This document provides specifications for a 21.82 kVA 50 Hz emergency standby generator set. It includes details on the engine, alternator, control panel, mechanical features, electrical components, and accessories. The generator set is rated for both emergency and prime power applications.

Uploaded by

Marian Dumitru
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
72 views9 pages

GBW22P 2023 10 08 11 36 46

This document provides specifications for a 21.82 kVA 50 Hz emergency standby generator set. It includes details on the engine, alternator, control panel, mechanical features, electrical components, and accessories. The generator set is rated for both emergency and prime power applications.

Uploaded by

Marian Dumitru
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

GBW22P

Main Features
Frequency Hz 50
Voltage V 400
Power factor cos ϕ 0.8
Phase 3

Power Rating
Emergency Standby Power ESP kVA 21.82
Emergency Standby Power ESP kW 17.46
Prime power PRP kVA 19.78
Prime power PRP kW 15.82

Ratings definition (ISO-8528)

ESP - Emergency Standby Power:


It is the maximum power available during a variable electrical power sequence, under the stated
operating conditions, for which a generating set is capable of delivering in the event of a utility power
outage or under test conditions for up to 200 h of operation per year with the maintenance intervals
and procedures being carried out as prescribed by the manufacturers. The permissible average power
output over 24 h of operation shall not exceed 70 % of the ESP.

PRP - Prime Power:


It is defined as being the maximum power which a generating set is capable of delivering continuously
whilst supplying a variable electrical load when operated for an unlimited number of hours per year under
the agreed operating conditions with the maintenance intervals and procedures being carried out as
prescribed by the manufacturer. The permissible average power output over 24 h of operation shall not
exceed 70 % of the prime power.
Engine specifications
Engine Brand Perkins
Model 404A-22G1
[50Hz] Exhaust emission level Non Emission
Certified
Engine cooling system Water
Nr. of cylinder and disposition 4 in line
Displacement cm³ 2216
Aspiration Natural
Speed governor Mechanical
Prime gross power PRP kW 18.7
Maximum gross power LTP ESP kW 20.6
Oil capacity l 10.6
Coolant capacity l 7
Fuel Diesel
Specific fuel consumption 75% PRP g/kWh 238
Specific fuel consumption PRP g/kWh 237
Starting system Electric
Starting engine capability kW 2
Electric circuit V 12

Engine Equipment

Standards

The above ratings represent the engine performance capabilities to conditions


specified in ISO 8528/1, ISO 3046/1:1986, BS 5514/1

Fuel system

Rotary type pump

Lube oil system

Wet steel sump with filler and dipstick

Filter

• Fuel filter
• Air filter
• Oil filter

Cooling system

• Mounted radiator
• Thermostatically-controlled system with belt driven coolant pump and pusher fan
Alternator Specifications
Alternator Linz
Model E1S13MF
Voltage V 400
Frequency Hz 50
Power factor cos ϕ 0.8
Poles 4
Type Brushes
Voltage tolerance % 4
Efficiency @ 75% load % 86.2
Class H
IP protection 21

Mechanical structure
Robust mechanical structure which permits easy access to the connections and
components during routine maintenance check-ups.

Voltage accuracy:
± 4% from no load to full load, cosϕ = 0.8 at constant rotation speed.

Output voltage wave form:


The low harmonic content (<5%) allows supplying any type of load, including distorting
loads.

Short circuit current:


In case of short circuit the permanent current exceeds rated current by three times,
ensuring the correct operation of protections.

Overload:
10% overload for one hour every 6 hours is normally accepted. Short overloads can
be very high (three times the rated current).
Genset equipment

BASE FRAME MADE OF WELDER STEEL PROFILE, COMPLETE WITH:

• Anti-vibration mountings properly sized

• Visual fuel level indicator

• Integrated support legs.

PLASTIC FUEL TANK, COMPLETE WITH:

• Filler neck

• Air breather (ventilation pipe)

• External fuel refilling

OIL DRAININ PIPE WITH CAP:

• Oil draining facilities

CANOPY:

• Single piece hinged soundproof canopy equipped with pneumatic arms and handles
to lift up the canopy allowing easy access to the genset for maintenance purposes.

• Simple handling operations with central lifting eye

SOUNDPROOF:

• Noise attenuation thanks to soundproofing material (polyurethane foam) and efficient


residential silencer placed inside the canopy.
Dimensional data
Length (L) mm 1645
Width (W) mm 870
Height (H) mm 1072
Dry weight kg 565
Fuel tank capacity l 51
Fuel tank material Plastic

Autonomy
Fuel consumption @ 75% PRP l/h 3.98
Fuel consumption @ 100% PRP l/h 5.27
Running time 75% PRP h 12.81
Running time 100% PRP h 9.68

Noise level
Guaranteed noise level (LWA) dB(A) 95
Noise pressure level @ 7 m dB(A) 66

Installation data
Exhaust gas flow m³/min 3.64
Exhaust gas temperature °C 445

Electrical Data
Battery capacity Ah 70
Max current A 31.50
Circuit breaker A 32

Control panel availability


MANUAL CONTROL PANEL MCP
AUTOMATIC CONTROL PANEL ACP
MCP - Manual control panel

Manual control panel, mounted on the genset and complete of: instrumentation,
control, protection and sockets

INSTRUMENTATION (ANALOGUE)

• Voltmeter (1 phase)
• Ammeter (1 phase)
• Hours-counter

COMMANDS AND OTHERS

• Start/stop selector switch with key (Glow plugs preheating function also included).
• Emergency stop button

PROTECTION WITH ALARM

• Battery charger failure


• Low oil pressure
• High engine temperature
• Earth Fault

PROTECTIONS WITH SHUTDOWN

• Battery charger failure


• Low oil pressure
• High engine temperature
• Circuit breaker protection: III poles

OTHERS

• Cower protection power switch

OUT PUT PANEL MCP


Socket kit Standard
Thermal protections
3P+N+T CEE 400V 32A n 1
3P+N+T CEE 400V 16A n 1
2P+T CEE 230V 16A n 2
230V 16A SCHUKO n 1
ACP - Automatic control panel

Automatic control panel mounted on the genset, complete with digital control unit for
monitoring, control and protection of the generating set.

INSTRUMENTATION DIGITAL

• Mains voltage.
• Generating set voltage (3 phases).
• Generating set frequency.
• Generator set current.
• Battery voltage
• Hours-counter.

COMMANDS AND OTHERS

• Operation modes: OFF - Manual Starting - Automatic Starting.


• Push-buttons: start/stop, fault reset, up/down/page/enter selection.
• Emergency stop button.
• Remote starting availability.
• Automatic battery charger.
• USB port.

PROTECTIONS WITH ALARM

• Engine protections: low oil pressure, high engine temperature


• Genset protections: under/over voltage, overload, under/over frequency, starting
failure, under/over battery voltage, battery charger failure

PROTECTIONS WITH SHUTDOWN

• Engine protections: low oil pressure, high engine temperature


• Genset protection: under/over voltage, overload, under/over battery voltage
• Circuit breaker protection: III poles
• Differential protection

OTHERS

• Cover protection Power switch

OUT PUT PANEL ACP


Plinth row for connection from ACP to LTS panel. √
3P+N+T CEE 400V 32A n 1
Supplements:
To be ordered with equipment (when necessary) :

ENGINE SUPPLEMENTS
PHS - Coolant Pre-Heating System ACP
Accessories
Items available as accessory equipment
Site trailer •
Road Trailer •

LTS - Load Transfer Switch [Accessories for ACP Automatic Control Panel]

The Load Transfer Switch (LTS) panel operates the power supply changeover
between the generator and the Mains in backup applications, guarantying the feeding
to the load within a short period of time.
It consists of a standalone cabinet which can be installed separate from the generating
set. The logic control of the power supply changeover is operated by means of the
Automatic Control panel mounted on the generating set, so therefore none logic
device is required on the LTS panel.

The information is aligned with the Data file at the time of download. Printed on 08/10/2023 (ID 13462)

©2023 | PR Industrial S.r.L unipersonale – Loc. Il Piano – 53031 Casole d’Elsa (SI) – ITALY. Company
subject to the management and coordination of Generac Power Systems Inc.| All rights reserved |
Image shown may not reflect actual package. Specifications subject to change without notice

You might also like