Product datasheet
Specifications
Thermal overload relay, TeSys
LRD, 9...13 A, class 10A
LRD16
Main
Range TeSys
TeSys Deca
Product Name TeSys LRD
TeSys Deca
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Or Component Type Differential thermal overload relay
Device Short Name LRD
Relay Application Motor protection
Product Compatibility LC1D18
LC1D38
LC1D32
LC1D12
LC1D25
Network Type DC
AC
Thermal Overload Class Class 10A conforming to IEC 60947-4-1
Thermal Protection Adjustment 9…13 A
Range
[Ui] Rated Insulation Voltage Power circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL
Power circuit: 690 V conforming to IEC 60947-4-1
Complementary
Network Frequency 0...400 Hz
Mounting Support Plate, with specific accessories
Rail, with specific accessories
Under contactor
Tripping Threshold 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Auxiliary Contact Composition 1 NO + 1 NC
[Ith] Conventional Free Air 5 A for signalling circuit
Thermal Current
Permissible Current 1.5 A at 240 V AC-15 for signalling circuit
0.1 A at 250 V DC-13 for signalling circuit
[Ue] Rated Operational Voltage 690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
Associated Fuse Rating 4 A gG for signalling circuit
4 A BS for signalling circuit
[Uimp] Rated Impulse Withstand 6 kV
Voltage
Phase Failure Sensitivity Tripping current 130 % of Ir on two phase, the last one at 0
Control Type Red push-button: stop
Blue push-button: reset
Temperature Compensation -20…60 °C
Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.
Mar 18, 2024 1
Connections - Terminals Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable
end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid
Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm² flexible without cable
end
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm² flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² solid
Tightening Torque Control circuit: 1.7 N.m - on screw clamp terminals
Power circuit: 1.7 N.m - on screw clamp terminals
Height 66 mm
Width 45 mm
Depth 70 mm
Net Weight 0.124 kg
Environment
Climatic Withstand conforming to IACS E10
Ip Degree Of Protection IP20 conforming to IEC 60529
Ambient Air Temperature For -20…60 °C without derating conforming to IEC 60947-4-1
Operation
Ambient Air Temperature For -60…70 °C
Storage
Flame Retardance V1 conforming to UL 94
Mechanical Robustness Vibrations: 6 Gn conforming to IEC 60068-2-6
Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
Dielectric Strength 1.89 kV at 50 Hz conforming to IEC 60947-1
Standards EN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4
GB/T 14048.5
EN 50495
Product Certifications IEC
UL
CSA
CCC
EAC
BV
RINA
DNV-GL
LROS (Lloyds register of shipping)
ATEX INERIS
UKCA
Packing Units
Unit Type Of Package 1 PCE
Number Of Units In Package 1 1
Package 1 Height 5.000 cm
Package 1 Width 7.800 cm
Package 1 Length 9.000 cm
Package 1 Weight 141.000 g
Unit Type Of Package 2 S02
Number Of Units In Package 2 24
2 Mar 18, 2024
Package 2 Height 15.000 cm
Package 2 Width 30.000 cm
Package 2 Length 40.000 cm
Package 2 Weight 3.715 kg
Unit Type Of Package 3 P06
Number Of Units In Package 3 384
Package 3 Height 80.000 cm
Package 3 Width 80.000 cm
Package 3 Length 60.000 cm
Package 3 Weight 68.772 kg
Contractual warranty
Warranty 18 months
Mar 18, 2024 3
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right
Transparency RoHS/REACh
Well-being performance
Mercury Free
Rohs Exemption Information Yes
Certifications & Standards
Reach Regulation REACh Declaration
Eu Rohs Directive Compliant with Exemptions
China Rohs Regulation China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure Product Environmental Profile
Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins
Circularity Profile End of Life Information
4 Mar 18, 2024