G9SP to CJ2 PLC Ethernet IP Setup Guide

The document provides step-by-step instructions for configuring communication between a G9SP safety controller and an Omron CJ2 PLC using Ethernet/IP. It details setting the IP addresses, creating tags for data exchange, downloading the configuration to the PLC, and monitoring data in the controllers.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
75 views18 pages

G9SP to CJ2 PLC Ethernet IP Setup Guide

The document provides step-by-step instructions for configuring communication between a G9SP safety controller and an Omron CJ2 PLC using Ethernet/IP. It details setting the IP addresses, creating tags for data exchange, downloading the configuration to the PLC, and monitoring data in the controllers.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 18

www.infoPLC.

net

G9SP Ethernet IP Communication to


Omron’s CJ2 PLC’s
Rev1.0

Micheal Paradiso
www.infoPLC.net

This document will walk you through a step by step setup


for communication from a G9SP to a Omron’s CJ PLC
using Ethernet IP communications .
Example code for this presentation can be opened using
Omron’s Network Configurator for Safety Devices.
File Name
G9SP_Ethernet_IP_CJ2_Exsample_Rev1.nfc
Overview of G9SP Ethernet IP
www.infoPLC.net
G9SP Ethernet IP Adapter Setup www.infoPLC.net

For the setting to take affect, reboot


the G9SP safety controller after
changing the IP address through the
web page interface

Note: The IP address for the CM-EIP-


1 cannot be configured from within the
G9SP Configurator. The configuration
section is only for Ethernet for the
FINS Ethernet Adapter CP1W-CIG41
Data Exchange With A G9SP
www.infoPLC.net
Data Exchange With A G9SP
www.infoPLC.net
Data Exchange With A G9SP
www.infoPLC.net
Data Exchange With A G9SP
www.infoPLC.net
Setting up EIP Network For CJ2
www.infoPLC.net

• Drag a CM-EIP-1 and CJ2B-EIP21 into the


network diagram as shown. Change the IP
address of the CJ2 to 192.168.1.26 and the
G9SP to 192.168.1.25 as shown, by right
clicking on the controller and selecting
Change Node Address.

• Double click on the CJ2B-EIP21 in the


network diagram

• Click on the Tag Set tab, In-Consume,


and then Edit Tags
Setting up EIP Tags For CJ2 www.infoPLC.net

For this example we are doing a reading and write data in the G9SP the In-Consume section
and Out-Produce will be configured for this example.

IN-Consume Configuration

• Click New to create a new tag

• Enter D0 for name, this field will determine the memory location written
too in the PLC. D0 would be location DM0 in the PLC. In the size field
put 68 bytes, this number has to match the number of Target Input
bytes on the G9SP.
• Click Regist to create the tag.
• Click Close after creating the D0 tag, as the software assumes that
another tag will be created.
Setting up EIP Tags For CJ2
www.infoPLC.net

Out-Produce Configuration

• Ensure you are on the Out-Produce tab then


Click New to create a new tag

• Enter D100 for name, this field will determine the memory location
written too in the PLC. D100 would be location DM100 in the PLC. In
the size field put 8 bytes, this number has to match the number of
Target Input bytes on the G9SP.
• Click Regist to create the tag.
• Click Close after creating the D100 tag, as the software assumes that
another tag will be created.
Setting up EIP Tags For CJ2
www.infoPLC.net

• Click Ok to complete the creation of the tag

• When prompted, click Yes to create Tag Set


with the same name as the Tags that they
contain
Setting up EIP Tags For CJ2 www.infoPLC.net

Click on the Connections tab, highlight the CM-EIP-1 and click the Down Arrow as shown to
move the device from Unregistered device list to the Registered device list. This will register the
NE1A as a slave device to the CJ2

Double click on the device in the Registered device list. This will pop a new window that can be
used to configure the tag usage in the PLC
Setting up EIP Tags For CJ2 www.infoPLC.net

Once this box pops up you have a number of field that will need to be configured.

• The first field to configure would be Connection


Name, this can be any name you would like.
• The next field would be Connection I/O type
select I/O Connection with 66-byte Input.
• In the Consume Variable field select D00000-
(68byte), this should be the only choice you
have
• In the Produce Variable field select Input_100-
(68byte)

• Target Outputs, should be configured as


shown

• Click Regist when finished to complete the


device registration.
• Click Close after creating the connection, as
the software will assume that another
connection will be created.
Setting up EIP Tags For CJ2
www.infoPLC.net

• Click OK in the edit device parameters.


• This is all that is needed to configure the Tags
Down Loading EIP Configuration For CJ2
www.infoPLC.net

• To select the connection method to connect to


the EtherNet/IP network, click on the Options/
Select Interface menus. Select Ethernet I/F

• Click the Connect icon as shown

• Select the appropriate network adapter, and click


OK

• Click OK to select TCP port2 to connect to


network directly
Down Loading EIP Configuration For CJ2
www.infoPLC.net

• Select Use the existing network, and click OK

• Right click on the CJ2B-EIP21 module in the


network diagram, and select Download

• Click Yes to download the parameters


Down Loading EIP Configuration For CJ2 www.infoPLC.net

• To download to the EIP module without changing


the PLC to Program mode, click Download with
Current Mode

• When the download is complete, click OK

Using CX Programmer to monitor the PLC data, and the G9SP Configurator to
monitor the G9SP