0% found this document useful (0 votes)
48 views4 pages

Schneider Electric - Acti9-iC40 - A9P54640

This document provides specifications for a miniature circuit-breaker called the Acti9 iC40N. It has a rated current of 40A, is rated for a breaking capacity of 10kA, and conforms to various industry standards. Key features include a thermal-magnetic trip unit, a C curve type, IP20 degree of protection, DIN rail mounting, and packaging information for 1, 12, or 132 unit packages. It also notes the product has a Green Premium label and provides sustainability information.

Uploaded by

naveen204
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
48 views4 pages

Schneider Electric - Acti9-iC40 - A9P54640

This document provides specifications for a miniature circuit-breaker called the Acti9 iC40N. It has a rated current of 40A, is rated for a breaking capacity of 10kA, and conforms to various industry standards. Key features include a thermal-magnetic trip unit, a C curve type, IP20 degree of protection, DIN rail mounting, and packaging information for 1, 12, or 132 unit packages. It also notes the product has a Green Premium label and provides sustainability information.

Uploaded by

naveen204
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Product datasheet

Specifications

Miniature circuit-breaker, Acti9


iC40N, 1P+N, 40 A, C curve, 6000
A (IEC 60898-1), 10 kA (IEC
60947-2)
A9P54640

Main
Range Acti9

Product Name Acti9 iC40

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Or Component Type Miniature circuit-breaker

Device Short Name iC40N

Device Application Distribution

Poles Description 1P + N

Number Of Protected Poles 1

Neutral Position Left

[In] Rated Current 40 A

Network Type AC

Trip Unit Technology Thermal-magnetic

Curve Code C

Breaking Capacity 10 kA Icu at 230 V AC 50/60 Hz conforming to EN/IEC 60947-2


6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1

Suitability For Isolation Yes conforming to EN/IEC 60947-2

Quality Labels IMQ


AENOR
OVE
RCM

Complementary
Network Frequency 50/60 Hz

[Ue] Rated Operational Voltage 230 V AC 50/60 Hz

Magnetic Tripping Limit 5...10 x In conforming to EN/IEC 60898-1


8 x In +/- 20 % conforming to EN/IEC 60947-2

[Ics] Rated Service Breaking 6000 A 100 % x Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Capacity 5 kA 50 % x Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60947-2

Limitation Class 3 conforming to EN/IEC 60898-1

[Ui] Rated Insulation Voltage 400 V AC 50/60 Hz conforming to EN/IEC 60947-2

[Uimp] Rated Impulse Withstand 4 kV conforming to EN/IEC 60947-2


Voltage
Contact Position Indicator Yes

Control Type Toggle

Local Signalling ON/OFF indication


Trip indicator

2 Jan 2024 1
Mounting Mode Clip-on

Mounting Support DIN rail

9 Mm Pitches 2

Height 85 mm

Width 18 mm

Depth 74 mm

Net Weight 120 g

Colour White

Mechanical Durability 20000 cycles

Electrical Durability 10000 cycles

Locking Options Description Padlocking device

Connections - Terminals Tunnel type terminals top or bottom 1…10 mm² flexible
Tunnel type terminals top or bottom 1…16 mm² rigid

Wire Stripping Length 14 mm for top or bottom connection

Tightening Torque 2 N.m top or bottom

Earth-Leakage Protection Separate block

Environment
Standards EN/IEC 60898-1
EN/IEC 60947-2

Product Certifications CE
BV
RINA
DNV

Ip Degree Of Protection IP20 conforming to IEC 60529


IP40 (modular enclosure) conforming to IEC 60529

Pollution Degree 3 conforming to EN/IEC 60947-2

Relative Humidity 95 % at 55 °C

Operating Altitude 2000 m

Ambient Air Temperature For -25…70 °C


Operation
Ambient Air Temperature For -40…85 °C
Storage

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 7.4 cm

Package 1 Width 1.8 cm

Package 1 Length 9.4 cm

Package 1 Weight 121.0 g

Unit Type Of Package 2 BB1

Number Of Units In Package 2 12

Package 2 Height 8.0 cm

Package 2 Width 10.0 cm

Package 2 Length 22.5 cm

2 2 Jan 2024
Package 2 Weight 1.522 kg

Unit Type Of Package 3 S03

Number Of Units In Package 3 132

Package 3 Height 30.0 cm

Package 3 Width 30.0 cm

Package 3 Length 40.0 cm

Package 3 Weight 17.235 kg

2 Jan 2024 3
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Sustainable Packaging Transparency RoHS/REACh

Resource performance

 Sustainable Packaging

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

 Halogen Free Product

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Compliant with Exemptions

China Rohs Regulation China RoHS declaration


Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure Product Environmental Profile

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

Circularity Profile No need of specific recycling operations