0% found this document useful (0 votes)
67 views3 pages

Re 717MZ Rev 03 - 18 - 9 en

The document describes an addressable zone interface module that permits an addressable fire alarm control panel to interface and monitor conventional smoke detectors and call points. The module transmits the status of a zone of detectors to the panel and supervises the zone and external power supply. It has features like analogue communication, DIP switch addressing, and compatible panels include Avani, Avani DB, and Avani XL models.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
67 views3 pages

Re 717MZ Rev 03 - 18 - 9 en

The document describes an addressable zone interface module that permits an addressable fire alarm control panel to interface and monitor conventional smoke detectors and call points. The module transmits the status of a zone of detectors to the panel and supervises the zone and external power supply. It has features like analogue communication, DIP switch addressing, and compatible panels include Avani, Avani DB, and Avani XL models.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

ADDRESSABLE ZONE INTERFACE MODULE

General
Zone Interface module permits the addressable FACP to interface and
monitor 2-wire / 4-wire conventional smoke detectors and manual call
point. The Zone module is addressed by using the DIP switch to
communicate with addressable FACP. It transmits the status (normal,
open, short or alarm) of one zone of 2-wire / 4- wire detectors to the
FACP. Zone module supervises the zone of detectors and the
connection of the external power supply respectively.

Features
- Complies UL standard.
- CE Approved.
- Module Status by RED LED.
- Analogue Communication with the panel.
- Module Addressing by 8 way DIP Switches.
- Low Standby Current.
- 24V Monitoring resettable output
- Available with suitable back boxes.

Specification
Electrical Specification
Operating Voltage 24 VDC Nominal
Current Draw(SLC) 0.5mA, (2 mA Max.Latched)
External Supply Voltage Regulated 24VDC
ExternalSupply Standby Current 5mA
ExternalSupply Alarm Current 60mA Max
Loop Impedance 40 Ohms
End Of Line Resistor 4.7K Ohms
o o o o
Temperature Range 0 C to 49 C / 32 to 120 F
o o
Storage Temperature 0 C to 60 C
Humidity 93 ± 2% RH (non-condensing) at 32 ± 2° C / 90 ± 3° F
Mechanical Specification
Dimensions (95 W X 75 H X 24 D) mm
Color Black
Weight 0.35 Kg

1 RE-717MZ / Rev 03-EN / 2020-2021


Dimensions

Wiring Configuration

Compatible Panels
Model Description
Avani Analogue addressable Fire Alarm Control panel expandable upto 4 loop
Avani db Analogue Addressable Fire Alarm Control panel expandable upto 2 loop
Avani XL Analogue Addressable Fire Alarm Control Panel expandable upto 8 Loop

2 RE-717MZ / Rev 03-EN / 2020-2021


Compatible Device

Model Description
RE-
RE-316S-
316S-2L Conventional Photoelectric Smoke detector with base.
RE-
RE-316H-
316H-2L Conventional Heat detector with base.
RE-
RE-316SH-
316SH-2L Conventional Multi sensor detector with base
RE-
RE-428 Series Optical Beam Detector
EazyBeam Beam Detector

Ordering Information
Models Description
RE-717MZ Addressable Zone Interface Module

India United Kingdom USA


RAVEL ELECTRONICS PVT LTD., RAVEL ELECTRONICS LTD., RAVEL AMERICAS INC.,
150A, Electronics Industrial Estate, Unit 11, Chancel Industrial Estate, Newhall street, 2855 NW 112th Ave ST#2 Miami,
Perungudi,Chennai – 96, India. Willenhall WV13 1NX, West Midlands, United Kingdom. Doral, Florida 33172, USA.
E-mail: [email protected]; Web: www.ravelfire.com E-mail: [email protected]; Web: www.ravelfire.co.uk

*Ravel reserve the right to change the specification without prior notice. RE-717MZ / Rev 03-EN / 2020-2021