f S 12 Spring Mount (Deflection:痴m)

■ Features
As a type of FSL series, it uses SM垃type (static deflection of 50mm)
and prevents damage and distortion of the equipment and pipe. The
upper housing (compression plate) has a restrain bolt and level bolt,
while the CR-type acoustical non s k id pad on the bottom is to
prevent the transfer of high-frequency vibration)

®®®@
■Usage

♦「or refrigerator of reciprocating and turbo types


♦「or cooling towers
♦「or other large pieces of equipment of which weight often changes
@G)

■ Specification
N

M
Name of C Standard
1 Non Skid Pad CR KS M 6617
2 Lower Housing SS400 KS D 3503
3 Spring Seat CR KS M 6617
SUP9 KS B 2402
4 Coil Spring
HSW3 KS B 2403
5 Restraint Bolt SS400 KS B 1002
6 Space Bar Plastic
7 Upper Housing SS400 KS D 3503
8 Level Bolt SS400 KS B 1002

■ Dimension & Selection Guide


Ca acWy Spnng Constant We`ht Dimension(mm)
[gf)
- · (kgf/mm) (kg
FSL2-100 100 2 10.4 |
FSL2-150 150 3 10.5
FSL2-200 200 4 10.6
FSL2-300 300 6 10.7
FSL2-400 400 8 10.9 280 234 150 14 64 288 M20X110
FSL2-500 500 10 18.0
FSL2-600 600 12 18.5
FSL2-750 750 15 19.0
FSL2-1000 1,(XX) 20 19.5
FSL2-1200 1,200 24 20.0
FSL2-1500 1,500 30 32.5
FSL2-1800 1,800 36 33.0 280 234 150 14 64 288 M20X110
FSL2-2000 2,(XX) 40 33.5
FSL2-2500 2,500 50 34.0
FSL2-320l 3,200 64 39.5 |
FSL2-3500 3,500 70 40.0 330 276 180 16 64 338 M24X120
FSL2-4000 4,閶 80 42.0
FSL2-5000 5,(XX) 100 49.0 I

FSL2-6000 6,(XX) 120 49.5


FSL2-8000 8,(XX) 160 50.0 552 516 180 17 100 369 M30 X180
FSL2-10000 10,CXX) 200 52.0 |
(NOTE) The specification and data are subject to change without prior to for improvement of product pe而rmance and qualin;
Project: Link 2324 - Tai Wo
Date: 27/10/2023

Point Load of Chiller, model: CVE310KG5GG9 (350RT)

Point A B C D Total
Operating Weight (kg) 1774 1356 2966 2266 8362

The above operating weights include refrigerant, chiller water, cooling water, etc..
LEGEND ACOUSTICS ENGINEERING LTD.
UNIT 12, 4/F., BLOCK A, WAH TAT IND. CENTRE, 8-10 WAH SING ST., KWAI CHUNG, N.T. Selection Guideline: Selection Criteria
TEL : (852) 2815 0928, 2815 0899 FAX : (852) 2854 0123 As the water-cooled chiller unit width is >6m, the minimum static deflection should be >38mm (By ASHRAE handbook & NSV handbook) rate deflection =50mm
The requirement of Isolation Efficiency is > 95% E > 95%
By equation E=(1-TR)x100%, Transimssion Rate TR should be < 0.05 TR < 0.05
By equation TR=1/-(1-η2), Frequency Ratio η should be > 4.58 η > 4.58
CLIENT : ATAL By equation η=fd/fn, fn should be < fd/4.58
As given by manufacturer, the lowest fd is 1500 RPM. By fn < 1500/4.58, fn should be < 327RPM
fn < 327RPM
PROJECT : Tai Wo As given by manufacturer, the highest fd is 13500 RPM. By fn < 13500/4.58, fn should be < 2946RPM
Under such circumstance, the 327 RPM is used as the criteria for fn
TITLE : Summary Table for Vibration Isolator - Water-Cooled Chiller By equation fn=1/2(3.14)Sqrt((9800/ds))*60, static deflection ds should be > 8mm to achieve 95% isolation efficiency
Minimum static deflection > 38mm
Also required by the specification, minimum 50% deflection should be achieved. Minimum static deflection should be > 38mm
DATE : 2023/12/2 (Rev.1) By equation K=W/ds, Spring Constant K should be less than Point Load/38 for each point K < (Point Load/38)
As suggested by supplier, the safety factor for point load should be 1.4 Point load = Operation weight x 1.4 safety factor

Selection Criteria Dynamic Weight x 1.4 Safety Factor 38 < ds < 50 Spring > 38mm > Point Load 1 fn < 327 Given fd (by manufacturer) K < (Point Load/38) η > 4.58 TR < 0.05 E > 95%
Isolation
Chiller Lowest Highest Frequency Frequency Isolation
Chiller Deflection of Rate Rate No. of Natural Spring constant Spring TR TR Efficiency
No. of Operation Point Selection of Operating Operating Ratio η Ratio η Efficiency
Item Designation Point Weight Point Load Deflection Capacity Spring frequency K criteria constant K (Lowest (Highest %
Chiller weight with Load (kg) Spring model Frequency Frequency (Lowest (Highest % (Lowest
(kg) (mm) (mm) (kg) Isolator fn (RPM) (kg/mm) (kg/mm) fd) fd) (Highest
40% S.F. (kg) fd (RPM) fd (RPM) fd) fd) fd)
fd)
1 A 2390 3346 3346 47.8 FSL2-3500 50 3500 1 137 1500 13500 < 88.1 70.0 10.97 98.75 0.008 0.000 99.16 99.99
2 B 2792 3909 3909 48.9 FSL2-4000 50 4000 1 135 1500 13500 < 102.9 80.0 11.09 99.83 0.008 0.000 99.18 99.99
WCC-02 1
3 C 2430 3402 3402 48.6 FSL2-3500 50 3500 1 136 1500 13500 < 89.5 70.0 11.06 99.57 0.008 0.000 99.18 99.99
4 D 2840 3976 3976 49.7 FSL2-4000 50 4000 1 134 1500 13500 < 104.6 80.0 11.19 100.69 0.008 0.000 99.19 99.99

Vibration Isolation Efficiency E = (1-TR) x 100%


Transmission Rate TR = 1/-(1- η2)
Frequency Ratio η = fd/fn
Natural Frequency fn = 1/2(3.14)Sqrt((Ks*9800/W))*60
Spring Coefficient Ks = Rate Capcity/Rate Deflection
Weight W = Point Load
Operating Frequency fd

Point Load = Operatuion Weight/No. of Point Load


Deflection of Point Load = Point Load /Rate Capacity * Rate Deflection
No. of Spring Isolator = No. of Equipment * No. of Point Load