Installation Manual
TRANSMISION CONVERTER
TCP/RS485
VERSION 1.0
Installation & operation manual
GENERAL INFORMATION
TCP/RS485 converter is used to connect controllers network to the Ethernet
and with computer with the supervisor software. The device allows convert TCP/
IP to RS485/RS422 protocol. The converter has overvoltage protection and opti-
cal isolation in transmission bus. Predisposes it to use in large systems in an en-
vironment exposed to electrostatic interference and surges. The RS232 port is a
DB9-F connector and RS-485 port is DB9-M connector. Between this connectors
is located switch.
Technical parameters of the converter:
• Compatible with EIA RS-232C i RS-485, RS-422.
• Electrical interface:
- RS232 port - DB9-F connector
- RS485/RS422 port in the form of slots plus DB9-M module with terminals
• Level of protection against power surges - up to 1,5 kV
• Optical isolation
• RS485 port Modes: half-duplex
• Optical indicators work:
- Red LED (PWR) power signal
- Yellow LED (RXD) send signal
- 2 x Red LED - 100 M link signal
• Recommended cable for bus lines:
- unshielded twisted pair - two pairs
- shielded twisted pair - one pair
• Baud rate on port 485 - to 9,6 Kbps, up to 5000 m
• Dimensions: 67 x 93 x 22 mm
• Power - 9 - 30 VDC, 500 mA (included supply power)
• Power consumption: static - 120 mA, -350 mA dynamically
• Environmental parameters:
- Operating temperature - 20 ° C to 60 ° C
- Relative humidity - 5% to 95%
ALL rights reserved © AAT Holding sp. z o.o. 2
Installation & operation manual
Connection table for RS-232 port Connection table for RS-485 port
Number Function description Number Signal RS-485
at DB9-M at DB9-M Hal-duplex
terminal terminal
1 GND - save ground 1 T/R+ RS-485 (A+)
2 RXD - data receive 2 T/R- RS-485 (B-)
3 TXD - data send 3 GND GND
4 DTR - transmission ready 4 VCC 10-30VDC
5 GND - signal ground
6 DSR
RS-485
TCP
7 RTS
8 CTS
Converter
9 RI
TCP/RS485
Connection with controller using RS-485
RS232/485 port switch Supply power
socket
RS232 port
Rs485 port Ethernet socket
TCP/ RS485 converter
ALL rights reserved © AAT Holding sp. z o.o. 3
Installation & operation manual
Converter Configuration
Parameters of the converter can be configured using a web browser using the IP
address. The default IP address and MAC address is on the label. If the IP ad-
dress has been changed it can be read using a search engine for LAN converters
available in the supervisory KaDe software.
To connect to the device's IP address must be entered in the browser. The de-
fault address is: http://192.168.168.125.
Note: If you can not connect to the converter via this address then you should
find it through search engine converters Each program that displays the address.
In the login window, enter your login and password - default:
Login - admin
Password - admin
ALL rights reserved © AAT Holding sp. z o.o. 4
Installation & operation manual
Quick Setup Window - displays the basic parameters.
Note: The operating mode must be set as:
"TCP SERVER" and port 50000
Detailed configuration windows are available in the sections:
Advanced Settings (Advanced Setup)
Management (Management)
The most important of these windows are shown below.
ALL rights reserved © AAT Holding sp. z o.o. 5
Installation & operation manual
ALL rights reserved © AAT Holding sp. z o.o. 6
Installation & operation manual
Detail configuration of TCP converter can be done using web viewer - Setup