Protection Schemes For Electrical Power System
Protection Schemes For Electrical Power System
System
Electrical Power System is a highly invested area. The more reliable electricity we want, the
more is need to protect it. Protection is essential to keep equipment and personnel safe from any
kind of damage caused by an electrical unbalance or fault condition. Read more as we cover the
objectives of power system protection, different protection devices and schemes to provide
complete safety to an electrical power system.
Protection devices perform their purpose by keeping a faulty section isolated from the remaining
healthy system to make it work without any disturbances. The function of a protection system is
not to prevent faults as its name suggests, rather it minimizes repair costs as it senses fault
because it only acts after a fault occurs. Different protection schemes are explained in this article.
But first, we need to look at why protecting the power system is crucial?
• Only the faulty part of the system is completely isolated within a minimum time so that
the remaining system operates normally.
• In the case of normal conditions, there should be no nuisance tripping.
To isolate the system from the faulty section, fuses and circuit breakers are used and to detect
fault relays are used. In low voltage systems breakers perform both functions of detecting and
isolating the fault.
Following six categories of protection zones are possible in a system, we apply here a concept of
selective coordination.
• Generators and generator–transformer units
• Transformers
• Buses
• Lines (transmission, sub-transmission, and distribution)
• Utilization equipment (motors, static loads, or other)
• Capacitor or reactor banks (when separately protected).
• Fuse
• Instrument Transformer
• Relay
• Circuit Breaker
• Batteries
• ESD Protection Device
• Surge Protection Device
Fuse
Instrument Transformer
Accurate protection cannot be achieved without
properly measuring the normal and abnormal
conditions of a system. Instrument transformers
work as a transducer in electrical systems.
The voltage transformer steps down the high voltage of the line to a level safe enough for the
relaying system (pressure coil of the relay) and personnel to handle. A PT primary is connected
in parallel at the point where a measurement is desired.
Relay
Check out Power System Protection Fundamentals Course in which we briefly discussed
"Types of protective relays & design requirements". We started with the introduction to the
design and working mechanism of a Relay, based on a protection system. Then moved forward
to the discussion on the factors that need to consider when designing a relay-based protection
scheme. Then we introduced Overcurrent Relays, Directional Relays, Distance or Impedance
Relays & Reverse Power Flow Relays in detail.
Circuit Breaker
The opening of faulty circuits requires some time. However, the circuit breakers, which are used
to isolate the faulty circuits, can carry these fault currents until the fault currents are cleared.
Circuit breakers can be classified according to different design considerations like arc quenching
media, operation mechanism, voltage levels, etc.
We have written another blog on Selecting the Right Circuit Breaker and Its Type. Read it to
understand how circuit breakers work, what are their different types are and how to choose a
suitable breaker according to your requirements.
Batteries
The other component which is crucial in a protective system is batteries that are used to ensure
uninterrupted power to relays and breaker coils. The operation of relays and breakers require
power sources, which shall not be affected by faults.
Protection Schemes
There are several protection schemes invented along the line as protection engineers face new
challenges with the advancement in power systems. Here, we will discuss the most basic ones.
The source impedance depends upon the number of generating units that are in service at a given
time and keeps changing from time to time. So, the setpoint for the distinction of fault current
magnitude from the normal current as well as the operating time of over-current protection keep
changing from fault to fault, and time to time. This has led protection engineers to think of other
principles.
Instantaneous means no intentional time delay. The operating time of an instantaneous relay is in
milliseconds. Such a relay has only the pick-up setting and does not have any time setting.
A definite time overcurrent relay can be adjusted to issue a trip output at an adjustable definite
amount of time after it picks up. Thus, it has a pick-up adjustment and a time-setting adjustment.
Inverse time characteristic corresponds with the requirement that the more severe a fault is, the
faster it should be cleared to avoid damage to the apparatus. Following inverse time
characteristics have been standardized.
Differential protection is based on the assertion that the current leaving a protected section must
be equal to that entering it. Any difference between the two endpoints of a single section
indicates a fault. Thus, we can compare the two currents either their phase or magnitude or both.
This method of detecting faults is very popular if both ends of an apparatus are physically very
close to each other. It should remain steady in case of an external fault or through-fault which
will be outside of its protective zone and should only trip if the fault is internal. The ability of
this protection to discriminate between internal and external faults define its stability. Though, it
is impracticable to apply this scheme to a transmission line because the ends are at a great
distance, and it is not feasible to equate information.
Balanced Circulating Current System, External Fault (stable)
A distance protection scheme relates the voltage with the current at the same end. This scheme
computes the impedance between the protection location and the fault point. Then it compares it
with a pre-set value to make the trip decision.
Since the impedance of a transmission line can be directly proportional to the distance of the
fault in a line due to the simple series model, it helps in identifying fault location. This type of
protection is known as distance protection or under-impedance protection. In practice, the word
'under' is dropped and now it is simply called impedance protection.
4. Directional Protection Scheme
Directional protection scheme becomes functional in the case of a double-end feed system or
parallel lines or a ring main system, where a fault gets fed from both sides. From the selection
perspective, this type of protection is sensitive enough to detect the direction of the fault power
flow.
There are other situations where it becomes necessary to use a directional scheme to supervise
overcurrent schemes. Since directional protection units are much more costly and need the
provision of power transformers, they should be used only when necessarily needed.
There are many protection devices or components available, which are installed along with the
equipment so as to ensure safety of not only the equipment but the working personnel as well.
Also, we have various protection schemes and each of them is suitable for a particular
application and every type has some advantages over the other. Altogether, the different devices
and schemes are to make the electrical power system completely reliable and secure.