PL 1

The document provides details on the electrical layout and components for a residential building, including a schedule of loads listing the branch circuits and their ratings. It includes notes on general requirements for the electrical work in accordance with codes.

Uploaded by

20232889
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
45 views1 page

PL 1

The document provides details on the electrical layout and components for a residential building, including a schedule of loads listing the branch circuits and their ratings. It includes notes on general requirements for the electrical work in accordance with codes.

Uploaded by

20232889
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

GENERAL NOTES

SCHEDULE OF LOADS (PANEL BOARD)


GENERAL NOTES PANEL BOARD PROVIDE 20MMØC
ALL ELECTRICAL VWORKS HEREIN RACEWAY TERMINATING IN A 100MM BRANCH CKT. NO. LOAD DESCRIPTION NO. OF LOADS VA VOLTS AMPERES CB RATING / AT SIZE OF WIRE & CONDUIT
SHALL BE DONE IN ACCORDANCE DEEP TYPE SQUARE BOX WITH 1 LIGHTING OUTLET 6 600 230 2.60 15 2.0 MM² THHN WIRE IN 13MM ø UPVC PIPE
WITH THE PROVISIONS OF THE LATEST COVERAT CEILING SLAB
EDITION OF THE PHILIPPINE 9.ALL MATERIALS TO BE USED SHALL 2 LIGHTING OUTLET 5 500 230 2.17 15 2.0 MM² THHN WIRE IN 13MM ø UPVC PIPE

ELECTRICAL CODE, THE ORDINANCES BE NEW AND INSTALLED IN 3 CONVE. OUTLET 8 1440 230 3.47 20 3.5 MM² THHN WIRE IN 13MM ø UPVC PIPE
OF THE LOCAL CODE APPLICATION FOR WHICH THESE ARE 4 REFRIGERATOR 1 200 230 0.87 20 3.5 MM² THHN WIRE IN 13MM ø UPVC PIPE
ENFORCING AUTHORITIES AND THE INTENDED FOR.
REQUIREMENTS OF THE LOCAL 10. ALL METALLIC CONDUITS AND TOTAL 2740 230 9.11 30 2-8.0 MM² THHN WIRE IN 20MM ø UPVC PIPE

POWER SERVICE PROVIDER. BOXES SHALL BE PROPERLY


SYSTEM VOLTAGE SHALL BE THREE GROUNDED AND BONDED
PHASE, 400/230VOLTS, 4-WIRE, 11.LIGHTING BRANCHES CIRCUITS
60 HERTZ SYSTEM. WITHOUT DESIGNATION SHALL
WIRING METHOD SHALL BE DONE IN BE 2-WIRE AND 1-GROUND WIRE IN
COMPUTATIONS:
RIGID STEEL CONDUIT (RSC) 15MMØ IMC CONDUIT UNLESS TOTAL CONNECTED LOADS IL = 2740/230 = 17.57 AMPS LEGENDS
FOR EXPOSED WIRING AND OTHERWISE NOTED. 80% ACTUAL LOAD: DEMAND FACTOR = 217.57 x 80% = 9.11 AMPS
SIZE OF MAIN WIRE & CONDUIT:
60AT
UNPLASTICIZED 12. CONVENIENCE OUTLETS CIRCUITS
POLYVINYL-CLHLORIDE
THEREFORE USE 2 - 8.0 mm2 TW WIRE FOR THE MAIN-FEEDER AND W WATER CLOSET
IN GENERAL SHALL BE 2-WIRE AND 30 A FOR THE MAIN BREAKER ON 20MM ø UPVC PIPE.
1 15A 15A 2
(uPVC) CONDUIT FOR EMBEDDED 1-GROUND WIRE IN 15MMØ IMC
WIRING. CONDUIT UNLESs OTHERWISE NOTED. FD FLOOR DRAIN
3 20A 20A 4
14 13.MOUNTING HEIGHTS OF WIRING
SMALLEST BRANCH WIRE SHALL BE DEVICES SHALL BE AS FOLLOWS: LAV. LAVATORY
3,5MM² THHN FOR POWER AND LIGHTING SWITCHES -1.40M
LIGHTING SYSTEM IN RACEWAY 15MMØ CONVENIENCE OUTLET -0.30M CO CLEAN OUT
TRADE SIZE CONDUIT. KITCHEN CON. OUTLET -1.20M
WIRE SHALL BE INSULATED FOR 600 FUSE BOX-1.80M
VOLTS. SAFETY SWITCHES-1.80M CB CATCH BASIN
CIRCUIT
ALL BRANCH CIRCUIT HOMERUNS KILOWATT HR METER -1.80M SYMBOLS:
SHALL BE INSTALLED AS ALL RECEPTACLES OUTLETS SHALL BE HOMERUN HB HOSE BIBB
INDICATED IN THE PLAN. EXPOSED PROPERLY GROUNDED TO THE
CONDUIT RUN SHALL BE BOX BY MEANS OF UL-LISTED CEILING LIGHT KILOWATTHOUR
F FAUCET
INSTALLED PARALLEL TO OR GROUNDING LUGS AND SS METER
PERPENDICULAR WITH THE METAL FASTENERS. CONVENIENCE OUTLET
BUILDING LINE AND SUPPORTED BY GROUND KS KITCHEN SINK
15 FOR SWITCH BOXES WITH MORE
CONDUIT CLAMPS EVERY THAN FOUR WIRES ENTERING, OUTLET FOR A.C.U LUGS
1.50M. DIAGONAL CONDUIT RUN SHALL USE SQUARE BOX WITH ONE ADAPTER LW LEACHING WELL
NOT BE ACCEPTED. RING. LIGHTING CIRCUIT LINE
WHENEVER NECESSARY, PULLBOX OF 16 FOR SWITCH BOXES WITH MORE M WATT HOUR-METER VSP VENT STACK PIPE
PROPER SIZE AND DIMENSION THAN FOUR WIRES ENTERING, POWER CIRCUIT LINE
MPB

SHALL BE PROVIDED ALTHOUGH NOT USE SQUARE BOX WITH ONE ADAPTER MAIN PANEL BOARD - MPB
Sa 1 Gang Switch DC DIGESTIVE CHAMBER
INDICATED IN THE PLAN. RING. PB

ALL JUNCTION BOXES SHALL BE 17 ALL ELECTRICAL WORKS HEREIN PANEL BOARD - PB
PROVIDED WITH COVERS. SHALL BE UNDER THE DIRECT AND Sab 2 Gang Switch MH MANHOLE
7 ALL BRANCHES CIRCUIT HOMERUNS IMMEDIATE SUPERVISION OF A DULY FLUSH WALL SWITCH
FOR POWER AND LIGHTING SHALL LICENSED ELECTRICAL ENGINEER Sabc 3 Gang Switch WM WATER METER
CIRCUIT BRANCH
NOT BE ENCASED INA DEDICATED OR MASTER ELECTRICIAN AUTHORIZED
RACEWAY. AS PER R.A. 7920. GV GATE VALVE
FOR EACH SPARE CIRCUIT IN THE

STUDENT INSTRUCTOR PLATE NO. AND TITLE SHEET CONTENT REMARKS SHEET NO.

DANIELLE BILASA PL01 TWO STOREY RESIDENTIAL


COURSE AND YEAR AR. CHRIS JEFFERSON BUAZON DATE SUBMITTED LIGHTING LAYOUT PLANS

3RD YEAR BS ARCHITECTURE 09-22-2023