PM210011-NUI900-EC1-00008 - R01 (VIA MAIL) - LV Cable Sizing Calculation - (900-B903) - Comm

This document provides the objective, references, criteria, and calculations for determining the required size of low voltage power cables for a NEOM green hydrogen project in Saudi Arabia. It includes input data, design considerations, derating factors, and permissible voltage drop limits.

Uploaded by

Partha Sundar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 31

Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev:

01

LV CABLE SIZING CALCULATION

Doc. No.
PM210011-NUI900-EC1-00008

For

NEOM Green Hydrogen


Elements RC Buildings
(900-B903 Canteen
Building)
at

NEOM Industrial City, KSA


Issued for 100% Submittal
September 2023

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or
affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri#en permission.

Page | 1
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev:
01

TABLE OF CONTENTS
1. OBJECTIVE …………………………………………………………………………………………..…….….3
2. REFERENCE CODES AND STANDARDS……………………………………………….…..….…….3
3. CABLE VOLTAGE RATINGS………………………………………………………………..…..….……..3
4. DATA
INPUT………………………………………………………………………………….….…….………3
5. DESIGN CONSIDERATION……………………………………………………………….……….………3
6. CRITERIA FOR CABLE SELECTION…………………………………………………..……….……….4
7. DERATING FACTORS………………………………………………………………………………………..5
8. PERMISSIBLE VOLTAGE DROP………………………………………………………………………….5
9. CALCULATIONS………………………………………………………………………………………………..6
10. SAMPLE CALCULATIONS…………………………………………………………………………………..8
11. APPENDIX…………………………………………………………………………………….………………..
10

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or
affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri#en permission.

Page | 2
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev:
01

1.0 OBJECTIVE

The purpose of this document is to determine the required size of low voltage power cables for
NEOM green hydrogen project.

2.0 REFERENCE CODES AND STANDARDS

 IEC 60228
 IEC 60287:1982
 IEC60364-4-43
 IEC 60840
 IEC 60364
 Riyadh Cable Catalogue
 HCIS
 Saudi Building Code SBC 401
 AP Specifica?on SPEC-ENG-ED003

3.0 CABLE VOLTAGE RATINGS

For 400V System: All LV cable shall be required 1.1kV (E) Grade.

4.0 DATA INPUT

 PM210011-NUI900-ES6- 00001 - Electrical Single Line Diagram (900-B903)


 PM210011-NUI900-EC1- 00009 - Cable Schedule
 PM210011-NUI900-EL1- 00001 - Electrical Load List
 PM210011-NUI900-EL5 - 00002 - Ground Floor Power Layout
 PM210011-NUI900-EL5 - 00003 - Roof Floor Power Layout
 PM210011-NUI900-EC9 - 00001 - Ground Floor Cable Tray and Conduit Layout
 PM210011-NUI900-EC9 - 00002 - Roof Floor Cable Tray and Conduit Layout
 Riyadh Cables Catalogues for LV Cables

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or
affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri#en permission.

Page | 3
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev:
01

5.0 DESIGN CONSIDERATION

5.1 All cables are XLPE insulated PVC outer sheathed, copper conductor, mul? core cables,
armored for direct buried and un-armoured for above ground installa?on. NO separate
PE cable will be considered for armoured 3 core cable for Motors/ Welding outlets/
distribu?on board. Armour will be used as PE and armour earthing shall be done at
both the ends and for Power cables armouring shall be suitable for ground fault
current. Ground fault current shall be considered as per fault current calcula?on for
canteen building. The cable armouring shall be SWA*/AWA** and the outer sheath
shall be Flame retardant and termite resistant PVC suitable for 90°C maximum rated
conductor temperature. All cables shall be UV light resistant and shall be provided.

*Three core cables shall be with Steel Wire Armoured


**Single core cables shall be with Aluminium Wire Armoured

5.2 Motor power factor and efficiency shall be considered as per IEC and same shall be
updated upon receipt of actual data. The motors shall be IE3 type.

5.3 The following installa?on condi?ons are considered to arrive at overall de-ra?ng
factor for cable ampacity;
 Air temperature is considered as per temperature +45 deg.C for electrical
cable laying indoor and outdoor loca?ons.

5.4 Cables route length is taken from :


 Cable Schedule PM210011-NUI900- EC1 - 00009
 Electrical Load List PM210011- NUI900- EL1 - 00001
 Ground Floor Power Layout PM210011-NUI900 - EL5 - 00002
 Roof Floor Power Layout PM210011-NUI900 - EL5 - 00003
 Ground Floor Cable Tray and Conduit Layout PM210011-NUI900 - EC9 -
00001
 Roof Floor Cable Tray and Conduit PM210011-NUI900 - EC9 - 00002

5.5 Values of Resistance & Reactance are taken from Riyadh Cable catalogue (Please
refer Appendix-2)
5.6 Cable Ampacity is selected from Riyadh Cable catalogues (Please refer Appendix-2)

5.7 Cable Ampacity shall be based on maximum conductor temperature of 90ºC for XLPE
insula?on.
6.0 CRITERIA FOR CABLE SELECTION

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or
affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri#en permission.

Page | 4
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev:
01

The sizing of power cable shall be based on the following considera?ons:

A. Cable con?nuous current carrying capacity influenced by various de-ra?ng factors based on
installa?on method and site condi?ons.

B. When SCPD is current limi?ng type, conductor cross sec?on is based on let through energy
of short circuit protec?on device (SCPD). Cable k2S2 value should be more than SCPD let
through (I2t) value. Let through values of ABB make, SACE Tmax XT MCCBs are considered
for cable sizing purpose. When SCPD is not current limi?ng type, it is checked that short
circuit current withstand by cable for ≤ 1 second is greater than the fault current.

C. Voltage drop during running condi?on

D. Voltage drop during motor star?ng condi?on

Note:
Maximum of the conductor cross-sec?on calculated by A to D above is to be selected.
Criteria ‘D’ are applicable only for DOL started motor feeders.

7.0 DERATING FACTORS**

Mul?-core cable installa?on in cable tray:

Cable laid in cable


S. No Description Remarks
trays- indoor
Considered average
1 Ambient ground temperature(45°C) correction factor ( Ft ) 1.15 factor of 40 & 50
degree celsious
4 No of multy core
cable, single layer on a
2 Cable grouping correction factor ( Fg ) 0.77
horizontal or vertival
cable tray.
3 Total De-rating Factor 0.89

**Note: Dera?ng for single core and underground cable is not listed as same is not applicable.

8.0 PERMISSIBLE VOLTAGE DROP

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or
affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri#en permission.

Page | 5
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev:
01

The maximum voltage drops in various sec?ons of the electrical system shall be within the limits
stated in the below table:

Maximum Allowable Maximum Allowable


S. No. System Element
Running Voltage Drop Starting Voltage Drop

a) Cables between transformer secondary and switchboards 0.5%

b) Cables between Emergency DG and Emergency switchboards 0.5%

c) LV switchboard to LV motors 5% 15%


Cables between LV switchboard and LV sub distribution (Auxiliary
d) switchboard, MLDB, UPS, battery Charger) located within the same 0.5%
building

Cables between LV switchboard and LV sub distribution (Auxiliary


e) 2%
switchboard,MLDB, UPS, battery Charger) located in other building.

f) Cables between LV switchboard LV heaters/welding sockets 5%

g) Circuit between lighting panels and last lighting point 2.5%*

h) Circuit betweenpower panels and last socket 2.5%*

i) DC distribution board to DC supply current (electrical controls) 5%

j) AC Distribution board to UPS outgoing circuit 5%

Notes:*

1. In case of difficulty in achieving specified voltage drops in cables up to ligh?ng panel, 5% drop from
Auxiliary Switchboard / MLDB up to last ligh?ng points may be permiSed.

2. In case of LV VFD feeder total voltage drop from LV switchgear to LV motor shall be limited to 5%.
Distribu?on between LV switchgear to VFD and from VFD to Motor shall be decided accordingly.

9.0 CALCULATIONS

9.1 Full Load Current

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or
affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri#en permission.

Page | 6
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev:
01

 Full Load Current (IL) for Motor


KW*1000 ÷ (√3 * V * CosΦ * η)

 Full load current (I) for non-motor loads


KW*103 / (√3*V* CosΦ)

 Full load current (I) for non-motor loads


KVA*103 / (√3*V)

 Full load current (I) for motor loads


KW*103 / (√3*V* CosΦ * η)

HP = Horse Power
KW = Kilo waSs
V = Voltage
CosΦ = Power Factor
η = Efficiency
kVA = Kilo Volt Ampere

9.2 Percentage AC Voltage Drop for 3-Phase Motors:

 During Normal Opera?ng Condi?on


%Vd = [√3 * L * Ib* (R CosΦ + X SinΦ) ÷ (V * N * 1000)] * 100

 For Motor Star?ng Condi?on


%Vdst = [√3 * L * Ist * (R CosΦ + X SinΦ) ÷ (V * N * 1000)] * 100

L = Cable Length (Meters)


V = Line Voltage (3-phase)
R = Cable Resistance (Ohm/Km)
X = Cable Reactance (Ohm/Km)
CosΦ = Power Factor
SinΦ = √ (1 – Cos2Φ)
Ib = Full Load Current
N = No. of parallel cable Runs

Ist = Star?ng Current in Amps = 6*x Full Load Current (Ib) + 20% star?ng current
tolerance.
(Note: *Factor shall be aligned as per motor supplier’s data)
%Vd = Percentage Voltage Drop during Normal Opera?on
%Vdst = Percentage Voltage Drop during Motor Star?ng

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or
affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri#en permission.

Page | 7
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev:
01

(Note: Factor √3 shall be replaced by Factor 2.0 for 1-phase voltage drops.)

9.3 Short Circuit Withstand:

The minimum cross sec?on of any cable shall be such as to ensure that no damage occurs to
the cable in case of a short circuit un?l fault is cleared by protec?ve device such as breaker
or fuse.
 For short circuit clearance dura?ons of 0.1 sec. ≤ t < 5 sec., the following formula is
used for calcula?ng the minimum cable sizes:
K²S² ≥ I²t

i.e.

 For short circuit clearance dura?ons (< 0.1 sec.) of current limi?ng devices, k²S² must
be greater than the value of the transmiSed energy (I²t) specified by manufacturer
of the protec?ve device.

S Cross Sec?onal area in sq. mm


I Effec?ve short circuit current in amperes
t Dura?on of short circuit in seconds
k Cable characteris?c constant, based on resis?vity, temperature coefficient,
hea?ng capacity of conductor material and type of insula?on, k = 143 (as per
Table 43A of IEC 60364-4-43) for copper conductors with XLPE insula?on,
with 90°C ini?al conductor temperature and 250°C final conductor
temperature.

10.0 SAMPLE CALCULATIONS

(a) System Data

Load Name = DB-B903-N2


Feed from = SMDB-B903-N1

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or
affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri#en permission.

Page | 8
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev:
01

Length of Feeder = 12 meter


Demand Load = 19.27 kVA
Voltage = 400 V
Frequency = 60 Hz
The opera?ng characteris?cs of a device protec?ng a cable against overload shall
sa?sfy the two following condi?ons as per SBC_401, clause 43-3.1:

Condi?on 1 Ib ≤ In ≤ Iz and
Condi?on 2 I2 ≤ 1.45 x Iz

Where
Ib = Full load current for the circuit
Iz = Con?nuous current-carrying capacity of the cable (adjusted
ampacity)
In = Rated current of the protec?ve device

I2 is the current ensuring the effec?ve opera?on in the conven?onal ?me of protec?ve
device (conven?onal tripping current I2 = 1.45 In is assumed, The current I2 ensuring the
effec?ve opera?on of the protec?ve device shall be provided by the manufacturer.)

Note- For the adjustable protec?ve devices, the rated current In is the current seang
selected.

(b) (Step-1) Circuit breaker sizing

Full load current (Ib) = KVA*103 / (√3*V)


= 19.27 * 103 / (√3*400)
= 27.82 Amp
Nearest Nominal (In) = 40 A
Breaker Size (In) = 40 AT (100AF)

Since the selected breaker size is more than the Full load current, so the selec?on of breaker
is complying the condi?on 1.

(c) (Step-2) Continuous current-carrying capacity of the cable

Installa?on method Indoor Cable tray


Overall de-ra?ng factor 0.89 (Refer to dera?ng factor
calcula?on)
Demand Load 19.27 kVA
Voltage 400 V

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or
affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri#en permission.

Page | 9
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev:
01

Full load current (Ib) 27.82 Amp

Op?on 1
Ampacity of 4C x 10 Cu Cable 56 Amp (Refer the Appendix-2)
Con?nuous Ampacity aber de-ra?ng, Iz = 56x 0.89 = 49.84 Amp.
Op?on 2
Ampacity of 4C x 6 Cu Cable 41 Amp (Refer the Appendix-2)
Con?nuous Ampacity aber de-ra?ng, Iz = 41x 0.89 = 36.49 Amp.
Op?on 3
Ampacity of 4C x 4 Cu Cable 32 Amp (Refer the Appendix-2)
Con?nuous Ampacity aber de-ra?ng, Iz = 32x 0.89 = 28.48 Amp.

Iz is 49.84 A, clarify which is Considering the future load/addi?onal requirements we are proposing 10mm2 cables
correct ?
which can carry a full load current up to 49.84 Amps aber de-ra?ng.

Checking for Compliance the condi9on 1 and condi9on 2

Iz = 52.61 Amp (Refer the sec?on 10. c)


In = 40 AT (Refer the sec?on 10. b)
Since Iz ≥ In as per above data, so the selected breaker and cable size complying the
condi?on 1.

Now, The conven?onal tripping current I2 = 1.45 In =1.45 x 40 = 58 Amp.


Condi?on 2 is I2 ≤ 1.45 x Iz
58 amp ≤ 1.45 x 52.61 amp
58 ≤ 76.28

So, the compliance of condi?on 2 is also verified.

(d) (Step-3) Checking the cable for the Voltage drop

%Voltage Drop = [√3 * L * Ib * (R CosΦ + X SinΦ) ÷ (V * N * 1000)] * 100

L = 12 meter
V = 400 V
R = 2.33 Ohms/Kilometer (Refer the Appendix no-2)
X = 0.094 Ohms/Kilometer (Refer the Appendix no-2)
CosΦ = 0.85 (Assumed)

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or
affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri#en permission.

Page | 10
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev:
01

SinΦ = √ (1 – Cos2Φ) = 0.526


Ib = 27.82 Amp
N = No. of parallel cable Runs

%Voltage Drop = [√3 * L * Ib * (R CosΦ + X SinΦ) ÷ (V * N * 1000)] * 100

= [√3 * 12 * 27.82 * (2.33 x 0.85 + 0.094 x 0.526) ÷ (400 * 1 * 1000)] * 100


= 0.29

Hence for the selected cable (10 mm2 Cu Cable), the voltage drop is within limit.

e) (Step-4) Checking the minimum Cable Cross Section that Withstands the
Short Circuit Current

Refer the Appendix-3. (Data sheet of ABB has been aSached)

11.0 APPENDIX

Appendix-1: LV Cable Sizing Calcula?ons

Appendix-2: Riyadh Cable Catalog for LV cables

Appendix-3: Let through energy curve for MCCB

Note :
Soil thermal resis?vity data shall be considered 1.5K-m/W for underground rou?ng cable.

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or
affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri#en permission.

Page | 11
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev: 01

APPENDIX - 1

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri#en permission.
900-B903-CANTEEN BUILDING

These cables sizes are based on


Typical comment: DB numbering provided demand load and
shall be as per AP procedure. average power factor 0.8 given in
load list. Cable size will change if In above table, it is 0.77
load rating changes. considered, kindly clarify.
Add 2 line items here for UPS PDBs with
following cable sizes provided by AP: NEOM Green Hydrogen Company - Canteen Building Cable Sizing Calculation

1Rx3Cx35 sq. mm 3.5C


Correction Factor

Full load Current, Ib Depth of Soil Adj. Amp. Iz %Vd %Vdst


Ambient
Equipment (Amp) Breaker convention Laying thermal (A) = Condition ‐2 Percentage Percentage
IEC60364‐4‐ grouond Cable Condition ‐3 Cable Cable
Ib =KVA*10³ / (√3*V) for size al tripping No. of No. of Size Conductor Correction Resistivity Total Derating (IEC60364‐4‐ Cable Resistance Cable Reactance Voltage Voltage
CIRCUIT No. Load Rating Voltage (Volt) Ist = 9.24 Ib 43, Phase Insulation Type of Cable Type of Installation Temparat grouping 1.45 x Iz (IEC60364‐4‐ 43) Impedance Length
non-Motor Load & Ib = In current, Cores Runs mm² Ampacity (A) Factor Correction Derating factor * 43) (R) (X) Drop during Drop during
(In ≥ Ib) ure correction I2 ≤ 1.45 Iz (Z) (meters)
KW*10³ / (√3*V*COSØ*ƞ) (Amp) I2 = 1.45*In (1.0 factor (1.0 factor Conductor Iz ≥ In Normal Motor
Correction factor (Fg)
for Motor Load °C.m/W) °C.m/W) Ampacity Operation Starting
Factor (Ft)
(Fd) (Fth)
From To

2 150/70
300/150
900-900G03-SMDB1-LP-1 900-P413A (900-B902) 900-B903-SMDB1 178.11 KVA 400 257.09 400 Verified 580.00 3φ 4C XLPE

900-900G03-SMDB2-LP-2 900-P413A (900-B902) 900-B903-SMDB2 266.50 KVA 400 384.67 500 Verified 725.00 3φ 4C
2 XLPE

900-900G03-DB-E1-LP-3 900-P413E (900-B902) 900-B903-DB-E1 246.16 KVA 400 355.31 500 Verified 725.00 3φ 4C
2 XLPE
240/120
900-900G03-DB-N1-LP-4 900-B903-SMDB1 900-B903-DB-N1 49.84 KVA 400 71.94 100 Verified 145.00 3φ 4C 1 XLPE 50 Unarmoured 139 Cable Tray 1.15 0.72 0.83 115.09 166.88 Verified Verified 0.495 0.087 0.503 4 0.06

900-900G03-DB-N2-LP-5 900-B903-SMDB1 900-B903-DB-N2 20.77 KVA 400 29.99 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.72 0.83 46.37 67.23 Verified Verified 2.330 0.094 2.332 5 0.13

900-900G03-DB-N3-LP-6 900-B903-SMDB1 900-B903-DB-N3 33.16 KVA 400 47.86 80 Verified 116.00 3φ 4C 1 XLPE 25 Unarmoured 99 Cable Tray 1.15 0.72 0.83 81.97 118.86 Verified Verified 0.928 0.090 0.932 5 0.09

900-900G03-K72-LP-7 900-B903-SMDB1 900-B903-K72 (BAIN MARIE) 11.75 KVA 400 16.96 30 Verified 43.50 3φ 4C 1 XLPE 6 Unarmoured 41 Cable Tray 1.15 0.72 0.83 33.95 49.22 Verified Verified 3.930 0.099 3.931 41

900-900G03-K72-LP-8 900-B903-SMDB1 900-B903-K72 (BAIN MARIE) 11.75 KVA 400 16.96 30 Verified 43.50 3φ 4C 1 XLPE 6 Unarmoured 41 Cable Tray 1.15 0.72 0.83 33.95 49.22 Verified Verified 3.930 0.099 3.931 41 1.02

900-900G03-K69-LP-9 900-B903-SMDB1 900-B903-K69 (SALAD CUPBOARD) 1.25 KVA 230 3.14 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.72 0.83 25.67 37.22 Verified Verified 5.880 0.105 5.881 42 0.58

900-900G03-K69-LP-10 900-B903-SMDB1 900-B903-K69 (SALAD CUPBOARD) 1.25 KVA 230 3.14 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.72 0.83 25.67 37.22 Verified Verified 5.880 0.105 5.881 40 0.55

900-900G03-K61-LP-11 900-B903-SMDB1 900-B903-K61 (DISPLAY REFRIGIRATOR) 1.25 KVA 230 3.14 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.72 0.83 25.67 37.22 Verified Verified 5.880 0.105 5.881 40 0.55

900-900G03-K61-LP-12 900-B903-SMDB1 900-B903-K61 (DISPLAY REFRIGIRATOR) 1.25 KVA 230 3.14 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.72 0.83 25.67 37.22 Verified Verified 5.880 0.105 5.881 43 0.59

900-900G03-K55-LP-13 900-B903-SMDB1 900-B903-K55 (CASHIER STAND) 1.25 KVA 230 3.14 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.72 0.83 25.67 37.22 Verified Verified 5.880 0.105 5.881 44 0.61

900-900G03-K78-LP-14 900-B903-SMDB1 900-B903-K78 (SS HEAVY DUTY 4 HOT LATE) 13.00 KVA 400 18.76 30 Verified 43.50 3φ 4C 1 XLPE 6 Unarmoured 41 Cable Tray 1.15 0.72 0.83 33.95 49.22 Verified Verified 3.930 0.099 3.931 37 1.02

900-900G03-K79-LP-15 900-B903-SMDB1 900-B903-K79 (BAIN MARIE) 1.88 KVA 230 4.71 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.72 0.83 25.67 37.22 Verified Verified 5.880 0.105 5.881 37 0.77

900-900G03-K80-LP-16 900-B903-SMDB1 900-B903-K80 (ELECTRIC CONVECTION OVENS) 19.75 KVA 400 28.51 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.72 0.83 46.37 67.23 Verified Verified 2.330 0.094 2.332 37 0.93

900-900G03-K81-LP-17 900-B903-SMDB1 900-B903-K81 (ANALOGIC CONTROL PANEL) 1.75 KVA 230 4.39 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.72 0.83 25.67 37.22 Verified Verified 5.880 0.105 5.881 40 0.77

900-900G03-K82-LP-18 900-B903-SMDB1 900-B903-K82 (OVEN HOOD) 2.50 KVA 400 3.61 16 Verified 23.20 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.72 0.83 26.50 38.42 Verified Verified 5.880 0.105 5.881 41 0.32

900-900G03-K54-LP-19 900-B903-SMDB1 900-B903-K54 (AUTO VEG. PREP MACHINE) 1.38 KVA 400 1.98 16 Verified 23.20 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.72 0.83 26.50 38.42 Verified Verified 5.880 0.105 5.881 19 0.08

900-900G03-K58-LP-20 900-B903-SMDB1 900-B903-K58 (POTATO & CARROT PEELER) 1.38 KVA 400 1.98 16 Verified 23.20 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.72 0.83 26.50 38.42 Verified Verified 5.880 0.105 5.881 18 0.08

900-900G03-K59-LP-21 900-B903-SMDB1 900-B903-K59 (VEGETABLE DRYER) 0.46 KVA 400 0.67 16 Verified 23.20 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.72 0.83 26.50 38.42 Verified Verified 5.880 0.105 5.881 20 0.03

900-900G03-K60-LP-22 900-B903-SMDB1 900-B903-K60 (VEGETABLE WASHING MACHINE) 0.59 KVA 400 0.85 16 Verified 23.20 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.72 0.83 26.50 38.42 Verified Verified 5.880 0.105 5.881 21 0.04

900-900G03-K47-LP-23 900-B903-SMDB1 900-B903-K47 (COUNTER TOP BONE SAW) 1.00 KVA 400 1.44 16 Verified 23.20 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.72 0.83 26.50 38.42 Verified Verified 5.880 0.105 5.881 6 0.02

900-900G03-K34-LP-25 900-B903-SMDB1 900-B903-K34 (FOOD PROCESSOR CUTTER) 0.80 KVA 400 1.15 16 Verified 23.20 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.72 0.83 26.50 38.42 Verified Verified 5.880 0.105 5.881 6 0.02

900-900G03-K32-LP-26 900-B903-SMDB1 900-B903-K32 (MEAT MINCER) 2.20 KVA 400 3.18 16 Verified 23.20 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.72 0.83 26.50 38.42 Verified Verified 5.880 0.105 5.881 6 0.04

900-900G03-K93-LP-27 900-B903-SMDB2 900-B903-K93 (SS HEAVY DUTY BOILING PAN) 18.00 KVA 400 25.98 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.72 0.83 46.37 67.23 Verified Verified 2.330 0.094 2.332 36 0.82

900-900G03-K93-LP-28 900-B903-SMDB2 900-B903-K93 (SS HEAVY DUTY BOILING PAN) 18.00 KVA 400 25.98 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.72 0.83 46.37 67.23 Verified Verified 2.330 0.094 2.332 36 0.82

900-900G03-K101-LP-29 900-B903-SMDB2 900-B903-K101(SS SOLID TOP) 25.00 KVA 400 36.09 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.72 0.83 46.37 67.23 Verified Verified 2.330 0.094 2.332 34 1.08

900-900G03-K94-LP-30 900-B903-SMDB2 900-B903-K94 (SS HEAVY DUTY TILTING PAN) 15.00 KVA 400 21.65 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.72 0.83 46.37 67.23 Verified Verified 2.330 0.094 2.332 35 0.67

900-900G03-K102-LP-31 900-B903-SMDB2 900-B903-K102 (SS HEAVY DUTY HOT LATE WITH OVEN) 23.75 KVA 400 34.28 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.72 0.83 46.37 67.23 Verified Verified 2.330 0.094 2.332 36 1.08

900-900G03-K107-LP-32 900-B903-SMDB2 900-B903-K107 (PASTA COOKER) 22.50 KVA 400 32.48 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.72 0.83 46.37 67.23 Verified Verified 2.330 0.094 2.332 36 1.03

900-900G03-K95-LP-33 900-B903-SMDB2 900-B903-K95 (SS DEEP FRYER DOUBLE BOWL) 40.00 KVA 400 57.74 63 Verified 91.35 3φ 4C 1 XLPE 25 Unarmoured 99 Cable Tray 1.15 0.72 0.83 81.97 118.86 Verified Verified 0.928 0.090 0.932 36 0.75

900-900G03-K96-LP-34 900-B903-SMDB2 900-B903-K96 (SS LAVA STONE) 25.00 KVA 400 36.09 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.72 0.83 46.37 67.23 Verified Verified 2.330 0.094 2.332 38 1.21

900-900G03-K108-LP35 900-B903-SMDB2 900-B903-K108 (SS HEATED CABINET) 3.75 KVA 400 5.41 20 Verified 29.00 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.72 0.83 26.50 38.42 Verified Verified 5.880 0.011 5.880 33 0.39

900-900G03-K100-LP-36 900-B903-SMDB2 900-B903-K100 (SS SHIP DUMP) 1.69 KVA 230 4.23 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.72 0.83 25.67 37.22 Verified Verified 5.880 0.011 5.880 38 0.70

900-900G03-K100-LP-37 900-B903-SMDB2 900-B903-K100 (SS SHIP DUMP) 1.69 KVA 230 4.23 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.72 0.83 25.67 37.22 Verified Verified 5.880 0.011 5.880 39 0.72

900-900G03-K95-LP-38 900-B903-SMDB2 900-B903-K95 (SS DEEP FRYER DOUBLE BOWL) 40.00 KVA 400 57.74 63 Verified 91.35 3φ 4C 1 XLPE 25 Unarmoured 99 Cable Tray 1.15 0.72 0.83 81.97 118.86 Verified Verified 0.928 0.090 0.932 39 0.82

900-900G03-K97LP-39 900-B903-SMDB2 900-B903-K97 (SS GRIDDLE SMOOTH FREE STAND) 17.50 KVA 400 25.26 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.72 0.83 46.37 67.23 Verified Verified 2.330 0.094 2.332 39 0.87

900-900G03-K108-LP-40 900-B903-SMDB2 900-B903-K108 (SS HEATED CABINET) 3.75 KVA 400 5.41 20 Verified 29.00 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.72 0.83 26.50 38.42 Verified Verified 5.880 0.011 5.880 33 0.39

900-900G03-K103-LP-41 900-B903-SMDB2 900-B903-K103 (KITCHEN HOOD) 2.50 KVA 400 3.61 16 Verified 23.20 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.72 0.83 26.50 38.42 Verified Verified 5.880 0.011 5.880 34 0.27

900-900G03-K104-LP-42 900-B903-SMDB2 900-B903-K104 (BAIN MARIE) 11.75 KVA 400 16.96 30 Verified 43.50 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.72 0.83 46.37 67.23 Verified Verified 2.330 0.094 2.332 38 0.57

900-900G03-K104-LP-43 900-B903-SMDB2 900-B903-K104 (BAIN MARIE) 34.63 KVA 400 49.98 63 Verified 91.35 3φ 4C 1 XLPE 25 Unarmoured 99 Cable Tray 1.15 0.72 0.83 81.97 118.86 Verified Verified 0.928 0.090 0.932 24 0.43

900-900G03-K105-LP-44 900-B903-SMDB2 900-B903-K105 (OVEN HOOD) 1.25 KVA 400 1.80 16 Verified 23.20 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.72 0.83 26.50 38.42 Verified Verified 5.880 0.011 5.880 24 0.09

900-900G03-K-42-LP-44A 900-B903-SMDB2 900-B903-K-42(CONVEYOR DISHWASHER) 27.50 KVA 400 39.69 40 Verified 58.00 3φ 4C 1 XLPE 16 Unarmoured 74 Cable Tray 1.15 0.72 0.83 61.27 88.84 Verified Verified 0.928 0.090 0.932 38 0.55

It is NESMA's responsibility to include all cables in this document according to the


commented canteen building Load list and canteen building DB schedule.
900-B903-CANTEEN BUILDING

NEOM Green Hydrogen Company - Canteen Building Cable Sizing Calculation


Correction Factor

Full load Current, Ib Depth of Soil Adj. Amp. Iz %Vd %Vdst


Ambient
Equipment (Amp) Breaker convention Laying thermal (A) = Condition ‐2 Percentage Percentage
IEC60364‐4‐ grouond Cable Condition ‐3 Cable Cable
Ib =KVA*10³ / (√3*V) for size al tripping No. of No. of Size Conductor Correction Resistivity Total Derating (IEC60364‐4‐ Cable Resistance Cable Reactance Voltage Voltage
CIRCUIT No. Load Rating Voltage (Volt) Ist = 9.24 Ib 43, Phase Insulation Type of Cable Type of Installation Temparat Factor Correction grouping 1.45 x Iz (IEC60364‐4‐ 43) Impedance Length
non-Motor Load & Ib = In current, Cores Runs mm² Ampacity (A) Derating factor * 43) (R) (X) Drop during Drop during
(In ≥ Ib) ure correction I2 ≤ 1.45 Iz (Z) (meters)
KW*10³ / (√3*V*COSØ*ƞ) (Amp) I2 = 1.45*In (1.0 factor (1.0 factor Conductor Iz ≥ In Normal Motor
Correction factor (Fg)
for Motor Load °C.m/W) °C.m/W) Ampacity Operation Starting
Factor (Ft)
(Fd) (Fth)
From To

900-900G03-FZ-LP-45 900-B903-DB-N1 900-B903-FREEZER 6.25 KVA 400 9.02 20 Verified 29.00 3φ 4C 1 XLPE 4 Unarmoured 32 In Pipe 1.15 0.72 0.83 26.50 38.42 Verified Verified 5.880 0.011 5.880 31 0.61

900-900G03-MCS-LP-46 900-B903-DB-N1 900-B903-MEAT COLD STORAGE 5 KVA 400 7.22 20 Verified 29.00 3φ 4C 1 XLPE 4 Unarmoured 32 In Pipe 1.15 0.72 0.83 26.50 38.42 Verified Verified 5.880 0.011 5.880 27 0.42

900-900G03-VCS-LP-47 900-B903-DB-N1 900-B903-VEGETABLE COLD STORAGE 5 KVA 400 7.22 20 Verified 29.00 3φ 4C 1 XLPE 4 Unarmoured 32 In Pipe 1.15 0.72 0.83 26.50 38.42 Verified Verified 5.880 0.011 5.880 25 0.39

900-900G03-EDH-01-LP-48 900-B903-DB-N2 900-B903-EDH-01 11.25 KVA 400 19.10 30 Verified 43.50 3φ 4C 1 XLPE 6 Unarmoured 41 In Pipe 1.15 0.72 0.83 33.95 49.22 Verified Verified 3.930 0.099 3.931 25 0.70

900-900G03-EDH-02-LP-49 900-B903-DB-N2 900-B903-EDH-02 11.25 KVA 400 19.10 30 Verified 43.50 3φ 4C 1 XLPE 6 Unarmoured 41 In Pipe 1.15 0.72 0.83 33.95 49.22 Verified Verified 3.930 0.099 3.931 20 0.56

900-900G03-EDH-03-LP-50 900-B903-DB-N2 900-B903-EDH-03 5.5 KVA 400 9.34 20 Verified 29.00 3φ 4C 1 XLPE 6 Unarmoured 41 In Pipe 1.15 0.72 0.83 33.95 49.22 Verified Verified 3.930 0.099 3.931 11 0.15

900-900G03-EDH-04-LP-51 900-B903-DB-N2 900-B903-EDH-04 5.5 KVA 400 9.34 20 Verified 29.00 3φ 4C 1 XLPE 6 Unarmoured 41 In Pipe 1.15 0.72 0.83 33.95 49.22 Verified Verified 3.930 0.099 3.931 13 0.18

900-900G03-EF-01-LP-52 900-B903-DB-N3 900-B903-EF-01 0.22 KVA 230 1.13 6.98 16 Verified 23.20 1φ 3C 1 XLPE 4 Armoured 31 Cable Tray 1.15 0.72 0.83 25.67 37.22 Verified Verified 5.880 0.011 5.880 57 1.73

900-900G03-EF-03-LP-53 900-B903-DB-N3 900-B903-EF-03 0.05 KVA 230 0.26 1.59 16 Verified 23.20 1φ 3C 1 XLPE 4 Armoured 31 Cable Tray 1.15 0.72 0.83 25.67 37.22 Verified Verified 5.880 0.011 5.880 54 0.37

900-900G03-EF-08-LP-54 900-B903-DB-N3 900-B903-EF-08 0.13 KVA 230 0.66 4.12 16 Verified 23.20 1φ 3C 1 XLPE 4 Armoured 31 Cable Tray 1.15 0.72 0.83 25.67 37.22 Verified Verified 5.880 0.011 5.880 48 0.86

900-900G03-EF-06-LP-55 900-B903-DB-N3 900-B903-EF-06 2.75 KVA 400 4.67 28.95 16 Verified 23.20 3φ 4C 1 XLPE 6 Unarmoured 41 Cable Tray 1.15 0.72 0.83 33.95 49.22 Verified Verified 3.930 0.099 3.931 36 1.53

900-900G03-EF-07-LP-56 900-B903-DB-N3 900-B903-EF-07 0.5 KVA 400 0.85 5.26 16 Verified 23.20 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.72 0.83 26.50 38.42 Verified Verified 5.880 0.011 5.880 23 0.26

900-900G03-EF-04-LP-57 900-B903-DB-N3 900-B903-EF-04 0.56 KVA 230 2.86 17.76 16 Verified 23.20 1φ 3C 1 XLPE 4 Armoured 31 Cable Tray 1.15 0.72 0.83 25.67 37.22 Verified Verified 5.880 0.011 5.880 24 1.85

900-900G03-EF-02-LP-58 900-B903-DB-N3 900-B903-EF-02 0.06 KVA 230 0.31 1.90 16 Verified 23.20 1φ 3C 1 XLPE 4 Armoured 31 Cable Tray 1.15 0.72 0.83 25.67 37.22 Verified Verified 5.880 0.011 5.880 21 0.17

900-900G03-EF-09-LP-59 900-B903-DB-N3 900-B903-EF-09 0.37 KVA 230 1.89 11.73 16 Verified 23.20 1φ 3C 1 XLPE 4 Armoured 31 Cable Tray 1.15 0.72 0.83 25.67 37.22 Verified Verified 5.880 0.011 5.880 19 0.97

900-900G03-EF-05-LP-60 900-B903-DB-N3 900-B903-EF-05 0.05 KVA 230 0.26 1.59 16 Verified 23.20 1φ 3C 1 XLPE 4 Armoured 31 Cable Tray 1.15 0.72 0.83 25.67 37.22 Verified Verified 5.880 0.011 5.880 13 0.09

900-900G03-HWSP-1-LP-62 900-B903-DB-N3 HOT WATER RECIRCULATION PUMP SET-1 1.875 KVA 230 9.59 59.46 20 Verified 29.00 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.72 0.83 25.67 37.22 Verified Verified 5.880 0.011 5.880 33 8.54

900-900G03-EWH-1-LP-64 900-B903-DB-N3 900-B903-EWH-1 10.00 KVA 400 14.43 30 Verified 43.50 3φ 4C 1 XLPE 6 Unarmoured 41 Cable Tray 1.15 0.72 0.83 33.95 49.22 Verified Verified 5.880 0.011 5.880 29 0.91

900-900G03-EWH-2-LP-65 900-B903-DB-N3 900-B903-EWH-2 10.00 KVA 400 14.43 30 Verified 43.50 3φ 4C 1 XLPE 6 Unarmoured 41 Cable Tray 1.15 0.72 0.83 33.95 49.22 Verified Verified 5.880 0.011 5.880 30 0.94

900-900G03-EWH-3-LP-66 900-B903-DB-N3 900-B903-EWH-3 6.25 KVA 400 9.02 20 Verified 29.00 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.72 0.83 26.50 38.42 Verified Verified 5.880 0.011 5.880 29 0.57

900-900G03-EWH-4-LP-67 900-B903-DB-N3 900-B903-EWH-4 6.25 KVA 400 9.02 20 Verified 29.00 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.72 0.83 26.50 38.42 Verified Verified 5.880 0.011 5.880 29 0.57

900-900G03-SPU-OU-1A-LP-68 900-B903-DB-E1 900-B903-SPU-OU-1A 2.81 KVA 230 14.37 89.12 30 Verified 43.50 1φ 3C 1 XLPE 6 Armoured 39 Cable Tray 1.15 0.72 0.83 32.29 46.82 Verified Verified 3.930 0.099 3.931 15 3.94

900-900G03-SPU-OU-1B-LP-69 900-B903-DB-E1 900-B903-SPU-OU-1B 2.81 KVA 230 14.37 89.12 30 Verified 43.50 1φ 3C 1 XLPE 6 Armoured 39 Cable Tray 1.15 0.72 0.83 32.29 46.82 Verified Verified 3.930 0.099 3.931 13 3.42

900-900G03-SPU-OU-2A-LP-70 900-B903-DB-E1 900-B903-SPU-OU-2A 2.38 KVA 230 12.17 75.48 30 Verified 43.50 1φ 3C 1 XLPE 6 Armoured 39 Cable Tray 1.15 0.72 0.83 32.29 46.82 Verified Verified 3.930 0.099 3.931 50 11.13

900-900G03-SPU-OU-2B-LP-71 900-B903-DB-E1 900-B903-SPU-OU-2B 2.38 KVA 230 12.17 75.48 30 Verified 43.50 1φ 3C 1 XLPE 6 Armoured 39 Cable Tray 1.15 0.72 0.83 32.29 46.82 Verified Verified 3.930 0.099 3.931 55 12.25

900-900G03-SPU-OU-3 -LP-72 900-B903-DB-E1 900-B903-SPU-OU-3 2.43 KVA 230 12.43 77.06 30 Verified 43.50 1φ 3C 1 XLPE 6 Armoured 39 Cable Tray 1.15 0.72 0.83 32.29 46.82 Verified Verified 5.880 0.011 5.880 23 7.71

900-900G03-SPU-OU-4-LP-73 900-B903-DB-E1 900-B903-SPU-OU-4 2.81 KVA 230 14.37 89.12 30 Verified 43.50 1φ 3C 1 XLPE 6 Armoured 39 Cable Tray 1.15 0.72 0.83 32.29 46.82 Verified Verified 3.930 0.099 3.931 24 6.31

900-900G03-SPU-OU-5-LP-74 900-B903-DB-E1 900-B903-SPU-OU-5 2.38 KVA 230 12.17 75.48 30 Verified 43.50 1φ 3C 1 XLPE 6 Armoured 39 Cable Tray 1.15 0.72 0.83 32.29 46.82 Verified Verified 3.930 0.099 3.931 26 5.79

900-900G03-SPU-OU-6-LP-75 900-B903-DB-E1 900-B903-SPU-OU-6 2.81 KVA 230 14.37 89.12 30 Verified 43.50 1φ 3C 1 XLPE 6 Armoured 39 Cable Tray 1.15 0.72 0.83 32.29 46.82 Verified Verified 3.930 0.099 3.931 28 7.36

900-900G03-UPS-DDC-LP-76 900-B903-DB-E1 900-B903-UPS-DDC 2 KVA 230 10.23 30 Verified 43.50 1φ 3C 1 XLPE 6 Unarmoured 39 In Pipe 1.15 0.72 0.83 32.29 46.82 Verified Verified 3.930 0.099 3.931 3 0.09

900-900G03-PAU-01A-LP-77 900-B903-DB-E1 900-B903-PAU-01A (DUTY) 68.5 KVA 400 116.32 1074.82 125 Verified 181.25 3φ 4C 1 XLPE 95 Armoured 213 Cable Tray 1.15 0.72 0.83 176.36 255.73 Verified Verified 0.248 0.083 0.262 34 0.44 4.03

900-900G03-PAU-01B-LP-78 900-B903-DB-E1 900-B903-PAU-01B (STANDBY) 68.5 KVA 400 116.32 1074.82 125 Verified 181.25 3φ 4C 1 XLPE 95 Armoured 213 Cable Tray 1.15 0.72 0.83 176.36 255.73 Verified Verified 0.248 0.083 0.262 33 0.42 3.91

900-900G03-PAU-02A-LP-79 900-B903-DB-E1 900-B903-PAU-02A (DUTY) 71.12 KVA 400 120.77 1115.93 125 Verified 181.25 3φ 4C 1 XLPE 95 Armoured 213 Cable Tray 1.15 0.72 0.83 176.36 255.73 Verified Verified 0.248 0.083 0.262 22 0.29 2.70

900-900G03-PAU-02B-LP-80 900-B903-DB-E1 900-B903-PAU-02B (STANDBY) 71.12 KVA 400 120.77 1115.93 125 Verified 181.25 3φ 4C 1 XLPE 95 Armoured 213 Cable Tray 1.15 0.72 0.83 176.36 255.73 Verified Verified 0.248 0.083 0.262 16 0.21 1.97

900-900G03-MAU-01-LP-81 900-B903-DB-E1 900-B903-MAU-01 90.75 KVA 400 154.11 1423.94 200 Verified 290.00 3φ 4C 1 XLPE 120 Armoured 247 Cable Tray 1.15 0.72 0.83 204.52 296.55 Verified Verified 0.198 0.083 0.215 43 0.61 5.62

900-900G03-DB-E2-LP-82 900-B903-DB-E1 900-B903-DB-E2 11.77 KVA 400 16.99 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.72 0.83 46.37 67.23 Verified Verified 2.330 0.094 2.332 4 0.06

900-900G03-DAC01-LP-83 900-B903-DB-N3 900-B903-DAC-01 1 KVA 400 1.70 10.53 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.72 0.83 25.67 37.22 Verified Verified 5.880 0.011 5.880 29 0.66

900-900G03-DAC01-LP-84 900-B903-DB-N3 900-B903-DAC-01 1 KVA 400 1.70 10.53 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.72 0.83 25.67 37.22 Verified Verified 5.880 0.011 5.880 23 0.52

900-900G03-DAC01-LP-85 900-B903-DB-N3 900-B903-DAC-01 1 KVA 400 1.70 10.53 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.72 0.83 25.67 37.22 Verified Verified 5.880 0.011 5.880 19 0.43

900-900G03-UPS-IT-LP-61 900-B903-DB-E2 900-B903-UPS-IT 3 KVA 230 15.35 30 Verified 43.50 1φ 3C 1 XLPE 6 Unarmoured 39 Cable Tray 1.15 0.72 0.83 32.29 46.82 Verified Verified 5.880 0.011 5.880 4 0.27

900-900G03-DB-UPS-LP-86 900-B903-DB-E2 900-B903-DB-UPS 1.5 KVA 230 7.67 32 Verified 46.40 1φ 3C 1 XLPE 6 Unarmoured 39 Cable Tray 1.15 1.72 1.98 77.14 111.86 Verified Verified 5.880 0.011 5.880 5 0.17

UPS DB shall be fed from


DDC UPS shall be fed from
UPS only.
2nos. emergency supply.

RIO panel 2 nos. cables from


2nos. UPS DBs shall be
considered in cable sizing.
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev: 01

APPENDIX – 2

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri#en permission.
Single Core - Copper Conductor, XLPE Insulated Cables

Conductor : Round Stranded Copper


Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
1- Core CU/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1
Approx Nominal Nominal Approx. Approx.
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
1 x 1.5 7 1.6 0.7 1.4 6 50
1 x 2.5 7 2.0 0.7 1.4 7 70
1x4 7 2.6 0.7 1.4 7 80
1x6 7 3.1 0.7 1.4 8 110
1 x 10 7 4.0 0.7 1.4 9 150
1 x 16 7 5.0 0.7 1.4 10 210
1 x 25 7 6.3 0.9 1.4 11 310
1 x 35 7 7.4 0.9 1.4 13 410
1 x 50 19 8.8 1.0 1.4 14 530
1 x 70 19 10.6 1.1 1.4 16 740
1 x 95 19 12.4 1.1 1.5 18 1000
1 x 120 37 14.0 1.2 1.5 20 1240
1 x 150 37 15.5 1.4 1.6 22 1520
1 x 185 37 17.4 1.6 1.6 24 1890
1 x 240 61 20.3 1.7 1.7 28 2460
1 x 300 61 22.7 1.8 1.8 30 3060
1 x 400 61 25.4 2.0 1.9 34 3910
1 x 500 61 28.8 2.2 2.0 38 4980
1 x 630 61 30.4 2.4 2.2 40 6260
1 x 800 61 33.7 2.6 2.3 44 7950
*Overall Diameter Tolerence Range: [-2% , +6%]
Continuous Current Rating
Flat Flat Spaced
Nominal Trefoil in One Trefoil in Three Flat Spaced Flat Spaced Flat Touching
Trefoil [Gd] Touching in Three Trefoil [Air]
Area Duct [Gd] Ducts [Gd] [Gd] [Air] [Air]
[Gd] Ducts [Gd]
mm² Amps Amps Amps Amps Amps Amps Amps Amps Amps

1 x 1.5 22 21 21 22 24 21 18 25 19
1 x 2.5 29 27 29 29 31 27 25 34 26
1x4 38 34 37 37 39 35 32 44 33
1x6 47 43 45 47 49 44 42 56 43
1 x 10 62 57 59 61 65 57 58 77 59
1 x 16 80 73 77 79 83 75 76 101 79
1 x 25 102 94 98 100 106 95 100 133 103
1 x 35 122 113 119 120 128 115 127 166 131
1 x 50 144 134 139 142 150 135 153 200 157
1 x 70 176 164 172 173 184 167 195 254 201
1 x 95 211 197 204 206 220 199 241 313 248
1 x 120 240 225 234 234 251 228 282 365 291
1 x 150 268 253 261 262 281 256 325 418 335
1 x 185 302 286 297 295 318 291 375 482 387
1 x 240 351 333 347 341 371 341 455 583 470
1 x 300 392 373 393 381 417 385 517 667 535
1 x 400 443 423 448 430 476 441 605 781 625
1 x 500 496 475 515 481 541 505 697 909 721
1 x 630 547 525 574 530 606 566 777 1025 804
1 x 800 599 576 639 580 676 633 873 1167 903
- When cables are arranged in spaced flat formation they are spaced by one cable diameter.

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Multicore (Two & Three Cores) - Copper Conductor, XLPE Insulated Cables

Conductor : Round Stranded Copper


Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
2-Cores CU/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
2 x 1.5 7 1.6 0.7 1.8 13 190 22 21 21
2 x 2.5 7 2.0 0.7 1.8 13 240 29 27 29
2x4 7 2.6 0.7 1.8 14 290 38 34 37
2x6 7 3.1 0.7 1.8 16 350 47 43 45
2 x 10 7 4.0 0.7 1.8 17 480 62 57 59
2 x 16 7 5.0 0.7 1.8 19 650 80 73 77
2 x 25 7 6.3 0.9 1.8 23 930 102 94 98
2 x 35 7 7.4 0.9 1.8 25 1190 122 113 119
2 x 50 19 8.8 1.0 1.8 28 1540 144 134 139
2 x 70 19 10.6 1.1 1.8 32 2100 176 164 172
2 x 95 19 12.4 1.1 2.0 37 2830 211 197 204
2 x 120 37 14.0 1.2 2.1 40 3500 240 225 234
2 x 150 37 15.5 1.4 2.2 44 4260 268 253 261
2 x 185 37 17.4 1.6 2.3 50 5340 302 286 297
2 x 240 61 20.3 1.7 2.5 56 6900 351 333 347
2 x 300 61 22.7 1.8 2.7 62 8600 392 373 393
2 x 400 61 25.4 2.0 2.9 69 10830 443 423 448
2 x 500 61 28.8 2.2 3.1 77 13710 496 475 515
*Overall Diameter Tolerence Range: [-2% , +6%]

Conductor : Round Stranded Copper


Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
3-Cores CU/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
3 x 1.5 7 1.6 0.7 1.8 13 210 21 17 18
3 x 2.5 7 2.0 0.7 1.8 14 260 27 23 24
3x4 7 2.6 0.7 1.8 15 330 35 29 31
3x6 7 3.1 0.7 1.8 16 410 44 37 39
3 x 10 7 4.0 0.7 1.8 18 570 58 49 54
3 x 16 7 5.0 0.7 1.8 20 790 75 63 71
3 x 25 7 6.3 0.9 1.8 24 1160 98 82 96
3 x 35 7 7.4 0.9 1.8 27 1380 115 99 115
3 x 50 19 8.8 1.0 1.8 30 1790 137 118 140
3 x 70 19 10.6 1.1 1.9 35 2510 167 146 176
3 x 95 19 12.4 1.1 2.0 39 3350 200 176 216
3 x 120 37 14.0 1.2 2.1 43 4150 227 201 251
3 x 150 37 15.5 1.4 2.3 48 5120 254 227 285
3 x 185 37 17.4 1.6 2.4 53 6360 286 257 327
3 x 240 61 20.3 1.7 2.6 60 8280 330 299 386
3 x 300 61 22.7 1.8 2.8 67 10270 370 339 441
3 x 400 61 25.4 2.0 3.1 74 13040 414 383 502
3 x 500 61 28.8 2.2 3.3 83 16610 462 431 569
*Overall Diameter Tolerence Range: [-2% , +6%]

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Multicore (Three and half & Four Cores) - Copper Conductor, XLPE Insulated Cables

Conductor : Round Stranded Copper


Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
3½ -Cores CU/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Outer Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
Sheath Overall
Area* [Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne] Weight Amps Amps Amps
Thickness Diameter**

mm² No. mm mm mm mm kg/km


3x16+10 7/7 5/4 0.7 / 0.7 1.8 22 900 76 64 73
3x25+16 7/7 6.3 / 5 0.9 / 0.7 1.8 25 1320 98 83 97
3x35+16 7/7 6.6 / 5 0.9 / 0.7 1.8 25 1470 114 97 112
3x50+25 19 / 7 7.5 / 6.3 1.0 / 0.9 1.8 29 1950 135 117 137
3x70+35 19 / 7 9.1 / 7.4 1.1 / 0.9 1.9 33 2740 165 143 172
3x95+50 19 / 19 11 / 8.8 1.1 / 1.0 2.1 37 3670 198 173 211
3x120+70 37 / 19 12.2 / 10.6 1.2 / 1.1 2.2 41 4620 225 197 244
3x150+70 37 / 19 13.8 / 10.6 1.4 / 1.1 2.3 45 5580 251 224 278
3x185+95 37 / 19 15.1 / 12.4 1.6 / 1.1 2.5 50 7000 283 253 318
3x240+120 61 / 37 17.6 / 14 1.7 / 1.2 2.7 55 9040 326 294 373
3x300+150 61 / 37 19.8 / 15.5 1.8 / 1.4 2.9 61 11180 366 333 426
3x400+185 61 / 37 22.2 / 17.4 2.0 / 1.6 3.1 68 14160 412 379 490
3x500+240 61 / 61 26.3 / 20.3 2.2 / 1.7 3.4 76 18070 462 428 558
2
*Sectoral Shape for conductor size > 25 mm
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral

Conductor : Round Stranded Copper


Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
4-Cores CU/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Sheath Diameter** Weight
mm² No. mm mm mm mm kg/km
4 x 1.5 7 1.6 0.7 1.8 14 240 21 18 18
4 x 2.5 7 2.0 0.7 1.8 15 310 28 23 24
4x4 7 2.6 0.7 1.8 16 390 36 30 32
4x6 7 3.1 0.7 1.8 18 500 45 37 41
4 x 10 7 4.0 0.7 1.8 20 700 59 50 56
4 x 16 7 5.0 0.7 1.8 22 980 77 64 74
4 x 25 7 6.3 0.9 1.8 26 1450 99 84 99
4 x 35 7 6.6 0.9 1.8 26 1650 115 98 114
4 x 50 19 7.5 1.0 1.9 30 2160 136 117 139
4 x 70 19 9.1 1.1 2.0 34 3060 166 144 173
4 x 95 19 11.0 1.1 2.1 38 4100 199 175 213
4 x 120 37 12.2 1.2 2.3 43 5130 225 199 247
4 x 150 37 13.8 1.4 2.4 47 6320 253 225 281
4 x 185 37 15.1 1.6 2.6 52 7830 284 256 322
4 x 240 61 17.6 1.7 2.8 58 10180 328 298 378
4 x 300 61 19.8 1.8 3.0 64 12610 368 337 433
4 x 400 61 22.2 2.0 3.3 73 16120 415 384 497
4 x 500 61 26.3 2.2 3.5 80 20380 465 433 566
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Multicore (Five Cores) - Copper Conductor, XLPE Insulated Cables

Conductor : Round Stranded Copper


Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
5-Cores CU/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
5 x 1.5 7 1.6 0.7 1.8 15 280 21 18 19
5 x 2.5 7 2.0 0.7 1.8 16 360 28 23 25
5x4 7 2.6 0.7 1.8 17 460 36 30 33
5x6 7 3.1 0.7 1.8 19 590 45 38 42
5 x 10 7 4.0 0.7 1.8 21 840 60 50 57
5 x 16 7 5.0 0.7 1.8 24 1190 78 66 76
5 x 25 7 6.3 0.9 1.8 28 1770 100 85 102
5 x 35 7 7.4 0.9 1.8 32 2180 120 104 126
5 x 50 19 8.8 1.0 2.0 37 2920 142 124 154
5 x 70 19 10.6 1.1 2.1 42 4050 174 153 194
5 x 95 19 12.4 1.1 2.3 48 5510 208 186 238
5 x 120 37 14.0 1.2 2.4 53 6850 237 212 277
5 x 150 37 15.5 1.4 2.6 58 8380 265 239 315
5 x 185 37 17.4 1.6 2.8 65 10520 299 272 362
5 x 240 61 20.3 1.7 3.0 74 13620 346 318 431
5 x 300 61 22.7 1.8 3.2 82 16990 387 359 491
5 x 400 61 25.4 2.0 3.6 91 21640 434 406 560
5 x 500 61 28.8 2.2 3.8 102 27450 486 459 639
*Overall Diameter Tolerence Range: [-2% , +6%]

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Single Core - Copper Conductor, PVC Insulated Cables

Conductor : Round Stranded Copper


Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
1-Core CU/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1
Approx Nominal Nominal Approx. Approx.
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
1 x 1.5 7 1.6 0.8 1.4 6 60
1 x 2.5 7 2.0 0.8 1.4 7 70
1x4 7 2.6 1.0 1.4 8 100
1x6 7 3.1 1.0 1.4 8 120
1 x 10 7 4.0 1.0 1.4 9 170
1 x 16 7 5.0 1.0 1.4 10 230
1 x 25 7 6.3 1.2 1.4 12 340
1 x 35 7 7.4 1.2 1.4 13 440
1 x 50 19 8.8 1.4 1.4 15 580
1 x 70 19 10.6 1.4 1.4 17 790
1 x 95 19 12.4 1.6 1.5 19 1080
1 x 120 37 14.0 1.6 1.5 21 1320
1 x 150 37 15.5 1.8 1.6 23 1610
1 x 185 37 17.4 2.0 1.7 25 2010
1 x 240 61 20.3 2.2 1.8 29 2620
1 x 300 61 22.7 2.4 1.9 32 3260
1 x 400 61 25.4 2.6 2.0 35 4140
1 x 500 61 28.8 2.8 2.1 39 5260
1 x 630 61 30.4 2.8 2.2 41 6470
1 x 800 61 33.7 2.8 2.3 44 8160
*Overall Diameter Tolerence Range: [-2% , +6%]
Continuous Current Rating
Flat Flat Spaced
Nominal Trefoil in One Trefoil in Three Flat Spaced Flat Spaced Flat Touching
Trefoil [Gd] Touching in Three Trefoil [Air]
Area Duct [Gd] Ducts [Gd] [Gd] [Air] [Air]
[Gd] Ducts [Gd]
mm² Amps Amps Amps Amps Amps Amps Amps Amps Amps

1 x 1.5 18 16 17 18 19 16 11 15 12
1 x 2.5 23 21 23 23 24 22 15 21 16
1x4 30 28 29 30 31 28 21 27 21
1x6 37 34 36 37 39 34 25 34 26
1 x 10 49 45 47 49 51 46 35 47 36
1 x 16 63 58 61 62 66 59 46 62 48
1 x 25 81 75 78 80 85 76 63 83 65
1 x 35 97 90 94 95 101 91 77 101 79
1 x 50 115 107 111 113 120 108 95 123 98
1 x 70 141 132 137 138 147 133 121 156 124
1 x 95 168 158 164 164 175 160 149 191 153
1 x 120 191 180 186 187 200 182 174 224 180
1 x 150 214 202 210 209 224 205 200 256 206
1 x 185 241 228 236 235 253 232 230 294 237
1 x 240 279 265 279 271 295 273 277 354 286
1 x 300 313 298 316 304 333 309 319 408 330
1 x 400 351 336 359 341 378 352 367 472 379
1 x 500 392 376 407 380 428 401 422 548 436
1 x 630 433 416 453 420 480 449 472 621 488
1 x 800 471 453 504 456 533 500 524 703 542
- When cables are arranged in spaced flat formation they are spaced by one cable diameter.

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Multicore (Two & Three Cores) - Copper Conductor, PVC Insulated Cables

Conductor : Round Stranded Copper


Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
2-Cores CU/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
2 x 1.5 7 1.6 0.8 1.8 13 210 19 16 13
2 x 2.5 7 2.0 0.8 1.8 14 250 25 21 17
2x4 7 2.6 1.0 1.8 16 340 33 28 23
2x6 7 3.1 1.0 1.8 17 410 41 35 29
2 x 10 7 4.0 1.0 1.8 19 540 55 47 39
2 x 16 7 5.0 1.0 1.8 21 720 71 60 52
2 x 25 7 6.3 1.2 1.8 24 1030 91 78 69
2 x 35 7 7.4 1.2 1.8 26 1300 109 94 84
2 x 50 19 8.8 1.4 1.8 30 1700 130 113 103
2 x 70 19 10.6 1.4 1.9 33 2260 159 139 129
2 x 95 19 12.4 1.6 2.0 39 3080 191 169 160
2 x 120 37 14.0 1.6 2.1 42 3740 217 193 185
2 x 150 37 15.5 1.8 2.2 46 4540 243 217 211
2 x 185 37 17.4 2.0 2.4 51 5690 273 247 241
2 x 240 61 20.3 2.2 2.6 58 7370 316 288 286
2 x 300 61 22.7 2.4 2.7 65 9160 355 326 327
2 x 400 61 25.4 2.6 3.0 71 11510 398 368 373
2 x 500 61 28.8 2.8 3.2 80 14580 445 415 425
*Overall Diameter Tolerence Range: [-2% , +6%]

Conductor : Round Stranded Copper


Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
3-Cores CU/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
3 x 1.5 7 1.6 0.8 1.8 13 240 16 14 11
3 x 2.5 7 2.0 0.8 1.8 14 290 21 18 15
3x4 7 2.6 1.0 1.8 16 390 28 24 19
3x6 7 3.1 1.0 1.8 18 480 35 29 25
3 x 10 7 4.0 1.0 1.8 20 650 46 39 34
3 x 16 7 5.0 1.0 1.8 22 880 60 50 45
3 x 25 7 6.3 1.2 1.8 25 1280 77 65 59
3 x 35 7 7.4 1.2 1.8 28 1500 91 78 72
3 x 50 19 8.8 1.4 1.8 32 1950 108 94 87
3 x 70 19 10.6 1.4 2.0 36 2700 132 116 109
3 x 95 19 12.4 1.6 2.1 41 3630 158 139 134
3 x 120 37 14.0 1.6 2.2 45 4440 180 160 156
3 x 150 37 15.5 1.8 2.3 50 5440 201 180 178
3 x 185 37 17.4 2.0 2.5 55 6760 226 205 203
3 x 240 61 20.3 2.2 2.7 63 8800 261 238 240
3 x 300 61 22.7 2.4 2.9 69 10920 291 268 273
3 x 400 61 25.4 2.6 3.1 76 13770 327 304 311
3 x 500 61 28.8 2.8 3.4 86 17520 364 341 353
*Overall Diameter Tolerence Range: [-2% , +6%]

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Multicore (Three and half & Four Cores) - Copper Conductor, PVC Insulated Cables

Conductor : Round Stranded Copper


Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
3½ -Cores CU/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Outer Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
Sheath Overall
Area* [Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne] Weight Amps Amps Amps
Thickness Diameter**

mm² No. mm mm mm mm kg/km


3x16+10 7/7 5/4 1.0 / 1.0 1.8 23 1010 60 51 46
3x25+16 7/7 6.3 / 5 1.2 / 1.0 1.8 27 1460 78 67 61
3x35+16 7/7 6.6 / 5 1.2 / 1.0 1.8 27 1600 90 78 70
3x50+25 19 / 7 7.5 / 6.3 1.4 / 1.2 1.9 31 2150 107 93 86
3x70+35 19 / 7 9.1 / 7.4 1.4 / 1.2 2.0 35 2950 131 115 107
3x95+50 19 / 19 11 / 8.8 1.6 / 1.4 2.2 39 3980 156 138 131
3x120+70 37 / 19 12.2 / 10.6 1.6 / 1.4 2.3 43 4980 177 157 152
3x150+70 37 / 19 13.8 / 10.6 1.8 / 1.4 2.4 47 5950 198 177 173
3x185+95 37 / 19 15.1 / 12.4 2.0 / 1.6 2.6 52 7440 223 202 198
3x240+120 61 / 37 17.6 / 14 2.2 / 1.6 2.8 58 9600 257 234 232
3x300+150 61 / 37 19.8 / 15.5 2.4 / 1.8 3.0 64 11880 288 265 265
3x400+185 61 / 37 22.2 / 17.4 2.6 / 2.0 3.2 72 15060 325 300 304
3x500+240 61 / 61 26.3 / 20.3 2.8 / 2.2 3.5 79 19050 363 337 346
2
*Sectoral Shape for conductor size > 25 mm
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral

Conductor : Round Stranded Copper


Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
4-Cores CU/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Sheath Diameter** Weight
mm² No. mm mm mm mm kg/km
4 x 1.5 7 1.6 0.8 1.8 14 270 17 14 11
4 x 2.5 7 2.0 0.8 1.8 15 340 22 18 15
4x4 7 2.6 1.0 1.8 18 470 28 24 20
4x6 7 3.1 1.0 1.8 19 580 35 30 25
4 x 10 7 4.0 1.0 1.8 21 800 47 40 35
4 x 16 7 5.0 1.0 1.8 24 1090 61 52 46
4 x 25 7 6.3 1.2 1.8 28 1600 78 67 62
4 x 35 7 6.6 1.2 1.8 28 1790 91 78 71
4 x 50 19 7.5 1.4 1.9 32 2390 107 94 86
4 x 70 19 9.1 1.4 2.1 36 3280 131 115 108
4 x 95 19 11.0 1.6 2.2 41 4430 157 139 133
4 x 120 37 12.2 1.6 2.4 45 5470 178 159 154
4 x 150 37 13.8 1.8 2.5 49 6720 199 179 175
4 x 185 37 15.1 2.0 2.7 55 8360 224 204 201
4 x 240 61 17.6 2.2 2.9 61 10790 259 237 236
4 x 300 61 19.8 2.4 3.1 67 13370 290 267 269
4 x 400 61 22.2 2.6 3.4 76 17030 327 304 309
4 x 500 61 26.3 2.8 3.6 83 21440 365 342 351
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Multicore (Five Cores) - Copper Conductor, PVC Insulated Cables

Conductor : Round Stranded Copper


Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
5-Cores CU/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
5 x 1.5 7 1.6 0.8 1.8 15 310 17 14 12
5 x 2.5 7 2.0 0.8 1.8 16 400 22 19 15
5x4 7 2.6 1.0 1.8 19 550 29 24 21
5x6 7 3.1 1.0 1.8 20 690 36 30 26
5 x 10 7 4.0 1.0 1.8 23 960 47 40 36
5 x 16 7 5.0 1.0 1.8 26 1330 61 53 48
5 x 25 7 6.3 1.2 1.8 30 1960 79 68 63
5 x 35 7 7.4 1.2 1.9 33 2390 95 82 78
5 x 50 19 8.8 1.4 2.1 39 3210 112 99 95
5 x 70 19 10.6 1.4 2.2 44 4360 138 122 120
5 x 95 19 12.4 1.6 2.4 51 5980 165 148 148
5 x 120 37 14.0 1.6 2.5 55 7320 187 169 171
5 x 150 37 15.5 1.8 2.7 61 8990 209 191 195
5 x 185 37 17.4 2.0 2.9 68 11180 236 217 224
5 x 240 61 20.3 2.2 3.1 77 14480 273 253 266
5 x 300 61 22.7 2.4 3.3 85 18080 305 284 302
5 x 400 61 25.4 2.6 3.7 95 22910 343 323 345
5 x 500 61 28.8 2.8 4.0 106 29110 382 362 391
*Overall Diameter Tolerence Range: [-2% , +6%]

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Single Core - Copper Conductor, XLPE Insulated Cables [90oC]

Electrical Parameters [TOUCHED Cables in Trefoil & Flat Formation ]


DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance o Capacitance Current
Area [60 Hz] [90 C] 3-φ 1-φ Resistance [20oC]
[20 oC] o
[90 C] [90 oC] [Conductor]
mm² Ω /km Ω /km Ω /km mH/km Ω /km Ω /km V/A/km V/A/km µF/km MΩ
Ω .km kA
1 x 1.5 12.10 15.43 15.43 0.597 0.225 15.43 21.61 24.96 0.103 1045 0.21
1 x 2.5 7.41 9.45 9.45 0.546 0.206 9.45 13.31 15.37 0.114 840 0.36
1x4 4.61 5.88 5.88 0.514 0.194 5.88 8.35 9.64 0.121 720 0.57
1x6 3.08 3.93 3.93 0.474 0.179 3.93 5.63 6.50 0.131 585 0.86
1 x 10 1.83 2.33 2.33 0.439 0.165 2.34 3.41 3.93 0.140 475 1.43
1 x 16 1.15 1.47 1.47 0.407 0.153 1.48 2.19 2.53 0.149 385 2.29
1 x 25 0.727 0.927 0.927 0.387 0.146 0.939 1.44 1.66 0.147 400 3.58
1 x 35 0.524 0.668 0.668 0.365 0.138 0.683 1.07 1.24 0.153 340 5.01
1 x 50 0.387 0.494 0.494 0.353 0.133 0.511 0.823 0.950 0.155 330 7.15
1 x 70 0.268 0.342 0.342 0.336 0.127 0.365 0.606 0.700 0.157 310 10.02
1 x 95 0.193 0.246 0.247 0.321 0.121 0.275 0.468 0.541 0.162 260 13.59
1 x 120 0.153 0.195 0.197 0.305 0.115 0.228 0.392 0.452 0.163 255 17.17
1 x 150 0.124 0.158 0.160 0.307 0.116 0.198 0.342 0.395 0.161 270 21.46
1 x 185 0.0991 0.126 0.129 0.298 0.112 0.171 0.295 0.340 0.161 275 26.47
1 x 240 0.0754 0.0961 0.0992 0.292 0.110 0.148 0.252 0.291 0.163 255 34.34
1 x 300 0.0601 0.0766 0.0807 0.281 0.106 0.133 0.222 0.256 0.165 240 42.93
1 x 400 0.0470 0.0599 0.0650 0.280 0.105 0.123 0.199 0.230 0.165 235 57.23
1 x 500 0.0366 0.0467 0.0529 0.278 0.105 0.118 0.182 0.211 0.166 230 71.54
1 x 630 0.0283 0.0361 0.0436 0.276 0.104 0.113 0.168 0.195 0.166 235 90.14
1 x 800 0.0221 0.0282 0.0368 0.275 0.104 0.110 0.159 0.184 0.166 230 114.47

Electrical Parameters [SPACED Cables in Trefoil & Flat Formation ]


DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance o Capacitance Current
Area [60 Hz] [90 C] 3-φ 1-φ Resistance [20oC]
[20 oC] [90 oC] [90 oC] [Conductor]
mm² Ω /km Ω /km Ω /km mH/km Ω /km Ω /km V/A/km V/A/km µF/km MΩ
Ω .km kA
1 x 1.5 12.10 15.43 15.43 0.782 0.295 15.43 21.69 24.96 0.103 1045 0.21
1 x 2.5 7.41 9.45 9.45 0.731 0.276 9.45 13.38 15.37 0.114 840 0.36
1x4 4.61 5.88 5.88 0.699 0.264 5.88 8.42 9.64 0.121 720 0.57
1x6 3.08 3.93 3.93 0.659 0.248 3.94 5.70 6.50 0.131 585 0.86
1 x 10 1.83 2.33 2.33 0.624 0.235 2.35 3.48 3.93 0.140 475 1.43
1 x 16 1.15 1.47 1.47 0.592 0.223 1.48 2.26 2.53 0.149 385 2.29
1 x 25 0.727 0.927 0.927 0.572 0.216 0.952 1.51 1.66 0.147 400 3.58
1 x 35 0.524 0.668 0.668 0.550 0.207 0.700 1.14 1.24 0.153 340 5.01
1 x 50 0.387 0.494 0.494 0.538 0.203 0.534 0.895 0.950 0.155 330 7.15
1 x 70 0.268 0.342 0.342 0.520 0.196 0.394 0.678 0.700 0.157 310 10.02
1 x 95 0.193 0.246 0.247 0.506 0.191 0.312 0.541 0.541 0.162 260 13.59
1 x 120 0.153 0.195 0.196 0.489 0.185 0.269 0.465 0.452 0.163 255 17.17
1 x 150 0.124 0.158 0.159 0.492 0.186 0.245 0.415 0.395 0.161 270 21.46
1 x 185 0.0991 0.126 0.128 0.483 0.182 0.222 0.367 0.340 0.161 275 26.47
1 x 240 0.0754 0.0961 0.0978 0.477 0.180 0.205 0.325 0.291 0.163 255 34.34
1 x 300 0.0601 0.0766 0.0788 0.466 0.176 0.193 0.295 0.256 0.165 240 42.93
1 x 400 0.0470 0.0599 0.0626 0.464 0.175 0.186 0.272 0.230 0.165 235 57.23
1 x 500 0.0366 0.0467 0.0500 0.463 0.174 0.181 0.254 0.211 0.166 230 71.54
1 x 630 0.0283 0.0361 0.0402 0.461 0.174 0.179 0.241 0.195 0.166 235 90.14
1 x 800 0.0221 0.0282 0.0331 0.460 0.173 0.176 0.231 0.184 0.166 230 114.47

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Single Core - Copper Conductor, PVC Insulated Cables [70oC]

Electrical Parameters [TOUCHED Cables in Trefoil & Flat Formation ]


DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance o Capacitance o Current
Area o [60 Hz] [70 C] 3-φ 1-φ Resistance [20 C]
[20 C] [70 oC] [70 oC] [Conductor]
mm² Ω /km Ω /km Ω /km mH/km Ω /km Ω /km V/A/km V/A/km µF/km MΩ
Ω .km kA
1 x 1.5 12.10 14.48 14.48 0.597 0.225 14.48 20.30 23.43 0.315 15.0 0.17
1 x 2.5 7.41 8.87 8.87 0.546 0.206 8.87 12.50 14.43 0.348 10.0 0.29
1x4 4.61 5.52 5.52 0.514 0.194 5.52 7.85 9.06 0.346 10.0 0.46
1x6 3.08 3.69 3.69 0.489 0.184 3.69 5.30 6.17 0.375 10.0 0.69
1 x 10 1.83 2.19 2.19 0.452 0.171 2.20 3.21 3.71 0.405 10.0 1.15
1 x 16 1.15 1.38 1.38 0.420 0.158 1.39 2.07 2.39 0.434 10.0 1.84
1 x 25 0.727 0.870 0.870 0.387 0.146 0.882 1.36 1.57 0.437 5.1 2.88
1 x 35 0.524 0.627 0.627 0.376 0.142 0.643 1.02 1.17 0.459 5.0 4.03
1 x 50 0.387 0.463 0.463 0.353 0.133 0.482 0.780 0.901 0.458 5.0 5.75
1 x 70 0.268 0.321 0.321 0.336 0.127 0.346 0.577 0.667 0.477 5.0 8.05
1 x 95 0.193 0.231 0.232 0.329 0.124 0.263 0.450 0.52 0.482 5.0 10.93
1 x 120 0.153 0.183 0.186 0.312 0.118 0.219 0.378 0.437 0.494 5.0 13.8
1 x 150 0.124 0.148 0.150 0.307 0.116 0.190 0.329 0.38 0.492 5.0 17.25
1 x 185 0.0991 0.119 0.121 0.305 0.115 0.167 0.287 0.331 0.493 5.0 21.28
1 x 240 0.0754 0.0902 0.0934 0.298 0.112 0.146 0.246 0.284 0.498 5.0 27.6
1 x 300 0.0601 0.0719 0.0759 0.292 0.110 0.134 0.219 0.253 0.502 5.0 34.5
1 x 400 0.047 0.0562 0.0612 0.289 0.109 0.125 0.198 0.229 0.505 5.0 41.12
1 x 500 0.0366 0.0438 0.0501 0.282 0.106 0.117 0.180 0.207 0.510 5.0 51.4
1 x 630 0.0283 0.0339 0.0414 0.280 0.106 0.114 0.168 0.193 0.515 5.0 64.77
1 x 800 0.0221 0.0264 0.0353 0.275 0.104 0.110 0.157 0.181 0.525 5.0 82.24

Electrical Parameters [SPACED Cables in Trefoil & Flat Formation ]


DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance o Capacitance Current
Area [60 Hz] [70 C] 3-φ 1-φ Resistance [20oC]
[20 oC] [70 oC] [70 oC] [Conductor]
mm² Ω /km Ω /km Ω /km mH/km Ω /km Ω /km V/A/km V/A/km µF/km MΩ
Ω .km kA
1 x 1.5 12.10 14.48 14.48 0.782 0.295 14.48 20.37 23.43 0.315 15.0 0.17
1 x 2.5 7.41 8.87 8.87 0.731 0.276 8.87 12.57 14.43 0.348 10.0 0.29
1x4 4.61 5.52 5.52 0.699 0.264 5.52 7.92 9.06 0.346 10.0 0.46
1x6 3.08 3.69 3.69 0.674 0.254 3.69 5.37 6.17 0.375 10.0 0.69
1 x 10 1.83 2.19 2.19 0.637 0.240 2.20 3.28 3.71 0.405 10.0 1.15
1 x 16 1.15 1.38 1.38 0.605 0.228 1.40 2.14 2.39 0.434 10.0 1.84
1 x 25 0.727 0.870 0.870 0.572 0.216 0.900 1.43 1.57 0.437 5.1 2.88
1 x 35 0.524 0.627 0.627 0.561 0.211 0.662 1.09 1.17 0.459 5.0 4.03
1 x 50 0.387 0.463 0.463 0.538 0.203 0.506 0.853 0.901 0.458 5.0 5.75
1 x 70 0.268 0.321 0.321 0.520 0.196 0.376 0.649 0.667 0.477 5.0 8.05
1 x 95 0.193 0.231 0.232 0.514 0.194 0.302 0.523 0.52 0.482 5.0 10.93
1 x 120 0.153 0.183 0.184 0.497 0.187 0.262 0.450 0.437 0.494 5.0 13.8
1 x 150 0.124 0.148 0.149 0.492 0.186 0.239 0.401 0.38 0.492 5.0 17.25
1 x 185 0.0991 0.119 0.120 0.489 0.185 0.220 0.360 0.331 0.493 5.0 21.28
1 x 240 0.0754 0.0902 0.0920 0.483 0.182 0.204 0.319 0.284 0.498 5.0 27.6
1 x 300 0.0601 0.0719 0.0741 0.477 0.180 0.195 0.292 0.253 0.502 5.0 34.5
1 x 400 0.047 0.0562 0.0590 0.474 0.179 0.188 0.271 0.229 0.505 5.0 41.12
1 x 500 0.0366 0.0438 0.0473 0.467 0.176 0.182 0.252 0.207 0.510 5.0 51.4
1 x 630 0.0283 0.0339 0.0381 0.465 0.175 0.179 0.239 0.193 0.515 5.0 64.77
1 x 800 0.0221 0.0264 0.0316 0.460 0.173 0.176 0.229 0.181 0.525 5.0 82.24

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Multicore - Copper Conductor, XLPE Insulated Cables [90oC]
Electrical Parameters
DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance o Capacitance o Current
Area o [60 Hz] [90 C] 3-φ 1-φ Resistance [20 C]
[20 C] [90 oC] [90 oC] [Conductor]
mm² Ω /km Ω /km Ω /km mH/km Ω /km Ω /km V/A/km V/A/km µF/km MΩ
Ω .km kA
1.5 12.10 15.43 15.43 0.319 0.120 15.43 21.50 24.83 0.103 1045 0.21
2.5 7.41 9.45 9.45 0.294 0.111 9.45 13.21 15.25 0.114 840 0.36
4 4.61 5.88 5.88 0.279 0.105 5.88 8.25 9.53 0.121 720 0.57
6 3.08 3.93 3.93 0.262 0.099 3.93 5.55 6.40 0.131 585 0.86
10 1.83 2.33 2.33 0.248 0.094 2.33 3.33 3.85 0.140 475 1.43
16 1.15 1.47 1.47 0.237 0.089 1.47 2.13 2.45 0.149 385 2.29
25 0.727 0.927 0.928 0.239 0.090 0.932 1.38 1.59 0.147 400 3.58
35 0.524 0.668 0.669 0.231 0.087 0.675 1.02 1.18 0.153 340 5.01
50 0.387 0.494 0.495 0.230 0.087 0.502 0.775 0.895 0.155 330 7.15
70 0.268 0.342 0.343 0.227 0.086 0.354 0.565 0.652 0.157 310 10.02
95 0.193 0.246 0.248 0.221 0.083 0.262 0.430 0.497 0.162 260 13.59
120 0.153 0.195 0.198 0.220 0.083 0.214 0.360 0.416 0.163 255 17.17
150 0.124 0.158 0.161 0.222 0.084 0.182 0.311 0.359 0.161 270 21.46
185 0.0991 0.126 0.130 0.223 0.084 0.155 0.268 0.309 0.161 275 26.47
240 0.0754 0.0961 0.101 0.220 0.083 0.131 0.227 0.262 0.163 255 34.34
300 0.0601 0.0766 0.0830 0.218 0.082 0.117 0.200 0.231 0.165 240 42.93
400 0.0470 0.0599 0.0678 0.218 0.082 0.106 0.179 0.207 0.165 235 57.23
500 0.0366 0.0467 0.0562 0.217 0.082 0.099 0.163 0.188 0.166 230 71.54

Multicore - Copper Conductor, PVC Insulated Cables [70oC]


Electrical Parameters
DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance o Capacitance o Current
Area [60 Hz] [70 C] 3-φ 1-φ Resistance [20 C]
[20 oC] [70 oC] [70 oC] [Conductor]
mm² Ω /km Ω /km Ω /km mH/km Ω /km Ω /km V/A/km V/A/km µF/km MΩ
Ω .km kA
1.5 12.10 14.48 14.4777 0.332 0.125 14.478 20.191 23.31 0.315 15.0 0.17
2.5 7.41 8.87 8.8661 0.305 0.115 8.867 12.405 14.32 0.348 10.0 0.29
4 4.61 5.52 5.5159 0.307 0.116 5.517 7.764 8.97 0.346 10.0 0.46
6 3.08 3.69 3.6853 0.287 0.108 3.687 5.219 6.03 0.375 10.0 0.69
10 1.83 2.19 2.1898 0.269 0.101 2.192 3.139 3.63 0.405 10.0 1.15
16 1.15 1.38 1.3763 0.255 0.096 1.38 2.007 2.32 0.434 10.0 1.84
25 0.727 0.870 0.8703 0.253 0.095 0.875 1.305 1.51 0.437 5.1 2.88
35 0.524 0.627 0.6276 0.244 0.092 0.634 0.965 1.12 0.459 5.0 4.03
50 0.387 0.463 0.464 0.244 0.092 0.473 0.739 0.853 0.458 5.0 5.75
70 0.268 0.321 0.3221 0.236 0.089 0.334 0.539 0.622 0.477 5.0 8.05
95 0.193 0.231 0.2329 0.235 0.088 0.249 0.414 0.478 0.482 5.0 10.93
120 0.153 0.183 0.1856 0.23 0.087 0.205 0.348 0.401 0.494 5.0 13.8
150 0.124 0.148 0.1515 0.231 0.087 0.175 0.3 0.347 0.492 5.0 17.25
185 0.0991 0.119 0.1225 0.23 0.087 0.15 0.26 0.300 0.493 5.0 21.28
240 0.0754 0.0902 0.0953 0.228 0.086 0.128 0.221 0.256 0.498 5.0 27.6
300 0.0601 0.0719 0.0782 0.227 0.086 0.116 0.198 0.228 0.502 5.0 34.5
400 0.047 0.0562 0.064 0.226 0.085 0.106 0.177 0.204 0.505 5.0 41.12
500 0.0366 0.0438 0.0532 0.224 0.085 0.1 0.162 0.187 0.510 5.0 51.4

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Typical Cables' Correction Factors for Variation in
Installation Conditions In Ground
Correction Factors For Soil Thermal Resistivity
T.R Single-Core Multi-Core Single-Core Multi-Core
o
[ C.m/W] Cable Cable (in Duct) (in Duct)
1.00 1.36 1.29 1.25 1.17
1.20 1.26 1.21 1.18 1.12
1.50 1.14 1.12 1.10 1.07
2.00 1.00 1.00 1.00 1.00
2.50 0.90 0.91 0.91 0.93
3.00 0.80 0.80 0.80 0.80

Grouping Factors For Number of Circuits

No. of Circuits Trefoil [Gd] Flat Spaced [Gd] Multicore [Gd]

1 1.00 1.00 1.00


2
125mm 0.80 0.78 0.82
250mm 0.84 0.83 0.86
500mm 0.89 0.88 0.89
3
125mm 0.69 0.67 0.71
250mm 0.75 0.73 0.76
500mm 0.82 0.80 0.81
4
125mm 0.63 0.61 0.65
250mm 0.70 0.68 0.72
500mm 0.78 0.77 0.77
5
125mm 0.59 0.56 0.61
250mm 0.66 0.64 0.68
500mm 0.76 0.74 0.74
6
125mm 0.56 0.54 0.58
250mm 0.64 0.62 0.66
500mm 0.74 0.73 0.72

Correction Factors For Ground Correction Factors For Cable


Temperature Depth
o
Temp.[ C] Factor Depth [mm] Factor
20 1.18 500 1.02
30 1.09 700 1.00
35 1.04 1000 0.95
40 1.00 1200 0.94
50 0.89 1500 0.92
55 0.83 2000 0.85

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Typical Cables' Correction Factors for Variation in
Installation Conditions In Air

Grouping Factors
Cables No. of Circuits or Multi-Core Cables
arrangement 1 2 3 4 5 6 7 8 9
Bunched in air, on a
surface, embedded or 1.00 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50
enclosed
Single layer on wall,
floor or unperforated 1.00 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70
cable tray systems
Single layer fixed
directly under a 0.95 0.81 0.72 0.68 0.66 0.64 0.63 0.62 0.61
wooden ceiling
Single layer on a
perforated horizontal or
1.00 0.88 0.82 0.77 0.75 0.73 0.73 0.72 0.72
vertical cable tray
systems
Single layer on cable
ladder systems or cleats 1.00 0.87 0.82 0.80 0.80 0.79 0.79 0.78 0.78
etc.,

Correction Factors For Air


Temperature
o
Temp.[ C] Factor
20 1.49
30 1.36
35 1.29
40 1.22
50 1.08
55 1.00

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev: 01

APPENDIX - 3

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri#en permission.
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev: 01

Rated short
Min.
time I2t (Refer
Feeder Type of standard
withstand Attachment k2 S 2 Remarks
Cable Protection cable size
current of 3
(Required)
switchboard & 4)
Lighting DB / Criteria of k2S2 >
Small power MCB I2t is satisfied.
DB 16A (curvetype 10kA 28x103 2.5 sq. mm 127.8x103 Minimum cable
outgoingfeeder B/C, ABB size required is
make) 2.5 sq.mm.
Lighting DB / Criteria of k2S2 >
Small power MCB I2t is satisfied.
DB 63A (curvetype 10kA 78x103 2.5 sq. mm 127.8x103 Minimum cable
outgoingfeeder B/C, ABB size required is
make) 2.5 sq.mm.
LV Current Criteria of k2S2 >
motor/non- I2t is satisfied.
limiting
motor feeders 85kA 0.48x106 6 sq. mm 0.74x106 Minimum cable
ratedup to MCCB(ABB, size required is 6
160A SACE sq.mm.
Tmax XT2)
LV
motor/non- Current Criteria of k2S2 >
motor feeders I2t is satisfied.
limiting
ratedgreater 85kA 0.78x106 10 sq. mm 2.04x106 Minimum cable
than 160A and MCCB(ABB, size required is
up SACE 10 sq.mm.
to 320A Tmax T4)
LV
motor/non- Current Criteria of k2S2 >
motor feeders limiting I2t is satisfied.
ratedgreater 85kA 3.6x106 16 sq. mm 5.2x106 Minimum cable
MCCB(ABB,
than size required is
320A and upto SACE 16 sq.mm.
630A Tmax T6)
LV
Current Criteria of k2S2 >
motor/non-
limiting I2t is satisfied.
motor feeders
85kA 14x106 35 sq. mm 25.05x106 Minimum cable
> 630A to MCCB(ABB,
800A size required is
SACE 35 sq.mm.
Tmax T6)
LV Current Criteria of k2S2 >
motor/non- limiting I2t is satisfied.
motor feeders 85kA 19x106 35 sq. mm 25.05x106 Minimum cable
MCCB(ABB,
> size required is
800A SACE 35 sq.mm.
Tmax T6)

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri#en permission.
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev: 01

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri#en permission.