0% found this document useful (0 votes)
48 views

649 Ceac 0 Ee 098

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
48 views

649 Ceac 0 Ee 098

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 22

BS EN 14511‑2:2022

m /
. c o
ge s
a - gau
n
w .chi
BSI Standards Publication/ w w
tp : /
ht

Air conditioners, liquid chilling packages and heat


pumps for space heating and cooling and process
chillers, with electrically driven compressors

Part 2: Test conditions


BS EN 14511‑2:2022 BRITISH STANDARD

National foreword

/
This British Standard is the UK implementation of EN 14511‑2:2022. It
m
supersedes BS EN 14511‑2:2018, which is withdrawn.
. c o
e s
The UK participation in its preparation was entrusted to Technical
g
gau
Committee RHE/17, Testing of air conditioning units.

n a -
A list of organizations represented on this committee can be obtained on

chi
request to its committee manager.

.
Contractual and legal considerations
w
w w
This publication has been prepared in good faith, however no
/
: /
representation, warranty, assurance or undertaking (express or

h ttp
implied) is or will be made, and no responsibility or liability is or will be
accepted by BSI in relation to the adequacy, accuracy, completeness or
reasonableness of this publication. All and any such responsibility and
liability is expressly disclaimed to the full extent permitted by the law.
This publication is provided as is, and is to be used at the
recipient’s own risk.
The recipient is advised to consider seeking professional guidance with
respect to its use of this publication.
This publication is not intended to constitute a contract. Users are
responsible for its correct application.
© The British Standards Institution 2022
Published by BSI Standards Limited 2022
ISBN 978 0 539 16554 8
ICS 27.080; 91.140.30
Compliance with a British Standard cannot confer immunity from
legal obligations.
This British Standard was published under the authority of the
Standards Policy and Strategy Committee on 30 September 2022.

Amendments/corrigenda issued since publication


Date Text affected
EUROPEAN STANDARD EN 14511‑2
NORME EUROPÉENNE
EUROPÄISCHE NORM September 2022

m /
ICS 27.080; 91.140.30
. c o
Supersedes EN 14511‑2:2018

ge s
English Version

a - gau
n
chi
Air conditioners, liquid chilling packages and heat pumps
.
for space heating and cooling and process chillers, with
w
/ w w
electrically driven compressors - Part 2: Test conditions
: /
h ttp
Climatiseurs, groupes refroidisseurs de liquide
et pompes à chaleur pour le chauffage et le
Luftkonditionierer, Flüssigkeitskühlsätze und
Wärmepumpen für die Raumbeheizung und
refroidissement des locaux et refroidisseurs -kühlung und Prozess-Kühler mit elektrisch
industriels avec compresseur entraîné par angetriebenen Verdichtern - Teil 2: Prüfbedingungen
moteur électrique - Partie 2 : Conditions d'essai

This European Standard was approved by CEN on 10 July 2022.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving
this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical
references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre
or to any CEN member.

This European Standard exists in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark,
Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta,
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden,
Switzerland, Türkiye and United Kingdom.

EUROPEAN COMMITTEE FOR STANDARDIZATION


COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels

© 2022 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 14511‑2:2022: E
worldwide for CEN national Members
BS EN 14511‑2:2022
EN 14511‑2:2022 (E)

Annex ZA
(informative)
m /
Relationship between this European Standard and the ecodesign
. c o
requirements of Commission Regulation (EU) No 2015/1095
ge s
aimed to be covered
ga u
n a -
c h i
w .
This European Standard has been prepared under a Commission’s standardization request M/495 of

/ w w
27th July 2011 Amendment N°1 of 30th September 2013 (Annex B of M/495) to provide one voluntary
: /
means of conforming to the ecodesign requirements of Commission Regulation (EU) 2015/1095
tp
ht
of 5 May 2015 implementing Directive 2009/125/EC of the European Parliament and of the Council
with regard to ecodesign requirements for professional refrigerated storage cabinets, blast cabinets,
condensing units and process chillers.
Once this standard is cited in the Official Journal of the European Union under that Regulation,
compliance with the normative clauses of this standard given in Table ZA.1 confers, within the
limits of the scope of this standard, a presumption of conformity with the corresponding ecodesign
requirements of that Regulation and associated EFTA regulations.

Table ZA.1 — Correspondence between this European Standard and Commission Regulation
(EU) 2015/1095 of 5 May 2015 implementing Directive 2009/125/EC of the European
Parliament and of the Council with regard to ecodesign requirements for professional
refrigerated storage cabinets, blast cabinets, condensing units and process chillers and
Commission’s standardisation request M/495 and Amendment N°1
Ecodesign requirements of Clause(s)/sub-clause(s) of this EN Remarks/Notes
Commission Regulation (EU) No
2015/1095
Annex VIII Table 25

WARNING 1 Presumption of conformity stays valid only as long as a reference to this European Standard
is maintained in the list published in the Official Journal of the European Union. Users of this standard should
consult frequently the latest list published in the Official Journal of the European Union.

WARNING 2 Other Union legislation may be applicable to the products falling within the scope of
this standard.

ii
BS EN 14511‑2:2022
EN 14511‑2:2022 (E)

Contents Page

Annex ZA (informative) Relationship between this European Standard and the ecodesign
requirements of Commission Regulation (EU) No 2015/1095 aimed to be covered..................... ii m /
. c o
European foreword.............................................................................................................................................................................................................. iv
1 ge s
Scope.................................................................................................................................................................................................................................. 6
2
gau
Normative references....................................................................................................................................................................................... 6
a -
n
chi
3 Terms and definitions...................................................................................................................................................................................... 6
4
4.1 w .
Test conditions........................................................................................................................................................................................................ 6
Environmental conditions and electrical power supply requirements.................................................. 6
4.2
w w
Rating conditions................................................................................................................................................................................... 7
/
: /
h ttp
Annex ZA (informative) Relationship between this European Standard and the ecodesign
requirements of Commission Regulation (EU) No 2015/1095 aimed to be covered..................... ii
Bibliography.............................................................................................................................................................................................................................. 19

  3
BS EN 14511‑2:2022
EN 14511‑2:2022 (E)

European foreword
This document (EN 14511‑2:2022) has been prepared by Technical Committee CEN/TC 113 “Heat
pumps and air conditioning units”, the secretariat of which is held by UNE. m /
. c o
ge s
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by March 2023, and conflicting national standards shall

gau
be withdrawn at the latest by March 2023.

a -
Attention is drawn to the possibility that some of the elements of this document may be the subject of
n
This document supersedes EN 14511‑2:2018. w . chi
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.

/ w w
: /
The main changes compared with EN 14511‑2:2018 are as follows:
— update of normative references;
http
— deletion of Annex ZB on the relationship with Commission Regulation (EU) No 206/2012.
This document has been prepared in the frame of:
— Commission Regulation (EU) No 206/2012 of 6 March 2012 implementing Directive 2009/125/
EC of the European Parliament and of the Council with regard to ecodesign requirements for air
conditioners and comfort fans;
— Commission Delegated Regulation (EU) No 626/2011 of 4 May 2011 supplementing Directive
2010/30/EU of the European Parliament and of the Council with regard to energy labelling of air
conditioners;
— Commission Regulation (EU) No 813/2013 of 2 August 2013 implementing Directive 2009/125/
EC of the European Parliament and of the Council with regard to ecodesign requirements for space
heaters and combination heaters;
— Commission Delegated Regulation (EU) No 811/2013 of 18 February 2013 supplementing Directive
2010/30/EU of the European Parliament and of the Council with regard to the energy labelling of
space heaters, combination heaters, packages of space heater, temperature control and solar device
and packages of combination heater, temperature control and solar device;
— Commission Regulation (EU) 2015/1095 of 5 May 2015 implementing Directive 2009/125/EC of the
European Parliament and of the Council with regard to ecodesign requirements for professional
refrigerated storage cabinets, blast cabinets, condensing units and process chillers;
— Commission Regulation (EU) 2016/2281 of 30 November 2016 implementing Directive 2009/125/
EC of the European Parliament and of the Council establishing a framework for the setting of
ecodesign requirements for energy-related products, with regard to ecodesign requirements for air
heating products, cooling products, high temperature process chillers and fan coil units.
This document has been prepared under a Standardization Request given to CEN by the European
Commission and the European Free Trade Association, and supports essential requirements of EU
Regulation(s).
For relationship with Regulation(s), see informative Annex ZA, which is an integral part of this document.
EN 14511, Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and
process chillers, with electrically driven compressors, currently comprises the following parts:
— Part 1: Terms and definitions;
— Part 2: Test conditions;
— Part 3: Test methods;

iv
BS EN 14511‑2:2022
EN 14511‑2:2022 (E)

— Part 4: Requirements.
Any feedback and questions on this document should be directed to the users’ national standards body.
A complete listing of these bodies can be found on the CEN website.
m /
c o
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
.
ge s
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria,
Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland,

- gau
Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic
of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and the
a
n
chi
United Kingdom.

w .
/ w w
: /
http

 v
BS EN 14511‑2:2022
EN 14511‑2:2022 (E)

1 Scope

1.1 The scope of EN 14511‑1:2022 is applicable.


m /
c o
1.2 This document specifies the test conditions for the rating of air conditioners, liquid chilling
.
e s
packages and heat pumps, using either, air, water or brine as heat transfer media, with electrically
g
driven compressors when used for space heating and/or cooling. The document also specifies the test

a - gau
conditions for the rating of air-cooled and water(brine)-cooled process chillers.

n
chi
1.3 This document specifies the conditions for which performance data are to be declared for single

Regulation 626/2011. w .
duct and double duct units for compliance to the Ecodesign Regulation 206/2012 and Energy Labelling

/ w w
: /
2 Normative references
h ttp
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 14511‑1:2022, Air conditioners, liquid chilling packages and heat pumps for space heating and cooling
and process chillers with electrically driven compressors — Part 1: Terms and definitions
EN 14511‑4:2022, Air conditioners, liquid chilling packages and heat pumps for space heating and cooling
and process chillers, with electrically driven compressors — Part 4: Requirements
EN 15218:2013, Air conditioners and liquid chilling packages with evaporatively cooled condenser and with
electrically driven compressors for space cooling — Terms, definitions, test conditions, test methods and
requirements

3 Terms and definitions


For the purposes of this document, the terms and definitions given in EN 14511‑1:2022 apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https://www.iso.org/obp
— IEC Electropedia: available at https://www.electropedia.org/

4 Test conditions

4.1 Environmental conditions and electrical power supply requirements


The tests shall be carried out under the environmental conditions specified in Table 1 or Table 2
depending on the location of the unit.
For all units, electrical power voltage and frequency shall be given by the manufacturer.

Table 1 — Environmental conditions for units designed for installation indoors


Type Measured quantities Rating test
Water(brine)-to-water(brine) units Dry bulb temperature 15 °C to 30 °C
Air-to-water(brine) units with duct connec‑
Dry bulb temperature 15 °C to 30 °C
tion on the air inlet and outlet side

6 
BS EN 14511‑2:2022
EN 14511‑2:2022 (E)

Type Measured quantities Rating test


Air-to-water(brine) units without duct con‑ Dry bulb temperature
15 °C to 30 °C
nection on the air inlet side Wet bulb temperature
m /
Water(brine)-to-air units with duct connec‑
tion on the air inlet and outlet side
Dry bulb temperature
c o
15 °C to 30 °C
.
Water(brine)-to-air units without duct con‑ Dry bulb temperature
ge s
Inlet temperature (see Table 5

gau
nection on the air inlet and outlet side Wet bulb temperature or Table 6)
Air-to-air units with duct connection
n a -
Dry bulb temperature 15 °C to 30 °C

chi
on the outdoor air inlet and outlet side
Air-to-air units without duct connection
w .
Dry bulb temperature Inlet temperature (see Table 3
on the outdoor air inlet and outlet side
w
Wet bulb temperature or Table 4)

side
t tp ://w
Air-cooled process chillers ducted on the air
Dry bulb temperature 15 °C to 30 °C

h
Water(brine)-cooled process chillers Dry bulb temperature 15 °C to 30 °C

Table 2 — Environmental conditions for units designed for installation outdoors


Type Measured quantities Rating test
Dry bulb temperature Inlet temperature (see Tables
Air-to-water(brine) units
Wet bulb temperature 12 to 16)

Water(brine)-to-air units without duct con‑ Dry bulb temperature Inlet temperature (see Table 5
nection on the air inlet side Wet bulb temperature or Table 6)
Water(brine)-to-water(brine) units operating
Dry bulb temperature 15 °C to 30 °C
in cooling mode
Water(brine)-to-water(brine) units operating
Dry bulb temperature 0 °C to 7 °C
in heating mode
Air-to-air units with duct connection on the Dry bulb temperature Inlet temperature (see Table 3
indoor air inlet and outlet side Wet bulb temperature or Table 4)

Air-cooled process chillers (non-ducted on Dry bulb temperature Inlet temperature (see
the air side) Wet bulb temperature Table 25)
Water(brine)-cooled process chillers Dry bulb temperature 15 °C to 30 °C

4.2 Rating conditions


For the rating tests, the appropriate test conditions shall be applied in accordance with:
— Table 3 for air-to-air units in heating mode;
— Table 4 for air-to-air units in cooling mode;
— Table 5 for water(brine)-to-air units in heating mode;
— Table 6 for water(brine)-to-air units in cooling mode;
— Tables 7 to 10 for water(brine)-to-water(brine) units in heating mode, depending on the temperature
applications;
— Table 11 for water(brine)-to-water(brine) units in cooling mode;
— Tables 12 to 15 for air-to-water(brine) in heating mode, depending on the temperature applications;
— Table 16 for air-to-water(brine) units in cooling mode;
— Table 17 for liquid chilling packages with remote condenser;

  7
BS EN 14511‑2:2022
EN 14511‑2:2022 (E)

— Table 18 for liquid chilling packages for heat recovery condenser;


— Table 19 for air-cooled multisplit systems and modular air-cooled multisplit systems in the
heating mode;
m /

c o
Table 20 for air-cooled multisplit systems and modular air-cooled multisplit systems in the
.
cooling mode;
ge s
gau
— Table 21 for modular heat recovery air-cooled multisplit systems;

a -
Table 22 for water-cooled multisplit systems and modular water-cooled multisplit systems in the
n
chi
heating mode;

w .
Table 23 for water-cooled multisplit systems and modular water-cooled multisplit systems in the
cooling mode;
/ w w
: /

— Table 25 for process chillers h ttp
Table 24 for modular heat recovery water-cooled multisplit systems.

For units with brine, the test shall be carried out with the brine specified by the manufacturer, see
EN 14511‑4:2022, 6.2.1.
For air-to-water(brine), and water(brine)-to-water(brine) heat pumps, the manufacturer may
declare the water(brine) temperatures levels (low, intermediate, medium, and high) applicable to the
heating mode.
NOTE For comparison purposes between reverse cycle and non-reverse cycle units, the conditions on
water(brine) are given by the inlet and outlet temperatures, possibly leading to different flow rates in heating
and cooling modes.

The rating tests in heating mode also apply to units having evaporatively cooled condenser, whose
performance in cooling mode is determined in accordance with EN 15218:2013, and which can operate
in heating mode.
The standard rating conditions, extracted from Table 3 for heating mode, shall be used to determine the
rated capacity (P rated), the rated power input (P COP), the rated coefficient of performance (COP rated)
and the electricity consumption (Q DD, Q SD) in heating mode.

Table 3 — Air-to-air units - Heating mode


Outdoor heat exchanger Indoor heat exchanger
Inlet dry bulb Inlet wet bulb Inlet dry bulb Inlet wet bulb
temperature temperature temperature temperature
°C °C °C °C
Outdoor air / recycled air a 7 6 20 15 max
Standard
rating Exhaust air / recycled air b 20 12 20 12
conditions Exhaust air / outdoor air 20 12 7 6
Outdoor air / recycled air a 2 1 20 15 max.
Outdoor air / recycled air a −7 −8 20 15 max.
Application Outdoor air / recycled air a −15 — 20 15 max.
rating
Outdoor air / recycled air a 12 11 20 15 max.
conditions
Exhaust air / outdoor air 20 12 2 1
Exhaust air / outdoor air 20 12 −7 −8
a  For example, window, double duct, split units
b  For example, single duct units

8 
BS EN 14511‑2:2022
EN 14511‑2:2022 (E)

Table 4 — Air-to-air units - Cooling mode


Outdoor heat exchanger Indoor heat exchanger

m
temperature temperature temperature temperature
/
Inlet dry bulb Inlet wet bulb Inlet dry bulb Inlet wet bulb

°C °C °C
. c o °C
Outdoor air / recycled air a 35 24 b
ge s 27 19

gau
Exhaust air / recycled air 27 19 27 19
Standard
rating
Exhaust air / outdoor air 27
n a -19 35 24
Single duct c,d 35
i 24 35 24

.ch
conditions
Control cabinet 35 24 35 24
Close control
w w 35 24 24 17

p : /
Outdoor air / recycled air
/wa 27 19 b 21 15
Application
rating h t
Single duct
t c,d

Outdoor air / recycled air a


27
46
19
24 b
27
29
19
19
conditions Control cabinet 50 30 35 24
Close control 27 19 21 15
a  For example, window, double duct, split units
b  The wet bulb temperature condition is not required when testing units which do not evaporate condensate.
c  When using the calorimeter room method, pressure equilibrium between indoor and outdoor compartments shall be
obtained by introducing into indoor compartment, air at the same rating temperature conditions.
d  The pressure difference between the two compartments of the calorimeter room shall not be greater than 1,25 Pa. This
pressure equilibrium can be achieved by using an equalizing device or by creating an open space area in the separation
partition wall, which dimensions shall be calculated for the maximum airflow of the unit to be tested. If an open space
is created in the partition wall, an air sampling device or several temperature sensors shall be used to measure the
temperature of the air from the outdoor compartment to the indoor compartment.

Table 5 — Water(brine)-to-air units - Heating mode


Outdoor heat exchanger Indoor heat exchanger
Inlet temper‑ Outlet tem‑ Inlet dry bulb Inlet wet bulb
ature perature temperature temperature
°C °C °C °C
Water a 10 7 20 15 max.
Standard rating
Brine 0 −3 20 15 max.
conditions
Water loop 20 17 20 15 max.
Water(brine) 15 b 20 15 max.
Brine 10 b 20 15 max.
Application rating
conditions Water(brine) 5 b 20 15 max.
Brine −5 b 20 15 max.
a  The term “water” includes indifferently water from a river or a lake, ground water.
b  The test is performed with the fixed flow rate or with the ΔT obtained during the test at the corresponding standard
rating conditions for units with variable flow rate. If the resulting flow rate is below the minimum flow rate then this
minimum is used with the inlet temperature.

  9
BS EN 14511‑2:2022
EN 14511‑2:2022 (E)

Table 6 — Water(brine)-to-air units - Cooling mode


Outdoor heat exchanger Indoor heat exchanger
Inlet temper‑
ature
Outlet tem‑
perature m /
Inlet dry bulb Inlet wet bulb
temperature temperature
. c o
Cooling tower or water
°C °C

ge s°C °C

gau
30 35 27 19
loop
Standard rating Ground coupled (water or
10
n a -
15 27 19

chi
conditions brine)
Control cabinet 15 20 35 24
Close control 30 w. 35 24 17
Cooling tower or water
loop
p : / /ww 40 a 27 19

Application rating Ground coupled (water or


conditions brine) ht t 15 a 27 19

Close control 15 a 21 15
Close control 40 a 24 17
a  The test is performed with the fixed flow rate or with the ΔT obtained during the test at the corresponding standard
rating conditions for units with variable flow rate. If the resulting flow rate is below the minimum flow rate then this
minimum is used with the inlet temperature.

Table 7 — Water(brine)-to-water(brine) units - Heating mode (Low temperature)


Outdoor heat exchanger Indoor heat exchanger
low temperature application
Inlet tempera‑ Outlet tem‑ Inlet temper‑ Outlet tempera‑
ture perature ature ture
°C °C °C °C
Water a 10 7 30 35
Standard rating
conditions Brine 0 −3 30 35
Water(brine) 15 b c 35
Brine 10 b c 35
Application rat‑
ing conditions Water(brine) 5 b c 35
Brine −5 b c 35
a  The term “water” includes indifferently water from a river or a lake, ground water or water in a close water loop.
b  The test is performed with the fixed flow rate or with the ΔT obtained during the test at the corresponding standard
rating conditions for units with variable flow rate. If the resulting flow rate is below the minimum flow rate then this
minimum is used with the inlet temperature.
c  The test is performed with the fixed flow rate or with the ΔT obtained during the test at the corresponding standard
rating conditions for units with variable flow rate. If the resulting flow rate is below the minimum flow rate then this
minimum is used with the outlet temperature.

Table 8 — Water(brine)-to-water(brine) units - Heating mode (Intermediate temperature)


Outdoor heat exchanger Indoor heat exchanger interme‑
diate temperature application
Inlet temper‑ Outlet tem‑ Inlet temper‑ Outlet tempera‑
ature perature ature ture
°C °C °C °C
Water a 10 7 40 45
Standard rating
conditions Brine 0 −3 40 45

10 
BS EN 14511‑2:2022
EN 14511‑2:2022 (E)

Outdoor heat exchanger Indoor heat exchanger interme‑


diate temperature application
Inlet temper‑ Outlet tem‑ Inlet temper‑ Outlet tempera‑
ature perature ature
m / ture
°C °C
. c
°C o °C
Water(brine) 15 b
ge s c 45

gau
Brine 10 b c 45
Application rating
conditions Water(brine) 5
n a
b
- c 45

chi
Brine −5 b c 45

.
The term “water” includes indifferently water from a river or a lake, ground water or water in a close water loop.
w

w w
The test is performed with the fixed flow rate or with the ΔT obtained during the test at the corresponding standard
rating conditions for units with variable flow rate. If the resulting flow rate is below the minimum flow rate then this
/
:
minimum is used with the inlet temperature.
/
h ttp
c  The test is performed with the fixed flow rate or with the ΔT obtained during the test at the corresponding standard
rating conditions for units with variable flow rate. If the resulting flow rate is below the minimum flow rate then this
minimum is used with the outlet temperature.

Table 9 — Water(brine)-to-water(brine) units - Heating mode (Medium temperature)


Outdoor heat exchanger Indoor heat exchanger medium
temperature application
Inlet temper‑ Outlet tem‑ Inlet temper‑ Outlet temper‑
ature perature ature ature
°C °C °C °C
Water a 10 7 47 55
Standard rating
conditions Brine 0 −3 47 55
Water(brine) 15 b c 55
Brine 10 b c 55
Application rating
conditions Water(brine) 5 b c 55
Brine −5 b c 55
a  The term “water” includes indifferently water from a river or a lake, ground water or water in a close water loop.
b  The test is performed with the fixed flow rate or with the ΔT obtained during the test at the corresponding standard
rating conditions for units with variable flow rate. If the resulting flow rate is below the minimum flow rate then this
minimum is used with the inlet temperature.
c  The test is performed with the fixed flow rate or with the ΔT obtained during the test at the corresponding standard
rating conditions for units with variable flow rate. If the resulting flow rate is below the minimum flow rate then this
minimum is used with the outlet temperature.

Table 10 — Water(brine)-to-water(brine) units - Heating mode (High temperature)


Outdoor heat exchanger Indoor heat exchanger
High temperature application
Inlet temper‑ Outlet tem‑ Inlet temper‑ Outlet temper‑
ature perature ature ature
°C °C °C °C
Water a 10 7 55 65
Standard rating
conditions Brine 0 −3 55 65
Water(brine) 15 b c 65
Brine 10 b c 65
Application rating
conditions Water(brine) 5 b c 65
Brine −5 b c 65

  11
BS EN 14511‑2:2022
EN 14511‑2:2022 (E)

Outdoor heat exchanger Indoor heat exchanger


High temperature application
Inlet temper‑
ature
Outlet tem‑
perature
Inlet temper‑
ature m /Outlet temper‑
ature

. c o

°C °C °C

ge s °C
The term “water” includes indifferently water from a river or a lake, ground water or water in a close water loop.

gau
b  The test is performed with the fixed flow rate or with the ΔT obtained during the test at the corresponding standard

minimum is used with the inlet temperature.


n a -
rating conditions for units with variable flow rate. If the resulting flow rate is below the minimum flow rate then this

w . chi
c  The test is performed with the fixed flow rate or with the ΔT obtained during the test at the corresponding standard
rating conditions for units with variable flow rate. If the resulting flow rate is below the minimum flow rate then this
minimum is used with the outlet temperature.

/ w w
: /
h ttp
Table 11 — Water(brine)-to-water(brine)heat pumps, water-cooled and brine- cooled comfort
chillers - Cooling mode
Outdoor heat exchanger Indoor heat exchanger
Inlet Outlet temper‑ Inlet Outlet temper‑
temperature ature temperature ature
°C °C °C °C
Water(brine)-to-wa‑
30 35 12 7
Standard ter(brine)
rating con‑ Water(brine)-to-wa‑
ditions ter(brine) for mild tem‑ 30 35 23 18
perature applications

Table 12 — Air-to-water(brine) units - Heating mode (Low temperature)


Outdoor heat exchanger Indoor heat exchanger
Low temperature applica‑
tion
Inlet dry bulb Inlet wet bulb Inlet temper‑ Outlet tem‑
temperature temperature ature perature
°C °C °C °C
Standard rating Outdoor air 7 6 30 35
conditions Exhaust air 20 12 30 35
Outdoor air 2 1 a 35
Outdoor air −7 −8 a 35
Application rating
conditions Outdoor air −15 — a 35
Outdoor air 12 11 a 35
a  The test is performed with the fixed flow rate or with the ΔT obtained during the test at the corresponding standard
rating conditions for units with variable flow rate. If the resulting flow rate is below the minimum flow rate then this
minimum is used with the outlet temperature.

12 
BS EN 14511‑2:2022
EN 14511‑2:2022 (E)

Table 13 — Air-to-water(brine) units - Heating mode (Intermediate temperature)


Outdoor heat exchanger Indoor heat exchanger
/
intermediate temperature
m
. c o
application
Inlet dry bulb
temperature temperature
g s
Inlet wet bulb Inlet temper‑
e ature
Outlet tem‑
perature

gau
°C °C °C °C
Standard rating Outdoor air 7
n a -6 40 45
conditions Exhaust air 20 i 12 40 45
Outdoor air 2 .ch 1 a 45
Application rating Outdoor air
ww −7 −8 a 45
conditions Outdoor air

t tp
Outdoor air
://w −15
12

11
a
a
45
45
a  h
The test is performed with the fixed flow rate or with the ΔT obtained during the test at the corresponding standard
rating conditions for units with variable flow rate. If the resulting flow rate is below the minimum flow rate then this
minimum is used with the outlet temperature.

Table 14 — Air-to-water(brine)units - Heating mode (Medium temperature)


Outdoor heat exchanger Indoor heat exchanger
medium temperature appli‑
cation
Inlet dry bulb Inlet wet bulb Inlet temper‑ Outlet tem‑
temperature temperature ature perature
°C °C °C °C
Standard rating Outdoor air 7 6 47 55
conditions Exhaust air 20 12 47 55
Outdoor air 2 1 a 55
Outdoor air −7 −8 a 55
Application rating
conditions Outdoor air −15 — a 55
Outdoor air 12 11 a 55
a  The test is performed with the fixed flow rate or with the ΔT obtained during the test at the corresponding standard
rating conditions for units with variable flow rate. If the resulting flow rate is below the minimum flow rate then this
minimum is used with the outlet temperature.

Table 15 — Air-to-water(brine) units - Heating mode (High temperature)


Outdoor heat exchanger Indoor heat exchanger
High temperature application
Inlet dry bulb Inlet wet bulb Inlet tempera‑ Outlet temper‑
temperature temperature ture ature
°C °C °C °C
Standard rating Outdoor air 7 6 55 65
conditions Exhaust air 20 12 55 65
Outdoor air 2 1 a 65
Outdoor air −7 −8 a 65
Application rat‑
ing conditions Outdoor air −15 — a 65
Outdoor air 12 11 a 65
a  The test is performed with the fixed flow rate or with the ΔT obtained during the test at the corresponding standard
rating conditions for units with variable flow rate. If the resulting flow rate is below the minimum flow rate then this
minimum is used with the outlet temperature.

  13
BS EN 14511‑2:2022
EN 14511‑2:2022 (E)

Table 16 — Air-to-water(brine) units - Cooling mode


Outdoor heat exchanger Indoor heat exchanger
Inlet dry bulb Inlet wet bulb Inlet temper‑
temperature temperature ature m /
Outlet tem‑
perature
. c o
Water(brine)
°C
35
°C

ge s
°C
12
°C
7

gau
Standard rating
conditions Water(brine) for mild
35 — 23 18
temperature applications
n a -
chi
Water(brine) 27 — a 7
Application rating Water(brine) for mild
conditions temperature applications
27
w . — a 18

Water(brine)
/ w 46 w — a 7

tp : /
The test is performed with the fixed flow rate or with the ΔT obtained during the test at the corresponding standard

h t
rating conditions for units with variable flow rate. If the resulting flow rate is below the minimum flow rate then this
minimum is used with the outlet temperature.

Table 17 — Liquid chilling packages with remote condenser


Indoor heat exchanger Refrigerant side
Inlet temper‑ Outlet temper‑ Saturated liquid Liquid tem‑
ature ature bubble point tem‑ perature
perature
°C °C °C °C
Water(brine)-to-wa‑
12 7 45 40
ter(brine)
Standard rating Water(brine)-to-wa‑
conditions ter(brine) for mild
23 18 45 40
temperature appli‑
cations
Water(brine)-to-wa‑ a 7 35 30
ter(brine)
Application rating Water(brine)-to-wa‑
conditions ter(brine) for mild a 18 35 30
temperature appli‑
cations
a  The test is performed with the fixed flow rate or with the ΔT obtained during the test at the corresponding standard
rating conditions for units with variable flow rate. If the resulting flow rate is below the minimum flow rate then this
minimum is used with the outlet temperature.

Table 18 — Liquid chilling packages with heat recovery condenser


Heat recovery water heat
Condenser Evaporator
exchanger
Air inlet dry Water inlet Water outlet Water outlet Inlet temper‑ Outlet tem‑
bulb tempera‑ temperatureb temperature temperature ature perature
turea (e.g. for fan (e.g. for chilled
coil units) beams)
°C °C °C °C °C °C
Standard
rating condi‑ 35 30 7 c 18 c 40 45
tions

14 
BS EN 14511‑2:2022
EN 14511‑2:2022 (E)

Heat recovery water heat


Condenser Evaporator
exchanger
Air inlet dry Water inlet Water outlet Water outlet Inlet temper‑ Outlet tem‑
bulb tempera‑ temperatureb temperature temperature ature
m / perature
turea (e.g. for fan (e.g. for chilled
coil units) beams) . c o
°C °C °C °C
ge s °C °C

gau
a  If the air-cooled condenser is ducted then the test shall be conducted at the minimum flow rate specified by the
manufacturer.

n a -
chi
b  At the minimum flow rate specified by the manufacturer.

Table 16).
w .
c  With the flow rate as determined during the test at the corresponding standard rating conditions (see Table 11 or

/ w w
: /
Table 19 — Heating capacity conditions for air-cooled multisplit systems

h ttp
Outdoor heat exchanger Indoor heat exchanger
Inlet dry bulb tem‑ Inlet wet bulb tem‑ Inlet dry bulb tem‑ Inlet wet bulb tem‑
perature perature perature perature
°C °C °C °C
Standard rating condi‑
7 6 20 15 max.
tions
2 1 20 15 max.
Application rating con‑ −7 −8 20 15 max.
ditions 12 11 20 15 max.
−15 — 20 15 max.

Table 20 — Cooling capacity conditions for air-cooled multisplit systems


Outdoor heat exchanger Indoor heat exchanger
Inlet dry bulb tem‑ Inlet wet bulb tem‑ Inlet dry bulb tem‑ Inlet wet bulb tem‑
perature perature perature perature
°C °C °C °C
Standard rating condi‑ a
35 24 27 19
tions
27 19 a 21 15
Application rating con‑
ditions 46 24 a 29 19
a  The wet bulb temperature condition is not required when testing units which do not evaporate condensate.

Table 21 — Heat recovery conditions for air-cooled multisplit systems


Three room calorimeter or Two room
air enthalpy Air enthalpy
Dry bulb tem‑ Wet bulb tem‑ Dry bulb tem‑ Wet bulb tem‑
perature perature perature perature
°C °C °C °C
Outdoor 7 6 7 6
Application side
rating condi‑
Heating 20 — 20 19
tions Indoor side
Cooling 27 19 20 19

  15
BS EN 14511‑2:2022
EN 14511‑2:2022 (E)

Table 22 — Heating capacity conditions for water-cooled or brine-cooled multisplit systems


Outdoor heat exchanger Indoor heat exchanger
Inlet temper‑
ature
Outlet tem‑
perature m /
Inlet dry bulb Inlet wet bulb
temperature temperature
. c o
Water
°C
10
°C
7
ge s
°C
20
°C
15 max.

gau
Standard rating
Brine 0 −3 20 15 max.
conditions
Water loop 20
n a
17- 20 15 max.

chi
Water 15 a 20 15 max.
Application rating
conditions
Brine 5
w . a 20 15 max.
Brine −5 w a 20 15 max.

t tp ://w
The test is performed with the fixed flow rate or with the ΔT obtained during the test at the corresponding standard
rating conditions for units with variable flow rate. If the resulting flow rate is below the minimum flow rate then this
minimum is used with the inlet temperature.
h
Table 23 — Cooling capacity conditions for water-cooled and brine-cooled multisplit systems
Outdoor heat exchanger Indoor heat exchanger
Inlet temperature Outlet tempera‑ Inlet dry bulb Inlet wet bulb
ture temperature temperature
°C °C °C °C
Standard rating conditions 30 35 27 19
15 a 27 19
Application rating condi‑
tions 40 a 27 19
a  The test is performed with the fixed flow rate or with the ΔT obtained during the test at the corresponding standard
rating conditions for units with variable flow rate. If the resulting flow rate is below the minimum flow rate then this
minimum is used with the inlet temperature.

Table 24 — Heating recovery conditions for water-cooled and brine-cooled multisplit systems
Outdoor heat exchanger Indoor heat exchanger for Indoor heat exchanger for
units in heating mode units in cooling mode
Inlet temper‑ Outlet tem‑ Inlet dry bulb Inlet wet bulb Inlet dry bulb Inlet wet bulb
ature perature temperature temperature temperature temperature
°C °C °C °C °C °C
Water 10 7 20 15 max. 27 19
Brine 0 −3 20 15 max. 27 19
Water loop 20 17 20 15 max. 27 19

Table 25 — Cooling capacity conditions for air-cooled, water-cooled and brine-cooled


process chillers
Outdoor heat
Outdoor heat exchanger
exchanger Indoor heat exchanger
water(brine)-cooled
air-cooled
Inlet tempera‑ Inlet tempera‑ Outlet temper‑ Inlet tempera‑ Outlet temper‑
ture ture ature ture ature
°C °C °C °C °C
High tempera‑
35 30 35 12 7
ture
Medium temper‑ a
35 30 35 −2 −8
ature

16 
BS EN 14511‑2:2022
EN 14511‑2:2022 (E)

Outdoor heat
Outdoor heat exchanger
exchanger Indoor heat exchanger
water(brine)-cooled
air-cooled
Inlet tempera‑ Inlet tempera‑ Outlet temper‑ /
Inlet tempera‑
m Outlet temper‑
ture ture ature
. o
ture
c ature
°C °C °C
ge s °C °C

gau
Low temperature 35 30 35 −19 a −25
a  For units that do not allow to achieve a ΔT of 6 K, the minimum flow rate of the unit as declared by the manufacturer is
used with the outlet temperature.
n a -
w . chi
/ w w
: /
http

  17
BS EN 14511‑2:2022
EN 14511‑2:2022 (E)

Annex ZA
(informative)
m /
Relationship between this European Standard and the ecodesign
. c o
requirements of Commission Regulation (EU) No 2015/1095
ge s
aimed to be covered
ga u
n a -
c h i
w .
This European Standard has been prepared under a Commission’s standardization request M/495 of

/ w w
27th July 2011 Amendment N°1 of 30th September 2013 (Annex B of M/495) to provide one voluntary
: /
means of conforming to the ecodesign requirements of Commission Regulation (EU) 2015/1095
tp
ht
of 5 May 2015 implementing Directive 2009/125/EC of the European Parliament and of the Council
with regard to ecodesign requirements for professional refrigerated storage cabinets, blast cabinets,
condensing units and process chillers.
Once this standard is cited in the Official Journal of the European Union under that Regulation,
compliance with the normative clauses of this standard given in Table ZA.1 confers, within the
limits of the scope of this standard, a presumption of conformity with the corresponding ecodesign
requirements of that Regulation and associated EFTA regulations.

Table ZA.1 — Correspondence between this European Standard and Commission Regulation
(EU) 2015/1095 of 5 May 2015 implementing Directive 2009/125/EC of the European
Parliament and of the Council with regard to ecodesign requirements for professional
refrigerated storage cabinets, blast cabinets, condensing units and process chillers and
Commission’s standardisation request M/495 and Amendment N°1
Ecodesign requirements of Clause(s)/sub-clause(s) of this EN Remarks/Notes
Commission Regulation (EU) No
2015/1095
Annex VIII Table 25

WARNING 1 Presumption of conformity stays valid only as long as a reference to this European Standard
is maintained in the list published in the Official Journal of the European Union. Users of this standard should
consult frequently the latest list published in the Official Journal of the European Union.

WARNING 2 Other Union legislation may be applicable to the products falling within the scope of
this standard.

18 
BS EN 14511‑2:2022
EN 14511‑2:2022 (E)

Bibliography

m /
[1]
. c o
EN 14511‑3:2022, Air conditioners, liquid chilling packages and heat pumps for space heating and
cooling and process chillers, with electrically driven compressors — Part 3: Test methods

ge s
gau
[2] EN 14825, Air conditioners, liquid chilling packages and heat pumps, with electrically driven
compressors, for space heating and cooling — Testing and rating at part load conditions and
calculation of seasonal performance
n a -
w . chi
/ w w
: /
h ttp

  19
NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAW

British Standards Institution (BSI) /


BSI is the national body responsible for preparing British Standards and other
c o m
standards-related publications, information and services.
e s .
a
BSI is incorporated by Royal Charter. British Standards and other
g
ustandardization
products are published by BSI Standards Limited. a - g
h in
w . c
About us
/ w w Reproducing extracts

p : /
We bring together business, industry, government, consumers, innovators
t For permission to reproduce content from BSI publications contact the BSI

ht
and others to shape their combined experience and expertise into standards Copyright and Licensing team.
-based solutions.
The knowledge embodied in our standards has been carefully assembled in Subscriptions
a dependable format and refined through our open consultation process. Our range of subscription services are designed to make using standards
Organizations of all sizes and across all sectors choose standards to help easier for you. For further information on our subscription products go to bsigroup.
them achieve their goals. com/subscriptions.
With British Standards Online (BSOL) you’ll have instant access to over 55,000
Information on standards British and adopted European and international standards from your desktop.
We can provide you with the knowledge that your organization needs It’s available 24/7 and is refreshed daily so you’ll always be up to date.
to succeed. Find out more about British Standards by visiting our website at You can keep in touch with standards developments and receive substantial
bsigroup.com/standards or contacting our Customer Services team or discounts on the purchase price of standards, both in single copy and subscription
Knowledge Centre. format, by becoming a BSI Subscribing Member.

Buying standards PLUS is an updating service exclusive to BSI Subscribing Members. You will
automatically receive the latest hard copy of your standards when they’re
You can buy and download PDF versions of BSI publications, including British and revised or replaced.
adopted European and international standards, through our website at bsigroup.
com/shop, where hard copies can also be purchased. To find out more about becoming a BSI Subscribing Member and the benefits
of membership, please visit bsigroup.com/shop.
If you need international and foreign standards from other Standards Development
Organizations, hard copies can be ordered from our Customer Services team. With a Multi-User Network Licence (MUNL) you are able to host standards
publications on your intranet. Licences can cover as few or as many users as you
Copyright in BSI publications wish. With updates supplied as soon as they’re available, you can be sure your
documentation is current. For further information, email [email protected].
All the content in BSI publications, including British Standards, is the property
of and copyrighted by BSI or some person or entity that owns copyright in the Revisions
information used (such as the international standardization bodies) and has
formally licensed such information to BSI for commercial publication and use. Our British Standards and other publications are updated by amendment or revision.

Save for the provisions below, you may not transfer, share or disseminate any We continually improve the quality of our products and services to benefit your
portion of the standard to any other person. You may not adapt, distribute, business. If you find an inaccuracy or ambiguity within a British Standard or other
commercially exploit or publicly display the standard or any portion thereof in any BSI publication please inform the Knowledge Centre.
manner whatsoever without BSI’s prior written consent.
Useful Contacts
Storing and using standards Customer Services
Standards purchased in soft copy format: Tel: +44 345 086 9001
• A British Standard purchased in soft copy format is licensed to a sole named Email: [email protected]
user for personal or internal company use only.
Subscriptions
• The standard may be stored on more than one device provided that it is Tel: +44 345 086 9001
accessible by the sole named user only and that only one copy is accessed at Email: [email protected]
any one time.
• A single paper copy may be printed for personal or internal company use only. Knowledge Centre
Tel: +44 20 8996 7004
Standards purchased in hard copy format: Email: [email protected]
• A British Standard purchased in hard copy format is for personal or internal
company use only. Copyright & Licensing
Tel: +44 20 8996 7070
• It may not be further reproduced – in any format – to create an additional copy.
This includes scanning of the document. Email: [email protected]

If you need more than one copy of the document, or if you wish to share the BSI Group Headquarters
document on an internal network, you can save money by choosing a subscription
product (see ‘Subscriptions’). 389 Chiswick High Road London W4 4AL UK

This page deliberately left blank

You might also like