Risers
Risers
1.1 400A & 630A, 4W, Aluminium Conductor, Air Insulated - Rising Mains –
(Indoor Type)
400A & 630, 415V, TPN, 4W, Aluminium Conductor, Air Insulated Rising
Main, Indoor type, with Fire barrier, supporting clamps, vertical spring
loaded & rigid hangers, vertical supports and End Cover, Expansion joints
etc. & 2nos of Aluminium external earthing (minimum 50% of phase
conductor).
2.1 63A Tap Off Box with 2nos of 63A, 25kA, TP+NL MCCB with Necessary
wiring & Fixing of TAPOFF Box, etc.
Supply Nos RO
Installation & commissioning Nos 300 0.00 0.00
2.1a And also with suitable rating resin cast CTs and with dual reading prepaid
digital energy meters (DEM). The energy meters shall have RS485 port for
BMS Compatability. Including fixing of meter box with nessary cabling and
accessories as per site conditions as per direction of Engineers/Incharge
Supply Nos RO
Installation & commissioning Nos 550 0.00 0.00
2.2 250A Tap Off Box with 250A, 25kA, TP+NL MCCB with Necessary wiring &
Fixing of TAPOFF Box, etc.
Supply Nos RO
Installation & commissioning Nos 1 0.00 0.00
3.1 Supply of 400A, TPN, End Feed Unit with 400A TPN MCCB and On/Off
Indication. The MCCB shall shall have 2NO+2NC for status feedback.
Supply Nos RO
Installation & commissioning Nos 7 0.00 0.00
3.2 Supply of 630A, TPN, End Feed Unit with 630A TPN MCCB and On/Off
Indication. The MCCB shall shall have 2NO+2NC for status feedback.
Supply Nos RO
Installation & commissioning Nos 8 0.00 0.00
TOTAL OF RISERS 0
Remarks