Powersystem Protection ESSAMARIFI
Powersystem Protection ESSAMARIFI
net/publication/348788183
CITATION READS
1 5,936
2 authors, including:
SEE PROFILE
All content following this page was uploaded by Essam ABDULHAKEEM Arifi on 26 January 2021.
Professor: 郑涛
(15/04/2020)
1 |Pa ge
Page | 2
Abstract:
Synchronized wide area communication has become a mature technology, which
makes the real-time interaction between the substations and the wide area
protection and control system possible. However, the present protection and
control system to handle this real-time data has been recognized to be deficient.
This paper begins by reviewing the development history of power system
protection, with special attention paid to the recent development in the field of
wide-area and integrated protections, in order to look into the future
development of protection and control systems. Then the concept of integrated 2
wide area protection and control is introduced, where it can be shown that a
hierarchical protection and control system provides the protection and control for
wide area or regional power substations/plants and their associated power
networks.
The system is mainly divided into three levels: the local, the substation/plant,
and the wide area/regional. The integrated functions at each level are described
in details with an aim to develop an optimal coordination mechanism between
each level. The key element in the proposed system is the wide area real-time
protection and control information platform, which not only enables the merger
of three lines of defense for power system protection and control, but also
provides a perfect tool for the application of cloud computing in substations and
power networks.
KEYWORDS:
I. Introduction Power system protection
II. Three phase over current protection
III. Transformers Protection
IV distance protection (Transmission Line Protection)
V. Pilot Protection (Transmission Line Protection)
VI. Generator Protection
2 |Pa ge
Page | 3
At the same time, great theoretical progress had been made in the relay protection
software, algorithms, etc. As shown in Fig. 1, the progress in modern technology
stimulates the development in power system protection. In the last century from
the emergence of protection to the end of the 1990s, the relay protection had gone
through a number of development stages, migrating from electro-mechanical to
semiconductor, and subsequently to integrated circuit and microprocessor
technologies. Today, microprocessor-based digital and numeric relays are
replacing conventional relays in all areas of power system protection. However,
many of the same relaying principles of protection are still playing a dominant role
to date. In the late 1960s, the application of a centralized substation protection
system based on a centralized computer system was proposed [1].
3 |Pa ge
Page | 4
Fig. 1
4 |Pa ge
Page | 5
✓ Input data
Relay needs information from the system to take a decision. These data can be
collected in various ways. In some cases, the cables in the area can be connected
directly to the relay. In other applications, additional equipment needed to convert
the measured parameters as in a form that can relay process. These accessories can
be carrier current transformers, voltage transformers, RTD (Resistance Temperature
Detector) or other equipment.
✓ Reference values
Many protection relays have adjustable parameters. The user sets the parameters so
5
that the relay respond to the parameterization limit. Relay compares input values
with the values of these parameters and responds accordingly.
✓ Processes
Once entries (data) are connected and the parameters are set in the relay, the relay
compares these values and takes a decision. Depending on the needs of different
types of relays are available for various functions.
✓ Outputs (Results)
Relay has different ways of communicating. In typical relay, order will act on a
switch (relay contact) to indicate that an input value has exceeded a parameter, or
relay can provide a notification by a visual feedback such as an instrument or LED.
One advantage of the electronic relays is the ability to communicate with a network
or PLC.
✓ Before we talk for them, it should be noted that the use of the term protection does not mean
that protective equipment can prevent problems, such as errors and equipment failures or
electrical shocks due to unintentional human contact. It cannot predict problems. Protection
relays operate only after an abnormal or intolerable situation that has occurred. This protection
does not mean prevention, but rather, minimizing the duration of the problems and limitations
of damages, the time of interruption, and similar problems.
5 |Pa ge
Page | 6
❖ 1. Reliability
Reliability has two aspects, safety and security. Safety is defined as "the security levels which a
relay will function properly". The security has to do with "the level of security that a relay will not
act wrongly." In other words, safety it shows protection system's ability to work properly when
required, while the security is the ability to avoid unnecessary operations during normal operation.
➢ 2. Selectivity Relays have a designated area known as the primary protection zone, but they can
operate properly on responses to conditions outside this zone. In these cases, they provide backup
protection for the area outside the primary area.
Selectivity (coordination of the relay) is the application process and the establishment of relay
protection that surpasses other relays that they can act as quickly as possible within their primary area of
operation but has delays in the reserve area. This is necessary to allow the primary relay to operate in
the reserve area.
➢ 3. Speed
Of course, it is desirable for the protection to isolate the problem area as quickly as possible. In some
applications, it is not difficult, but in some other, especially when selectivity is involved, faster
operation can be achieved by more complex protection and higher costs.
➢ 4. Simplicity
A relay protection system should be simple and direct as much as possible. Each unit or added
components, which may provide improved protection, but it is not necessary under the protection
requirements should be considered very carefully.
➢ 5. Economy
It is essential to have maximum protection with minimum cost, and the cost is always a major factor.
The protection system with the lowest cost cannot be trusted, moreover, it can involve greater
difficulties in the installation and its operation, as well as higher maintenance costs.
6 |Pa ge
Page | 7
❖ Current transformers:
Current transformer (CT) is a type of measuring transformers which is designed to produce
alternative current in the second winding that is proportional to the measured current in the
primary winding.
Current transformers reduce currents of high voltage systems to a much lower value and
provide a convenient way to safely monitor the flow of current in transmission lines using
a standard ampere meter. The working principle of current transformers is the same as an
ordinary transformer.
7
Unlike ordinary transformer, the current transformer has one or several windings in the
primary winding, while secondary winding, on the contrary, may have a greater number of
windings. In the secondary winding are normally selected to pass currents of 1A or 5A.
/
𝑅𝐴𝐿𝐹 = 𝐼1𝑙 𝐼1𝑛
where the primary limiting current is the current for which the error is less than 5% for the
accuracy class 5P or 10% for the accuracy class 10P.
Based on the IEC standards, the rated accuracy limit factor has the following values: 5 - 10 - 15
- 20 – 30
Rated output at rated secondary is the value, marked on the rating current plate, of the apparent
power in VA that the transformer is intended to supply to the secondary circuit at the rated
secondary current.
✓ Protection is the art or science of continuously monitoring the power system, detecting the
presence of a fault and initiating the correct tripping of the circuit breaker.
• The objectives of power system protection are to:
— Limit the extent and duration of service interruption whenever equipment failure, human error, or
adverse natural events occur on any portion of the system
— Minimize damage to the system components involved in the failure and Prevention of human injury
• Protection engineering concerned with the design and operation of "protection schemes".
• Protection schemes are specialized control systems that monitor the power system, detecting faults or
abnormal conditions and then initiate correct action.
• In this course the power system is considered as all the plant and equipment necessary to generate,
transmit, distribute and utilize the electric power.
7 |Pa ge
Page | 8
8 |Pa ge
Page | 9
9 |Pa ge
P a g e | 10
10
10 | P a g e
P a g e | 11
11
1. Introduction
✓ Static relays
represent the second generation of the relays. These relays have started to be used around the early
60's. The term static means that the relay does not have mechanical moving parts in it. Compared to
electromechanical relays, static relays have a higher life expectancy, then they have a reduction in
noise during operation and react faster in case of any failure.
11 | P a g e
P a g e | 12
12
✓ Microprocessor
relays represent the latest generation of relays, the most advanced generation of relays. Their use began
about two decades ago. Microprocessor technology allows these relays to have features like static relays
and even more. In these relays, the signals of currents and voltages from current and voltage
transformers first are processed as analog signals and then converted to digital signals for further
processing.
Overcurrent protection:
Transmission and distribution systems are exposed to overcurrent flow into their elements. In an
electric power system, overcurrent or excess current is a situation where a larger than intended
electric current exists through a conductor, leading to excessive generation of heat, and the risk of
fire or damage to equipment.
Possible causes for overcurrent include short circuits, excessive load, transformer inrush current,
motor starting, incorrect design, or a ground fault.
13
Therefore, for normal system conditions, some tools such as demand - side management, load
shedding, and soft motor starting can be applied to avoid overloads. In addition, distribution
systems are equipped with protective relays that initiate action to enable switching equipment to
respond only to abnormal system conditions. The relay is connected to the circuit to be protected
via CTs and VTs according to the required protection function. In order for the relay to operate, it
needs to be energized. This energy can be provided by battery sets (mostly) or by the monitored
circuit itself.
❖ Overcurrent relays:
The basic element in overcurrent protection is an overcurrent relay. The ANSI device number is 50 for
an instantaneous overcurrent (IOC) or a Definite Time Overcurrent (DTOC) and 51 for the Inverse
Definite Minimum Time. There are three types of operating characteristics of overcurrent
relays:
✓ Definite(Instantaneous)-Current Protection,
✓ Definite-Time Protection and
✓ Inverse-Time Protection.
✓ Definite(instantaneous)-current protection
This relay is referred as definite(instantaneous) overcurrent relay. The relay
operates as soon as the current gets higher than a preset value. There is no
intentional time delay set. There is always an inherent time delay of the order
of a few milliseconds. 10 The relay setting is adjusted based on its location in
the network. The relay located furthest from the source, operates for a low
current value. Example, when the overcurrent relay is connected to the end
of distribution feeder it will operate for a current lower than that connected in
beginning of the feeder, especially when the feeder impedance is larger. In
the feeder with small impedance, distinguishing between the fault currents at
both ends is difficult and leads to poor discrimination and little selectivity at
high levels of short-circuit currents. While, when the impedance of feeder is
high, the instantaneous protection has advantages of reducing the relay’s
operating time for severe faults and avoiding the loss of selectivity.
13 | P a g e
P a g e | 14
14
Definite-time protection
In this type, two conditions must be satisfied for operation (tripping), current must exceed the setting
value and the fault must be continuous for at least a time equal to the time setting of the relay. This relay
is created by applying intentional time delay after crossing pick up value of the current. A definite time
overcurrent relay can be adjusted to issue a trip output at definite amount of time after it picks up. Thus,
is has a time setting and pick up adjustment. Modern relays may contain more than one stage of
protection each stage includes each own current and time setting. The settings of this kind of relay at
different locations in the network can be adjusted in such a way that the breaker closest to the fault is
tripped in the shortest time and then the other breakers in the direction toward the upstream network are
tripped successively with longer time delay. The disadvantage of this type of protection is that it’s
difficult to coordinate and requires changes with the addition of load and that the short-circuit fault
close to the source may be cleared in a relatively long time in spite of its highest current value. Definite
time overcurrent relay is used as a backup protection of distance relay of transmission line with time
delay, backup protection to differential relay of power transformer with time delay and main protection
to outgoing feeders and bus couplers with adjustable time delay setting.
14 | P a g e
P a g e | 15
Inverse-Time Protection:
In this type of relays, operating time is inversely changed with the current. So, high current will operate
overcurrent relay faster than lower ones. They are available with standard inverse, very inverse and
extremely inverse characteristics. Inverse Time relays are also referred to as Inverse Definite Minimum
Time (IDMT) relay. The operating time of both overcurrent definite-time relays and overcurrent
inverse-time relays must be adjusted in such a way that the relay closer to the fault trips before any
other protection. This is known as time grading. The difference in operating time of these two relays for
the same fault is defined as discrimination margin. The adjustment of definite-time and inverse-time
relays can be carried out by determining two settings: time dial setting and pickup setting. The time dial
15
setting adjusts the time delay before the relay operates whenever the fault current reaches a value equal
to, or greater than, the relay current setting. The time dial setting is also referred to as the time multiplier
setting. The tripping characteristics for different TMS settings using the IEC 60225 are shown in the
table to the right.
Pickup setting is used to define the pickup current of the relay by which the fault current exceeds its
value. It is determined by:
15 | P a g e
P a g e | 16
16
Current protection
Current protection schemes are integrated into power system designs to protect the power
system components from the excessive withdrawal of current and short-circuit currents.
16 | P a g e
P a g e | 17
Excessive overcurrent could occur on many different power system components such as
motors causing hazards if not cleared within the safe time frame.
Short-circuit currents are undesired currents that occur in electrical circuits and flow along
paths, which have low impedances (almost zero) causing severe hazards.
There are different types of current protection schemes such as overcurrent, undercurrent
and phase-sequence. However, overcurrent protection is also sub-classified into other
categories such as non-directional overcurrent, directional overcurrent and
voltage-dependent overcurrent.
17
Overcurrent protections follow 19 well-defined time characteristic curves, which define the
time delay before the tripping angle as a function of the current. The curves are divided
according to standard into IEC and ANSI, and the most popular of these curves are the
definite time curve (DT), the extremely long inverse time (ET), the very long inverse time
curve and the normal inverse time curve.
Figure 2 Inverse time characteristics of three different curve groups, the normal inverse, the very inverse and the extremely
inverse
Non-directional overcurrent
Non-directional overcurrent is a protection scheme developed to protect power system
equipment from overcurrent and short-circuit currents regardless of the direction of current
flow.
The overcurrent protection function utilizes different stages for alarming and tripping. It
consists of three stages, the low stage, the high stage and the instantaneous stage. The low
stage is the stage when set provides an alarm signal, the high stage is the stage which is
usually used to trip overcurrent faults and finally the instantaneous stage is the stage used for
tripping short-circuit currents.
In modern numerical protection relays, each stage has its own unique settings including the
time characteristic curve selection.
17 | P a g e
P a g e | 18
18
Directional overcurrent
Directional overcurrent is a protection scheme developed to operate on a desired overcurrent
value flowing in a predetermined direction. It is commonly used in power systems with ring
configuration and single supply to protect all feeders where the energy flow direction
depends on fault location.
Figure 3 Directional protection scheme in a power system with two parallel operating transformers, no current is
allowed to go back to the transformers from the downstream side
In other words, the function will not send any signals even though the set current has been
reached, unless the voltage also reaches a set value. Voltage-dependent overcurrent
protection is commonly used in generator protection.
18 | P a g e
P a g e | 19
19
Figure 4 The current protection starts only when the voltage reaches a certain value, thereby
voltage-dependent value
There are several current protection functions, however in this article we focused on three
of the most common overcurrent protection functions to acquaint the reader with their
basic operating principles. While they are all bound to the same time characteristic curve
groups, non-directional overcurrent is a protection function which is used to protect power
system element from overcurrent and short-circuit currents flowing in any direction of the
power system.
Directional over current protection functions are developed to protect the power system
from excessive current flowing in an already known direction and voltage-dependent
overcurrent protection is used to protect the equipment at predefined voltage levels.
19 | P a g e
P a g e | 20
and in the feeders and branch circuits of electrical systems for residential, commercial, institutional,
and industrial premises (Figure 5.3).
Figure 5.3. Overcurrent protection devices include circuit breakers and fuses.
20
Overcurrent protection devices are meant to protect against the potentially dangerous effects of
overcurrent, such as an overload current or a short-circuit current, which creates a fault current.
Equipment damage, personal injury, and even death can result from the improper application of a
device's voltage rating, current rating, or interrupting rating. Something as simple as a circuit
breaker can protect against this damage, but if a fuse or circuit breaker doesn't have an adequate
voltage rating, it can rupture or explode while attempting to stop fault currents beyond their
interrupting ratings. Grounding helps to protect against inadequate overcurrent protection or OCPD
failure. The two processes are designed to work together to protect equipment, property, and
people.
20 | P a g e
P a g e | 21
21
21 | P a g e
P a g e | 22
Introduction
22
22 | P a g e
P a g e | 23
23
23 | P a g e
P a g e | 24
24
❖ General
When a fault occurs in a transformer, the damage is proportional to the fault time. The
transformer should therefore be disconnected as fast as possible from the network. Fast reliable
Monitors can also detect faults and they can sense abnormal conditions which may develop into
a fault.
24 | P a g e
P a g e | 25
The size of the transformer and the voltage level have an influence on the extent and choice of
protective equipment. Monitors prevent faults and protective relays limit the damage in case of
a fault. The Gast for the protective equipment is marginal compared to the total cost and the
There are often different opinions about the extent of transformer protection. However, it is
more or less normal that transformers with an oil conservator are furnished with the following
equipment: 25
3.Overcurrent protection.
5.Differential protection
25 | P a g e
P a g e | 26
26
*Overload protection
*Overcurrent protection
26 | P a g e
P a g e | 27
27
27 | P a g e
P a g e | 28
28
Differential protection is the most important type of protection used for protection against
internal phase-to-phase and phase-to-earth faults. The other protection systems employed for
protection of transformers against internal faults are Buchholz protection, core-balance leakage
protection, combined leakage and overload protection, restricted earth-fault protection.
The heat generated by the large local currents causes the transformer oil to decompose and
generate gases, which can be used in detection of winding faults.
28 | P a g e
P a g e | 29
(i) Pressure relays and pressure relief devices which act on the measurement of the total
accumulated pressure,
(ii) Rate of pressure rise relay, which acts on the measurement of the rate of formation of the
gas and
(iii) Gas accumulator relay, most commonly known as Buchholz relay, actuated by the gas
formed.
Buchholz protection employing Buchholz relay is the simplest form of protection and is most
29
commonly used on all oil-immersed transformers provided with conservator.
This system consists of three primary conductors surrounded by the magnetic circuit of a
current transformer. This has a single secondary winding which is connected to the relay
operating coil. Under normal conditions i.e., when there is no earth fault the instantaneous sum
of the currents in the three phases is always zero, and there is no resultant flux in the core of
the CT no matter how much the load is out of balance.
Thus, no current flows through the relay operating coil and trip circuit remains open. When an
earth fault occurs, the sum of the three currents is no longer zero and a current is induced in the
secondary of the CT causing the trip relay to operate and isolate the transformer from the
bus-bars.
three separate CTs. In this system of protection two overload relays and one earth leakage
relay are connected. The overload relays used are high current setting ones and are arranged to
operate against phase-to-phase faults while the earth fault relay has low current setting and
operates under earth or leakage faults only.
The two overload relays are sufficient to protect all the three phases while the earth-fault or
leakage-fault relay is energized by the resultant currents from all the three CTs in case of
leakage fault. The trip contacts of the overload relays and earth-fault or leakage relay are
connected in parallel, as illustrated in the figure. So the circuit breaker will trip in the event of 30
energization of either overload relay or leakage relay. Thus, the protection against faults and
short circuits either to earth or between phases is achieved.
The power transformer is star connected on one side and delta connected on the other. The CTs
on the star-connected side are delta-connected and those on delta-connected side are
star-connected. The neutrals of CT star and power transformer star connections are grounded.
The restraining coils are connected across the secondary windings of CTs. The operating coils
30 | P a g e
P a g e | 31
are connected between the tapping points on the restraining coils and the star point of the CT
secondary windings.
The operating coils normally carry no current as they are balanced on both sides of the CTs.
On the occurrence of internal fault in the power transformer windings, the balance is disturbed
and the operating coils of the differential relays carry current corresponding to the difference
of the current between the two sides of the power transformers and operate the relays to trip the
main circuit breakers on both sides of the power transformer.
31
Harmonic Restraint Relay of Transformers:
The operation of the relays because of magnetizing inrush current can be avoided by using kick
fuses across the relay coils or using relays with inverse and definite minimum time (IDMT)
characteristics. However, for EHV transformers, the relay current and time ratings necessary to
ensure stability on the magnetizing inrush current caused by switching-in the transformer are
not adequate for providing high speed protection.
A high speed biased differential relay incorporating a harmonic restraint feature is immune to
the magnetizing inrush current. The magnetizing inrush currents have a high component of
even and odd harmonics (about 63% of second harmonics and 26.8% of third harmonics) while
harmonic component of short-circuit currents is negligible. The use of these facts is made for
restraining the relay from operation during initial current inrush.
The harmonic restraint differential relay is sensitive to fault currents but is immune to the
magnetizing currents. The operating coil of the relay carries only the fundamental component
of current only while the restraining coil carries the sum of the fundamental and harmonic
components.
Basic circuit of a harmonic restraint differential relay is illustrated in Fig. 9.8. The restraining
coil is energized by a direct current proportional to bias winding current as well as the direct
current due to harmonics. Harmonic restraint is had from the tuned circuit (XC – XL) that allows
only the fundamental component of current to enter the operating circuit.
The dc and higher harmonics (mostly second harmonics) are diverted into the rectifier bridge
feeding the restraining coil. The relay is adjusted so that it will not operate when the harmonic
current exceeds 15% of the fundamental current. Both the dc and higher harmonics are of large
magnitude during magnetizing inrush.
The relay may fail to operate due to harmonic restraint feature if an internal fault has
considerable harmonics that may be present in the fault current itself due to an arc, or due to
saturation of CT. Also, if a fault exists at the instant of energization of transformer harmonics
31 | P a g e
P a g e | 32
present in the magnetizing current may prevent the operation of the relay. This problem can be
overcome by providing instantaneous overcurrent relay in the differential circuit which is set
above the maximum inrush current but will operate in less than one cycle on internal faults.
Thus, fast tripping is ensured for all internal faults.
The other method used is harmonic blocking. In this method the harmonic component of
magnetizing inrush current is used for blocking a separate relay, called the blocking relay,
whose contacts are in series with the contacts of the differential relay. The blocking relay
contains a 100 Hz blocking filter in operating coil and 50 Hz blocking filter in the restraining 32
coil. During inrush currents the second harmonic component is predominant and the blocking
relay is blocked. The blocking relay contacts remain open. During short circuits, fundamental
component is predominant, so blocking relay operates and relay contact circuit is closed.
32 | P a g e
P a g e | 33
33
The current transformers used are bus type and are connected for circulating current protection.
Their current ratings are so adjusted that they provide equal secondary currents. The relay
operating coil instead of being connected to the equipotential point of the pilot wires is fed from
another winding on hv side CT (CT2). Since the core flux of Iv side CT (CT1) is more because of
its more ampere-turns, the turns of hv side CT are increased so as to make core flux of CT2 zero
under all load conditions resulting in no current flowing in the relay operating coil under normal
operating conditions. The CT2 is made with high permeability alloy core so as to reduce
magnetizing current and provide an accurate balance.
For any through fault CT2 continues to have no flux and so the relay operating coil remains
inoperative. On occurrence of fault in protection zone, say at F, excessive current flows through
CT1 causing flow of current in the relay operating coil. Thus, relay is energized and the circuit
breaker gets tripped.
Self-Stabilizing Magnetic Balance Protection System of Transformers:
For the protection of power transformer having tapings it is necessary that the protective CT
connected on hv side (i.e., CT2) must also be capable of changing its current ratio whenever
power transformer tapping are changed i.e., CT2 windings need some modification.
It is explained as- in Fig. 9.10 (a) plain magnetic balance protection system is illustrated, the
relay connections are not shown for sake of simplicity. CTs used are bus-bar type. In Fig. 9.10
(b) self-stabilizing circuit for magnetic balance protection system is shown. In this circuit the
magnetic core of CT2 is divided into two halves P1 and P2 and the secondary winding is so
wound that the flux developed by the two halves P1 and P2 is equal and opposing each other.
Thus in normal operating conditions no emf is induced in the secondary winding and the relay
operating coil remains inoperative.
33 | P a g e
P a g e | 34
34
When the transformer is operating under normal operating conditions and carrying full-load
currents, the flux developed by the two halves is equal and relay winding coil is un-energized.
Now when the tapings of the main transformer are changed, mmfs of the two halves are
changed causing the flux developed by them to be different. So, an emf, proportional to the
difference of the two fluxes, will be induced in the relay coil, as shown in Fig. 9.11.
34 | P a g e
P a g e | 35
35
If under this tap changed condition the load on the transformer is increased, mmf of the two
halves will increase but the difference of fluxes developed will decrease. Thus with the
increase in load on power transformer, the difference in fluxes developed by the two halves of
core of CT2 decreases, as shown in Fig. 9.11. Now if the relay is so designed that its minimum
operating voltage is much more than the induced voltage under any desirable load condition
but with no fault, as illustrated by OD in Fig. 9.11, then stability is ensured. In practice OD is
made twice the minimum ordinate.
Ideally, the output of the CTs is proportional to the sum of zero sequence currents in the line
and the neutral earth connection if the latter is within the protected zone. For external faults
zero sequence currents are either absent or sum to zero in the line and neutral earth connection.
For internal faults, the sum of zero sequence currents is equals twice the total fault current.
35 | P a g e
P a g e | 36
36
When there is an earth fault outside the protective zone, say at F1, it causes the currents I, and
I1 in CT secondaries as illustrated in Fig. 9.13. So the resultant current in earth fault relay is
negligible. For an earth fault within the protected zone, say at F2, only current I2 exists, being
negligible. Thus current I1 flows through the earth-fault relay. Thus restricted earth-fault relay
does not operate for earth fault beyond the protective zone of the transformer.
For an earth fault near the neutral point of the transformer the voltage available for driving
earth fault current is small. For the relay to sense such fault, it has to be too sensitive and
would, therefore, operate for spurious signals, external faults and switching surges. Hence the
relay is set as per practice, so as to operate for earth fault current of the order of 15% of rated
winding current. Such setting protects restricted portion of the winding, hence the name
restricted earth-fault protection. Stabilizing resistor is connected in series with the relay to
avoid magnetizing inrush current and also saturation of CT core.
36 | P a g e
P a g e | 37
Because of the occurrence of magnetizing inrush current transients the relay settings in this
protection scheme must be considerably higher than those for protecting a generator only. The
zone of differential protection includes the stator windings of the generator, the step-up
transformer and the intervening connections.
It is necessary to take care of the phase shift within the power transformer and the connections
of CTs. If a unit transformer is tapped off at the generator terminals, this also has to be taken
37 | P a g e
P a g e | 38
care of by suitable connections of the CTs for protection. CTs located on the neutral side of the
generator are star-connected while the CTs on the secondary (hv) side of the main transformer
are delta-connected so as to cancel the 30° displacement between line currents introduced by
delta-connected primary of the main transformer.
The unbalance caused between CT pairs due to load of unit transformer is avoided by
providing another set of star-connected CTs in the primary leads of the latter. In healthy
condition, the sum of secondary currents of these CTs and the secondary currents of the
generator star-point CTs is equal to the currents in the pilot wires from the secondaries of the 38
delta-connected CTs on the secondary side of the main transformer. On occurrence of fault
differential relays are energized. The hv winding of the main transformer is protected against
earth faults by the restricted earth fault protection scheme.
From the schematic diagram of generator-transformer unit protection shown in Fig. 9.15, it is
obvious that the stator winding of the generator and the LV or primary windings of the main
transformer and unit transformer comprise a separate circuit having no electrical connection
with the hv circuits. So an earth fault at any point of this separate circuit will cause a flow of
current through the earth connection and through a PT connected in series with it. An alarm
relay connected across the secondary winding of PT will get energized and give the necessary
signal.
38 | P a g e
P a g e | 39
Transmission lines can vary in length from several hundred feet to several hundred
miles, and in voltage (line-to-line) from 46KV to 750KV. Construction can be
simple, such as a single wood pole with insulators atop a crossarm, with little
spacing between the conductors and from the conductors to ground. At the other end 39
of the scale are metal lattice structures with bundled conductors (2 or more
conductors per phase) with large spacing between conductors and between
conductors and ground.
Faults
“Faults come uninvited and seldom go away voluntarily.” Fault Types:
●Single line-to-ground
● Line-to-line
● Three Phase
● Line-to-line-to-ground
How Do We Protect Transmission Lines?
A. Overcurrent
B. Directional Overcurrent
C. Distance (Impedance)
D. Pilot
1. DCB (Directional Comparison Blocking
2. POTT (Permissive Overreaching Transfer Trip)
E. Line Current Differential
39 | P a g e
P a g e | 40
40
40 | P a g e
P a g e | 41
41
41 | P a g e
P a g e | 42
42
42 | P a g e
P a g e | 43
43
✓ Introduction
A power system is a complex network with the main responsibility of supplying
reliable electrical energy to consumers within the entire network. Moreover, power
system has dynamic characteristics that acquire the balance between generation and
consumption of electricity in the system. It may experience transient instability
conditions before reaching a new steady state operating condition. Elements in such
system are usually designed to operate in normal operating conditions and transient
44 | P a g e
P a g e | 45
45 | P a g e
P a g e | 46
46 | P a g e
P a g e | 47
47
Obviously, nominal operating voltage level of a line has a significant effect on the SIRs
and therefore this classification will be assigned to different physical lengths in the
following lines:
➢ High Voltage (HV) transmission lines with voltage levels of 69-230kV,
➢ Extra High Voltage (EHV) transmission lines with voltage levels of 230-350kV,
➢ Ultra-High Voltage (UHV) transmission lines with voltage levels over 350kV.
47 | P a g e
P a g e | 48
48
➢ Non-pilot schemes are the schemes in which relays installed in each terminal
of the transmission line do not have any communications with each other and
the relaying decision is only made by analysis of local measurements at
location of the relay.
➢ Pilot schemes are the schemes in which relays installed in both end of the
transmission line utilize a communication link in order to make a relaying
decision. The following sections present an overview of both categories and
protection schemes belonging to each group.
❖ Non-pilot schemes
Non-pilot protection schemes are usually applicable to short or medium
transmission lines. Directional over current and step distance protection
schemes belong to this group of transmission protection scheme.
Directional over current protection scheme
The working principal of the relays used in this scheme is the same as over current
relays widely used for line protection in radial networks. By monitoring current
magnitude of the protected circuit and assigning proper boundaries for deviations of
48 | P a g e
P a g e | 49
However, to utilize the same principal for interconnected meshed transmission lines,
where the current could flow in both directions, the over current schemes are
enhanced by introducing a reference quantity which can provide the directionality.
These schemes are the simplest and least expensive form of fault protection
schemes and are used widely for protection of transmission lines
The tripping steps introduced in this scheme are adjusted by time delays in order to
provide higher selectivity. The first step is an instantaneous relaying step and is set
to operate for occurrence of faults located in Zone 1 of the protected line. This is a
distance on transmission line with approximately 80–90% of the line impedance. To
avoid overreaching operation of the relay or unnecessary operation for faults
beyond the remote terminal, the remaining distance plus some margins beyond the
remote end called Zone 2 will be protected after some time delay. Usually a third
step of operation is defined, which can be used as a backup for Zone 2 or even the
relay at remote bus. Consequently, the tripping function for Zone 3 must be time
delayed to coordinate with the Zone 1 and Zone 2 of the remote relay
❖ Pilot schemes
The non-pilot protection schemes discussed in previous section have usually an
acceptable performance on short or medium lines. However, for long lines which
are mostly operating in EHV or UHV levels and transmitting large electric power,
the tripping time delays would cause severe network stability problems due to the
system acceleration. Also, the huge fault currents could cause dramatic damages for
equipment. In such cases, more complex transmission line protection schemes are
required in order to perform a high-speed tripping in both ends of the line.
An alternative protective scheme which has been in use for protection of EHV/UHV
transmission lines, utilizes local information, as well as remote information for a
relaying decision. In this category known as “pilot protection schemes “the relays
installed at terminals, as shown in Figure 2.4, are able to make a common decision
about tripping the line in case of fault inceptions inside the protection zone
49 | P a g e
P a g e | 50
50
In case of an internal fault the result of the compared data will be a differential
value and for specific threshold values the relays in both terminals perform a
relaying operation. Since there is an instantaneous comparison between the analog
values, the information acquired from both relays needs to be time synchronized to
guarantee the comparison of measured data at same time instants from both ends.
50 | P a g e
P a g e | 51
In external faults the same current is entering to protected zone and leaving it from
51
the second end. But in case of internal fault the current entering the protected zone
is not equal to the current which is leaving the same zone. Therefore, this principal
could be utilized in directional protection schemes for protection of transmission
lines.
➢ Distance Scheme
Communication link between relays in pilot distance schemes can eliminate the
time delays for relay decision makings in case of occurrence of faults in second or
even third zones for distance protection schemes. Thus, the local relays can
communicate with the remote relay in order to make sure that the detected fault is
located on protected zone. This provides fast directional fault detection as well as
opportunity of implementing the step distance relays in protection of long
transmission lines
51 | P a g e
P a g e | 52
This course explains protection relay selection process by detailing how to protect
against each fault type or abnormal condition. Also, recommendations are made for
what is considered to be minimum protection as a baseline. After making the
baseline, extra protection relays, may be introduced. The topics included in this
course are as follows:
Generators are designed to run at a high load factor for a large number of years
and permit certain incidences of abnormal working conditions. The machine and its
auxiliaries are supervised by monitoring devices to keep the incidences of abnormal
working conditions down to a minimum. Despite the monitoring, electrical and
mechanical faults may occur, and the generators must be provided with protective
53
relays which, in case of a fault, quickly initiate a disconnection of the machine from
the system and, if necessary, initiate a complete shutdown of the machine. No
international standards exist regarding the extension of the protective schemes for
different types and sizes of generators. The so called "common standard" varies
between different countries and also between power companies within the same
country, depending on their past experience and different ways in which fault
statistics may be interpreted. A relay manufacturer working on the international
market should, therefore, be able to offer a protective system which can be easily
modified to meet different requirements from different users.
53 | P a g e
P a g e | 54
54
54 | P a g e
P a g e | 55
55
55 | P a g e
P a g e | 56
56
56 | P a g e
P a g e | 57
57
57 | P a g e
P a g e | 58
58
58 | P a g e
P a g e | 59
59
59 | P a g e
P a g e | 60
60
REFERENCES
2. Introduction_to_System_Protection-_Protection_Basics
5.https://na.eventscloud.com/file_uploads/8b5452d7f9376912edcba156cd1a5112_WSU_GENPROTOV
ERVIEW_180305.
6. IEEE Std C37.91-2000 IEEE Guide for Protective Relay Applications to Power Transformers
9. RAZOA Three-zone, phase and ground distance relay for transmission lines
12.
https://na.eventscloud.com/file_uploads/fcdbd21cac1909692839b242e46c9a3c_TransformerProtection_
_180306.pdf
60 | P a g e
P a g e | 61
14. https://www.sciencedirect.com/topics/engineering/overcurrent-protection
15. https://electrical-engineering-portal.com/res/res4/The-Basics-Of-Overcurrent-Protection.pdf
16. file:///C:/Users/ESSAM%20%20ARIFI/Downloads/25862722%20(1).pdf
17. http://engineering.electrical-equipment.org/
61
61 | P a g e