Data sheet for SINAMICS Power module PM240-2
Article No. : 6SL3210-1PE31-8UL0
Client order no. : Item no. : Figure similar
Order no. : Consignment no. :
Offer no. : Project :
Remarks :
Rated data Ambient conditions
Input Cooling Internal air cooling
Number of phases 3 AC Cooling air requirement 0.153 m³/s (5.403 ft³/s)
Line voltage 380 ... 480 V ±10 % Installation altitude 1,000 m (3,280.84 ft)
Line frequency 47 ... 63 Hz Ambient temperature
Rated current (LO) 172.00 A Operation LO -20 ... 40 °C (-4 ... 104 °F)
Rated current (HO) 154.00 A Operation HO -20 ... 50 °C (-4 ... 122 °F)
Output Transport -40 ... 70 °C (-40 ... 158 °F)
Number of phases 3 AC Storage -40 ... 70 °C (-40 ... 158 °F)
Rated voltage 400V IEC 480V NEC 1) Relative humidity
Rated power (LO) 90.00 kW 125.00 hp Max. operation 95 % RH, condensation not permitted
Rated power (HO) 75.00 kW 100.00 hp
Connections
Rated current (LO) 178.00 A
Line side
Rated current (HO) 145.00 A
Version M10 bolt
Max. output current 290.00 A
35.00 ... 120.00 mm²
Conductor cross-section
Pulse frequency 2 kHz (AWG 2 ... AWG -3)
Output frequency for vector control 0 ... 200 Hz Motor end
Output frequency for V/f control 0 ... 550 Hz Version M10 bolt
Overload capability 35.00 ... 120.00 mm²
Conductor cross-section
(AWG 2 ... AWG -3)
Low Overload (LO)
DC link (for braking resistor)
1.1 x rated output current (i.e. 110 % overload) for 57 s with a cycle time of
300 s 1.5 × rated output current (i.e. 150 % overload) for 3 s with a cycle time Version Screw-type terminals
of 300 s
25.00 ... 70.00 mm²
Conductor cross-section
High Overload (HO) (AWG 4 ... AWG -1)
1.5 × output current rating (i.e., 150 % overload) for 57 s with a cycle time of Cable length 10 m (32.81 ft)
300 s 2 × output current rating (i.e., 200 % overload) for 3 s with a cycle time
of 300 s PE connection M10 screw studs
Max. motor cable length
General tech. specifications
Shielded 300 m (984.25 ft)
Power factor λ 0.95
Unshielded 450 m (1,476.38 ft)
Offset factor cos φ 0.99
Efficiency η 0.98 Mechanical data
Sound pressure level (1m) 68 dB Degree of protection IP20 / UL open type
Power loss 2.31 kW Frame size FSF
Filter class (integrated) - Net weight 57.00 kg (125.66 lb)
Dimensions
Width 305 mm (12.01 in)
Height 708 mm (27.87 in)
Depth 357 mm (14.06 in)
Standards
Compliance with standards UL, cUL, CE, C-Tick (RCM), SEMI F47
CE marking Low-voltage directive 2006/95/EC
Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Page 1 of 2 Generated Thu Sep 21 14:10:17 CET 2023
Data sheet for SINAMICS Power module PM240-2
Article No. : 6SL3210-1PE31-8UL0
Converter losses to IEC61800-9-2*
Efficiency class IE2
Comparison with the reference
50.60 %
converter (90% / 100%)
I 1,760.0 W (1.40 %) 2,060.0 W (1.70 %) 2,560.0 W (2.10 %)
100%
967.0 W (0.80 %) 1,070.0 W (0.90 %) 1,240.0 W (1.00 %)
50%
703.0 W (0.60 %) 748.0 W (0.60 %)
25%
50% 90% f
The percentage values show the losses in relation to the rated apparent power of
the converter.
The diagram shows the losses for the points (as per standard IEC61800-9-2) of
the relative torque generating current (I) over the relative motor stator frequency
(f). The values are valid for the basic version of the converter without
options/components.
*converted values
1) The output current and HP ratings are valid for the voltage range 440V-480V
Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Page 2 of 2 Generated Thu Sep 21 14:10:17 CET 2023