Cable 4 X 6mm2 Non-Armoured

The document provides specifications for low voltage Cu/PVC/PVC cables including dimensional data, electrical data, and usage notes. It lists various cable sizes gauged by nominal cross-sectional area and cores, giving properties like resistance, current capacity, and bending radius for each. Main uses listed are for indoor installation and in ducts or underground where not subject to mechanical damage.

Uploaded by

jack.izzati
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
87 views1 page

Cable 4 X 6mm2 Non-Armoured

The document provides specifications for low voltage Cu/PVC/PVC cables including dimensional data, electrical data, and usage notes. It lists various cable sizes gauged by nominal cross-sectional area and cores, giving properties like resistance, current capacity, and bending radius for each. Main uses listed are for indoor installation and in ducts or underground where not subject to mechanical damage.

Uploaded by

jack.izzati
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

SUPREME Low Voltage Cables

Cu/PVC/PVC (NYY) 0.6/1(1.2) kV


IEC 60502-1/ SNI IEC 60502-1
Copper conductor, PVC insulated and PVC sheathed cable
Main Uses : used for indoor, in ducts installation for laying in the ground, where not sustain mechanical damage

DIMENSIONAL & MECHANICAL DATA 4 Cores


Nominal Thickness Approximately
Nominal cross- No of wire and Bending Standard
sectional area conductor shape radius min delivery length
Overall
Insulation Outer sheath Net Weight
diameter
mm
2
pcs - mm Kg/Km mm m

1.5 1 re 0.8 1.8 14 262 170 1,000


1.5 7 rm 0.8 1.8 14 272 170 1,000
2.5 1 re 0.8 1.8 15 320 180 1,000
2.5 7 rm 0.8 1.8 15 343 180 1,000
4 1 re 1.0 1.8 17 443 210 1,000
4 7 rm 1.0 1.8 18 477 220 1,000
6 1 re 1.0 1.8 18 546 220 1,000
6 7 rm 1.0 1.8 19 589 230 1,000
10 1 re 1.0 1.8 20 749 240 1,000
10 7 rm 1.0 1.8 21 807 260 1,000
16 7 rm 1.0 1.8 24 1,113 290 1,000
25 7 rm 1.2 1.8 28 1,630 340 1,000
35 7 rm 1.2 1.8 30 2,092 360 1,000
35 19 sm 1.2 1.8 28 1,869 340 1,000
50 19 sm 1.4 1.9 32 2,491 390 1,000
70 19 sm 1.4 2.1 36 3,381 440 1,000
95 19 sm 1.6 2.2 40 4,534 480 500
120 37 sm 1.6 2.3 44 5,596 530 500
150 37 sm 1.8 2.5 49 6,877 590 500
185 37 sm 2.0 2.7 53 8,462 640 500
240 37 sm 2.2 2.9 60 10,999 720 300
300 37 sm 2.4 3.1 66 13,616 800 300

ELECTRICAL DATA
Resistance at 20 ºC
Current Carrying Capacity at 30 ºC
Nominal cross- Short circuit current of
sectional area DC conductor max Insulation min conductor at 1.0 sec
(Calculated) In AIR In GROUND

mm2 Ω/Km MΩ.Km A kA

1.5 12.1 12 18 24 0.19


2.5 7.41 10 25 32 0.32
4 4.61 10 34 41 0.50
6 3.08 8 44 52 0.73
10 1.83 6 60 69 1.20
16 1.15 5 80 89 1.91
25 0.727 5 105 116 2.96
35 0.524 4 130 138 4.13
50 0.387 4 160 165 5.87
70 0.268 3 200 205 8.19
95 0.193 3 245 245 11.09
120 0.153 3 285 285 13.98
150 0.124 3 325 315 17.46
185 0.0991 3 370 355 21.50
240 0.0754 3 435 415 27.86
300 0.0601 3 500 465 34.79
Note : This is only general information. For other specific requirement, please contact our marketing.