X-DCS2000/EN
DIGITAL INTEGRATED
SYSTEM MANAGER
• Highly integrated
• Easy-access preset buttons
• Built-in fault diagnosis
• Automatic volume control
• Extendable zones connections via software
configuration
DESCRIPTION
X-DCS2000/EN Digital Integrated System Manager (abbr. storage, net audio, broadcasting, zone control, monitoring,
DCS) is the basic unit of X-618 Public Address and Voice fault diagnosis etc. The supplied X-SMART management
Alarm System. DCS integrates plentiful functions such as software allows users to easily and efficiently manage and
zone expansion, multiple audio sources support, audio file control the system.
FEATURES
Input/ Output input gain of each volume control input to the main power supply. When
DCS has 8 dry-contact outputs that can on the rear panel. a shortcircuit error is detected in DCS,
be used to activate external devices. It the power supplied from main power will
has 8 pairs of loudspeaker line output Connections Expansion be cut off and switched to the backup
where each one allows multiple 100V DCS can connect with devices and the one. Same technology is also used in
loudspeakers to network to extend zone connections via amplifier switchover. User can configure
be connected in parallel. A record output 4 10M/100M adaptable Ethernet the amplifier backup solution as 3
port is dedicated for external recording. interfaces. backup for 1 main, 2 backup for 1 main,
1 backup for 1 main or 2 backup for 2
DCS also has 8 dry-contact inputs that Safety and Robustness main.
can be linked with a fire alarm control
center which supports broadcasting DCS can detect errors on main power
alarm tones and evac- uation Audio Storage
supply, backup power supply, amplifier
announcement when fire happens. On DCS is built with a 1GB flash memory.
circuit, amplifier protection, software,
the rear panel, there are 4 network audio Via X-618 Config software, users can
communications, and loudspeaker line
input and 4 auxiliary inputs, which upload audio files for later playback or
in runtime. By locating the error’s
provide con- nections to external audio audio synthesis. Volume controllers can
occurrence, DCS provides valuable
sources such as CD/DVD, cassette, FM be connect- ed with the DCS contact
information for repairing or replacing
tun- er etc. In addition, there are 4 audio outputs to adjust the zones volume or
the malfunctioned devices.
inputs that are capable to adjust volume force switching.
automatically according to ambient DCS supports power supply and
noise (when HN-D32N Noise Detector is amplifier redundancy. Built-in fuse
installed). Users can set the phantom provides over-current protection
power and
Broadcasting Zone Control Shortcut Control
DCS supports a variable range of audio User can select audio sources and A highlight of DCS is the one-click
sources, such as audio files from zones to broadcast by clicking directly emergency mode switchover feature. A
external devices (CD/DVD, cassette, FM on the control buttons on the front red emergency mode button can be
tuner and etc.), remote paging panel. found on the front panel, which can
announcement or broadcasting from X- activate the fire alarm broadcast mode
NPMI, announcements from the PTT DCS supports audio matrix, allowing any in an emergency by a single click. In
emergency microphone etc. audio sources to be played in any zones. emergency mode, the recorded
evacuation announcement will be
Monitoring broadcasted and the zone alarm
DCS can broadcast 4 audio message or DCS has a built-in loudspeaker and it indicator lights will be turned on. This
internet audio simultaneously. Timer can enable zone and audio source function significantly improves the
broadcast setting can be configured via monitoring. When the system has been evacuation efficiency.
software to allow system to play specific extended via Ethernet, network remote
programs at a specific time even when it supervision can be performed.
is not supervised. With the software, user Users can preset the functions for the
can also handle up to 255 priorities to other buttons or their combo usage.
meet complex public address The label describing buttons’ functions
requirements. can be replaced easily.
Components Certification and Standard
Buttons for special operations: select all, reset, error confirm Category Region Certification
and etc.
Safety Europe CE Complied
Zone selection buttons
Voice Alarm Europe EN 54 (Part 16) Certified
Audio source selection buttons
Emergency mode button
Interfaces Indicator Lights
8 dry-contact outputs Device status indicator lights can show whether the device
is powered, malfunctioned, disabled, running or delayed
8 loudspeaker line outputs
Zone status indicator lights
8 dry-contact inputs
Audio source status indicator lights
4 auxiliary audio inputs with AVC
4 noise detector inputs
4 amplifier interfaces
Ordering Information
RS - 485 port for fi re alarm
Description
Main power port
X-DCS2000/EN Digital X-DCS2000/EN
Backup power port (DC 24V) Integrated System Manager
Push-to-Talk Microphone HN-PTT
4 10/100M adaptable Ethernet interfaces (accessory)
Technical Specifications
Power Supply Others
Main power supply ~100 - 240 V,50/60 Hz Monitoring loudspeaker 10W / 8Ω
Backup power supply DC 21.5 V - 28.5 V Ethernet speed 10 M / 100 M
DC power output DC24V/1A Ethernet interface number 4
Max. input power 120 W Storage space 1 GB
Rated power 50 W Work Condition
Audio Input Humidity < 95 %, non condensing
Auxiliary input 1V(0dBV) Operating temperature -10 °C ~ +55 °C
Input impedance 20 kΩ Storage temperature -40 °C ~ +70 °C
Frequency response 60 Hz - 16 kHz Specification
SNR >85 dB Dimension (W×H×D) 482 × 88× 420 mm
Audio Output Mount dimension (W×H×D) 580 × 235 × 552 mm
Audio output channels 4 Net weight 9.3 kg
Output signal 1.2V(1.6dBV) Gross weight 12.5 kg
Record output 1V(0dBV)
AVC Input Parts included
Channels 4 Component Quantity
14mV(-37dBV) or 330mV X-DCS2000/EN 1
Input signal (-9.6dBV) configured by
switch Panel paper 6
Input impedance 20 kΩ Dry-contact input connector (8P) 2
Phantom power DC 24V, configured by switch Dry-contact output connector (6P) 4
Frequency response 60 Hz - 16 kHz Loudspeaker connector (16P) 2
SNR >65 dB Amplifier connector (4P) 2
Loudspeaker Circuit
AVC connector (8P) 2
Output channels 8, with circuit fault detection function
DC power wiring terminal (4P) 1
Max. output load 500 W (If the line supervision is used,
Twist-pair cable (2 m) 1
the load shall be less than 250W.)
Trigger Input / Output Audio cable 1
Trigger input ports 8 AC power cable 1
Trigger output ports 8 (NO, NC and COM) Fuse (2A) 1
Max. working voltage AC 250 V / DC 30 V Product Instructions 1
Max. working current 2.5 A CD-ROM 1
For more information,
https://honeywellbuildings.in
Call: 1-800-103-0339
Email:
[email protected]Honeywell HBT India Buildings
Unitech Trade Center, 5th Floor, Sector-43, X-DCS2000/EN
Block C, Sushant Lok Phase - I, DIGITAL INTEGRATED
Gurgaon - 122002 SYSTEM MANAGER
www.honeywell.com © 2020 Honeywell International Inc.