Misuse of Ieee Device 52 - Medium Voltage Contactors & Breakers Are Not The Same!
Misuse of Ieee Device 52 - Medium Voltage Contactors & Breakers Are Not The Same!
  John A. Kay, C.E.T.             Lorraine K. Padden, P.E.                David C. Mazur, PhD                 Herman Weber, P.E.
  Fellow, IEEE                    Senior Member, IEEE                     Member, IEEE                       Member, IEEE
  Rockwell Automation Inc.        Padden Engineering LLC                  Rockwell Automation Inc.           Electrical SME
  135 Dundas St.                  PO Box 5745                             Global Technical Consultant        The Dow Chemical Co.
  Cambridge, ON N1R 5X1           Katy, TX 77491                          1201 South Second Street           332 SH 332 E
  Canada                          USA                                     Milwaukee, WI 53204, USA           Lake Jackson, TX 77566
  [email protected]           [email protected]                       [email protected]            [email protected]
Abstract – Many standards and specifications, related to                    As a result, overcurrent, ground-fault and differential functions
medium voltage (MV) motor and feeder circuits, continue to                (50/51, 50N/51N, and 87 respectively [1]) should not open the
center around the generic use of the IEEE Device 52 as a circuit          contactor unless rated for the available fault current. The
identifier for the switching device used within those power               manufacturer performs short-circuit tests on the combination
systems. IEEE Device 52 is defined as a device that is used to            controller to confirm safe performance when interrupting the
close and interrupt an ac power circuit under normal conditions           fault on the system within its rating [2] [3].
or to interrupt this circuit under fault or emergency conditions.           For example, the misuse of Device 52 occurs when a MV
Many of the current standards include detailed protection and             motor bus, such as shown in Fig. 1, does not distinguish which
coordination recommendations that are centered on circuit                 motors are controlled with vacuum contactors and which motors
breaker protective settings. Some of these recommended                    are controlled with circuit breakers. Modern MV protection
protective settings can be detrimental when medium voltage                schemes often use a multifunction motor protection relay,
vacuum contactors are used instead of ac circuit breakers to              identified as Device 11M in Fig. 1, to detect problems and send
interrupt the circuit under fault conditions such as in motor and         a signal to either the contactor or breaker to interrupt the circuit.
feeder applications. This paper will outline MV contactor and             A Device 11 is a device that performs three or more
breaker rating differences, compare the appropriate protection            comparatively important functions that could only be designated
variations and requirements between the two, and highlight the            by combining several device function numbers. Using the same
dangers to personnel and equipment when assuming that a                   protection philosophy to open both devices may over duty the
medium voltage vacuum contactor can provide the same                      contactor, resulting in equipment damage and exposing
performance and require the same protective settings as a                 personnel to dangerous conditions.
medium voltage circuit breaker.
I. INTRODUCTION
                                                                      1
                        II. DEFINITIONS                                       Because of these issues, developers continued to pursue
                                                                           alternative technologies including more compact air insulated
   The most commonly used MV switching devices discussed in                systems. The two most popular technologies that were
this paper are defined below:                                              developed focused on the encapsulation of the switched
   ACB             Air Circuit Breakers                                    contacts in either an inert gas or evacuated (vacuum) container.
   VCB             Vacuum Circuit Breakers                                    Sulfur hexafluoride (SF6) was first used as a dielectric
   SF6CB           SF6 (sulfur hexafluoride) Circuit Breaker               insulating gas in the mid-1950s. SF6 is a heavy, chemically inert
   VC              Vacuum Contactors                                       gas that has a dielectric strength similar to that of oil. All
                                                                           switching components must be totally protected from the
   The IEEE Std. 551-2006 [Violet Book] defines a circuit                  environment within a sealed SF6 insulated tank or tubes.
breaker as: “A switching device capable of making, carrying,
and breaking currents under normal circuit conditions and also
making, carrying for a specified time, and breaking currents
under specified abnormal conditions such as those of short
circuit.” [4].
   The National Electrical Code® [5] and Occupation Safety and
Health Administration (OSHA) [6] defines a circuit breaker as “a
device designed to open and close a circuit by non-automatic
means, and to open the circuit automatically on a predetermined
overcurrent without damage to itself when properly applied
within its rating.”
   The IEEE C37.2 standard defined device number 52 as an ac
circuit breaker that is used to close and interrupt a power circuit
under normal conditions or to interrupt this circuit under fault or
emergency conditions [1].
   While the IEEE standards and the NEC definitions describe
the same family of devices, they do have some differences; the
same is true with the actual circuit breakers themselves. They
are much the same in general terms; however, there are a
number of significant differences between the many types of                    Fig. 2 Size Comparison between Vacuum Interrupters
electrical circuit breakers installed in various types of facilities
today.                                                                        Evacuated interrupting devices open a circuit within a vacuum
   None of the above mentioned standards, including C37.2,                 chamber. This does not allow the development of ionized gas,
contains a device number or a complete definition for MV                   which can sustain an arc, to continue past the next zero-
contactors used to switch motor, transformer or capacitive                 crossing of the waveform as shown in Fig. 5. The first
loads.                                                                     commercially available vacuum switching devices were
                                                                           introduced into the market in the late 1960s. Vacuum
             III. HISTORICAL BACKGROUND                                    technology continues to be the most widely used switching
                                                                           media.
A.   General History                                                           Vacuum circuit breakers were designed to replace their
                                                                           larger air break counterparts. These devices could be designed
   The term ‘switchgear’ has been a generic term used since the            to interrupt high levels of short-circuit current, see Table I. A
dawn of electric power in the early part of the 19th century. The          general size comparison between contactor and breaker styles
switching technologies and innovations used within switchgear              of vacuum interrupters is shown in Fig. 2.
have steadily progressed over the decades. The switching
controls and technologies used just a few years ago have
rapidly become outdated, even though the life cycle of
switchgear, in the industrial marketplace, is measured in
decades. Steady progress has been made in the areas of size,
reliability, environmental, and safety considerations.
   The first current switching devices used air as the dielectric
media. However, the use of air generally required larger
electrical clearances making the switching device very large and
bulky. The next evolution came in the mid-1920s when oil was
used as a media for arc quenching. The use of oil as a switching
media facilitated a significant reduction in the switching device’s
size and ultimately the switchgear enclosures when compared
to the previous generation of air-insulated equipment. The
dielectric properties of oil were much better than air and could
withstand much higher system voltages. However, as the oil
ages it may require periodic maintenance; and oil needs proper                 Fig. 3 Circa 1970 Air Magnetic Breaker still being used
handling and disposal.
                                                                       2
   Smaller more compact vacuum interrupters were designed to              in 1987, that the mega volt amp (MVA) Class was dropped from
handle motor and transformer loads which did not require the              ratings tables.
large switching capabilities of a circuit breaker. When paired
with a current limiting power fuse, very small and compact                                          TABLE I
switching contactors were developed. These devices brought                      COMPARISON OF UL CLASS E2 CONTROLLER
advantages of lower chop current and high duty cycles and they                  WITH FUSES AND MV VACUUM CONTACTOR
were virtually maintenance free. An older air circuit breaker still                  VS. MV VACUUM CIRCUIT BREAKER
in use today is shown in Fig. 3.                                                           Vacuum Contactor
                                                                                               UL Class E2         Vacuum Circuit
B.   History of Device Numbering                                                              Controller with           Breaker
                                                                                                  Fuses
  IEEE C37.2 [1] is probably the oldest IEEE standard in regular                             Contactor up to
use. It was first published in 1928 as American Institute of                 Electrical                         Up to 100 full short-
                                                                                                1,000,000
Electrical Engineers (AIEE) No. 26, and provided a language to              Endurance                            circuit interruptions
                                                                                                operations
describe “automatic substations” as well as other applications.             Mechanical
In order to describe the control systems of the day, on                                      Up to 2,500,000         Up to 10,000
                                                                            Endurance
elementary electrical diagrams, a set of device numbers and                 Continuous                           1200, 2000, 3000,
contact designations were standardized in AIEE No. 26 [7].                                  200, 400, 800 A a
                                                                           Current Rating                                4000 A
  That original 1928 version had many protective device                                                                  Higher
numbers that are still in use today such as Device 7 (Rate of                Peak let-            Lower
                                                                                                                (VCB interrupts fault
Change), Device 50 (Instantaneous Overcurrent), Device 52                     through        (current-limiting
                                                                                                                   in 3 cycles or 5
(Circuit Breaker), Device 52a (Normally open auxiliary contact               current b     fuse clears fault in
                                                                                                                   cycles after trip
on an AC circuit breaker), Device 82 (DC load measuring                                        <1/2 cycle)
                                                                                                                         signal)
reclosing), just to name a few [7].                                                         Coordinated with
  In the past nine decades, since the origins of the first                  Overcurrent     MV power fuses       Requires protective
standard, many new device numbers have been added, some                     Protection      and an overload             relay(s)
renamed and reused along with the inclusion of new prefixes                                       device
and suffixes. During the update of C37.2 in 1996, Device 11 was
                                                                                            From very low to      From very low to
added to identify microprocessor based multifunction devices
                                                                             Switching        approximately        full rated short-
along with several other new device numbers. The revisions
                                                                             Capability    10-15X continuous        circuit current
made in the 2008 edition of C37.2 [1] also included a
                                                                                                  rating             (e.g. 63 kA)
comprehensive cross-reference table of IEEE C37.2 function
numbers to IEC 61850 logical nodes, along with several other                                     Electrically held
                                                                                                                             Mechanically
key additions. However, in all of these editions, no recognition            Functional             Mechanically           latched –remains
has yet been given specifically to the use of vacuum contactors            Characteristics       latched–remains          closed on loss of
used in place of circuit breakers.                                                               closed on loss of         system voltage
                                                                                                  control voltage
C.   History of Vacuum Interrupters
                                                                                                                           IEEE C37.20.2c
   Vacuum switching technology was developed originally in the                                                             (metal-clad) [20]
USA in the 1920’s [8] but remained non-viable until the late                                         UL 347c                  Draw out
1940’s and early 1950’s, when the supporting technologies and                                  (ac controllers) [11]
                                                                               Mounting                                     IEEE C37.20.3c
expertise in vacuum systems, materials technology and clean                                       Stationary or
                                                                                                                           (metal-enclosed)
room assembly had become mature and widely available.                                               Draw out
                                                                                                                                   [21]
Serious development of power vacuum interrupters started both                                                                 Stationary or
in Europe and North America in 1953 [9].                                                                                       Draw Out
                                                                           Maintenance
D.   History of Circuit Breaker Standards                                                            Very Low               Medium - High
                                                                           Requirements
                                                                           a
                                                                             Enclosed ratings may be lower depending on application.
   In 1951, the AIEE began reviews and revisions to their high-            b
                                                                             Peak let-through current is the highest current flowing in the circuit
voltage circuit breaker standards. The outcome was the                       following inception of a fault (instantaneous value, not RMS)
abandonment of a Total Current basis of rating and a change to             c
                                                                             Includes arc-resistant equipment tested to IEEE C37.20.7 [14]
a Symmetrical Current basis of rating for breakers. The intent
was to simplify the application of circuit breakers, harmonize                               IV. SWITCHING DEVICES
with the basic ratings of the IEC standards of the time, and
display a relationship between total asymmetrical interrupting            A.   Various Types of Switching Devices
capabilities versus symmetrical interrupting capabilities. In
1964, the series of circuit breaker standards which include                 The range and style of switch devices has varied over the
C37.04 (ratings basis) [10], C37.09 (test methods) [11],                  generations but there are now primarily four defined types of MV
C37.010 (application guide) [12] and C37.06 (preferred ratings            switching devices: Air Circuit Breakers (ACB), Vacuum Circuit
values) [13] were revised to include the changes related to the           Breakers (VCB), SF6 Circuit Breaker (SF6CB) and Vacuum
standardization of the ratings. It wasn’t until the revisions made        Contactors (VC). The contents of this technical paper will cover
                                                                      3
the most commonly used three-phase vacuum switching                        B.   MV Vacuum Contactors
devices, VCB and VC.
    Inside vacuum interrupters, the contacts operate within an                The vacuum interrupters, used in MV vacuum contactors, are
evacuated chamber which creates a strong dielectric                        typically rated for 200, 400 or 800 A for system voltages from 1
environment. The vacuum level in these chambers can be as                  kV to 10 kV. Some vacuum contactors may have lower enclosed
high as 13 x 10-5 Pascal. When the contacts are parted, a rapid            ratings.     The vacuum interrupters, used within vacuum
separation of the fixed and moving contacts is required. Fig. 4            contactors, cannot be opened under high fault current
illustrates some of the various styles of contact sizes and                conditions. In these applications, the interrupters rely on MV
shapes used within vacuum interrupters.                                    power fuses to interrupt and remove high fault current. Most
                                                                           vacuum contactor interrupters can only interrupt between 10-15
                                                                           times their continuous current ratings. Some typical vacuum
                                                                           contactor configurations are shown in Fig. 6.
                                                                       4
contactor. The contactor’s interrupting rating and breaking time            duration (up to 10 s) of current in excess of six times its nominal
must be coordinated with the medium-voltage fuses such that                 current carrying capacity without causing any physical damage
the contactor does not attempt to interrupt currents above its              to the internal element. This type of fuse is normally used for
interrupt rating.                                                           motor loads where this type of current profile is to be expected.
   UL 347 also stipulated that the Class E2 controller’s overload                  2) E-Rated MV Power Fuses
protection (function 49) shall be selected to:                                  “E”-rated fuses are general-purpose fuses. General purpose
   1. Prevent continuous operation above the rated                          current-limiting fuses can interrupt all currents from their
        continuous current of the controller,                               maximum interrupting rating down to the current that causes the
   2. Provide protection of branch circuit conductors and                   element to melt in no less than 1 hour. The “E” rating is used as
        connected loads,                                                    both an open air ampere rating and a description of the fuse’s
   3. Operate before any fuse melts at currents below the                   operating characteristics. “E”-rated fuses can be provided in two
        rated minimum interrupting current of the power circuit             basic types: current limiting and expulsion type. The current-
        fuses                                                               limiting fuse is self-contained, extinguishing the arc in its “sand”
   As well, the MV power fuses must be selected to be able to:              filler. These fuses are “one time” fuses-once the fuse operates,
   1. Permit repetitive switching of the load, with consideration           all three fuses must be replaced.
        given to inrush current and time, without damaging a                       3) X-Rated MV Power Fuses
        fuse,                                                                   Currently, the MV fuse standard ANSI C37.46 [18] only
   2. Interrupt faults at or beyond the controller load terminals,          defines the “R”-rating designations up to the 38R size. MV
        and                                                                 power fuse manufacturers have designed power fuses with
   3. Continuously carry overload relay ultimate trip current.              current ratings much higher than those of the 38R rating.
   In addition, all vacuum contactors must also be selected to be           Because the standard currently does not specifically call out
able to:                                                                    these larger fuses, an “X” designation is used on these larger
   1. Continuously carry the overload relay ultimate trip                   fuse sizes with R-type performance characteristics. The X
        current, and                                                        indicates that there is something in the fuse performance or
   2. Interrupt normal running currents and operating overload              rating which does not meet the ANSI C37.46 standard or it has
        currents up to the rated minimum interrupting current of            not been tested or verified to this standard. This definition also
        the power circuit fuses.                                            includes fuses not included in the C37.46 standard.
   For example, the vacuum interrupters used in MV circuit
breakers can interrupt currents up to 63 kA even when the                   D.   Coordination of Power Fuses with Vacuum Contactors
continuous current ratings are typically 1200 A, 2000 A, 3000 A
or 4000 A.                                                                     The coordination between the vacuum contactor and the
                                                                            power fuses is one of the most critical coordination issues. The
C.   MV Power Fuses                                                         MV fuses must interrupt all fault currents greater than the
                                                                            interrupting rating of the contactor.
   In North America, MV fuses used in combination with vacuum                  The fuse should interrupt the larger fault currents before the
contactors are supplied in two basic element types. These are               overload can also signal a trip to the contactor. The overload
described by the fuse manufacturers with either an “E” or “R”               protection element will provide protection up to the locked rotor
designation or rating. The primary difference is related to the             current. Refer to the IEEE Std. 242 Recommended Practice for
fuse’s element design. In some cases, a fuse is designated with             Protection and Coordination of Industrial and Commercial
an “X” by fuse vendors [16]. The most common fuses utilized in              Power systems [2] [3] [19].
the MV control apparatus in North American industries are
typically the current-limiting type.
    A current limiting (CL) fuse limits the peak-let-through current
to less than the prospective system current. CL fuses are used
on low-voltage and medium-voltage motors as primary fault
protection device and on some small motors as fault and
overload protection devices. [3]
   The peak let-through current is highest current flowing in the
circuit after the inception of the fault that the circuit breaker and
the protected system must withstand, expressed as an
instantaneous rather than a root-mean-square (rms) value [17]
      1) R-Rated MV Power Fuses
   The “R”-rated fuses are current-limiting back-up fuses
typically used in conjunction with MV contactors to increase the
interrupting capacity of the class E2 controller vs the E1. A back-
up current-limiting fuse is capable of interrupting all currents                Fig. 7 Typical Fault Clearing Timing with Fuses and MV
from its maximum interrupting rating down to the minimum                                        Contactor Opening Time
interrupting rating. These types of fuses limit both the magnitude            Fig. 7 shows a typical fault clearing timing with fuses and MV
and duration of a fault current. ANSI C37.46 [18] states that an            contactor opening time; and Fig. 8 shows a typical coordination
“R”-rated fuse must melt in 15 s to 35 s when a current of 100              diagram. It shows the controller the overload protective element
times the “R” number is applied. The “R” rating is not an ampere            curve, the fuse minimum melt time (MMT) and total clear time
rating. The “R”-rated fuse is designed to withstand a long
                                                                        5
(TCT) curves along with the motor and contactor current                    and require very little maintenance. In both designs, the primary
characteristics.                                                           goal is to close and stay closed under rated continuous current
                                                                           or short-circuit current conditions (through-fault) and operate
                                                                           (open) safely when a trip signal is received.
                                                                       6
                            TABLE II                                       systems, the ground fault elements of Device 11M can provide
     TYPICAL FAULT CLEARING TIME COMPARISON                                an alarm; however industrial systems often trip the faulted
                 AT 20 X RATED CURRENT                                     circuit.
      Vacuum Contactors                                                       Referring to the breaker controlled motor control application
                                 Vacuum Circuit Breakers
  (UL 347 Class E2 controller)                                             one-line diagram, shown in Fig. A-2, the breaker interrupts the
      Current-limiting fuse      3 cycle or 5 cycle breaker                circuit for all protection functions including short-circuit. Table III
         clearing time               interrupting time,                    provides a summary of the typical protection functions, in a
           <½ cycle              after the relay trip signal               Device 11M, used for a critical protection of an induction motor.
   In the current-limiting range, the peak let-through current will        B.   The Consequences of Using Incorrect Settings
be lower for the fuse. Also for this example, the MV circuit
breaker system takes longer than the current-limiting fuse to                 Use care when applying fused contactors on solidly grounded
interrupt this level fault current resulting in higher let-through         systems because the contactor is incapable of interrupting high
energy (I2t) for the MV circuit breaker. The difference in time            fault currents, especially ground faults. As a result, load
between a MV power fuse clearing a high current level fault                protection, ground-fault and differential relays should not open
versus the detection of the fault current, any intentional relay           the contactor unless rated for the available fault current.
delays and the subsequent trip relay triggering the opening of                Most microprocessor based motor and transformer protection
the MV circuit breaker could be greater than 100 milliseconds              systems (Device 11, 11M), also sometimes generically referred
different. Shown in Fig. 7 is a typical short circuit fault clearing       to as Intelligent Electronic Devices (IED), have the capabilities
sequence utilizing MV power fuses and a vacuum contactor and               to provide a very wide variety of protection settings based on
Fig. 9 illustrates the sequence for a MV circuit breaker as it             current, voltage, frequency, harmonics, etc. Only the
clears a fault. Table II compares the fault clearing times at 20           appropriate protection elements, for each given application
times rated current. Because the MV circuit breaker system                 should be applied. Even though the IED can provide a wide
takes longer to open higher level fault currents, the highest I2t          array of protection elements, the inappropriate enabling of some
and peak let through current are permitted to flow into the fault          of these elements may not be prudent for some of the
until the current is interrupted. The MV power fuses clear these           application. This could result in unwanted, intermittent or
fault currents much quicker than a circuit breaker and with much           erroneous trip conditions. For example, the implementation of
lower let through energy permitted to flow into the fault.                 anti-jogging protection on a pipeline pump, where jogging is
                                                                           never an issue, could result in nuisance tripping and lost
                V. PROTECTIVE SETTINGS                                     revenue.
A.   How the Switching Device Type Impacts Specific                        C. Utilizing the Capabilities of Intelligent Electronic Devices
     Protective Settings                                                      for Protection
   The primary and most significant difference between MV                     For the fuse contactor configurations, the contactor must
circuit breakers compared to contactors is their associated                remain closed when currents greater than its unfused
interrupting current capabilities. In the case of the vacuum               interrupting rating are flowing. This insures that the MV power
contactor, the contactor’s vacuum interrupters generally have a            fuses interrupt the fault current rather than the contactor. This is
very low interrupting capability compared to those of the                  why the coordination between the fuses, overload settings and
interrupters used in a vacuum circuit breaker. The other                   contactor are so important. Unlike a circuit breaker, where an
difference between the two types of vacuum interrupters is their           overcurrent setting can initiate the opening of the breaker, this
overall size, rigidity and contact materials. A typical vacuum             condition is not what should occur with fused vacuum
interrupter used on a vacuum contactor will have a standalone              contactors.
(E1) interrupting rating of between 5 kA and 12 kA, depending                 In many newer multifunction protection devices, protection
on the interrupter’s continuous current rating. In comparison, a           elements can be electronically blocked from operating by using
MV circuit breaker can have interrupting ratings to about 63 kA.           other internal and external signals. For example, internal relay
   Selecting motor protection functions for a multifunction motor          signals or logic outputs, start and trip signals from other stages
protection relay (Device 11M) depends on the size (hp/kW                   and external signals can be utilized within a matrix style blocking
rating), voltage, critical service of the application, and type of         method to disable a tripping function under certain operating
switching device. Refer to Table III for typical motor protection          conditions. On fused vacuum contactor applications, the
functions for commercial and industrial applications [2] [3]. Fig.         protective relay overcurrent settings should be used only for
A-1 illustrates a typical one-line diagram for a fused class E2            other purposes such as jam, locked rotor or general motor
controller. It shows a MV induction motor application using a              overload conditions. For current settings greater than those
fused non-load break disconnect for short-circuit protection, a            mentioned above, a high setting level for the overload should
vacuum contactor for control, and a Device 11M for overload                actually be used to block the jam, locked rotor or motor overload
and other protection. The multifunction motor protection relay             protective settings so that they do not initiate a trip of the
can open the contactor for various application conditions except           contactor at a current level greater than its interrupting
for short-circuit protection which is provided by the fuses. The           capabilities. This is defined as applying a protective element
51N residually-connected ground fault protection can be used               blocking function within the protective relay.
in a MV low resistance grounded power system, where the                       The current inhibit (50B) blocking function facilitates keeping
ground fault current does not exceed the interrupting rating for           the contactor closed so that the power fuses interrupt the fault
the vacuum contactor. For high resistance grounded power                   currents. If the contactor were to be opened during a high fault
                                                                       7
condition, above its interrupt rating, it would be seriously               breakers versus vacuum contactors. This variance facilitates
damaged and could fail catastrophically.                                   different control and application features and requirements in
                                                                           the multi-function motor protection relay (Device 11M).
                               TABLE III                                   However, vacuum contactors provide other benefits such as
      TYPICAL MV MOTOR PROTECTION FUNCTIONS [2] [3]                        high duty cycles, low maintenance requirements and more
                         INDUCTION MOTORS                                  compact designs. For the fused vacuum contactor controller,
                       PROTECTION FUNCTIONS                                the Device 11M would generally require fewer protection
                                   Class E2 Fused   Circuit                functions than those used for a vacuum circuit breaker and
                                    MV Contactor   Breaker                 generally are lower cost.
                                      Controlled  Controlled                  If the one-line diagrams don’t clearly illustrate the difference
    Volts (U/O)                            27       27/59                  between the two switching methods, the Device 11M may not
    Undercurrent                                      37                   have all of the features needed for the vacuum circuit breaker
    Bearing Temp. Protection               38         38                   application. This may leave the motor less protected than
    Vibration Protection                              39                   desired. Alternatively, the Device 11M may have more features
    Current Balance                        46         46                   than needed when used with the fused vacuum contactor
                                                                           controller. This can result in the improper application of these
    Negative Sequence                      47         47
                                                                           protection settings where the Device 11M may signal for the
    Thermal overload relay
                                                                           contactor to open above its interrupt rating. Without the proper
    Overload operated by motor             49         49
                                                                           consideration for their capabilities and the protection
    current (replica),
                                                                           requirement variations between the two, personnel and
    Stator winding thermal                                                 equipment can be at risk.
    overload (embedded                    49S        49S                      Although the IEEE C37.2 standard does not provide a clear
    detectors)                                                             device number definition for vacuum contactors used in MV
    Breaker Failure                                                        motor controls, the NEMA ICS 19-2002 standard does provide
                                                    50BF
    (breaker only)                                                         a designation that should be used. [22]. In the ICS 19-2002
    IOC ground (zero sequence                                              standard the letter ‘M’ is used to designate a Main Contactor.
    CT) (delayed on start)                                                 We highly recommend, in the absence of a defined device
    - Breaker Trip or                    50G         50G                   number, that proper symbology and terminology be used for
    - Vacuum Contactor within                                              vacuum contactors. The use of a contact symbol with an
    rating                                                                 adjacent “M” should be used to identify a vacuum contactor,
    TOC ground (residually                                                 rather than the Device number 52. This method provides a more
    connected)                                                             clear indication the switching device is a vacuum contactor used
    - Breaker Trip or                     51N        51N                   for load control and application rather than a circuit breaker.
    - Vacuum Contactor within
    rating                                                                                        VII. REFERENCES
    IOC-Locked Rotor (delayed
                                         50LR       50LR
    on start)                                                              [1]   IEEE Std. C37.2-2008, IEEE Standard for Electrical Power
    TOC phase                                         51                         System Device Function Numbers, Acronyms, and
    Short-circuit                    Power Fuse       50                         Contact Designations, New York, NY: IEEE.
    Current Inhibit                                                        [2]    IEEE 3004.8 D10.4, draft document, Recommended
                                          50B                                     Practice for Motor Protection for Industrial and
    (Blocks Contactor Opening) a
    Voltage Balance                                                               Commercial Power Systems, March 2016. IEEE.
                                                      60                   [3]    IEEE C37.96-2012 - IEEE Guide for AC Motor Protection,
    (Loss of Phase)
    # of Starts                            66         66                          New York, NY: IEEE.
                                                                           [4]    IEEE Std. 551-2006 [Violet Book], IEEE Recommended
    Trip Circuit Monitor, alarm                     TCM
                                                                                  Practice for Calculating AC Short-Circuit Currents in
    Frequency                                      81U/O
                                                                                  Industrial and Commercial Power Systems, New York,
    Lockout                                86         86                          NY: IEEE.
    Motor Differential                               87M                   [5]    NFPA Std. 70-2014, National Electrical Code®, National
a
  Instantaneous phase overcurrent (50B) function blocks opening of                Fires Protection Association, Quincy, MA: NFPA.
the contactor when the fault current exceeds its interrupting rating
                                                                           [6]    DOL/OSHA 29 CFR, Part 1910, Subpart S, Electrical,
                                                                                  1910.399;, Washington, DC, Occupational Safety &
                      VI. CONCLUSIONS
                                                                                  Health Administration, United States Department of
   The electrical one-line diagrams form the foundation for                       Labor.
selecting the proper protective devices that are specified and             [7]   J. T. Tengdin and E. A. Udren, “The 2008 Revision of IEEE
influence the settings, equipment type, and control philosophy                   C37.2 Standard Electrical Power System Device Function
for petrochemical facilities. The importance of knowing upfront                  Numbers, Acronyms and Contact Designations”, 2009
the type of control and protection equipment selected for the MV                 62nd Annual Conference for Protective Relay Engineers,
motor is illustrated in this paper.                                              Pages: 21 - 32, DOI: 10.1109/CPRE.2009.4982502.
   The comparison between applying vacuum circuit breaker                  [8]   J R. W. Sorensen and H. E. Mendenhall, “Switching
and fused vacuum contactor type control and protection                           Experiment of California Institute of Technology”, AIEE
highlights the higher interrupt capabilities for the vacuum circuit              Trans., Vol. 45, pp.1102-1105,1926.
                                                                       8
[9]    Falkingham, L.T.; Montillet, G.F. “A history of fifty years of       the conference committees and on several sub-committees. He
       vacuum interrupter development - (the English                        serves on several other technical groups and participated on the
       connection)”, Power Engineering Society General                      local planning committees for the 2011 IEEE-PCIC, 2002 IEEE-
       Meeting, 2004. IEEE Year: 2004 Pages: 706 - 711 Vol.1,               PPIC and serves on the IAS executive board as the Process
       DOI: 10.1109/PES.2004.1372906.                                       Industry Department Chairman. He has won several IEEE
[10]   IEEE Std. C37.04-1999, IEEE Standard Rating Structure                paper awards and was awarded a Meritorious Service Award
       for AC High-Voltage Circuit Breakers, New York, NY:                  from the IEEE Pulp and Paper Industry Committee (PPIC). Mr.
       IEEE.                                                                Kay is also an active voting member of the IEEE Standards
[11]   IEEE Std. C37.09-1999, IEEE Standard Test Procedure                  Association (SA). Mr. Kay is a Certified Engineering
       for AC High-Voltage Circuit Breakers Rated on a                      Technologist, in the province of Ontario.
       Symmetrical Current Basis, New York, NY: IEEE.
[12]   IEEE Std. C37.010-1999, IEEE Application Guide for AC                   Lorraine K. Padden (M’80, SM’94) is Chair of the IEEE
       High-Voltage Circuit Breakers Rated on a Symmetrical                 1349 and IEEE 3004.8 standard working groups for motors in
       Current Basis, New York, NY: IEEE.                                   hazardous locations and motor protection, respectively. She is
[13]   IEEE Std. C37.06-2000, American National Standard for                President of Padden Engineering, LLC, a consulting firm in
       AC High-Voltage Circuit Breakers - Rated on a                        Katy, Texas, and has been in the petrochemical industry for
       Symmetrical Current Basis - Preferred Ratings and                    over 30 years. Ms. Padden graduated from South Dakota
       Related Required Capabilities, New York, NY: IEEE.                   School of Mines with a BSEE degree. She is a member of the
[14]   IEEE Std. C37.20.7, IEEE Guide for Testing Switchgear                IEEE-SA, NFPA, API, ISA, and NSPE. She has Chaired
       Rated Up to 52 kV for Internal Arcing Faults, New York,              chapters of the IEEE Buff Book and Blue Book and contributed
       NY: IEEE.                                                            to several other IEEE and API standards, including API RP
[15]   ANSI/UL 347-2009, Medium-Voltage AC Contactors,                      500/505 Task Group on electrical area classification. She has
       Controllers, and Control Centers, Northbrook, IL:                    published and presented papers at PCIC and other IEEE
       Underwriters Laboratories Inc.                                       conferences. Ms. Padden is a recipient of the IEEE Standards
[16]   J.A. Kay, “Selection, Application, and Interchangeability of         Medallion and is a licensed professional engineer in the states
       Medium-Voltage Power Fuses in Motor Control Centers”,                of California, Texas, and Washington.
       IEEE Transactions on Industry Applications, Vol. 42, No.
       6, Nov./Dec. 2006, P 1574 – 1581.                                       David C. Mazur (S’07, M’12) works as a global technical
[17]   IEEE Std. 1015-2006, IEEE Recommended Practice for                   consultant for Rockwell Automation in Milwaukee, WI with a
       Applying Low-Voltage Circuit Breakers Used in Industrial             current focus on SCADA communications and substation
       and Commercial Power Systems (IEEE Blue Book), New                   automation. His experience includes the development of
       York, NY: IEEE.                                                      regenerative variable frequency drive technology. David has
[18]   C37.46-2010 - IEEE Standard Specifications for High-                 facilitated the develop technology for time synchronized
       Voltage (>1000 V) Expulsion and Current-Limiting Power               continuous casters for the steel industry. He also facilitated a
       Class Fuses and Fuse Disconnecting Switches, New                     project that aimed to assess the power quality of Asia-Pacific
       York, NY: IEEE.                                                      and European countries.
[19]   IEEE Std. 242-2001 - IEEE Recommended Practice for                      David received his B.S. EE degree summa cum laude and
       Protection and Coordination of Industrial and Commercial             first in his class from Virginia Polytechnic Institute and State
       Power Systems (IEEE Buff Book), New York, NY: IEEE.                  University, Blacksburg, VA in 2011. David graduated with his
[20]   IEEE Std. C37.20.2, IEEE Standard for Metal-Clad                     M.S. EE degree in 2012 for his work based on rotor angle
       Switchgear, New York, NY: IEEE.                                      measurement of synchronous machines from Virginia
[21]   IEEE Std. C37.20.3, IEEE Standard for Metal-Enclosed                 Polytechnic Institute and State University. He graduated with
       Interrupter Switchgear (1 kV – 38 kV), New York, NY:                 the Ph.D. in Mining Engineering in September 2013 for his work
       IEEE.                                                                with automation and control of the IEC 61850 standard.
[22]   NEMA ICS 19-2002 (R2007) – Diagrams, Device                             David is an active member of the IEEE IAS and serves as
       Designations and Symbols for Industrial Control Systems,             working group chair for the Communication-Based Protection of
       National Electrical Equipment Manufacturers Association,             Industrial Applications Working Group. He also serves as a
       Rosslyn, VA: NEMA.                                                   member of the Mining Industry Committee (MIC) as well as the
                                                                            Industrial and Commercial Power Systems Committee (I&CPS).
                            VIII. VITAE                                     David is also an active voting member of the IEEE Standards
                                                                            Association (SA).
   John A. Kay (M’94, SM’98, F’12), received his degree in
Electrical/Electronic Engineering Technology from Conestoga                    Herman Weber (M’ 07) works as the Global Technical
College, Kitchener, Ontario in 1977. He has authored a wide                 Resource Leader for Motor Control with The Dow Chemical
variety of award winning technical papers and other technical               Company. He also serves as an Electrical SME with the
articles and manuals related to MV electrical control and                   Engineering Solutions Technology Center with Dow. Herman
protection systems, arc resistant equipment and infrared                    has served in various functions in his 40 years of experience
technologies. Several of his papers have been published in the              including maintenance, supervision, plant startup, as well as
IEEE IAS Transactions and the IAS magazine. He is a Fellow                  project design. He is an IEEE member. Herman received his
member of the IEEE, the Industry Application Society and                    B.S. EE degree in 1976 from Texas A&I University in Kingsville,
actively involved with the IEEE Pulp and Paper Industry                     Texas.
Committee, serving as the chairman of the executive board, on
                                                                        9
                                   APPENDIX A
Fig. A-1 MV Induction motor 1-line diagram showing typical Device 11M protection functions
                    used in combination with MV power fuses [12] [14]
                                            10
Fig. A-2 MV induction motor protection 1-line diagram showing an example of
        Device 11M protection functions used with a breaker [12] [14]
11