I-P A19 Ch6 Indoor Swimming Pools
I-P A19 Ch6 Indoor Swimming Pools
CHAPTER 6
6.1 fungus
Copyright © 2019, ASHRAE This file is licensed to Luiz Bueno ([email protected]). Copyright ASHRAE 2022.
6.2 2019 ASHRAE Handbook—HVAC Applications
• Relative humidity (rh) expresses the moisture content of air as a temperature at indoor temperatures of 82°F db, 84°F db, and 86°F db
percentage of saturation. and relative humidity values from 30 to 60%. An example is shown at
• Specific humidity is the weight of the moisture in the air com- 84°F db and 50% rh, showing that the dew point is 64°F.
pared to the weight of air. The weight is measured in grains, and This example shows that all surfaces inside the pool room must
there are 7000 grains in a pound of air. be kept above the dew-point temperature of 64°F to prevent visible
condensation. Common design practice adds 5°F to this tempera-
A complete understanding of dew point is important. Figure 2 ture as a safety factor.
shows three stages of moisture condensation from the air: The architect’s responsibility is to design wall and ceiling com-
• In Figure 2A, the surface of the glass is clear. This means the glass ponents with this surface temperature in mind, to assist the HVAC
temperature is above the dew-point temperature. design engineer in preventing moisture from forming inside the
structure.
• In Figure 2B, water is starting to form on the surface of the glass,
so the glass temperature is at the dew point. Equation (1) calculates the surface temperature of a structural
component:
• In Figure 2C, the glass surface is below the dew point and con-
densate has formed on the surface. Ts = Ti – [K(1/R)(Ti – To)] (1)
Without proper understanding and control of dew point and con-
densation, moisture can form on the indoor and outdoor surfaces of where
the structure. Figure 3 shows examples of moisture formation and Ts = surface temperature
Ti = indoor space temperature
the results. K = indoor air film coefficient; 0.68 for vertical surface, 0.95 for
In a typical indoor pool, indoor temperature ranges from 78 to horizontal roof or skylight, 0.76 for 45º roof or skylight
86°F db. Figure 4 shows three plotted curves with values derived from R = total R-value of structural component
the psychometric chart. This graph allows plotting the dew-point To = outdoor temperature
Table 1 Typical Activity Factors for Various Pool Table 2 Typical Natatorium Design Conditions
Feature Types
Air Water Relative
Type of Pool Typical Activity Factor (Fa) Type of Pool Temperature, °F Temperature, °F Humidity, %
Baseline (pool unoccupied) 0.5 Recreational 75 to 85 75 to 85 50 to 60
Residential pool 0.5 Therapeutic 80 to 85 85 to 95 50 to 60
Condominium 0.65 Competition 78 to 85 76 to 82 50 to 60
Therapy 0.65 Diving 80 to 85 80 to 90 50 to 60
Hotel 0.8 Elderly swimmers 84 to 90 85 to 90 50 to 60
Public, schools 1.0 Hotel 82 to 85 82 to 86 50 to 60
Whirlpools, spas 1.0 Whirlpool/spa 80 to 85 97 to 104 50 to 60
Wavepools, water slides 1.5 (minimum)
natatoriums. Applying higher activity factors when evaluating the
A evaporation rates at water parks and water features/toys is only one
wp = --- (pw – pa)(95 + 0.425V) (2) component of accounting for this evaporation. Currently the design
Y
professional must rely on experience and professional judgment
where when calculating the evaporation in water parks and from the water
wp = evaporation of water, lb/h features/toys.
A = area of pool surface, ft2 It is recommended that the dehumidification load generated by
Y = latent heat required to change water to vapor at surface water each water feature be calculated individually. The water toys’ man-
temperature, Btu/lb ufacturers should be contacted to provide specifications related to
pw = saturation vapor pressure taken at surface water temperature, in. the pattern and size of the sheet of water that is generated by each
Hg
pa = saturation pressure at room air dew point, in. Hg
water feature/toy to allow for proper load determination. The wet
V = air velocity over water surface, fpm area created by the water toy/feature must be included as wet deck
when calculating the ventilation air required for the space as well as
Units for the constant 95 are Btu/(h·ft2 ·in. Hg). Units for the the wetted surface for the evaporation load. Because of the concen-
constant 0.425 are Btu· min/(h·ft3 ·in. Hg). trated nature of the loads in these facilities, it is recommended that
Equation (2) may be modified by multiplying it by an activity more supply air and outdoor air be used in these facilities compared
factor Fa to alter the estimate of evaporation rate based on the level to what is recommended for traditional pools.
of activity supported. For Y values of about 1000 Btu/lb and V values
ranging from 10 to 30 fpm, Equation (2) can be reduced to Ventilation Requirements
wp = 0.1A(pw – pa)Fa (3) Air Quality. Outdoor air ventilation rates prescribed by ASH-
RAE Standard 62.1 are intended to provide acceptable air quality
Table 1 lists activity factors that should be applied to the areas of conditions for the average pool (where chlorine is used for primary
specific features, and not to the entire wetted area. disinfection). The ventilation requirement may be excessive for pri-
The effectiveness of controlling the natatorium environment vate pools and installations with low use, and may also prove inad-
depends on correct estimation of water evaporation rates. Applying equate for high-occupancy public or water park installations.
the correct activity factors is extremely important in determining
Air quality problems in pools and spas are often caused by water
water evaporation rates. The difference in peak evaporation rates
quality problems, so simply increasing ventilation rates may prove
between private pools and active public pools of comparable size
both expensive and ineffective. Water quality conditions are a direct
may be more than 100%.
function of pool use and the type and effectiveness of water disin-
Actual operating temperatures and relative humidity conditions
fection used.
should be established before design. How the area will be used usu-
ally dictates design (Table 2). It is recommended that the ASHRAE climate data included with
Air temperatures in public and institutional pools are recom- Chapter 14 of the 2017 ASHRAE Handbook—Fundamentals (full
mended to be maintained 2 to 4°F above the water temperature (but data are in the CD and Handbook Online versions of the chapter) be
not above the comfort threshold of 86°F) for energy conservation used when calculating the effects of ventilation air on the natato-
through reduced evaporation and to avoid chill effects on swimmers. rium’s latent load, as mentioned in ASHRAE Standard 62.1.
Competition pools that host swim meets have two distinct oper- Because indoor pools usually have high ceilings, temperature
ating profiles: (1) swim meets and (2) normal occupancy. It is rec- stratification and stack effect (see Chapter 16 of the 2017 ASHRAE
ommended that both be fully modeled to evaluate the facility’s Handbook—Fundamentals) can have a detrimental effect on indoor
needs. Although swim meets tend to be infrequent, the loads during air quality. Careful duct layout is necessary to ensure that the space
meets are often considerably higher than during normal operations. receives proper air changes and homogeneous air quality through-
To model the swim meet load accurately, it is recommended that the out. Some air movement at the deck and pool water level is essential
designer know the number of spectators, number of swimmers on to ensure acceptable air quality. Complaints from swimmers indi-
the deck, and operating conditions required during the meets. The cate that the greatest chloramine (see the section on Pool Water
operator may request a peak relative humidity of 55%, which has a Chemistry) concentrations occur at the water surface. Children are
significant effect on total loads. A system designed for swim meet especially vulnerable to the ill effects of chloramine inhalation.
loads should also be designed to operate for considerable portions of Pool and spa areas should be maintained at a negative pressure of
the year at part loads. Depending on the layout of the space and loca- 0.05 to 0.15 in. of water relative to the outdoors and adjacent areas of
tion of the spectator gallery, it might be beneficial to provide a sep- the building to prevent moisture and chloramine odor migration.
arate microclimate to that area, with a separate dedicated unit. Active methods of pressure control may prove more effective than
Water parks and water feature (slides, spray cannons, arches, static balancing and may be necessary where outdoor air is used as a
etc.) loads are not fully covered by this chapter. Use caution when part of an active humidity control strategy. Openings from the pool to
evaluating the evaporation from water features/toys installed in other areas should be minimized and controlled. Passageways should
be equipped with doors with automatic closers and sweeps to inhibit that incoming ventilation air reaches the breathing zone, as rec-
migration of moisture and air. ommended in ASHRAE Standard 62.1.
Exhaust air from pools is rich in moisture and may contain high • Exhaust air inlets should be located to maximize capture effec-
levels of corrosive chloramine compounds. Exhaust air intake grilles tiveness and minimize recirculation of chloramines. Exhausting
should be located as close as possible to the warmest body of water from directly above whirlpools is also desirable. Exhaust air
in the facility. Warmer and more agitated waters offgas chemicals at should be taken directly to the outdoors, through heat recovery
higher rates compared to traditional pools. This also allows body oils devices when provided.
to become airborne. Ideally, these pollutants should be removed from • Duct materials and hardware must be resistant to chemical corro-
close to the source before they have a chance to diffuse and nega- sion from the pool atmosphere. Stainless steels, even the 316 series,
tively affect air quality. Installations with intakes directly above are readily attacked by chlorides and are prone to pitting. They
whirlpools have resulted in the best air quality. require treatment to adequately perform in a natatorium environ-
Air Delivery Rates. Most codes require a minimum of six air ment. Galvanized steel and aluminum sheet metal may be used for
changes per hour, except where mechanical cooling is used. This exposed duct systems. If galvanized duct is used, steps should be
rate may prove inadequate for some occupancy and use. taken to adequately protect the metal from corrosion. It is recom-
Where mechanical dehumidification is provided, air delivery mended that, at a minimum, the galvanized ducts be properly pre-
rates should be established to maintain appropriate conditions of pared and painted with epoxy-based or other durable paint suitable
temperature and humidity. The following rates are typically desired: to protect metal surfaces in a pool environment. Note that galvan-
nealed ductwork is easier to weld and paint than hot-dip galva-
Pools areas 4 to 6 air changes per hour nized, but galvannealed is more susceptible to corrosion if left
Spectator areas 6 to 8 air changes per hour bare. Certain types of fabric duct (airtight) with appropriate grilles
Therapeutic pools 4 to 6 air changes per hour sewn in are also a good choice. Buried ductwork should be con-
structed from nonmetallic fiberglass-reinforced or PVC materials
Outdoor air delivery rates may be constant or variable, depend- because of the more demanding environment. Proper means of
ing on design. Minimum rates, however, must adequately dilute water drainage in the duct must be considered when ductwork is
contaminants generated by pool water and must maintain accept- buried.
able ventilation for occupancy. • Grilles, registers, and diffusers should be constructed from alumi-
Where a minimum outdoor air ventilation rate is established to num. They should be selected for low static pressure loss and for
protect against condensation in a building’s structural elements, the appropriate throws for proper air distribution.
rates are typically used for 100% outdoor air systems. These rates • Filtration should be selected to provide 45 to 65% efficiencies (as
usually result in excessive humidity levels under most operating defined in ASHRAE Standard 52.1) and be installed in locations
conditions and are generally not adequate to produce acceptable in- selected to prevent condensation in the filter bank. Filter media
door air quality, especially in public facilities subject to heavy use. and support materials should be resistant to moisture degradation.
In colder/drier climates, greater amounts of outdoor air may de- • Fiberglass duct liner should not be used. Where condensation
crease humidity levels below the recommended 40 to 60% range. may occur, the insulation must be applied to the duct exterior.
This increases evaporation, adds to costs for makeup water and • Air systems should be designed for noise levels listed in Table 1
chemicals, and may make it difficult to maintain the proper water of Chapter 48 (NC 45 to 50); however the room wall, floor, and
chemistry. ceiling surfaces should be evaluated for their reverberation times
and speech intelligibility.
Air Distribution Effectiveness and Duct Design
Proper duct design and installation in a natatorium is critical. Envelope Design
Failure to effectively deliver air where needed will result in air An indoor pool is a special-application structure and requires
quality problems, condensation, stratification, and poor equipment care to ensure the entire structure is suitable for a high-dew-point
performance. Ductwork that fails to deliver airflow into the breath- application. There must be
ing zone at the pool deck level and water surface, for example, will • Enough insulation that no exterior wall or roof surface ever falls
lead to air quality problems in those areas. The following duct con- below the space dew-point temperature in cold weather.
struction practices apply to indoor pools: • Effective vapor migration protections to ensure moisture from the
• Deliver air into the breathing zone at the deck. ASHRAE Stan- space is prevented from migrating into any build sections (walls,
dard 62.1 defines the breathing zone as the area between 3 and 72 roofs, joints where they meet). A vapor retarder analysis (as in
in. from the floor level. The best quality air in the facility is what Figure 10 in Chapter 27 of the 2017 ASHRAE Handbook—Fun-
is delivered from the supply duct. That air must get to where the damentals) should be prepared. Failure to install an effective
patrons are to ensure they are breathing the best possible quality vapor retarder results in condensation forming in the structure,
air. and potentially serious envelope damage.
• Supply air should be directed against envelope surfaces prone to • Complete elimination of thermal bridging. Window and door
condensation (glass and doors). Air movement over the pool water frames must be thermally broken.
surface must not exceed 30 fpm (as per the evaporation rate wp in Figure 7 shows where the vapor retarder should be located in a
Equation [2]). If air movement over the water surface is increased wall for an indoor pool application. The vapor retarder must be on
from the standard 30 fpm to 125 fpm, the evaporation will increase the warm side of the dew point. The entire pool enclosure (walls and
by approximately 30%. Air that moves across the water surface is ceilings) must have a vapor retarder in the correct location. Where
best handled by a source-capture-type exhaust system. Evapora- walls join the roof or floor meet, it is especially vital to ensure there
tion from the water surface should be evaluated using Equation (2). is no breach in the vapor barrier.
• Return air inlets should be located to recover warm, humid air and A properly located and installed vapor retarder is the only way to
return it to the ventilation system for treatment, to prevent supply protect a structure from vapor migration and the ensuing moisture
air from short-circuiting and to minimize recirculation of damage.
chloramines. It is recommended that return air inlets be located Condensation forms on exterior windows when the outdoor
both high and low. This helps prevent air stratification and ensure temperature drops below the pool room’s dew point (typically
between 62 and 70°F). The design goal is to keep the surface tem- as combined chlorine. Adding chemicals to pool water increases
perature of the glass and the window frames at least 3 to 5°F above total contaminant levels. In high-occupancy pools, water contami-
the pool room’s dew point. Windows must allow unobstructed air nant levels can double in a single day of operation.
movement on indoor surfaces, and thermal break frames should be Chlorine’s efficiency at reducing ammonia is affected by several
used to raise the window’s indoor temperature. Avoid recessed factors, including water temperature, water pH, total chlorine con-
windows and protruding window frames. Skylights are especially
centration, and level of dissolved solids in the water. Because of
vulnerable and require attention to control condensation. Wall and
their higher operating temperature and higher ratio of occupancy
roof vapor retarder designs should be carefully reviewed, espe-
cially at wall-to-wall and wall-to-roof junctures and at window, per unit water volume, spas produce greater quantities of air con-
door, skylight, and duct penetrations. taminants than pools.
The following measures have demonstrated a potential to reduce
Condensation Control chloramine concentrations in the air and water:
Exterior windows and doors are primary condensation concerns,
• Ozonation. In low concentrations, ozone can substantially reduce
so it is extremely important that supply air is focused there. Warm
the concentration of combined chlorine in the water. In high con-
air from the dehumidifier keeps the window surface temperature
above the dew-point temperature, which ensures that windows and centrations, ozone can replace chlorine as the primary disinfection
exterior doors remain condensation free. process; however, ozone cannot remain at sufficient residual levels
in the water to maintain a latent biocidal effect, so chlorine must be
Exterior windows, exterior surfaces, and other condensation-
prone areas should be blanketed with supply air (Figure 8). A good kept as a residual process at concentrations of 0.5 to 1.5 ppm.
rule of thumb is 3 to 5 cfm per square foot of exterior glass. Select • Water exchange rates. High concentrations of dissolved solids
grilles, registers, and diffusers that deliver the required throw dis- in water directly contribute to high combined chlorine (chlora-
tance, and the specified volumetric flow rating. mine) levels. Adequate water exchange rates are necessary to pre-
vent build-up of biological wastes and their oxidized components
Pool Water Chemistry in pool and spa water. Conductivity measurement is an effective
Failure to maintain proper chemistry in the pool water causes method to control the exchange rate of water in pools and spas to
serious air quality problems and deterioration of mechanical effectively maintain water quality and minimize water use. In
systems and building components. Water treatment equipment high-occupancy pools, heat recovery may prove useful in reduc-
and chemicals should be located in a separate, dedicated, well- ing water heating energy requirements.
ventilated space that is under negative pressure. Pool water treat- • Medium-pressure UV. Using medium-pressure UV lamps for
ment consists of primary disinfection, pH control, water filtration water treatment can reduce the amount of chloramines, and
and purging, and water heating. For further information, see Kow- should be evaluated during design. Medium-pressure UV can
alsky (1990). replace chlorine as the primary disinfection process; however, it
Air quality problems are usually caused by the reaction of chlo- does not remain at sufficient residual levels in the water to main-
rine with biological wastes, and particularly with ammonia, which is tain a latent biocidal effect. Consequently, chlorine is required as
a by-product of the breakdown of urine and perspiration. Chlorine a residual process at concentrations of 0.5 to 1.5 ppm.
reacts with these wastes, creating chloramines (monochloramine,
dichloramine, and nitrogen trichloride) that are commonly measured • Swimmer showers. Requiring each swimmer to shower before
entering the water helps reduce the amount of body oils released
into the water, thereby reducing the amount of chloramines gen-
erated.
• Bathroom breaks. Facilities that require all swimmers to exit the
pool every hour and visit the restrooms dramatically reduce the
amount of urine introduced into the pool.
Fig. 7 Vapor Retarder Location for Indoor Pool Fig. 8 Supply Air Blanketing of Condensation-Prone Areas
(Courtesy Seresco Technologies, Inc. 2013) (Courtesy Seresco Technologies, Inc. 2013)
Energy Considerations • With design team and owner/operators, identify (1) indoor space
temperature, (2) water temperature, and (3) design relative hu-
Natatoriums can be a major energy burden on facilities, so they
midity levels for both summer and winter.
represent a significant opportunity for energy conservation and
• Obtain minimum R and U values from architect to determine min-
recovery. ASHRAE Standard 90.1 offers some recommendations.
imum surface temperature for condensation.
Several design solutions are possible using both dehumidification
and ventilation strategies. When evaluating a system, the seasonal • Include a proper vapor retarder and install it correctly with no
space conditions and energy consumed by all elements should be breaks.
considered, including primary heating and cooling systems, fan • Determine correct amount of ventilation air required for proper
motors, water heaters, and pumps. IAQ and to meet local code requirements.
• Determine correct amount of exhaust air to provide negative
Operating conditions factor significantly in the total energy
building pressure.
requirements of a natatorium. Although occupant comfort is a pri-
mary concern, the effects of low space temperatures and relative • Evaluate whether a source capture exhaust system is needed.
humidity levels below 50% (especially in winter) should be dis- • Evaluate outdoor air/exhaust air energy recovery systems.
cussed with the owner/operator: • Use correct dehumidification weather data to determine moisture
load from the ventilation air.
• Lower room air temperature or lower relative humidity increases • Total all moisture/latent loads from (1) people, (2) ventilation air,
evaporation from the pools, thus increasing dehumidification and (3) water surface.
requirements and increasing pool water heating costs • Total all sensible loads from (1) building envelope, (2) people, (3)
• Warmer water temperatures increase evaporation from the pools, ventilation air, (4) lighting, and (5) other sources.
thus increasing the dehumidification requirements and increasing • Select equipment to meet both sensible and latent peak loads.
pool water heating costs • Design air distribution system to deliver air into the breathing
zone and prevent air stratification and visible condensation.
It is recommended to model the space on both a summer and win- • Properly commission equipment and building.
ter design day to establish whether higher summertime indoor rela-
• Include a quarterly equipment maintenance contract as part of
tive humidity level is beneficial to reducing equipment size and
operating expense.
operating costs.
Because these facilities require considerable air movement and REFERENCES
the supply fans operate 24/7/365, fans and equipment that uses less
fan energy lead to considerable energy savings over the equipment ASHRAE members can access ASHRAE Journal articles and
life. ASHRAE research project final reports at technologyportal.ashrae
These facilities require outdoor and exhaust air. This gives the .org. Articles and reports are also available for purchase by nonmem-
opportunity for energy recovery from the exhaust air to preheat out- bers in the online ASHRAE Bookstore at www.ashrae.org/bookstore.
door air. The economics of a heat recovery decision should be ASHRAE. 2016. Ventilation for acceptable indoor air quality. ANSI/
always reviewed, regardless of the facility location: these facilities ASHRAE Standard 62.1-2016.
have warm indoor conditions and show good paybacks for energy ASHRAE. 2016. Energy standard for buildings except low-rise residential
recovery, even in warmer climates. A detailed evaluation of the heat buildings. ANSI/ASHRAE Standard 90.1-2016.
exchange process must be done to ensure no condensation develops Kowalsky, L., ed. 1990. Pool/spa operators handbook. National Swimming
in the energy recovery device so, in cold climates, ice does not Pool Foundation, Merrick, NY.
develop and damage equipment or develop an imbalance of airflow. Seresco. 2013. Natatorium design guide. Seresco, Ottawa, ON. seresco.net
/engineers/indoor-pool-design/condensation-control.php.
Compressorized systems can optionally heat pool water with Smith, C.C., R.W. Jones, and G.O.G. Löf. 1993. Energy requirements and
compressor waste heat. The economics of this option should always potential savings for heated indoor swimming pools. ASHRAE Transac-
be reviewed: the heating contributions can be significant and have a tions 99(2):864-874.
dramatic return on investment (ROI).
Natatoriums with fixed outdoor air ventilation rates without BIBLIOGRAPHY
dehumidification generally have seasonally fluctuating space tem-
ACCA. 2017. HVAC design for swimming pools and spas. ANSI/ACCA 10
perature and humidity levels. Systems designed to provide mini- Manual SPS-2011 (RA 2017). Air Conditioning Contractors of America,
mum ventilation rates without dehumidification are unable to Arlington, VA.
maintain relative humidity conditions within prescribed limits, and ASHRAE. 2016. Safety standard for refrigeration systems. ANSI/ASHRAE
may facilitate mold and mildew growth and be unable to provide Standard 15-2016.
acceptable IAQ. Peak dehumidification loads vary with activity ASHRAE. 2016. Designation and safety classification of refrigerants.
levels and during the cooling season, when ventilation air becomes ANSI/ASHRAE Standard 34-2016.
an additional dehumidification load to the space. CDC. 2018. Model aquatic health code (MAHC): An all-inclusive model
public swimming pool and spa code. Centers for Disease Control and
Design Checklist Prevention, Atlanta. www.cdc.gov/mahc/editions/current.html.
Harriman, L., G. Brundrett, and R. Kittler. 2001. Humidity control design
The following items should be addressed when evaluating and guide for commercial and institutional buildings, Ch. 27: Swimming
designing a system for an indoor pool climate control system. This pools. ASHRAE.
list is a minimum, and additional items can be added by the design Kittler, R. 1989. Indoor natatorium design and energy recycling. ASHRAE
team. Transactions 95(1):521-526. Paper CH-89-02-3.
HOSPITALITY
Load Characteristics....................................................................................................................... 7.1
Design Concepts and Criteria......................................................................................................... 7.1
Systems ............................................................................................................................................ 7.1
Hotels and Motels ........................................................................................................................... 7.3
Dormitories ..................................................................................................................................... 7.8
Multiple-Use Complexes ................................................................................................................. 7.8
7.1
Copyright © 2019, ASHRAE This file is licensed to Luiz Bueno ([email protected]). Copyright ASHRAE 2022.