AFE14C5E-IAA
HFO, R-448A, 60 Hz, 1 -Phase, 115 V
Low Temperature
Production Status: Available for sale to all U.S. customers. Please check with your local Emerson Climate
Technologies Representative for international availability.
Performance Mechanical
Evaporator Temp. (°F) -10 -25 Displacment(in^3/Rev): 0.54
Condensing Temp. (°F) 120 105 Displacment(ft^3/hr): 65.10
Return Gas Temp. (°F) 40 40 Overall Length (in): 10.50
Liquid Temp. (°F) 120 105 Overall Width (in): 6.40
Capacity (Btu/hr) 1305 997 Overall Height (in): 7.87
Power (W): 350 264 Mounting Length (in): 6.50
Current (Amps): 4.05 3.55 Mounting Width (in): 4.00
EER (Btu/Wh): 3.75 3.80 Mounting Height (in): 8.25 *
Mass Flow (lbs/hr): 21 14 Suction Size (in),Type: 5/16 Stub
Sound Data @ Discharge Size (in),Type: 1/4 Stub
Sound Power (dBA): 0 Avg 0 Max Initial Oil Charge (oz): 12
Vibration mils(peak-peak): 0.0 Avg 0.0 Max Oil Recharge (oz): 10
Record Date: 2016-11-03 Net Weight (lbs): 24.0
Internal Free Volume (in^3):
Electrical Horse Power:
*Overall compressor height on Copeland Brand Product's specified
LRA-High*(Amp): 30.0 mounting grommets.
LRA Low* (Amp):
LRA-Half Winding (Amp):
MCC (Amps): 8.4
Capacitors
Max Operating Current(Amp): Type Part No Low MFD High MFD Volts User Description
RLA, MCC/1.4;use for contactor selection (Amp): 6.0 Start Capacitor 014-0053-25 189.0 227.0 250
RLA, MCC/1.56;use for breaker & wire size selection (Amp): 5.4
RPM:
UL File No:
UL File Date:
*Low and High refer to the low and high nominal voltage ranges for
which the motor is approved.
Alternate Applications
Refrigerant Voltage Phase Freq (Hz) Application
R-404A HFC 115 1 60 Extended Medium Temp, A-Line
R-449A HFO 115 1 60 Low Temperature
Public Public Page 1 Of 1
12/07/2018