Data sheet for SINAMICS V20
Article No. : 6SL3210-5BB17-5UV1
Client order no. : Item no. : Figure similar
Order no. : Consignment no. :
Offer no. : Project :
Remarks :
Rated data Ambient conditions
Input Cooling convection cooling
Number of phases 1 AC Installation altitude 1,000 m (3,280.84 ft)
Line voltage 200 ... 240 V -15 % +10 % Ambient temperature
Line frequency 47 ... 63 Hz Operation -10 ... 60 °C (14 ... 140 °F)
Output Storage -40 ... 70 °C (-40 ... 158 °F)
Number of phases 3 AC Relative humidity
Rated voltage 230V IEC 240V NEC 1) Max. operation 95 %
Rated power (LO) 0.75 kW 0.75 hp
Connections
Rated power (HO) 0.75 kW 1.00 hp Max. motor cable length
Rated current (LO) 4.20 A 4.20 A Shielded 25 m (82.02 ft)
Rated current (HO) 4.20 A 4.20 A Unshielded 50 m (164.04 ft)
Rated current (IN) 4.20 A
Mechanical data
Pulse frequency 8.00 kHz
Mounting position Wall mounting / side-by-side mounting
Output frequency 0 ... 550 Hz
Degree of protection IP20 / UL open type
Overload capability
Frame size FSAB
Low Overload (LO)
Net weight 0.90 kg (1.98 lb)
110 % rated output current for 60 s, cycle time 300 s
Dimensions
High Overload (HO)
Width 68.0 mm (2.68 in)
150 % rated output current for 60 s, cycle time 300 s
Height 142.0 mm (5.59 in)
General tech. specifications Depth 127.8 mm (5.03 in)
Power factor λ 0.72
Standards
Offset factor cos φ 0.95
Compliance with standards CE, cULus, C-Tick (RCM), KC
Efficiency η 0.98
EN 61800-5-1 /EN 60204-1 and EN
CE marking
Filter class (integrated) Unfiltered 61800-3
Communication
1)
The output current and HP ratings are valid for the voltage range 220V-240V
Communication USS, Modbus RTU
Inputs / outputs
Standard digital inputs
Number 4
Digital outputs
Number as relay changeover contact 1
Number as transistor 1
Analog inputs
2 (Can be used as additional digital
Number
input)
Analog outputs
Number 1
Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Page 1 of 1 Generated Wed Jul 13 15:45:12 CET 2022