0% found this document useful (0 votes)
69 views5 pages

J8328A-E-DS-15069 Rev B1 Datasheet For 60kV Gas Insulated Switchgear (GIS)

The document provides specifications for a 60kV gas insulated switchgear project in Algeria. It includes requirements for the switchboard, incomers, protection and interlocks, instrumentation, current transformers, and voltage transformers.

Uploaded by

ABDELKADER
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
69 views5 pages

J8328A-E-DS-15069 Rev B1 Datasheet For 60kV Gas Insulated Switchgear (GIS)

The document provides specifications for a 60kV gas insulated switchgear project in Algeria. It includes requirements for the switchboard, incomers, protection and interlocks, instrumentation, current transformers, and voltage transformers.

Uploaded by

ABDELKADER
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

SWITCHBOARD GENERAL REQUIREMENTS

PROJECT: MENZEL LEDJMET EAST (MLE) TAG No.: CPF-EH-80-01

LOCATION: ALGERIA No. REQ'D: 1

PLANT: CENTRAL PROCESSING FACILITY DATE: 22.10.07

SERVICE: 60kV GAS INSULATED SWITCHGEAR COMPANY: FCP / SONATRACH

SPECIFICATION No.: J8328A-E-SP-15001 CONTRACTOR:


ONE LINE DIAG. No.: J8328A-E-DW- CONTRACTOR REFERENCE:
SYSTEM NOMINAL RATING: 60 kV SWITCHBOARD RATED VOLTAGE: 72.5 kV
BUS-BAR SYSTEM RATED CURRENT: 2500 A BUS-BAR INSULATION: SF6
RATED (RMS) WITHSTAND: 31.5 kA DESIGN TEMPERATURE: 40 °C
RATED (RMS) WITHSTAND TIME: 3 Seconds NEUTRAL EARTHING: Solid
ASYMMETRIC PEAK MAKING DUTY: HOLD kA EARTH BAR X SECTION: Rated for full fault level

DEGREE OF PROTECTION: Gas Tight FORM OF SEGREGATION: Individual Panels. Fully segregated

EARTH BAR POSITION: Manufacturers standard DESIGN LIFE: 25 yrs


SHORT CIRCUIT TESTING AUTH.: See note 1 BUS-BAR SYSTEM TEST CERT No.: See note 1
SWITCHBOARD TEST CERT No.: See note 1 CB TEST CERT No.: See note 1
CONTRACTORS TEST CERT No.: See note 1
SWBD. ARRANGEMENT: Front / Rear Access MAXIMUM HEIGHT: 2.5 m
EARTHING REQ: Bus-bars & circuits VIA:
PAINT COLOUR: Refer note 5 EARTH SWITCH FAULT MAKE RATING: Asymmetric peak 'make' rating
CONTROL SUPPLIES:
OPEN / CLOSE 110 V DC SUPPLY INTERNAL / EXTERNAL
SPRING CHARGE 110 V DC SUPPLY INTERNAL / EXTERNAL
PROTECTION RELAYS 110 V DC SUPPLY INTERNAL / EXTERNAL
VT SECONDARIES 110 V AC SUPPLY INTERNAL / EXTERNAL
CABLE ENTRY:
POWER CABLE: BOTTOM / TOP CONTROL CABLE: BOTTOM / TOP
NOTES:
1. Information required with bid
2. Double Bus Bar Arrangement is required
3. All relays to be withdrawable types from the Protection and Control Panels (PCPs)
4. 2 out of 3 auto transfer scheme required for 2 incomers and bus section circuit breakers
5. Refer painting specification J8328A-L-SP-14010
6. Auxiliary enclosures to be protected to IP 31

60kV SWITCHBOARD DATA SHEET

PROJECT DOCUMENT NUMBER Sht No. REV


J8328A-E-DS-15069 2 B1
SWITCHBOARD INCOMERS
PROJECT: MENZEL LEDJMET EAST (MLE) TAG No.: CPF-EH-80-1
LOCATION: ALGERIA No. REQ'D: 2
PLANT: CENTRAL PROCESSING FACILITY DATE: 22.10.07
SERVICE: 60kV GAS INSULATED SWITCHGEAR COMPANY: FCP / SONATRACH
INCOMER TYPE: CIRCUIT BREAKER
A. BASIC REQUIREMENTS: SUPPLIER'S INFORMATION:
1 NUMBER OF POLES THREE 1. CIRCUIT BREAKER TYPE Refer note 1
2 RATED NORMAL CURRENT 1250A 2. RATED NORMAL CURRENT Refer note 1
3 INTERRUPTING MEDIUM SF6 3. TRIPPING TIME Refer note 1
4 CLOSING MECHANISM (SPRING) MOTOR DRIVEN 4. CLOSING TIME Refer note 1
5 SHORT CCT BREAKING CURRENT HOLD 5. TYPE TEST CERT No. Refer note 1
6 ASYMMETRIC PEAK CURRENT HOLD
7 AUX CONTACTS - WIRED OUT (min) 2 x N/O + 2 x N/C
(additional as required)

B. PROTECTION & INTERLOCKS:


QUANTITY ANSI No. MANUFACTURER TYPE RESET REMARKS
1 DEF. TIME OVERCURRENT 3 51
2 INST. OVERCURRENT 3 50 Auto-transfer block
3 DEF. TIME EARTH FAULT 1 51N
4 INST. EARTH FAULT 50N
5 RESTRICTED E/FAULT 64 (REF)
6 DIRECTIONAL 67
7 DIFFERENTIAL 87
8 PILOT WIRE 85
9 LOCKOUT RELAY 1 86
10 TRIP SEND/RECEIVE 1 94
11 UNDERVOLTAGE 1 27 3 Phase
12 OVERVOLTAGE 1 59
13 THERMAL RELAY 49
14 UNDER/OVER FREQUENCY 1 81
15 TRIP CIRCUIT SUPERVISION 1
16 REVERSE POWER
17 CHECK SYNCH 1 25
18 TIMER
19 DISTANCE 3 21
20
C. INSTRUMENTATION, METERING & CONTROLS D. CURRENT TRANSFORMERS
REQUIRED SCALE/COLOUR REMARKS RATIO CLASS QUANTITY SERVING ITEMS
1 LOCAL AMMETER √ Protection relay display 1250/1 3 3 C1, C4, C5, C7
2 REMOTE AMMETER C8
3 VOLTMETER √ Protection relay display 1250/1 5P20 3 B1, B2, B3, B19
4 PWR FACTOR MTR √ Protection relay display 1250/1 1 3 Free issue for
5 kW METER √ Protection relay display Fiscal metering
6 FREQUENCY METER √ Protection relay display
7 kWhr METER √ Protection relay display
8 VAR METER √ Protection relay display
9 SELECTOR SWITCH 1 Off / Test / In Service Note: 4-20mA transducer to be provided by
10 PUSH BUTTONS 2 Open / Closed switchgear manufacturer
11 OPERATIONS COUNTER 1
12 CLOSED LAMP 1 WHITE CB Closed
13 OPEN LAMP 1 GREEN CB Open
14 TRIPPED LAMP 1 RED Fault E. VOLTAGE TRANSFORMERS
15 EARTH SWITCH CLOSED LAMP 1 YELLOW Switch closed 60000/110/110√3 3 3ph B11, B12, B14, B19
16 SERVICE POSITION LAMP 1 BLUE CB withdrawn C3, C4, C5, C6, C7
17 TRIP-OFF-CLOSED SWITCH 1 C8
60000/110/110√3 1 3ph Free issue for
fiscal metering

60 kV SWITCHBOARD DATA SHEET


0
PROJECT DOCUMENT NUMBER Sht No. REV
J8328A-E-DS-15069 3 B2
SWITCHBOARD BUS SECTION
PROJECT: MENZEL LEDJMET EAST (MLE) TAG No.: CPF-EH-01
LOCATION: ALGERIA No. REQ'D: 1
PLANT: CENTRAL PROCESSING FACILITY DATE: 22.10.07
SERVICE: 60kV GAS INSULATED SWITCHGEAR COMPANY: FCP / SONATRACH
BUS SECTION TYPE: CIRCUIT BREAKER
A. BASIC REQUIREMENTS: SUPPLIER'S INFORMATION:
1 NUMBER OF POLES THREE 1. CIRCUIT BREAKER TYPE Refer note 1
2 RATED NORMAL CURRENT 2500A 2. RATED NORMAL CURRENT Refer note 1
3 INTERRUPTING MEDIUM SF6 3. TRIPPING TIME Refer note 1
4 CLOSING MECHANISM (SPRING) MOTOR DRIVEN 4. CLOSING TIME Refer note 1
5 SHORT CCT BREAKING CURRENT HOLD 5. TYPE TEST CERT No. Refer note 1
6 ASYMMETRIC PEAK CURRENT HOLD
7 AUX CONTACTS - WIRED OUT 2 x N/O + 2 x N/C
(additional as required)

B. PROTECTION & INTERLOCKS:


QUANTITY ANSI No. MANUFACTURER TYPE RESET REMARKS
1 DEF. TIME OVERCURRENT 51
2 INST. OVERCURRENT 50
3 DEF. TIME EARTH FAULT 51N
4 INST. EARTH FAULT 50N
5 RESTRICTED E/FAULT 64
6 DIRECTIONAL 67
7 DIFFERENTIAL 87
8 PILOT WIRE 85
9 LOCKOUT RELAY 86
10 TRIP SEND/RECEIVE 1 94
11 UNDERVOLTAGE 2 27 1 each bus-bar (A / B)
12 OVERVOLTAGE
13 THERMAL RELAY 49
14 VROC RELAY
15 TRIP CIRCUIT SUPERVISION 1
16 REVERSE POWER
17 CHECK SYNCH Y 25
18 TIMER
19 LOAD SHEDDING

C. INSTRUMENTATION, METERING & CONTROLS D. CURRENT TRANSFORMERS


REQUIRED SCALE/COLOUR REMARKS RATIO CLASS QUANTITY SERVING ITEMS
1 LOCAL AMMETER √ Protection relay display
2 REMOTE AMMETER
3 VOLTMETER 2 Protection relay display
4 PWR FACTOR MTR √ Protection relay display
5 kW METER √ Protection relay display
6 FREQUENCY METER √ Protection relay display
7 kWhr METER √ Protection relay display
8 VAR METER √ Protection relay display
9 SELECTOR SWITCH 1 Off / Test / In Service
10 PUSH BUTTONS 2 Open / Closed
11 OPERATIONS COUNTER 1
12 CLOSED LAMP 1 WHITE CB Closed
13 OPEN LAMP 1 GREEN CB Open
14 TRIPPED LAMP 1 RED Fault E. VOLTAGE TRANSFORMERS
15 EARTH SWITCH CLOSED LAMP 1 YELLOW Switch closed 60000/110/110√3 4 x 3ph B11, 1 set per bus
16 SERVICE POSITION LAMP 1 BLUE CB withdrawn
17 TRIP-OFF-CLOSED SWITCH 1

60kV SWITCHBOARD DATA SHEET


PROJECT DOCUMENT NUMBER Sht No. REV
J8328A-E-DS-15069 4 B2
SWITCHBOARD OUTGOING CIRCUITS - TRANSFORMER FEEDER
PROJECT: MENZEL LEDJMET EAST (MLE) TAG No.: CPF-EH-80-01
LOCATION: ALGERIA No. REQ'D: 4
PLANT: CENTRAL PROCESSING FACILITY DATE: 22.10.07
SERVICE: 60kV GAS INSULATED SWITCHGEAR COMPANY: FCP / SONATRACH
OUTGOING CIRCUIT TYPE: CIRCUIT BREAKER
A. BASIC REQUIREMENTS: SUPPLIER'S INFORMATION:
1 NUMBER OF POLES THREE 1. CIRCUIT BREAKER TYPE Refer note 1
2 RATED NORMAL CURRENT 800A 2. RATED NORMAL CURRENT Refer note 1
3 INTERRUPTING MEDIUM SF6 3. TRIPPING TIME Refer note 1
4 CLOSING MECHANISM (SPRING) MOTOR DRIVEN 4. CLOSING TIME Refer note 1
5 SHORT CCT BREAKING CURRENT HOLD 5. TYPE TEST CERT No. Refer note 1
6 ASYMMETRIC PEAK CURRENT HOLD
7 AUX CONTACTS - WIRED OUT 2 x N/O + 2 x N/C
(additional as required)

B. PROTECTION & INTERLOCKS:


QUANTITY ANSI No. MANUFACTURER TYPE RESET REMARKS
1 DEF. TIME OVERCURRENT 3 51
2 INST. OVERCURRENT 3 50
3 DEF. TIME EARTH FAULT 51N
4 INST. EARTH FAULT 64 (REF)
5 INST. UNRESTRICTED E/FAULT 50G
6 DIRECTIONAL 67
7 DIFFERENTIAL Y 87 Located in 5.5kV Switchboard
8 PILOT WIRE 85
9 LOCKOUT RELAY 1 86
10 TRIP SEND/RECEIVE 94
11 UNDERVOLTAGE 27
12 OVERVOLTAGE
13 THERMAL RELAY 49
14 VROC RELAY
15 TRIP CIRCUIT SUPERVISION 1
16 REVERSE POWER
17 CHECK SYNCH
18 TIMER
19 TEMPERATURE Y 26 Transformer winding (by others)

C. INSTRUMENTATION, METERING & CONTROLS D. CURRENT TRANSFORMERS


REQUIRED SCALE/COLOUR REMARKS RATIO CLASS QUANTITY SERVING ITEMS
1 LOCAL AMMETER √ Protection relay display 500/1 3 3 C1, C7, C4
2 REMOTE AMMETER 500/1 5P20 3 B1, B2
3 VOLMETER √ Protection relay display 500/1 X 3 B7, free issue
4 PWR FACTOR MTR √ Protection relay display from 5.5kV
5 kW METER √ Protection relay display swrd.
6 FREQUENCY METER √ Protection relay display manufacturer
7 kWhr METER √ Protection relay display
8 VAR METER √ Protection relay display Note: 4-20mA transducer to be provided by
9 SELECTOR SWITCH 1 OFF / TEST / IN SERVICE switchgear manufacturer
10 PUSH BUTTONS 2 Open / Closed
11 OPERATIONS COUNTER 1
12 CLOSED LAMP 1 WHITE CB Closed
13 OPEN LAMP 1 GREEN CB Open
14 TRIPPED LAMP 1 RED Fault E. VOLTAGE TRANSFORMERS
15 EARTH SWITCH CLOSED LAMP 1 YELLOW Switch closed
16 SERVICE POSITION LAMP 1 BLUE CB withdrawn
17 TRIP-OFF-CLOSED SWITCH 1

60kV SWITCHBOARD DATA SHEET


PROJECT DOCUMENT NUMBER Sht No. REV
J8328A-E-DS-15069 5 B1