ED-2002-010 16-Point Relay Output Module (4720)

The document provides information about a 16-point relay output module for a NEXGEN PLC system. It includes specifications, wiring details, troubleshooting information, and safety guidelines. Diagrams and an index are also included to illustrate the module and organize the content.

Uploaded by

ambresh.09
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
71 views12 pages

ED-2002-010 16-Point Relay Output Module (4720)

The document provides information about a 16-point relay output module for a NEXGEN PLC system. It includes specifications, wiring details, troubleshooting information, and safety guidelines. Diagrams and an index are also included to illustrate the module and organize the content.

Uploaded by

ambresh.09
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

Messung Systems NEXGEN PLC I/O Modules

NEXGEN Series of PLCs


16- Point Relay Output Module (4720)

Document No.:ED-2002-010

Version: 1.0

Published July 2002

MESSUNG SYSTEMS
EL-2, J- Block MIDC Bhosari,
Pune – 411026.(INDIA)

Tel: (+91)-020-7120807, 7122807.


Email : [email protected]
WEB: www.messung.com

16 Relay Output Module (4720).doc Published July 2002


Document No.: ED-2002-010/V1.0 Page 1 of 12
NEXGEN PLC I/O Modules Messung Systems

Revision

Version Date Description

16- Point Relay Output Module (4720) NEXGEN


1.0 July 2002
Series of PLCs.

Published July 2002 16 Relay Output Module (4720).doc


Page 2 of 12 Document No.: ED-2002-010/V1.0
Messung Systems NEXGEN PLC I/O Modules

INDEX

1. 16- POINT RELAY OUTPUT MODULE (4720) ................................................................ 5

1.1 MODULE SPECIFICATIONS ............................................................................................. 5

2. MODULE WIRING ............................................................................................................. 6

3. TROUBLESHOOTING ...................................................................................................... 8

3.1 OUTPUT SECTION ......................................................................................................... 8

3.2 DIAGNOSTIC FLOWCHART .............................................................................................. 9

INDEX OF FIGURES

FIGURE 1 : FRONT VIEW OF 16- POINT RELAY OUTPUT MODULE ................................................... 5

FIGURE 2 : FIELD CONNECTIONS FOR 16- POINT RELAY OUTPUT MODULE...................................... 6

FIGURE 3 : OUTPUT SECTION CIRCUIT ........................................................................................... 8

FIGURE 4 : DIAGNOSTIC FLOW CHART IF LED ON OUTPUT MODULE IS ON. .......................................... 9

FIGURE 5 : DIAGNOSTIC FLOW CHART IF LED ON OUTPUT MODULE IS OFF.................................. 10

16 Relay Output Module (4720).doc Published July 2002


Document No.: ED-2002-010/V1.0 Page 3 of 12
NEXGEN PLC I/O Modules Messung Systems

Guidelines for the safety of the user and protection of I/O modules

This manual provides information for the use of I/O Module. The manual has
been written to be used by trained and competent personnel. The definition of
such a person or persons is as follows:
a) DESIGN ENGINEER Any engineer who is responsible for the planning,
design, and construction of automatic equipment using the product
associated with this manual should be of a competent nature, trained
and qualified to the local and national standards required to fulfill the
role.. These engineers should be fully aware of all the aspects of safety
with regards to automated equipment.
b) COMMISSIONING/SERVICE ENGINEER. Any engineer who is
responsible for the commissioning, use and maintenance of automatic
equipment using the product associated with this manual should be of a
competent nature, trained and qualified to the local and national
standards required to fulfill the role .This includes being completely
familiar with all the associated documentation for the said system.
Maintenance to be carried out in accordance to the established safety
practices.
c) OPERATORS. The personnel using the completed equipment should
be trained to use the product in a safe and co-ordinated manner in
compliance to established safety practices. They should be also familiar
with documentation, which is relevant to the actual operation of the
equipment.
Note: The term-completed equipment refers to a third party constructed
device, which contains or uses the product associated with this manual.

Warning !

This product can only function correctly and safely if it is


installed correctly and operated and maintained as
recommended.

Warning !

The specifications of product and contents of manual are subject


to change without notice.

Published July 2002 16 Relay Output Module (4720).doc


Page 4 of 12 Document No.: ED-2002-010/V1.0
Messung Systems NEXGEN PLC I/O Modules

1. 16- Point Relay Output Module (4720)


This is NEXGEN PLC family I/O module. This is 16-point
discrete output module which controls AC output through
4720 electro-mechanical relay contacts.
RELAY OUTPUT
16 OP The discrete output module receives commands from
Processor Module in order to switch ON or OFF various field
actuators and elements like relays, contactors, solenoid
valves, etc.

1.1 Module Specifications


The technical specifications are given in table.

Number of outputs 16
Voltage rating 24 – 250 VAC, 47-53Hz
Non Latching NO Relay contact
Type of Output
(in groups of 8)
Output device Electro-mechanical relay
3 mm Red LED for each channel at
Indication for output
digital side.
Response OFF to ON 10 ms
time ON to OFF 5 ms
0.75 Amp
Current per output (Maximum 4 Amp per group)
(Maximum 8 Amp per module)
OFF state leakage current 3 mΑ
5
Number of ON/OFF 1.5 x 10 operations for resistive load
operations of 5 Amp
Protections • RC snubber across relay contact
Fault Indications • NO 24 V SUPPLY
Relay Coil Optical (1.5 KV from internal bus)
Isolation
Field devices Galvanic
Back-plane current 200 mA (All outputs ON)
Relay coil supply 24 VDC (5mA per output)
(External) (18-30 VDC including ripple)
IO point consumption 16 output points
Connection Removable 20-pin terminal block
Ordering code 4720

Figure 1 : Front View of 16- Point Relay Output Module

16 Relay Output Module (4720).doc Published July 2002


Document No.: ED-2002-010/V1.0 Page 5 of 12
NEXGEN PLC I/O Modules Messung Systems

2. Module Wiring

The front side of module is provided with red LEDs for individual output. LED
glows if Processor puts ON corresponding output. Below front door, 20-pin
terminal block is provided for wiring of field output devices. This is easily
removable which facilitate wiring. This module can be inserted in any of the
I/O slots.

24-250 Neutral GND +24 VDC


VAC

Figure 2 : Field Connections for 16- point Relay Output Module

Published July 2002 16 Relay Output Module (4720).doc


Page 6 of 12 Document No.: ED-2002-010/V1.0
Messung Systems NEXGEN PLC I/O Modules

This is relay contact type of output module.Two common points for AC


supply (terminal numbers 1 and 18), each for group of consecutive eight
outputs are provided. Connect output device ( load less than 0.75 Amp) to
output point as shown in figure with other terminal of output device
connected to neutral.

User should ensure that total load on a module at a time should not exceed
8 Amp.

Filtered 24 VDC (18 to 30 VDC including ripple) is required for energizing


relays on module. If supply is below 18 VDC (including ripple), orange LED
'NO 24 V SUPPLY' glows. In this case, any output LED shows digital status
but relay does not get energized and output relay contact is not closed.

Recommendations for using relay type of outputs are

DC voltage switching is not recommended through the relay contacts.

It is always recommended to insert external fuse protection (1 Amp) for


each output to avoid damage to output module in case of short circuit at
output device side.

Care to be taken when light loads like ‘neon lamps’ , some relays are
connected as output devices. Due to OFF state leakage current such
Output devices may turn ON and give false indications. Hence a suitable
dummy load (Resistive) should be wired up in parallel with such output
device. Recommended dummy resistor value is 10kΩ / 10 Watts.

Maximum voltage between any two pins not to exceed 250 VAC. Hence
connection to two and three phase supply not permitted if line voltage exceeds
110 VAC.

Replacement of Module:
For user safety replacement of live modules not permitted. Module
replacement allowed only on PLC and machine switched off and voltage on pins
confirmed to be safe.
Switching off PLC does not guarantee voltages at terminals to be safe.

16 Relay Output Module (4720).doc Published July 2002


Document No.: ED-2002-010/V1.0 Page 7 of 12
NEXGEN PLC I/O Modules Messung Systems

3. Troubleshooting

This section explains the output section of relay output module and
diagnostic flowchart.

3.1 Output Section


The figure below shows output section of relay output module.

Electro-
Mechanical
+5V Relay +24 V

COM 24 – 250 VAC


R1 R2 Supply
RC
LED Snubber

Output
Output Device like
Relay / contactor/
solenoid valve, etc

From digital Neutral


circuit 0V
Opto
Isolation

Figure 3 : Output section circuit

Published July 2002 16 Relay Output Module (4720).doc


Page 8 of 12 Document No.: ED-2002-010/V1.0
Messung Systems NEXGEN PLC I/O Modules

3.2 Diagnostic Flowchart


The following flow chart illustrates various possibilities of faults with discrete
output module and corrective action to be taken.

LED on Output module is ON.

Output device is energized but not working Output device is not energized.
as per application requirement.

Probable reason Recommended action Probable reason Recommended action


1. Output is forced Unforce output. 1. Low / no voltage Check output device
to one Forcing is indicated by across output specifications. Check
blinking ‘ON’ LED module specifications.
on Processor module. Check source voltage.
2. Output circuit Check output 2. Incorrect wiring Check output device
incompatibility specifications. connections. Check
3. Application Check for the effect of common connection
program fault (JMP), (MCR)/(ME) 3. Open circuit Output device may be
instructions, double faulty. Replace it. Check
output updation wiring for open circuit, if
through coil or functions, any.
etc. 4. Output switching Check output
4. Output circuit Try spare output frequency is high specification &
damaged channel application need.
if any or replace module. 5. Output circuit Try spare output
5. Output device Check output device damaged channel if any or replace
faulty operation. the module

Figure 4 : Diagnostic Flow chart if LED on Output Module is ON.

16 Relay Output Module (4720).doc Published July 2002


Document No.: ED-2002-010/V1.0 Page 9 of 12
NEXGEN PLC I/O Modules Messung Systems

LED on Output module is OFF

Output device is de-energized but not Output device is energized.


working as per application requirement.

Probable reason Recommended action Probable reason Recommended action


1. Output is forced Unforce output. Forcing 1. Output device is Check output device
to zero, is indicated by blinking incompatible specification. Check
'ON' LED on Processor module specifications.
module. If output device is
2. Output circuit Check output faulty, replace it.
incompatibility specifications. 2. Incorrect wiring Check output device
3. Application Check for the effect of connections.
program fault (JMP), (MCR) / (ME) 3. Output OFF state Check output device
instructions, double leakage current may specifications. Check
output updation drive output device module specification.
through coil or Check output module
functions. etc specification. If
4. Output circuit Try spare output required connect
damaged channel if any or dummy load across
replace module. output device
5. Output device Check output device 4. Short circuit Output device may be
faulty operation. faulty. Replace it.
Check wiring for any
short circuit, if any.
5. Output circuit Try spare output
damaged channel if any or
replace the module

Figure 5 : Diagnostic Flow chart if LED on Output Module is OFF

Published July 2002 16 Relay Output Module (4720).doc


Page 10 of 12 Document No.: ED-2002-010/V1.0
Messung Systems NEXGEN PLC I/O Modules

16 Relay Output Module (4720).doc Published July 2002


Document No.: ED-2002-010/V1.0 Page 11 of 12
NEXGEN PLC I/O Modules Messung Systems

MESSUNG SYSTEMS
EL – 2, J - Block, MIDC, Bhosari,
PUNE – 411 026. INDIA
Tel. – (+91) –020 – 712 0807, 712 2807
Fax. – (+91) –020 –712 0391

NEXGEN PLC I/O Modules


16- Point Relay Output Module (4720)

Document No.:ED-2002-010

Published July 2002 16 Relay Output Module (4720).doc


Page 12 of 12 Document No.: ED-2002-010/V1.0