Job Name: NFE 12 B,D CHILLER-5 oct Unit Tag: CRTAG-2, CRTAG-2-1, CRTAG-2-2
Prepared For: Quantity: 3
Sales Office:
Unit Overview
RTAG - air cooled chiller series
Chiller Model
R
Refrigeration Capacity 966.1 kW
Cooling Efficiency 2.213 COP (kW/kW)
Evaporator Configuration Standard Cooling (4 To 27C)
High Ambient (14-125F/-10-
Condenser Configuration
52C)
IPLV.IP 5.091 COP (kW/kW)
NPLV.IP 4.289 COP (kW/kW)
COP 2.215 COP (kW/kW)
Unit Voltage 415.V/50.Hz/3 Phase
Refrigerant Type R134a
Agency Listing No agency listing
Pressure Vessel Code ASME code
A-weighted sound pressure 106 dBA
Model Number R
Evaporator Information
Fluid Properties Flow Rate Construction Features
Fluid Type Water Design Flow 41.81 L/s 1 Pass arrangement,
Number of Passes
insulated
Fluid Temperatures Min Flow 28.10 L/s
0.017610 m2-deg
Evaporator Leaving 5.0 C Fluid Pressure Drop Fouling Factor
C/kW
Evaporator Entering 10.5 C Design PD 31.4 kPa
Saturated evap - ckt 1 4.8 C Min PD 12.2 kPa
Saturated evap - ckt 2 2.3 C Max PD 130 kPa
Condenser Information
Ambient air temp 48.0 C Elevation 0.000 m
Condenser Options Copper tube/Al fin coil Saturated cond temp - ckt 1 62.5 C
Number of Condenser Fans 20.00 Each Saturated cond temp - ckt 2 63.8 C
Fan Motor Power 29.87 kW
Unit Electrical
Unit Voltage 415.V/50.Hz/3 Phase RLA - condenser fan (each) 4.70 A
Total Power 436.2 kW Fan motor power 29.87 kW
Compressor Power 405.6 kW LRA - compressor 1A 385.00 A
RLA - compressor 1A 185.00 A LRA - compressor 2A 385.00 A
Number of condenser fans 20.00 Each RLA - compressor 1B 185.00 A
Wye-delta closed transition LRA - compressor 1B 385.00 A
Compressor starter type
starter
Dual point unit starting current-
695.00 A
RLA - compressor 2A 185.00 A ckt 1
Dual point Max amps- ckt 1 513.00 A Dual point unit starting current-
486.00 A
ckt 2
Dual point Max amps- ckt 2 254.00 A
Physical Information
Dimensions Weights Charge
Length 11810 mm Operating Weight 8810 kg Ckt 1 Charge 198 kg
Width 2245 mm Shipping Weight 8673 kg Ckt 2 Charge 82 kg
Height 2480 mm Oil charge circuit 1 16.00 L
Oil charge circuit 2 8.00 L
Unit Acoustics
Octave Bands 63 125 250 500 1K 2K 4K 8K A-weighted
Sound Power 48 dB 48 dB 59 dB 70 dB 69 dB 63 dB 66 dB 60 dB 106 dBA
2022/11/28 13:04:42 Page 1 of 2
Job Name: NFE 12 B,D CHILLER-5 oct Unit Tag: CRTAG-2, CRTAG-2-1, CRTAG-2-2
Prepared For: Quantity: 3
Sales Office:
Warranty
Standard Warranty
Certified in accordance with the AHRI Water-Cooled Water-Chilling
and Heat Pump Water-Heating Packages Certification Program,
which is based on AHRI Standard 550/590 (I-P) and AHRI Standard
551/591 (SI). Certified units may be found in the AHRI Directory at
www.ahridirectory.org
Trane Select Assist
265
Version Number:
Data Generation Date: 11/28/2022