Water Demand Calculations

This document calculates the total water demand for fixtures in a non-residential building. It lists the various fixtures, their fixture unit weights for cold and hot water, and the quantity of each fixture. The total fixture units are 47, resulting in a peak water demand of 27.8 GPM or 6.31 cubic meters per hour. Based on a peak factor of 1.5 and a 60 minute duration, the mean demand is calculated to be 18.5 GPM. The required overhead tank size is 556 gallons and the recommended transfer pump capacity is 18.5 GPM.

Uploaded by

sorryfrom66
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
60 views2 pages

Water Demand Calculations

This document calculates the total water demand for fixtures in a non-residential building. It lists the various fixtures, their fixture unit weights for cold and hot water, and the quantity of each fixture. The total fixture units are 47, resulting in a peak water demand of 27.8 GPM or 6.31 cubic meters per hour. Based on a peak factor of 1.5 and a 60 minute duration, the mean demand is calculated to be 18.5 GPM. The required overhead tank size is 556 gallons and the recommended transfer pump capacity is 18.5 GPM.

Uploaded by

sorryfrom66
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

TOTAL DEMAND CALCULATION : FOR , NNH

Fixtures type : private


Weight in Fixture units Total weight in fixture units
FIXTURES Quantity
Cold Hot Total Cold Hot
Water closet (flush valve) 6 0 6 0 0 0
Water closet (flush tank) 3 0 3 8 24 0
Water Bidet 0.75 0.75 1 0 0 0
Hose for W.C 0.75 0.75 1 0 0
Lavatory (& H.B., J.S.) 0.75 0.75 1 10 7.5 7.5
Service sink 1.5 1.5 2 0 0
Shower 1.5 1.5 2 1 1.5 1.5
Bath tub 1.5 1.5 2 3 4.5 4.5
Kitchen sink 1.5 1.5 2 1 1.5 1.5
Dishwashing machine 0 1 1 1 0 1
Laundry 1.5 1.5 2 1 1.5 1.5
Ablution (Public) 1 1 1.5 0 0
Urinal (1" flush valve) 10 0 10 0 0
Urinal (3/4" flush valve) 5 0 5 0 0
Urinal (flush tank) 3 0 3 0 0
Total Fixture Units 40.5 17.5
WATER DEMAND ( GPM ) 25.0 GPM 12.5 GPM
WATER DEMAND ( m3/ h ) 5.68 m3/h 2.84 m3/h

Assuming Peak factor : 1.5


Duration : 60 min

The mean demand 18.5 gpm (mean demand = peak demand / peak factor )
Overhead tank size 556 gallon ( Overhead tank size = (peak demand - mean demand) x duration }
2.10 m3

Transfer pump capacity 18.5 gpm ( Transfer pump capacity = mean demand , Assuming one pump
4.21 m3/h running & one standby)
1.17 l/s
Total weight in fixture units
Total
0
24
0
0
10
0
2
6
2
1
2
0
0
0
0
47
27.8 GPM
6.31 m3/h