0 ratings0% found this document useful (0 votes) 124 views57 pagesHB - 7ut75 76 - C73000 G1176 C43 1 - en
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
SIEMENS
7UT75/7UT76
Static Two-Stage Differential Protection
| Le.
€73000-G1176-C43-1SIEMENS
Static Two-Stage Differential Protection
TUT7S5 for two-winding transformers and motors
7UT76 for three-winding transformers
Instruction Manual Order No: C73000-G1176~C43~1-2-
Contents
- Page
fs THustration 1
2. Application 4
2d Features 6
3 Composition of apparatus 7
3a Dimensions 7
3.2 Arrangement of device functions/modules 7
3.3 Ordering data 9
a Techwical data 10
Mode of operation 12 r
Function of complete unit 12
Taput /output portion M4
Input transformers with input interfaces 14
Power supply 4
Output stages 15
Current input circuits 5
Measurement module 16
Complete circuit 16
6. ‘Installation instructions 23
6. Unpacking, 23
6.2 Readiness for use 23
6.3 Preparation for use 23
6.3.1 Checking the external connections (Check list) 2
1 Operating instructions 28
aL Safety precautions 28
22 Arrangement and setting of the setting elements 28
7.2.1 Setting principles 28
7.2.2 Installation and selection of matching transformers 29
7.2.3 Getting the pick-up current 36
73 Preparation for testing 38
14 Test procedure 39
7.4.1 General 39
7.4.2 Checking the output contacts 39
7.4.3 Checking the operating values 40
7.4.4 Checking of all settings ad
7.4.5 Checking the response voltages 41
7.4.6 Checking the inrush stabilization 42
7.4.7 Checking the characteristic for 7UT75 43
7.4.8 Checking the characteristic for 7UT76 4
7.4.9 Checking the operating time 45
75 Making ready for service 47Abbi
deo
et
vt
Mechanical parts
Maintenance
Fault tracing
systematic fault tracing
Repairs
Storage
Circuit diagrams
alternating current
direct current
current transformer
voltage transformer
= Current
= Rated current (normally relay rated current)
= Tripping effect current (operating current)
= Stabilizing effect current (stabilizing current)
= Turns ratio
= Voltage
51
51
522 Application
The two-stage differential relay is a highly sensitive current comparison pro-
tection relay which will detect short-circuits within a zone determined by two
or three sets of current transformers. Principally, 7UT75 is used for the pro-
tection of motors and two-winding transformers and 7UT76 for the protection of
three-winding transformers.
The relay will detect 1, 2 or 3-phase and double earth faults, including those
for which one earth point lies outside the protected zone.
If two-stage relay 7UT75 is used for the protection of 3-phase motors, not
only the usual features - fast response for internal faults, stability against
external faults - but also inrush currents which must not cause faulty opera-
tion, must be considered. Their influence on the differential circuite is
quite different for a motor than for a transformer.
When energizing a power transformer, the inrush current always flows only
through the cts on the energizing side of the transformer. The ct secondary
currents flow at their full value through the out-of-balance path of the dif-
ferential system, whilst the cts on the non-energizing side of the transfor-
mer contribute absolutely no balancing current. In contrast, with 3+phase
motors, both the line side and star-point cts are loaded simultaneously with
the motor breakaway current. When using cts with identical characteristics
on both sides of the motor no out-of-balance current is supposed to occur
under these conditions.
Not:
This booklet describes static transformer differential protection relays
7UT75 and 7UT76 of factory production series 7UT7##**-#kK/CD and .../CC.Such good conformity of cts and their burdens is rarely possible in practice.
Matching of the real component of secondary current can be achieved with
a realistic investment but not so the inductive component. Thus, unequal
time constants for demagnetizing of the ct cores result during inrush tran-
sients with dc components. Because the cts then operate at different points
on their magnetizing characteristics for a transient period, differences
in transformation occur, which lead to differential currents in the tripping
relay path, detectable by this sensitive relay. These currents usually occur
immediately after the inrush transient.
Thus, currents which flow through the tripping path of a differential relay
during inrush have different causes and are of different types and values
for motors and transformers. When energizing a transformer, the inrush is
seen only by the cts of the energizing side and is characterized by very
strong 2nd harmonic content. This characteristic is identified by the relay
and is used to prevent erroneous operation.
In contrast, when energizing a motor, any ct differential current caused by
the transient behaviour of the cts themselves resp. their burden flows through
the tripping circuit of the relay. Although very significantly less than those
for a transformer, they often lie above the pick-up value and have no iden-
tifying 2nd harmonic.
Differential relay 7UT7* has, therefore, two stages (figures 4 and 8).
- a highly sensitive fine stage which operates only after a specific time
delay
- a coarse stage which operates only for large differential currents, but
then instantaneously. Dependant upon the value of the inrush differential
current, this stage can be set at a value 3 to 5 times that of the sensitive
(fine) stage.
This two stage design guarantees fast response to winding faults with high
fault currents plus sensitive response to faults with low level currents
which, practice shows, can be tolerated for a longer time.Since large motors are often 'block connected’ with a transformer, so that
energizing currents with second harmonic content also appear, the motor dif-
ferential protection relay also incorporates 2nd harmonic stabilization as
the transformer differential relays (e.g. 7UT72/73). Thus, relay 7UT75 is
suitable for applications with the most difficult switching characteristics
for motors, transformers and motor-transformer combinations.
Particularly in power station auxiliary circuits, the use of the two-stage
differential relay for the protection of transformers can be advantageous
since in such applications high de content transients during transfer swit-
ching operations can cause temporary saturation of the ct cores. Under these
conditions the two-stage operation of 7UT75 prevents false tripping. Relay
7UT76 is particularly suitable for the protection of inrush-critical three-
winding transformers with very long transient decay times and with low 2nd
harmonic content.
2a Features
- 3 independant measuring circuits with one common limit-value evaluation
circuit
- tripping characteristic independant of type of fault
- two-stage measured value processing
- fast response coarse stage
- time delayed high sensitivity stage
= current stabilization against through-fault operation
= filter stabilization against heavy magnetizing inrush currents.Differential protection relays 7UI7* are assembled in self-contained cases
type 7XP7720-2, available for either surface or flush mounting. Fixing dimen-
sions correspond to those of the earlier, conventional, relay case series
EG12 (7XP7021-2).
cr
= ° ae
i csente 7
‘rounding serew HS
8
woh
Grounding screw M5
) Case 777720 1p) £288, 7X87720
Surface mounting Flush mounting
Fig 2 Case 7KP7720
3.2 Arranger
Differential relays 7UT7* are members of a family of protective devices in
modular plug-in technique. That is, the functional components of the devices,
measured input, measured value processing are all mounted on printed circuit
board assemblies.Das}
Ba
° Hien
Bas|
Bs
Be
en
Be
‘Bos
Boe
Bes
po ft
a
wreTie
® For 70175 ~ a blank plate
For 7UT76 - 6 interface circuits
for measured value inputs
@ Measuring module 77D34
@ current input module
for phase Ll
Front view of differential
Fig 3
®
@ Current input module
for phase L2
® current input module
for phase L3
@© 9 interface circuits
for measured value inputs,
plus output relays
relay 7UT75/7UT763.3 Ordering data
Solid-state, two-stage differential
protection relay 7UT7
for 2-winding transformers
for 3-winding transformers
Order No.
7ur7
o-Caall
Rated Rated frequency fy
we Ty,
60/125 V d.c.
110/220 V dec.
Case
78P77 2 case, for surface mounting
for flush mounting
Example:
Transformer differential protection fort
Two-winding transformer
Iy 7 1 A/50 He
Battery: 110 V
panel mounting: surface
Ordering code; 7UT7510-3AA0
Accessories Order No.
Matching transformer 4AMB1 70-748ore
Measuring circuits
Rated current I,
Rated frequency fy
Power consumption per phase in
current transformer circuit at I
1A or 5 A ac
50 Hz or 60 Hz
= 1A model N approx. 0.15 VA
= 5A model approx. 0.30 VA
Thermal overload capacity Iyt dA A
= continuous andy 2x Ty
- 108 30 x Ty 20 x I
- 1s 100 x 1, 70 % Ty,
- 0.5 5 250 x Ty 100 x Ty
Settings |
- fine stage, delayed
~ coarse stage, instantaneous
In-rush stabilisation
Operating time at 1
and setting 0.2 Ty
s"°
at 0.5 x 1y
atl oxIy
at 20 x Ty
Resetting time
Drop-out to pick-up ratio
0.2/0.3/0.4/0.5 x Ty
fine stage x 3 and x 5
To en! Ten = 0.2 at Tey elx Ty
approx. 650 ms (fine stage)
approx. 55 eal
approx. 12 ms | (3 fold coarse stage)
>0.08 ... 1.08
approx. 0.7
Auxiliary supply cireuit
Battery voltage
Working range
Consumption, approx.
at U, = 220 V de
at U, = 125 v de
at Uy = 110 V de
= 60 V de
at Uy
U, = 220 V/110 V de reconnectable
or
Uy = 125 ¥/60 V de reconnectable
80 to 115 %
19.3
1.4 Ww
11.0W
6.98-n-
Output circuits
Tripping relays
Signal relays
Indicators
Remote reset
4 volt-free make contacts
Switching voltage < 250 V=
Current capacity <5 A=
Switching capacity <1000 W; vA
Ors 20 W5 va
Local indication of trip Signal
and readiness for operation
Local or remote reset
Rated voltages 24 ... 60 V de
or 110 ... 250 V de (reconnectable)
System data
High-voltage tests
High-voltage test
Impulse voltage test
High-frequency test
(mal-function test)
in accordance with VDE 0435 and
TEC 255-4
2 kV mms, 1 min (routine test)
5 kV; 1.2/50 ps
3 positive and 3 negative shots
at intervals of 5 s (type test)
2.5 kV; 1 Miz} 400 shots/second;
T= 15 ps; duration 2 5
Climatic test
Permissible ambient temperature
= during service max.
~ during storage
~ during transport
Humidity class
according to DIN 40040
© °,
= 5 Se to +40 2c
25 0C to 455 °c
-25 °C to +70 °C
Classification F
condensation not permissible
Mechanical stress tests
- During service
- During transport
according to DIN 40046
10 Hz to 60 H:
> 60 Hz to 500 Hi
0.035 mm amplitude
5 g acceleration
5 Hz to
> 8 Hz to 500 Hi:
7.5 mm amplitude
2 g acceleration
Dimensions /Wei ght
Dimensions:
Weight:
70175/76 (see 3.1)
7UT75:
7UT76:
approx. 7.7 kg
approx. 9.5 kg-2-
5. Function of complete unit
Transformer differential relay 7UT75/7UT76 will ensure rapid and selective
clearance of short circuits within the zone which it protects. It will detect
2-, or S-phase faults; also double earth faults, for which latter one
earth point may lie outside the protected zone. (See block diagram, fig. 4).
The relay is available for connection to cts with rated secondary currents
(1y) of 1 A or 5 A and for frequencies of 50 Hz or 60 Hz, dependent on ver-
sion.
70175 is designed for motors or two-winding transformers, 7UI76 for three-
winding transformers.
To ensure stability, even under conditions of differential currents caused
by transformer tap-change settings or asymmetry, the pick-up value of the
relay is designed to increase as the line current increases. To prevent false
operation due to ct error, stronger stabilization occurs for through currents
over 1.5 x Iy (figure 6 ) and the relay is also stabilized against inrush
currents (figure 7), using the conventional principle of evaluation of the
second harmonic content. The relay remains stable when the ratio of 2nd har-
monic to fundamental frequency is as low as 0,20. This stabilization effect
is itself limited to a maximum of inrush equal to 18 x Iy-
The relay is so designed, that measured value evaluation, formation of sta~
bilizing and tripping effect signals are processed individually for each
phase and only then fed via an OR-analogue circuit to a common trip trigger
output. Thus each phase has its own separate filter network for determination
of tripping effect and stabilizing effect currents.-13-
In relay 7UI75, the differential current a1 for each phase can be measured
by opening the bridges at the connection terminals (2-10, 5-11 and 8-12) and
connecting a suitable instrument (see figures 10, 11). For the type 7UT76
this can be achieved by opening the relay starpoint at terminals 13, 14, 15
(see figure 12) in a similar way. Further, the voltages which are proportio~
nal to the differential currents can be measured at test sockets on the in-
put modules (figure 9).
Two output relays for tripping and indication signals have altogether 4 volt-
free, closing contacts.
Matching tmpet Input neasuring ovtput
temsforer interface circuit circuit interfaces
yl
a A
ute o
Ties
1} 42+ 0
=ul4Exg Todication
Fig 4 Block diagram - 7UT75
(70T76 is similar, but for 3-winding transformer)
The protection is made up of a number of modules. Schematic diagrams are in
figures 20 and 21, the physical arrangement of the modules is shown in Fi-
gure 3, They are:14 -
Input matching module (7UT76 only)
Measuring module 77D34
Current input module 71D28 Phase Li
Current input module 77D28 Phase L2
Current input module 71D28 Phase L3
©GGO6080
Input /output portion, with interfaces, tripping relays and power
supply.
5.2 Input /output_portion
This comprises: 5.2.1 Input transformers with input interface
5.2.2 Power supply
5.2.3 Output stages
This section is fixed, but with the exception of the power supply unit, can
be removed after releasing the fixing screws.
5.261
input interfaces
Por motor and two-winding transformer relay 7UT75, this unit contains for
each phase 3 input circuits to form tripping effect, in-rush and through
fault stabilization effect currents, assembled on one fixed module (figure 3,
@®). For three-winding transformer relay 7UT76, two further input units for
each phase are assembled on a further fixed module (figure 3,(2)). In the ine
put section, the through fault current stabilization component is rectified
and converted to voltage across a measuring resistor. The input relay for re-
mote reset of the indicators is also mounted on this pcb.
5.262
The power supply unit will convert available auxiliary voltages into a stabi-
lized voltage for the relay. For cooling purposes, some components are moun-
ted on a fixed heat sink. Components for voltage stabilization are also moun-
ted on peb (diagrams 20, 21).= 15 -
5.2.3 Output stages (output interface relays)
Also mounted on peb (diagrams 20, 21), are two electro-magnetic relays for
tripping and remote indication with two contacts each.
Of the four available (closing) contacts, three are intended for circuit
breaker tripping (2 or 3 breakers) and one for remote indication. However,
the use of each contact can be freely chosen.
5.3 Current input cir:
These comprise three-identical plug-in pebs LPl, LP2, LP3 (each 71D28) for
the three phases. (Schematic diagrams 20 and 21; physical arrangement figure
3; ®@, © and @). wach peb is fitted with capacitors which, together with
the inductivity of the input transformers, form resonance filter circuits to
distinguish the desired tripping effect current (at rated frequency, fy) from
inrush stabilizing effect at 2 £,, These signals are also rectified and
converted to voltages across shunt resistors on these pcbs and combined with
the through-fault current stabilization signal which comes from the input/
output portion (5.2). Subsequent circuits form the required pick-up characte-
ristic (Figure 6).
On the front plates of the modules, sockets are provided for measuring the
following parameters: voltages proportional to the tripping effect currents
(A) (Figure 9) and the value formed from the sum of I,, I, and I, i.e.
S s 2H?
the resultant value of {1, ~ I, ~ Tay] (the dynamic case, Ainere I, = tripping
effect, I, = throughfauit stabilization effect and 1 = dnd eseonte inrush
stabilization), or the static case [T, - 1,] for each separate phase (socket
Avs).
Note!
Since the 3 modules LP1, LP2, LP3 are, for current comparison purposes, fac~
tory calibrated for each phase, interchange of these modules may lead to loss
of relay accuracy,~ 16 -
5.4
This module comprises a plug-in pcb (LPS) with 32 connecting pins (schematic
diagrams 20, 21; physical location figure 3, @)). Here the three output sig-
nals from the 3 phase modules are amplified and combined. If their value ex-
ceeds the set pick-up value (adjustable in steps), the tripping relays and
indicator LED will be energized.
Sockets and pin-plugs for selection of the setting are located on the front
plate of the module, together with a green LED to indicate the readiness of
the relay; a red LED to indicate “trip command operated" and a reset button
for reset of the red LED. Equally, this indicator can be reset without open-
ing the relay cover, by a button on the lower left hand side of the case, or
remotely, by energization of the remote reset relay.
565 Compl
The complete circuit for relay 7UT75 (for a motor or a two-winding transfor-
mer) is shown in figure 5. Since a differential system can only compare cur-
rents which are equal in phase angle and magnitude, a set of matching trans-
formers (AW), for example, type 4AN5170-7AA is required when used for trans-
formers. Selected to suit the ratio and connection of the protected power
transformer they ensure that the ct secondary currents are converted to the
same ratio and phase shift. Even if the main cts are of the correct ratio
it is advisable to use matching transformers of ratio to ensure galvanic
separation, When used as motor protection, matching transfarmers are not nec
essary if only one of the main ct sets is earthed.
It is important to ensure that the connection of the transformer star-point
is correctly represented. In principle, any combination of transformer con-
nection and current transformer ratios can be correctly matched to the dif-
ferential protection system by using an appropriate matching transformer.
In each case, the necessary ratio is determined from the power, rated volt
ages, regulation and phase relationship of the protected transformer to-
gether with the transformation ratio of the current transformers.are
To prevent damage to a transformer by the passage of currents due to faults
outside the protected zone, an overcurrent relay would be added to figure 5.
This back-up protection will clear the fault after a specific time.
Under fault conditions the protection system must completely disconnect the
protected object from the network; the output module therefore controle all
connected circuit breakers. The back-up protection, for which time delayed
overcurrent relay is mostly used, has only to interrupt the current in the
concerned circuit and thus trips only one breaker.
For three-winding transformers the same considerations apply. The only dif-
ference lies in the use of type 7UT76.
In the case of 7UT76, the "TRIP" command is issued to all three circuit brea-
kers.
Uh ih
u Li] aw
in
ot ives
Y | 1d 5
= | — 3
ig 5 Principle diagram of differential protection for motor and trans—
former with two windings= 18 -
Figures 6 to 9 show the various characteristics of the 7UT7 series of relays.
Figure 7 illustrates the way in which the pick-up value is increased by the
effect of inrush stabilization (fed from one side of the transformer resp.
motor only) in relation to the second harmonic content, that is in relation
to the proportion Lyeu/Teye
Even more precisely than by the second harmonic content, an inrush magneti-
zing current is characterized by a displaced sinusoidal current. Characte-
ristics of this current are the amplitude of the peak value f and its base
width b. Since the circuits of the transformer differential relay produce
from this displaced sine wave a stabilizing effect curve practically identi-
cal to that of the second harmonic stabilization, the curve in figure 7 can
be given an additional pair of axes based on the characteristic values f and
>.
To clarify these factors, two examples:
A) Tyeq = 0) that is, Iy,,/Ie, = 0. There is no component of current con-
taining second harmonic. The pick-up value corresponds to the point of
intersection of the fault characteristic (for single sided feed) with the
tripping characteristic shown in figure 6.
B) If Igy = 5 x Ty and Tyey/Tgy = 0-3, the relay will be blocked. That i
Tygy 7 O13 ¥ gy = O03 XS x Tye LS oTy
Thus if one feeds a single sided current I,, = 5 x Iy to the relay and
superimposes upon this a current of magnitude Iy¢y = 1.5 x Iy, the relay
is blocked.-19-
IMy
10
5 fold coarse stage
3 fold coarse stage
Fine stage
4
Operating characteristic (T = 7. g
Tor 3
rating value: 0.2 x
Operating value: 0.2 x 14
2 4 6 a 10 2 % 16 Islly
@ current which flows in one stabilizing
winding or, sum of the currents in all
branch windings
Effect of temperature
on the characteristic
5 TurT* wre
anata
a 0 Is!ly
Fig 6 Tripping characteristics 7UT75/76~ 20 -
4
Tain ew
b
sued 05 7 ores
105°] 0,4
206° 0,3
237° 0,2
265° 01
T225°C
3o0et 0
02 03 08 1 alaaes) 5 10 Iwiin
aya G2 62 102 2v2 fin
Fig 7 Typical stabilization characteristic with sinusoidal mixed frequency
currents, 7UT75/7UT76tls
-~21-
414734
054
O64
034
024
Fine stage
ot
0,05 4
0.04 4
0.03 4
0,024
3 fold coarse stege 5 fold coarse stage
0.01
02 03 04 05 1 2 34s 10
Tripping time characteristic 7UT75/76
20
Lan= 22 -
a
7 ~
5 <
2
s
2
s
+
s
x
s
=
«+ T
2 n = n °
) a = S
Differential current-proportional voltage at test sockets -A and M=~ 23 -
6 Install.
6.1 Unpacking
The quality of packing is such that it will protect the equipment during
transport, to the standard specified in DIN 40046 Part 7, Class 23.
The equipment must be unpacked with care and without the use of force or
inappropriate tools. The packing can be re-used for further transport, if
applied in the same way. If alternative packing is used, it must also meet
the requirements of DIN 40046 Part 7, Clace 23.
6.2 Readiness for use
The relay is ready for operation immediately the auxiliary power supply is
switched on.
6.3 Prep:
The conditions for use, as laid down in VDE 0100/5.73 and VDE 0105 Part 1/7.83
must be observed.
The relay must be connected to the protective earthing system at the terminal
provided.
Connections must be checked for correctness, using the checklist 6.3.1 and
diagrams 10, 11 or 12. At 7UT75, the terminals 2 and 10, 5 and 11, 8 and 12
must be bridged each pair (may be via current measuring terminals); at 7UT76,
from production series ... / CD on, the terminals 13, 14 and 15 must be brid-
ged together in similar manner. Further, check the rated data of the system
(frequency, ct rating etc) against the rated data of the relay, Also check
that the complete identification code of each module agrees with the code
printed on the lettered retaining strip. Check the MLFB* codes:
* network frequency against that of modules 77D28 and 77D34
* the required case design.
Check the settings against the procedure in section 7.2 "Arrangement and set-
ting of the setting elements’.
* Computer readable ordering code= 4 -
6.3.1 Checking the e:
Switch off all Switch on main
auxiliary power duc. battery /
supplies auxiliary supply
Polarity
! correct 2
Check continuity
off all ct cir-
cuits, using foltage
system diagrams correct ?
Switch off main
hase sequence
dic. battery /
auxiliary supply
Check continuity
of wiring to
polarit; circuit breaker
| trip coil, using
|
7 [eyetem a:
agrans
Check that dic. Check continuity
aux. supply (60,
110,125 or 220¥)
of signal cir-
cuits, using
is connected to
term'}s 19...22
system diagrams
@ does the connection correspond with the available battery voltage?
(see connection diagram 10, 11 or 12)Sisk
(aoyszea Kepas 03 Burps0992) 2p A 09 30 A OTT I-1/41 ———=
(uotszea AvTox 03 Surpx0s9e) 2p A GZT 30 A OZ 27/47
*
ie
gufzuujou of af cl of gf of ef 2] a
SRT
SLINL
i i bys
AM 0z
SPX
AMOLL
Mcri64 i>) "Gq
| qa2
eee ee RH SZ ATT OT oY BY A Gy
sa9equos Gurddyay, roy
it
poten eee
Ve:
suoraaauuos Kraaqeg
3 2
33
andut yasai ajomey
Differential relay 7UT75 for a 2-winding transformer
Example for Yd~ 26 -
é
(2déa Keyea 03 Burpscoze) 2p A 09 40 A OIL t-1/41 ————
(944 keqoa 03 Burpzos2") 2p A GzT 40 A O%Z 3-1/4
zu] woul
seen
SLIME
Coa fie
OE ez Be Se He ER CET Te eT ay i] Lif 9H]
sqovquo> Buydd ray iy
4 m2 8
suozqoeuu0s 1939ed 3
t
AOST
anduy qasex eq0woy,
ery
75 connected for motor protection
Differential relay 7U
Fig itar" 9LANe
ther
ws~ 28 -
t Operating instructions
7a Safety precautions
All safety precautions which apply for work in electrical installation are to
be observed during commissioning.
7.2 Arran,
All adjusting elements are located on the module front plates or directly on
the printed circuit boards. The location of the individual modules is shown
in figure 3. The settings are described in detail in the following.
7.261 Setting principles
The settings are made by the positioning of pin-plugs on the fronts of the
modules (see figure 13). The method of setting is described individually for
each module. The setting is given by the position of the pin-plug and its
location. If the marking line is horizontal, the plug is effective. If the
line is vertical, the plug is not effective. Only one plug may be used in
each module.
Setting
on
1S2
sz
Gor
152
soz
:
were
Fig 13 Selection of setting~ 29 -
7.262
When 7UT75 used as motor protection, matching is not necessary if both sets
of cts on either side of the motor windings have the same ratio. Nevertheless,
matching transformers with ratio 1:1 are recommended to separate the main ets
galvanically. If matching transformers are not installed, only one set of main
cts must be earthed to avoid spurious currents flowing via ground. The rest
of this chapter 7.2.2 is irrelevant for motors.
Since differential relay 7UT75 (or 7UT76) monitors the equality of input
current with output current in each of the thiee phases, the currents given
by ctl and ct2 (Figure 14) must agree with each other in phase relationship
and magnitude. For this purpose one installs a set of matching transformers,
AW.
In principle, any combination of transformer connection and current trans-
former ratios can be correctly matched to the differential protection system
by using appropriate matching transformers.
In each case, the necessary ratio is determined from the power, rated vol-
tages, regulation and phase relationship of the protected transformer to~
gether with the transformation ratio of the current transformers and, final-
ly, the phase relationship of the matching transformers themselves. For
regulated transformers, the mean current value of both extreme positions of
the tap changer is to be taken as determining the ratio of the matching trans
formers.
In determining the current transformer connections, the treatment of the
transformer star-point is important. If the transformer is directly earthed
or earthed via resistance of Petersen coil, a phase-to-ground fault - even
anywhere in the system - will cause a fault current to flow through the star-
point. No similar earth fault current flows on the other side of the protect-
ed power transformer. Consequently, for an earth fault beyond the protected
zone, current would flow through the ster-point causing a zero sequence compo-
nent unbalance in the relay and consequent nuisance tripping.= 30 -
This nuisance tripping can be avoided by providing a delta connected tertiary
winding in the matching transformer set, this will short circuit the zero-se-
quence component allowing secondary ct currents to remain in balance.
Matching transformers should always be installed, even for YyO group trans-
formers where the secondary currents of the cts are equal at their respec-
tive load currents, because of the benefits of galvanic separation between
the two main ct sets.
If one star-point of the protected transformer is earthed, the matching
transformers should be installed on this side of the relay. This also applies
when an earthed synthetic star-point (zig-zag choke) is present within the
protected zone.
For transformers with two earthed star-points (or two synthetic star-points),
both sides of the relay shall be provided with a set of matching transfor-
mers. These shall be so connected that the side facing the relay is connected
in delta.
If the star-point of a protected transformer is earthed via a Petersen coil
(are suppressed), it must always be treated as an earthed star-point.
If the star-point of the protected transformer is earthed, the star-point of
the associated ct set must not be connected to the relay star-point (termi-
nal 13 in figure 14). On the other hand, the star-point of a ct set shall
never be left 'floating’.
If the protected transformer is group Dy or Yd, it is recommended that the
matching transformers be connected on the ¥ side.
If, even after considering the above guidelines, the choice of location of
the matching transformers is still free, it is logical to install them on
the side on which the cts have the smaller burden.-a-
It is recommended that one checks the connection groups by assuming that all
the ratios are 1:1 and, assuming an external phase-to-phase fault, draws
arrows for current flow on the sketch as in figure 14:
AW
Matching transformer
Fig 14 Checking the matching circuits for a star/star transformer-32-
Determination of the number of turns for the matching transformers is best
made in the following way:
1, Obtain the necessary transformer data:
Transfr. Rated output =P
Rated voltages U,, U, (tapping range in case)
Connection group
Star-point treatment
et. Nominal ratiog no.) and nogy
Rated outputs
Overcurrent factors
where appropriate, existing burden
2. Prepare basic sketch (see figure 14), using data obtained under 1.
3. From the rated output and the upper and lower voltages of the protect~
ed transformer, calculate the rated currents of the upper and lower
voltage sides. If the protected transformer has a voltage regulation
range, then use the average value of the currents determined from the
maximum and minimum voltages as the ‘rated’ current. (Do not use a cur-
rent value calculated from the average value of the voltages!)
4, From the currents calculated under 3. and the ct ratios, determine
the et secondary currents for the upper and lower voltage sides.
5. From 4. calculate the currents in the windings of the matching trans-
formers;
wheres
wind fae
for ¥ winding, Ty: .aing = Tphase
; 5
for D winding, Tyinaing * phase M2
6. If matching transformers are used on both sides of the protective relay,
one should choose the ratios such that rated relay current flows in the
protective relay when rated current flows in the protected transformer.ame
7. Calculate the transformation ratios of the matching transformers and
thus the numbers of turns in the windings. It is convenient to set the
ratio on a slide-rule and, with this setting, to search for a turns
ratio whose sum does not exceed 20 turns (at 5 A rating) or 52 turns (at
1A rating).
It is advantageous:
a) to include as many turns as possible, to achieve the minimum vol-
tage per turn.
b) to avoid negative turns on the transformers.
For group Yy, connect the remaining turns to form a delta winding.
An example of calculation of the required ratio is as follows:
Figure 15.
Transformer 110/20 kV 35 MVA Y(N)d5, ctl 200/1, et2 1000/5.
Rated current primary 183.7 A on the 110 kV, 1010 A on the 20 kV side.
0.919 A and 5.05 A.
The relay 7UT75 will be connected on the 20 kV side:
ct secondary current:
Because, if an earth fault occurs in the 110 kV network, any zero sequence com-
ponent which would flow through an earthed transformer star- point, would be
withheld from the relay by the matching transformers, thus preventing incor-
rect operation.
Therefore, the 5 A version of 7UT75 is selected. The matching transformers
shall have a ratio of approximately 0.919 A/ (5.05/V3 Ja.
This transformation ratio results in selection of matching transformer type
4AM5170-7AA with turns ratio 38/12.
For transformers with 3 windings, it depends on the power ratios of the win-
dings, whether an overcurrent or distance relay is necessary for all three
or only two windings.~ 34 =
Considering the transformer in figure 12:
Ratio 220 kV/110 kV + 22 %/20 kV
Ratings 100 MVA/100 MVA/30 MVA
Group YNyn0d5
ct ratios: ct1 300/1, ct2 500/1, ct3 800/5
Since the 20 kV winding could be overloaded with a multiple of its rated cur-
rent without any adverse effect on either of the other windings, an overcur-
rent protective device is essential for this winding. Also, the 220 kV wind-
ing could suffer an unacceptable overload under conditions of simultaneous
feed into the 110 kV and the 20 kV networks, without any other protective de-
vice responding. Thus an overcurrent or distance relay is also necessary
here. If the network conditions would allow the same circumstances for the
100 kV winding, an overcurrent or distance relay would also be essential for
this limb.
In determination of the matching transformer connections, the winding with
the largest rating is used as the basis; in this case 100 MVA.
This results in the following currents:
220 kV side primary 262.4 A, sec. 0.875 A
110 kv side primary min, 430.2 A, max. 672.9 A
Average primary 551.6 A, sec. 1.103 A
20 kV side primary 2887 A, sec. 18.4 A
To connect a 7UT76 relay of 1 A rating one could, for example, select the
following ratios for the matching transformers:
AWL: 16/26 turns
AW2: 16/33 turns
AWS: 2/39 turns
For the relay settings, since 0.93 A flows at rated current, 0.4 seens at
first sight to be the correct value but, in consideration of the + 22 % regu-
lation, use 0.5.- 35 -
it jen 20011 i | aa
toe? YUN) GS.
4
rus Tits
4
aprhoe
wom BAT flee 201s
wet
Fig 15 Connection of differential relay for transformer
connection group Y(N)d5
Accessories
Auxiliary current transformers 4AN51, 4AM52
Overview
Tee ‘pstcation [Feesures
4AM51 70-7AA | tult-tap aux current rancformer to match diferent eurent von
4AMs2 72-2aa | tates imac ean
AME2 72-388 | casio 7o~-TAA: stancara version, primary for transformer overall
Gitferental protein,
Muti-top aux
400152. 72-2AK: Version with double thermal withstand capability. eg, when
connecting te wide-range curtenttransforme” {continuous
rating 2 * Iu
AMS2 72-34: Version with higher set
I iver al protections |
Windings of au:
iary current transformers
| numer of turns Ap oco fe
VE LM HO Pos woight
Uinreition to each other) Wa bi ut ty is approx
2AMB1 70-7AA | Rated current hy’) ale © & seers Heat 34kg
Mar waltege vj) 2 4 48 2 4 wo 2
GAMS2 72-200 Rotes crvent i!) A} i 1 1 2 1 1 1 2 5 tg
Max voltage 2 a i
4AMS2 72-3AA Rated current /') als 5 5 4 5 5s 5 4 5 9
| Max vottage vi 4 8 2% 6 2 8 2 6h
max, thermal load if all windings are charged at the sane tine = 1.2x Ty/cont.
10 x 1/10 6
25x Ty/ ls- 36 -
7.2.3 Setting the pick-up current
Setting of the pick-up (response) current is made, in coumon for all three
phases, by pin-plugs on the module 77D34 @) (see figure 16).
(eee Seiue ts pontion BF operating vet fr
(green) "Ready" fine stage value
1D Indicator
(red) "Trip
Reset
button
As operating vatve for
foarse stage is 5 fold
fine seage value
(eaceory setting)
a) Front view b) part view of pcb
Fig 16 Front view and part view of pcb of the measurenent module 77D34
When exact data are not available, the following table can be used as a start-
ing point for the sensitivity setting:
Where: I, is the rated current of the protected unit, Ty is the ct rated
current, I, is the current setting. If the transformer tapping range is
more than 10 %, the next higher setting - if possible - is chosen and for a
tapping range over 20 % yet the next higher. Ranges over 30 % will normally
require switching of the matching transformers.-~37-
When setting the relay, it should be remembered that the relay current is
not necessarily the relay rated value (1 A or 5 A) when rated current flows
in the protected object. It is most important, however, to calculate ratio
I,/ly exactly.
Using the procedure:
Uns, = maximum voltage at the top end of the tapping range
Vain 7 Minium voltage at the bottom end of the tapping range
Pay, § Bayp 7 tFansformation ratios of matching transformers
all other reference data as described in 7.2.2, so that for a Yy connection
of the matching transformers we havet
and thus, for the setting when regulation is effected on the lower voltage
side:
tas
The next higher available setting is selected. If regulation is effected
on the high voltage side, use the appropriate method.
If a Yd connection is used, the appropriate value for the current I, shall be
calculated from the correct ratio:
™
Paw ~ NV
Setting of the coarse stage (3 times or 5 times the fine stage) is made on
the pcb of 7TD34 by relocating a solder bridge (see figure 16b).- 38 -
73 Preparations for testing
If relay performance is to be checked against original performance data, the
reference values for temperature, frequency etc. must be ensured (IEC 255).
For electrical tests, the following equipment is recommended:
2 Adjustable voltage sources 50 Hz P220 VA
1 Adjustable voltage source 100 Hz P 220 VA
2 Matching transformers (current source) for max. 10 A
(for max. 50 A for 5 A relays) with separate windings. (Own power consump-
tion approx. 5 VA.
1 Phase shifter 50 Hz 20 VA for setting phase angle between 50 Hz and 100 Hz
current components.
(Can be omitted if one voltage source itself has phase angle adjustment).
Oscilloscope (for monitoring phase angle).
Timer (e.g. Siemens 7KB2041).
Continuity tester.
Universal ammeter ...0.2...10 A, 50-100 Hz, + 0.5 %
Universal voltmeter 0.3 13: 30V, de, + 0.5 %
Internal resistance 100 kOhm/V resp. >1 Mohn
1 Test adaptor for module 77D34 (C74334-A83-A1)))
1 On/ofé switch 10 A (50 A for 5 A relay)
1 Current transformer 50/5 A Class 0.2} 5 VA
only for 5 A relay).
Arrangements of the test circuits are shown in figures 10, 11, 12, 17 and 18.
Functional check of the remote indicator contact(s) is best made with a con-
tinuity tester.
D po not use type 6XK1 O11 or model C74334-A83~Al-2= 39 -
14 Test procedure
7.6.1 General
Accuracy of test results will depend, amongst other things, on the electrical
characteristics of the test equipment. For example, the harmonic content of
the test quantities shall not exceed + 3 % if the stated accuracy is to be
achieved.
Note: The tolerances given in the following test instructions refer to the
device at operating temperature (voltage at least 4 hours applied). Other-
wise an additional error of 5 % is to be considered.
If a brand new relay is being commissioned, it is necessary only to check
that all connections are correct and that the relay functions correctly. All
tests relating to accuracy of performance can be ignored.
764.2
Check the position of the contacts, using a continuity tester, as auxiliary
power is applied to the relay. Availability of auxiliary power is indicated
by energization of the green LED on module 71D34 @.
Output contacts, terminals 23-24; 25-26; 27-28; 29-30, are ‘normally open’
and should not close momentarily as the auxiliary voltage is switched on.
When the tripping output contacts close, the red LED on 7TD34 is also ener-
gized.7.4.3 Ghecking the operating
- 40 -
pd
[Fe
test velue into
terminals 10 4
3
See fig. 10 to 12
Sot 1/Iy at 0.2
Sot Wy
Slouly raise test,
current far phase
Ut up to max 1.2
tines expected
operating value,
nest ind
on 77036,
3
current a!
operating
setting.
Permiesibi
0. 2a, 40.
120
are clk
Tern. 23/26;25/264
37/28;20/30)
f test
.
by
push button
front of 77034
Repeat cane test
for phage L2 Dut
feed into
teraipale 11. 13
aa)’
Repeat vane test
for phase L3 bi
Teed into
terminals 12 473
as)"
Stovly raise test
current for
U2 up to max 1.2
188 expected
Gntsl indicator’
on 71034 comes
Slouly reise test
current for phase
LS up to max 1.2
times expected
operating value,
on 71034 cones
at
1g point/
wath
bie vai
10.051,
3a 36 oY
Read off teat Ros off tot
current
operating point/
setting.
Permissible value
0. 2ety40-031y
asf
contacts
|e cuca
Term, 23/24125/26)
| 27/20;29/30
Suitch off test
set/Rosot
insieaters by
pressing button
Bt Botton of
nausing
Suitch off test
sot/Rovet
indicaters by
nergising
note" relay,
(Term. 16,17, 78)
*) Terminals in ( ) for 7UT76 from production series .../CD on-a-
Check the settings as detailed in check procedure 7.4.3 but omit repeated
check of the TRIP contact. Check the settings in ell three phases in accor-
dance with the following table, with due regard to the given tolerances:
Setting on 77D34 Pick-up value Permissible tolerance
0.2 x Ty 0.2 x Ty ESR +0002 x Ty
0.3 x1, 0.3 x 1y 25% +£0.02 x Iy
0.4 x Ty 0.4 x Ty FSR +002 x15
0.5 x 1, 0.5 x Ty 45% +002 x1,
7.45 ages
Check the voltages which appear at test sockets -A and M on the front of mo-
dule 7728, at the following input test currents, for all three phases volt
meter R, 1 NOhm:
i
0.2 Ty + 3% UV yyy = 360 nv + 50 mv
LO £37 Uy = 25 VF 0.250
Application of test current as in 7.4.3
The inrush stability of the relay can be tested by measuring the voltage
which appears between sockets A-S and M at the moment when the power trans~
former is energized. In principle, it is possible tu measure the vectorially
added values for tripping effect, through-fault stabilization and inrush
stabilization currents, for each phase at these sockets. Under steady state
conditions, the value of the difference between tripping effect and through
fault stabilization effect is a criterion for the tripping quantity. In the
initial (or quiescent) condition, when the differential current is zero, a
voltage of approx. + 1.0 V should be present. As a measure of the stability
of the relay, the difference between the measured voltage and the operating
threshold is critical. The operating threshold is related to the set pick-up
value and is + 1.4 V (at 0.2 x 1y)5 + 1.9 V (0.3 x Iy)s # 2.3 V (0.4 x Ty
and + 2.7 V (0.5 x 1,). (All voltages dc, of course).~ 42 -
7.4.6 Checking the inrush stabili
7 1
Pheee Repest sana tect Repeat sane tost,
Check test for Phage L2. ‘or Phase L3.
circuit. Food
test value into
check tast check test
oe iret Fong circuits Feed
‘ est valve into test veiun into
put W/Iy plug on terngnale 44 13 teengnals 7413
ino aa) as)
Ser figure 17. See figure 17.
But 1/3) pug on ut 1/fy p2ug on
front of 77034 front af 71034
in bees in dee.
Slouly raise
mixed. frequene
currents for
Phase Li, one
after tha other.
First raise 100
He current to
0.25x1,, then 50
Siouly raise Stouly raise
" ixed frequency
currents for currents for
Phase L2, ono Phase L3, one
after tha other. after the other.
inst raise 100 First rales 100
irrent to He current to
Hz current to
thy 2.25x1, thon $0
“ wa curlent to
oat a
does not eS |
operate. fed LED
chee
fon T1034 does not sues
fone ane Fela) coen not
i operete. Rea LED
en 71034 ees ni on T1034 does not
6.2
|
Stouly decrease
|100 Hz test
current until LEO
Compare teat
Slovly decrease
100 Hz test
current until LED
fon &1D3¢ comes on,
Conpare test
operating point
uith correct
(.2090.03)1,
juith correct
value:
(0,2020.03)1y
a
Suiteh off test |
set.
Reset incicetora. Suiten off test Suiten off test
| set. set.
Reset indicators. Reset incicators.
% The phase difference betvesn +) Terminals in () for 7UTT6 from
fon series .../CD on,
ive produ
the maxima of the po:
half waves shall be 0.~ 43 -
7.4.7 Checking the
—t
1
Chock tha test
circuit, tees 8 tri
effect current 1,"
into terningle
io 13 anda
stabilising current
I, into terainele
156 3, both
currents equal in
phase,uith plug
setting 1/1,=0.2
en front of 71034
Slouly reise test
curronts one after
the other, firet
0 Sx, then
1 to Sxd,)0th
I, untii ingicetor
ch 77034 cones:
ae
Read off test
current at
eparating point
compere with
cores t value:
1,24,61,488
1
Suttch off test
*/Rseet
inciceters
Repeat the sane
test for phose
U2 but feed
Current 1, inte
ferninene’t &
33 end Ty inte
terninald 446
:
Repost the sane
test for phase
LS but feed test
current J, into
termineie"12 &
T'ang ie ante
terminal 789
Sleuly raise
test currents
one after the
other, fiat 1,
to Sxi)ehen 15
until indicator
on 71034 cones,
Slouly ress
test currents
fone efter the
other, first 15
Pehen
te Sx1,)0then 15
Until incicator
on 77034 cones
12
v2 |
Ross off test
current at
operating point/|
inpere ufth
correct value:
Rese off tost
current at
operating point/|
compare uith
correct vsluer
etd Tynes 6x1 48%
Susten Suitch off test
set/ Reset set/ Reset
indicators incieatore
1) Do not exceed thermal overload capacity ace. "4. Technical datalt!
Wait for cooling periods if necessary.= a4 =
7.4.8 Checking the characteristic for 7UT76
1 4
Check the test eat tho sane Repost the sane
Arcuit. Food toate for phase tests for phase
2 trip ofre LZioue Feed trip US"be Fone trie
current’ I, into ofrost current ttect curzent
ene I, into teomina Ty into tominad
13'ane 116.13 (14)"sne 12 & 13 (15Y"and
stabilising sees stebs2ising
effect curzen te one urgent T, one
ig into the. teen thePother after tneScther
ince terminals {nto tepsinale
143, thon
aeacee "t's," than 72°, then
lleaacen 645) than 38 8) then
ff as. rae.
Stouly raise ly raise
Put seteing test currants feat currents
plug T/ty on fer obese for: phase L3 ond
roe tao. titer the after the others
socket. tsat Ie gt Sat
Slouly rates then Ty untia nts
fest currents inatcator on for on
for phase Li 7036 cones en.
one aftr the
other, Fanet 1
to Sat," then 2.2 I
otf an
next BE
Read off test ut
current. Comp
Note! ‘tls’ = ‘terminals’
JOD on.
terminals in ( ) for 7UT76 from production series .
Do not exceed thermal overload capacity acc. "4. Technical data.
Wait for cooling period if necessary.7.4.9
45 -
Repeat test for
Phase 2 but feos
Repeat test for
Pheses U1, 12
Up stert!) end
terminal 29 & 30.
"Stop! att
expired tine
Put plug 1/ty in
0.2 on front of
rosa,
} crose auiteh st.
Sieuly raise test
current for Phase
1 to Dedxty 43K
Andicetore
est
Fapoat sane teat
Tor Phosa L3 but
feed unto
terminals 12 413
as)
1
Suiten off teat
s0t/ Re
incizators
|
Dpen eviteh 1S.
Recieve auiteh SJ
Read off operating
with
70 ms +10 ne
value
Suitch off teat
set/ Reset
neicats
into ternigets 11 Jand U3, but
© 13 (4a) jchenge.
Cranest Timer te So ee 38
terminal & ('Pick- set/ Re: ene
erating
toh off test
set / Rosct
indicators
Caution!
The current value 10 x 1,
chal not
be applied for longer thin 30 s. All
compared time values should be the
average of at least 3 separate rea~
dings.
*
> terminals in ( ) for TUTT6 from
production series .../CD on,Paar
258 # Lele: 220 V o 125 ¥ (according to relay version)
28 TWA 10 ¥ or 60 ¥ (according to relay version)
Battery connections
- %
; Tripping contacts
fo _tols tala |e ne mo7 mn
as ereststy}
ba |
Tur 8 |
won
Fig 17 Connection for testing with mixed frequency currents
&
a
| | 3 j ctr
|
| |
W195
vats
Tere ere sara
so
‘ly shall be of the value of output voltage of the 50 He-generstor
Fig 18 Connection for checking the operating time= 47 =
75 Making ready for servic
Re-check all the settings (they may have been changed during the tests).
Check that 11 modules are properly pushed into position and that all the
setting plugs are fully inserted. Tighten down all terminal screws (inclu-
ding those not used) and secure the module clamping rails.
The mechanical parts are not stressed in any way during operation and there-
fore need no maintenance.
The correct location of the p.c.b. modules are shown in figure 3.
For fault tracing it may be necessary to withdraw module 7TD34 and to rein-
sert it with the adapter C74334-A83-Al. This allows access to further termi-
nals for test measurements.
CAUTION! Before withdrawing or inserting 7TD34, switch off the auxiliary
supply.
9%
The relay does not require any particular maintenance. All the measuring
circuits are static and maintenance free, Input relays are hermetically
sealed and output relays have protective caps. Approximately 3 months after
commissioning it is recommended that a hrief functional tect be repeated.
At this time, the conventional practice of checking all screwed terminals
for tightness is also recommended. This one-time investment, shortly after
the first commissioning can significantly increase the reliability of the
terminal connections.
Subsequently an occasional functional check at approximately 2 year inter-
vals is adequate. at this opportunity, the tripping circuits and circuit
breakers should be included. If, during these checks, any fault is discover-
ed, the following various procedures are available:~ 48 =
a1 Fault tracing
In many cases an immediate identification of faulty circuits is possible
when, for example, the LED on 7TD34 remains off, or the ‘trip! display does
not appear on 77D34 when it should. The fault can be cleared by replacing
the modules by spares, so long as these are available. If a fault is cleared
by this procedure, the whole unit should be re-checked, as described in item
Teds
Modules 77D28, phases Ll, L2, L3 are not directly interchangeable and are
not therefore fitted with tabs to allow them to be withdrawn (factory cali-
brated). In the unavoidable event of exchange or interchange, the accuracy
of the unit may be impaired,
After replacement of any of these modules, a recalibration is required to
keep the specified tolerances.
When injection test sets are used for such tests it must be remembered that
the relay will only demonstrate its design accuracy when supplied with para~
meters which themselves have harmonic content and frequencies within the
reference conditions laid down in VDE 0435 Part 303, also test intruments
with the required accuracies must be used (laboratory standard), All measure~
ments must be made at normal operating temperature.
9.2 Syster ing
When the Lests described under item 7.4 are carried out exactly in the given
sequence, the failure to meet tolerances, the non-appearance of LED signals
or non-operation of contacts may indicate faulty modules.
To aid systematic fault tracing, the schematic diagrams are numbered with
the relevant references (3.2 or 3.3 or 7.2). If a fault occurs at one of
these test steps then it can be attributed to the one (or more) of the modu-
les identified from figure 19. Replace the concerned module(s) in the order
given by the numbers 1, 2, 3 etc. If more than one module has the same se-
quence number, these should be replaced simultaneously.- 49 -
Simultaneous exchange of more than one module can be avoided by making addi-
tional measurements. If, for example, a faulty indication appears when check-
ing the tripping effect under criterion 3.1, the fault could equally be on
module 77D28 or 71D34, By measuring the voltage between sockets -A and M as
described in item 7.4.5 at 0.2 Iy, a decision can be made. If the toleran-
ces are not achieved, the fault lies in module 77D28.
For further localizing, module 77D34 can be reconnected via the test adaptor.
After resetting in accordance item 7.4.3, point 3.1, 10 wA + 5 mA must flow
through the adapter connections:
When checking Ll, vie connection b16
12, via connection b20
13, via connection b26
If the tolerances are then maintained, the fault lies on module 7TD34.
If identification of the faulty module is still not possible, one can also
use an adaptor to check the auxiliary power supply. A voltage of + 15 V with
@ tolerance of + 1 V must be present at connections (2L+), (M) and (2L-).
The current consumption in the 'rest' (initial) and operated conditions is
55 +5 ms.
Current consumption from the battery circuit (terminals 19 to 22), at Uy +
1% is:
vu, Ty (ma) CH" ~ aux. supply voleage)
220 82... 95
110 91...109
125 B4...100
60 101...133
If these values are exceeded, a fault may be present in the power supply
unit, replacement of which, as with other parts of the fixed portion, is not
easy.- 50 -
77028
TIO34
Item Test step Ly} Lz
peb 4
7.6.2
3.2
33 1
3b 2 1
35
36 2
37
38
113656
Eig 19 Allocation of faults to modules-~S51-
After replacement of any module, the tests listed in 7.4 should be repeated.
These described tests do not claim to be comprehensive. If it is not possible
to trace and correct a fault by this method, the relay should be returned to
the manufacturer for repair.
10. Repairs
Repairs of faulty modules should, where possible, be carried out by the
manufacturer or an authorised repairer. Such repairs require the use of
specially selected components and correct calibration requires special test
gear. Furthermore, work on the circuit boards requires special techniques to
avoid damage to the ripple-bath soldered boards, printed circuits and protec~
tive coatings.
ie Storage
During storage, complete units and spare modules will withstand temperatures
from -25° to 55°C, as described in VDE 0435 Part 303 or IEC Publication
255.
The relative humidity should not be such as to cause condensation or ice
formation.
After long storage in extreme conditions (tropics) it is advisable to leave
the unit switched on for 1 or 2 days before use, in order to warm it through,
and specially to regenerate the electrolytic capacitors in the auxiliary vol-
tage circuit.we= 54 -
Subject to alteration
Siemens Aktiengesellschaft €73000-G1176-C43-1
Available from: MWB Berlin
Printed in the Federal Republic of Germany
AG 0587 0.20 UBN 54 EnFeinstufe
p}-—
eee a
Motor—Diff.-Schutz
ec eaenl : C73207-AZ47-X6—x-12
_ 6 T 8[41028%2-0 U4
Siemens AG