOP Down
P1040 20 Starting SP for MOP
P1080 0 Min. frequency
P1082 50 Max. frequency
P1120 5 Ramp Up time
P1121 5 Ramp down time
P2000 50 Reference frequency
P2001 400 Reference Voltage
P2002 25 Reference Current
P2040 0 CB monitoring time
P2041.0 3 PZD to CB
P2041.1 0 PZD to CB
P2041.2 1 PZD to CB
P2041.3 0 PZD to CB
P2051.0 r52 CB to PZD
P2051.1 r21 CB to PZD
P2051.2 r27 CB to PZD
P2051.3 r53 CB to PZD
5‐ To acknowledge any fault
P2103 = 1