Maf 567 HBS DX Unit - 1
Maf 567 HBS DX Unit - 1
Form detail
Forms
Status Closed
Supporting information
Material Approval Form
1. Placeholder title
MAF XXXX/YYYY
MAF 567/2024
BHSARP-00-ZZZ-ZZ-XX-MAF-70XXXX
BHSARP-00-ZZZ-ZZ-XX-MAF-700567
1.3 Date:
Created by Fida Sulaiman with Autodesk® Construction Cloud™ on Mar 5, 2024 at 9:27 AM UTC+08:00 Page 1 of 6
BHS Asset Replacement Programme Form detail report
DD/MM/YYYY
DD/MM/YYYY
BHS/HLC
MEC/ELC
ARC/ID
STRUCT
IT INFRA
Other
1.5 Other
1.8 Specification
Appendix 4.2(1.1)-Air cooled split unit system
Material Description
DX UNITS
Created by Fida Sulaiman with Autodesk® Construction Cloud™ on Mar 5, 2024 at 9:27 AM UTC+08:00 Page 2 of 6
BHS Asset Replacement Programme Form detail report
Alternative Material
Non-specified Material
1st Submission
Re-submission
1.12 Attachment:
Material Certificate/No.
Test Report
Warranties provided
Material Origin
Others
Created by Fida Sulaiman with Autodesk® Construction Cloud™ on Mar 5, 2024 at 9:27 AM UTC+08:00 Page 3 of 6
BHS Asset Replacement Programme Form detail report
2. Submission
Turnkey Contractor’s Consultant Review and Recommendation
2.1 Comment:
Can be recommended for use.
2.2 Recommendation:
Recommended For Use
3. Technical Review
AECOM Technical Committee Review
3.1 Comment:
No comment.
3.2 Recommendation:
Recommended For Use
Created by Fida Sulaiman with Autodesk® Construction Cloud™ on Mar 5, 2024 at 9:27 AM UTC+08:00 Page 4 of 6
BHS Asset Replacement Programme Form detail report
4. Approval Committee
CO KLIA Material Approval Committee
4.1 Comments:
No objection
DD/MM/YYYY
4.1 Signature
Committee Member
4.1 Signature
Committee Member
Created by Fida Sulaiman with Autodesk® Construction Cloud™ on Mar 5, 2024 at 9:27 AM UTC+08:00 Page 5 of 6
BHS Asset Replacement Programme Form detail report
4.1 Signature
Chairman (PD/PDR)
References
Files (19)
Created by Fida Sulaiman with Autodesk® Construction Cloud™ on Mar 5, 2024 at 9:27 AM UTC+08:00 Page 6 of 6
VRV Indoor Units
Middle-High Static Pressure Duct Type
FXMQ-PA
Cleanliness
Middle and high static pressure allows for exible duct design Silver ion anti-bacterial drain pan
Prevents the growth of slime, bacteria, and mould that cause odours and clogging.
*Drain pan should be changed once every two to three years.
Indoor Units
Motor replacement, Damper
replacement, etc.
rpm 7 System
operation MODEL FXMQ63PAVE FXMQ80PAVE FXMQ100PAVE FXMQ125PAVE FXMQ140PAVE
Field setting Innovating Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
rpm 8
Design Installation
with “air ow rate Function! Btu/h 24,200 30,700 38,200 47,800 54,600
auto adjustment function” Cooling capacity
by remote controller
kW 7.1 9.0 11.2 14.0 16.0
Power consumption kW 0.138 *1 0.185 *1 0.215 *1 0.284 *1 0.405 *1
<Mechanism> Rated air ow Air ow Casing Galvanised steel plate
1. During eld setting, power input of DC fan is detected.
2. External static pressure is estimated from power input of DC fan because PCB of Notes: ”Air ow rate auto adjustment function” can be adjusted within ±10% of rated m3/min 19.5/17.5/16 25/22.5/20 32/27/23 39/33/28 46/39/32
Air ow rate (HH/H/L)
FXMQ-PA has table of external static pressure vs. power input of DC fan. air ow. (Refer to Engineering Data Book for details) cfm 688/618/565 883/794/706 1,130/953/812 1,377/1,165/988 1,624/1,377/1,130
3. Actual duct resistance is calculated according to 1 and 2. ”Air ow rate auto adjustment function” should be used at eld setting only.
4. Fan speed is automatically adjusted to produce rated air ow. External static pressure Pa 50-200 (100) * 2
50-140 (100) *2
Sound level (HH/H/L) dB(A) 42/40/38 43/41/39 44/42/40 46/45/43
• All models are only 300 mm in height and the weight of the FXMQ40-140PA has been reduced. Dimensions (H×W×D) mm 300×1,000×700 300×1,400×700
• Drain pump is equipped as standard accessory with 700 mm lift. Machine weight kg 35 45 46
Liquid (Flare) 9.5
Piping
Gas (Flare) mm 15.9
connections
Comfort Drain
• Control of the air ow rate can be selected from 3-step control and Auto. Auto air ow rate control can • Cooling: Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Height difference: 0 m.
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
be selected with wired remote controller. • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
• Low operation sound level: down to 29 dB(A) *1: Power consumption values are based on conditions of rated external static pressure.
*2: External static pressure can be modi ed using a remote controller that offers seven (FXMQ20-32PA), thirteen (FXMQ40PA), fourteen (FXMQ50-125PA) or
ten (FXMQ140PA) levels of control.
These values indicate the lowest and highest possible static pressures. The rated static pressure is 50 Pa for FXMQ20-32PA and 100 Pa for FXMQ40-140PA.
Energy saving
• DC fan motor is used to realise energy-saving operation. Separate drain pipe and inspection opening
Easy maintenance
Inspection and cleaning is facilitated by separating the drain pipe
Drain pan maintenance
149
and inspection opening and by the drain pan maintenance check hole. check hole 150
VRV S High Seasonal E ciency Series
Outdoor Units
VRV S High Seasonal E ciency Series
HP 4 5 6 7 8 9
Power supply 1-phase, 220-240 V/220-230 V, 50/60 Hz 3-phase, 380-415 V/380 V, 50/60 Hz Maximum number of connectable indoor units 6 8 9 11 13 14
Btu/h 38,200 47,800 54,600 68,200 76,400 81,900 Note: Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit.
Cooling capacity
kW 11.2 14.0 16.0 20.0 22.4 24.0
Type R-410A
Refrigerant
Charge kg 4.0 4.2 5.4
57 58
Equipment Tabulation
Project : HBS CENTRALIZED SCREENING LEVEL 2 & 3
System : VRV + Inverter R32
Date : 2ND JAN 2024
Remark : * Select wire size based on MCA
* Select circuit breaker based on MFA
Requirement DAIKIN Selection DAIKIN Selection
FCU CU
HBS ROOM - ZONE 1 50,809 14.89 24.0 17.8 1 30 DX-1 24.0 17.8 VRV S FXMQ140PAVE C.DUCTED 53,227 53,227 1,624 50-140(100) 47.0 300x1400x700 3.40 16 0.405 240/1/50 1 CU-1 RSUQ7AYM 68,200 50,000 115 870x1100x460 18.9 25 5.46 415/3/50 1
HBS ROOM - ZONE 2 46,717 13.69 24.0 17.8 2 35 DX-2,3 24.0 17.8 VRV S FXMQ140PAVE C.DUCTED 53,227 53,227 1,624 50-140(100) 47.0 300x1400x700 3.40 16 0.405 240/1/50 2 CU-2,3 RSUQ7AYM 68,200 49,200 115 870x1100x460 18.9 25 5.46 415/3/50 2
EQUIPMENT ROOM 21,824 6.40 22.0 16.0 2 30 DX-4, 5 22.0 16.0 Split FCF100CVM C.CASSETTE 32,000 28,800 1,218 Free Blow 24.0 298X840X840 Power take from CU 240/1/50 2 CU-4,5 RZF100CVM - - 48.0 695X930X350 27.4 32.0 2.97 240/1/50 2
5 5 5
SUMMARY
FXMQ140PAVE - 3
- RSUQ7AYM 3
FCF100CVM RZF100CVM 2
DMS502B51 1
TOTAL :
DX-1 / CU-1
RSUQ7AYM
Capacity ratio for this system is 80%, from cooling capacity table on the left, via
interpolation method
Cooling Cap @ 80% at 16.0⁰C wet bulb : 14.7kW
Cooling Cap @ 80% at 18.0⁰C wet bulb : 15.6kW
15.51 kW x 0.945
Corrected capacity = 14.66 kW
= 50,000 btu/hr
Pipe length 30m
0.945
DX-2,3 / CU-2,3
RSUQ7AYM
Capacity ratio for this system is 80%, from cooling capacity table on the left, via
interpolation method
Cooling Cap @ 80% at 16.0⁰C wet bulb : 14.7kW
Cooling Cap @ 80% at 18.0⁰C wet bulb : 15.6kW
15.51 kW x 0.93
Corrected capacity = 14.42 kW
= 49,200 btu/hr
Pipe length 35m
0.93
DX-4, 5 / CU-4, 5
FCF100CVM / RZF100CVM
10%
9.4 kW x 0.9
Corrected capacity = 8.46 kW
Pipe length 30m = 28,800 btu/hr
90%
SPECIFICATIONS
39
KLIA BHS - CCR Room VRV Clarification
has the rights to use the MyHIJAU Mark on the following item:
Compliance Category:
Certification Scheme:
T : 603-8921 0800
F : 603-8921 0801
www.myhijau.my This certificate is granted subject to the Terms and Condition of usage of MyHIJAU Mark certificate and label.
www.greentechmalaysia.my
Certificate No. : MyHP00040/21
Issue Date : 01-02-2021
Expiry Date : 26-01-2024
SCHEDULE PAGE