IRC 112-2020-Part
IRC 112-2020-Part
6.4.2.1 General
(1) The recommended design properties are co-related to 28 days characteristic compressive
strength, unless specified otherwise.
(2) Depending on the purpose of analysis, some of the properties are used either at their mean
(average) value, or at lower characteristic value or at upper characteristic value based on 5
percent fractile or 95 percent fractile respectively.
(3) Stress-strain relationship for overall analysis of structure, stress-strain relationship
for sectional design, various moduli of elasticity, Poisson’s ratio, tensile strength,
fracture mechanical strength, multiaxial strengths, etc., are the mechanical properties
29
IRC:112-2020
needed for various purposes of design. Unless greater accuracy is needed justifying
separate and direct testing for these characteristics, the values given in Table 6.5 may
be used in design, which are based on their relation to the compressive strength. The
co-relation equations are given in Annexure A-2.
(4) Some of the time-dependent behaviours of structure and time dependent effects are permitted
to be evaluated by using simplified expressions, using appropriately modified values of
some properties, (e.g. factored value of the modulus of elasticity to incorporate creep
effects). Where greater accuracy is needed, specialist literature or relevant international
codes may be referred.
(5) Relationship between Strength and Time:
The development of compressive strength of concrete depends on the type of cement,
curing conditions and maturity of concrete. Maturity is measured as a sum of the product
of time and mean temperature of concrete, measured in appropriate units as given below:
Maturity in day Celsius or hour Celsius = ∑ time in days (or hours) x (temperature in
°C+11°C). Eq. 6.1
In normal applications instead of the exact strength-maturity relationship simplified
strength-time relationship is used, with limits of validity as given in Clause 6.4.2.2. For
special applications, where temperature history deviates from the limits given, Annexure
A-2 may be referred.
30
IRC:112-2020
TABLE 6.5 Stress and Deformation Characteristics for Normal Concrete
Strength Classes for Concrete
Strength class M 15 M 20 M 25 M 30 M 35 M 40 M 45 M 50 M 55 M 60 M 65 M 70 M 75 M 80 M 85 M 90
1 fck (MPa) 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90
2 fcm (MPa) 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
3 fctm (MPa) 1.6 1.9 2.2 2.5 2.8 3.0 3.3 3.5 3.7 4.0 4.4 4.5 4.7 4.8 4.9 5.0
4 fctk,0.05 (MPa) 1.1 1.3 1.5 1.7 1.9 2.1 2.3 2.5 2.6 2.8 2.9 3.0 3.1 3.2 3.3 3.3
5 fctk,0.95 (MPa) 2.0 2.5 2.9 3.2 3.6 3.9 4.3 4.6 4.9 5.2 5.4 5.6 5.7 5.9 6.1 6.2
6 Ecm (GPa) 27 29 30 31 32 33 34 35 36 37 38 38 39 40 40 41
7 εc1 (0/00) 1.8 1.9 2.0 2.0 2.1 2.2 2.3 2.3 2.4 2.4 2.5 2.5 2.6 2.6 2.7 2.7
8 εcu1 (0/00) 3.5 3.4 3.2 3.0 2.9 2.9 2.8
9 εc2 (0/00) 2.0 2.1 2.2 2.3 2.3 2.4 2.4
10 εcu2 (0/00) 3.5 3.3 3.1 2.9 2.8 2.7 2.6
11 n 2.0 1.9 1.7 1.6 1.5 1.5 1.4
12 εc3 (0/00) 1.8 1.8 1.8 1.9 1.9 2.0 2.1
13 εcu3 (0/00) 3.5 3.3 3.1 2.9 2.8 2.7 2.6
Notes:
(1) Strength designation of concrete, (based on characteristic strength) and corresponding properties to be
used in the design are given above. The strains are expressed in per thousand by o/oo sign. The co-relation
equations used are given in Annexure A-2.
(2) The tabulated values of Ecm are for quartzite/granite aggregates. For other aggregates, they should be
multiplied by factors as given below:
limestone = 0.9, sandstone = 0.7, basalt = 1.2.
(3) Properties of materials to be used in bridge construction given in Section 18 and the acceptance criteria
based on sampling theory of statistics are to be used for procurement purposes only.
31
IRC:112-2020
f
f cd ck
m
where
α = 0.67
γm = 1.5 For Basic & Seismic Combination
= 1.2 for Accidental Combination
σc
fck
fcd
0 εc2 εcu2 εc
39
IRC:112-2020
judgement is exercised in deciding whether torsion plays only a minor role in the behaviour of the
structure; otherwise torsional stiffness should be used in the analysis.
7.6.1 Beams
44
IRC:112-2020
(2) lo = The distance between the points of zero moments (in the absence of rigorous calculations
for continuous span it may be taken as 0.7 times effective span). The effective width may
be taken as constant for the full span.
(3) For limit state check of vibration for footbridge the actual flange width may be used.
7.6.2 Slabs
7.6.3 Columns
7.6.3.1 Definitions
A reinforced concrete column is a compression member whose largest lateral crosssectional dimension
is less than or equal to four times its lesser lateral dimension. A column should be considered as short
if the ratio le /i in each plane of buckling is such that the failure takes place without involving secondary
effects. In practice, the limits upto which the secondary effects can be neglected is given in Clause
11.2.
45
IRC:112-2020
0.33
V
Rd .c 0.12 K 801 . f ck 0.15cp bw .d
Subject to a minimum of VRd.c = (vmin + 0.15 σcp) bwd Eq. 10.1
200
K
1 2.0 where d is depth in milimeters. Eq. 10.2
d
and vmin = 0.031K3/2 fck1/2 Eq. 10.3
σcp is limited to 0.2 fcd (MPa) where cp NEd / Ac 0.2 fcd (MPa)
Asl
1 0.02
bw .d (Fig. 10.5)
l bd l bd
VEd VEd
d
Asl A Asl A
A Asl
d
VEd lbd
A - section considered
Fig. 10.5 Definition of Asl in Expression ρ1
Ast is the tensile reinforcement which extends by length greater than lbd+d beyond section considered
(Fig. 10.5)
70
IRC:112-2020
(3) In prestressed single span members without design shear reinforcement both Zone B and
Zone C may exist. For Zone C, cracked in bending the expression for VRd.c as given in
Eq 10.1 can be used. For Zone B uncracked in bending, where flexural tensile stress in
the region under maximum bending moment is smaller than fctk 0.05/γm, the shear resistance
should be limited by the tensile strength of concrete. In these regions the shear resistance is
given by
I .bwc
VRd .c fctd 2 k1cp fctd Eq. 10.4
s
Where notations are as per Section 10.3.1
For cross-sections where the width varies over the height, the maximum principal stress
may occur on an axis other than the centroidal axis. In such a case the minimum value of
the shear capacity should be found by calculating VRd.c at various axes in the cross-sections.
4) The calculation of the shear resistance according to the Eq. 10.4 is not required for cross-
sections between the support and the section which contains the intersection of the elastic
centroidaI axis and a line inclined from the inner edge of the support at an angle of 45°.
5) For members with concentrated loads applied on the upper side at a distance av where av is
within 0.5d to 2d from the edge of a support (or centre of bearing where flexible bearings
are used), the contribution of this load to the shear force VEd may be multiplied β= av/2d.
This reduction may be applied for checking VRd.c in Eq.10.1. This is only valid provided that
the longitudinal reinforcement is fully anchored at the support. For av≤0.5d, the value of
av=0.5d should be used.
The shear force VEd , calculated without reduction by β should however always satisfy the
condition.
VEd<0.5bwdvfcd
Eq. 10.5
where v is a strength reduction factor for concrete cracked in shear.
f
v 0.6 1 ck fck in MPa
310 where fck is in MPa Eq. 10.6
(6) For the design of longitudinal reinforcement in the region cracked in flexure, the MEd line
shall be shifted over a distance αl = d in the unfavourable direction (Ref. Section 16.5.1.3
and Fig. 16.2).
72
IRC:112-2020
(4) Deviators
(a) A deviator shall satisfy the following requirements:
- Withstand both longitudinal and transverse forces that the tendon applies to it
and transmit these forces to the structure;
- ensure that the radius of curvature of the prestressing tendon does not cause any
overstressing or damage to it.
(b) In the deviation zones the tubes forming the sheaths shall be able to sustain the radial
pressure and longitudinal movement of the prestressing tendon, without damage and
without impairing its proper functioning.
(c) The radius of curvature of the tendon in a deviation zone shall not be less than 40
times the diameter of wire/strand.
(d) Designed tendon deviations up to an angle of 0.01 radians may be permitted without
using a deviator. The forces developed by the change of angle shall be considered in
design.
141
IRC:112-2020
16.4.1 Detailing rules IRC:112-2011
(1) For wall type pier of non-circular hollow section with length less than four times the width,
the rules for solid columns stipulated in Clause 16.2 will apply.
(2) For wall type pier of non-circular of hollow section with length more than 4 times the
width, the rules as per Clause 16.3 will apply.
16.5 Beams
145
175
IRC:112-2020
16.5.2 Shear reinforcement
(1) The shear reinforcement should form an angle of 45° to 90° with the longitudinal axis of
the structural element.
(2) The shear reinforcement may consist of a combination of
(a) Links enclosing the longitudinal tensile reinforcement as well as the compression
zone of concrete,
(b) Bent-up bars;
(c) Shear assemblies in the form of cages, ladders etc. of HYSD bars which do not enclose
the longitudinal reinforcement, but are properly anchored both in the compression
and tension zones.
(3) At least 50 percent of the necessary shear reinforcement should be in the form of links.
(4) Links should be effectively anchored. A lap joint may be allowed in web only for high yield
strength deformed bars.
(5) The shear reinforcement ratio is given by Eq. 16.4
ASW
w
s.bw .sin Eq. 16.4
The minimum value ρw.min for ρw is as given by:
w.min
0.072 fck
f yk
Eq. 16.5
In above equations:
ρw = is the shear reinforcement ratio.
Asw = is the area of shear reinforcement within lengths.
s = is the spacing of the shear reinforcement, measured along longitudinal axis of the
member.
bw = is the minimum breadth of the web of the member.
α = is the angle between the shear reinforcement and the longitudinal axis (i.e. for
vertical stirrups α = 90° and sin α = 1).
(6) The minimum clear distance between vertical legs of shear reinforcement should be largest
of :
• dg + 10 mm
• 40 mm
• 2φ of shear Reinforcement.
(7) The maximum longitudinal spacing sl.max of successive series of stirrups or shear assemblies
should not exceed sl.max , where,
sl.max =0.75d (1+ cot α) Eq, 16.6
(8) The maximum longitudinal spacing of bent-up bars should not exceed sb.max where,
149
IRC:112-2020
sb.max = 0.6 d (1+cot α) Eq, 16.7
(9) The transverse spacing of the legs in a series of shear links should not exceed:
st.max = 0.75d ≤ 600 mm Eq. 16.8
150
IRC:112-2020
16.6.1 Flexural reinforcement
16.6.1.1 General
(1) For curtailment of the main reinforcement, clauses for beam given in Clause 16.5.1.3 apply.
(2) The minimum and maximum steel percentages in the main direction should be as for beam
given in Clause 16.5.1.1.
(3) Secondary transverse reinforcement should be provided in one-way slab. This should be at
least 20 percent of the main reinforcement.
(4) The maximum spacing of the bars for structural purposes is as follows where ‘h’ denotes
the total depth of the slab:
- For the principal reinforcement in one-way slab and reinforcement in both directions
in two-way slab : Smax shall be lesser of 2h or 250 mm.
- For secondary reinforcement in one way slab Smax shall be lesser of 3 h or 400 mm.
(5) For slabs provided with shear reinforcement, additional force in the main
longitudinal reinforcement as per Clause 16.5.1.3 shall be considered, taking
ae = effective depth.
(6) Rules as per Clause 16.5.1.3 also apply to slabs.
(7) Where the principal reinforcement in a slab which is considered as the flange of a T-beam
or L-beam is parallel to the beam, transverse reinforcement shall be provided at the top of
the flange. This reinforcement shall not be less than sixty percent of the main reinforcement
of the slab at its mid-span unless it is specially calculated. The length of such reinforcing
bars shall be as indicated in Fig. 16.5.
bw
151
IRC:112-2020
Table 18.1 Reinforcing Steel
Relevant BIS
Type of Steel
Yield Stress/
proof stress/
0.2% proof-
actual 0.2%
Designation
yield stress
Minimum
elongation
Minimum
stress ƒyk
Standard
Strength,
Min. %
Grade /
Tensile
than
Bars upto & including
IS:432 410 MPa 23
20mm dia. = 250 MPa
Mild Steel Grade-I (Part-1)-
1982 20mm ≤dia 50mm
410 MPa 23
240 Mpa
110% (not less than
Fe 415 14.5
485MPa)
IS:1786 415 MPa 112% (not less than
Fe 415D 18.0
500MPa)
Fe 415S ≥ 125% 20.0
108% (not less than
Fe 500 12.0
545MPa)
High Strength
IS:1786 500 MPa 110% (not less than
Deformed Steel Fe 500D 16.0
565MPa)
(HSD Steel)
Fe 500S ≥ 125% 18.0
106% (not less than
Fe 550 10.0
585MPa)
IS:1786 550 MPa
108% (not less than
Fe 550D 14.5
600MPa)
106% (not less than
Fe 600 IS:1786 600 MPa 10.0
660MPa)
Note:
1. Elongation on a gauge length of 5.65√A, where A is the cross-sectional area of the test
piece, when tested in accordance with IS:1608.
2. For seismic zones III, IV & V, HSD steel bars having minimum elongation of 14.5% and
conforming to other requirements of IS:1786 shall be used.
3. For seismic zones III, IV and V, HSD steel bars shall possess following properties:
a. The actual 0.2% proof strength of steel bars based on tensile test must not exceed
their characteristic 0.2% proof strength by more than 20 percent.
b. The ratio of the actual ultimate strength to the actual 0.2 percent proof strength/yield
strength shall be at least 1.15.
169
IRC:112-2020
INFORMATIVE ANNEXURE B-3
B3.1 Scope
The effect of concentrated loads on slabs spanning in one or two directions or on cantilever slabs may
be calculated from the influence fields of such loads or by any other rational method. A value of 0.2
may be assumed for Poisson’s ratio. A simplified method for estimating the action of concentrated
loads on slab, based on effective width method for cantilever and simply supported slab, is described
below, which may be used where more detailed calculations are not performed.
where
bef = the effective width of slab on which the load acts,
lo = the effective span,
a = the distance of the centre of gravity of the concentrated load from the nearer support,
b1 = the breadth of concentration area of the load, i.e., the dimension of the tyre or
track contact area over the road surface of the slab in a direction at right angles to
the span plus twice the thickness of the wearing coat or surface finish above the
structural slab, and
α = a constant having the following values depending upon the ratio b/lo where b is the
width of the slab.
Provided that the effective width shall not exceed the actual width of the slab; and
provided further that in case of a load near the unsupported edge of a slab, the effective
width shall not exceed the above value nor half the above value plus the distance of
the load from the unsupported edge.
240
IRC:112-2020
241
IRC:112-2020
(ii) For two or more concentrated loads
If the effective width of slab for one load overlaps the effective width of slab for an
adjacent load, resultant effective width for the two loads shall be taken as equal to
the sum of the respective effective width for each load minus the width of overlap,
provided that the slab so designed is tested for the two loads acting separately.
242