136-03/636-03
INSTALLATION / OPERATION / MAINTENANCE
MODEL
Solenoid Control Valve
iNTRODUCTiON
The Cla-Val Model 136-03/636-03 Solenoid Control Valve is an
automatic valve designed to either close drip tight or open fully by
means of a Three-Way Solenoid Control. It is a hydraulically oper-
ated, solenoid controlled, diaphragm type globe or angle valve.
iNSTALLATiON
1. Allow sufficient room around the valve assembly to make
adjustments and for disassembly.
Note: Before the valve is installed, the pipeline should be
flushed to remove all chips, scale and foreign matter.
2. It is recommended that gate or line block valves be installed 4. Check that solenoid (2) is set to close main valve. Slowly open
upstream and downstream of the Model136-03/636-03 to facilitate the gate or block valve upstream of the valve.
isolating the valve for preventive maintenance.
3. Place the valve in the line with flow in the direction of flow 5. Carefully loosen tube fittings at highest points and bleed air
arrows or by the inlet nameplate. Check all fittings and hardware from system. Carefully loosen the plug at top of main valve cover.
for proper makeup and that no apparent damage is evident. Be If X101 Valve Position Indicator is installed, carefully open the
bleed valve at top of Indicator. Bleed air from cover and tighten
sure main valve cover nuts/bolts are tight. Pressure in some appli- plug or bleed screw. Tighten tube fittings.
cations can be very high so be thorough in checking and inspect-
ing for proper installation and makeup. 6. Slowly open downstream gate or block valve. Check the oper-
4. Cla-Val Valves operate with maximum efficiency when mounted ation of the valve by energizing and de-energizing the solenoid.
in horizontal piping with the cover UP; however, other positions are The valve should open fully and close drip tight.
acceptable. Due to size and weight of cover and internal compo- Need minimum 5 psi differential under flowing coditions.
nents of six inch valves and larger, installation with the cover up is
advisable. This makes periodic inspection of internal parts readily MAiNTENANCE
accessible. 1. Cla-Val Valves and Controls require no lubrication or packing
5. Caution must be taken in the installation of this valve to insure and a minimum of maintenance. However, a periodic inspection
that galvanic and/or electrolytic action does not take place. The schedule should be established to determine how the fluid han-
proper use of dielectric fittings and gaskets are required in all sys- dled is affecting the efficiency of the valve assembly. Minimum of
tems using dissimilar metals. once per year.
6. Comply with local and national electrical codes when wiring the 2. Repair and adjustment procedures of the Cla-Val Hytrol main
Solenoid Control. valve and control components are included in a more detailed
IOM manual. It can be downloaded from our web site ([Link]-
OPERATiON AND START-UP [Link]) or by contacting a Cla-Val Regional Sales Office.
3. When ordering parts always refer to the catalog number
1. Prior to pressurizing the valve assembly make sure the neces- and stock number on the valve nameplate.
sary gauges to measure pressure in the system are installed as
required by the system engineer. A Cla-Val Model X101 Valve SYMPTON PROBABLE CAUSE REMEDY
Position Indicator can be installed in the center cover port to pro-
vide visual indication of the valve diaphragm assembly position Main Valve
Fails to Close
No flow condition Inspect downstream piping for
closed valve or obstruction
during start-up.
Too low pressure differential Restrict valve opening with
CAUTiON: During start-up and test procedures a large volume of across valve Cla-Val X102A
water may be discharged downstream. Check that the downstream Need minimum 5psi differential limiting assembly
venting is adequate to prevent damage to personnel and equip- under flow coditions (Contact Cla-Val)
ment. If the main valve closes too fast it may cause surging in Closed isolation valves in pilot Open valves
upstream piping. system, or in main line
Lack of cover chamber pressure Check upstream
2. If isolation valves (B) are installed in pilot system open these pressure, tubing needle
valves. (see schematic). valves for restriction
Diaphragm damaged Replac diaphragm
3. The three-way Solenoid Control applies or relieves pressure in Mechanical obstruction Remove obstruction
the 102E three-way valve cover chamber. This, in turn, applies or Object lodged in valve
relieves pressure in the main valve cover chamber. The following Worn disc Replace disc
action takes place: Badly scored seat Replace seat
SOLENOiD CONTROL(2) ENERgizED TO OPEN DE-ENERgizED TO OPEN CNA needle valve closed Open this speed control to
136-03 SERIES 136-03 SERIES allow pressure to cover
THREE-WAY MAIN THREE-WAY MAIN Main Valve Closed isolation valves in pilot Open valves
POSITION FLOW VALVE FLOW(3) VALVE (1) VALVE FLOW(3) VALVE 1 Fails to Open system, or in main line
ENERGIZED 1TO2 COM. TO N.O. OPEN N.C. TO COM. CLOSED Insufficient line pressure Clean & polish stem
Diaphragm assembly inoperative Replace and defective or
DE-ENERGIZED 3TO1 N.C. TO COM. CLOSED COM. TO N.O. OPEN
damaged parts
Note: Solenoids are not reversible because of different internal Main Valve Air in cover Bleed all air from valve
construction between Energize to open and De-energize to open Vibrates when
solenoids. Closed
136-03/636-03 SCHEMATiC BASiC COMPONENTS
1 100-01 Hytrol (Main Valve)
SOLENOiD WiRiNg
100-20 600 Series Hytrol (Main Valve) Wiring must comply with local and
2 CS3 Solenoid Control
3 102E Three-Way Valve
National Electrical Codes. For valves
4 CNA Angle Needle Valve (Closing) equipped with an explosion-proof,
watertight solenoid enclosure, the elec-
OPTiONAL FEATURES
A X46A Flow Clean Strainer trical fittings must be approved for use
B CK2 (Isolation Valve) in the approved hazardous locations.
D Check Valves with Isolation Valve Housings for all solenoids have con-
F Independent Operating Pressure nections for 1/2 inch conduit. The
H Atmospheric Drain
P X141 Pressure Gauge enclosure may be rotated to facilitate
S CNA Angle Needle Valve (Opening) wiring.
V X101 ValveY X43Y Strainer
102E
CS3 4
3
3 2
S
1
D1
2
3
Upper Cover
COM NO
Diaphragm Socket Head
Washer Cap Screw
NC
P1
Y
P3 P2 Diaphragm
V
D2
Lower
O-Ring Diaphragm
Washer
B B B
F H Body
D3
INDEPENDENT DRAIN TO
OPERATING ATMOSPHERE
PRESSURE INLET OUTLET
Stem Lower Disc
A
1
Lower Seat
HYTROL MAiN vALvE
Spring
1
O-Ring
PIPE PLUG Washer O-Ring
HEX NUT
8" and Larger
COVER
FLAT WASHER Hex Nut Fitting
CS3
Cover Bolt PIPE PLUG
6" and Smaller
FLAT WASHER
COVER BEARING
2
Manual Operator
SPRING
(Optional) 102E
STEM NUT
3
DIAPHRAGM WASHER
CNA
*DIAPHRAGM
X46A
4
A
DISC RETAINER
*SPACER WASHERS
*DISC
DISC GUIDE
CV
CK2
STEM
C
Seat Screw B
SEAT 8" and Larger
CDC-1 X43
SEAT O-RING
STUD
D Y
8" and Larger
BODY
PIPE PLUG
(Globe or Angle)
*SUGGESTED REPAIR PARTS
*Repair Parts
For a more detailed iOM Manual go to [Link] or contact a Cla-val Regional Sales Office.