0% found this document useful (0 votes)
125 views13 pages

Belimo EV..F BAC Datasheet En-Gb

This document provides technical specifications for an energy valve used to control the flow rate or power of water in closed heating and cooling systems. It lists various models of the valve along with their nominal voltage, flow rates, pressures ratings, communication protocols, and accuracy of sensors for measuring temperature, flow rate and glycol concentration.

Uploaded by

Haj Sma
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
125 views13 pages

Belimo EV..F BAC Datasheet En-Gb

This document provides technical specifications for an energy valve used to control the flow rate or power of water in closed heating and cooling systems. It lists various models of the valve along with their nominal voltage, flow rates, pressures ratings, communication protocols, and accuracy of sensors for measuring temperature, flow rate and glycol concentration.

Uploaded by

Haj Sma
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 13

Technical data sheet EV..

F+BAC

Characterised control valve with sensor-


operated flow rate or power control, power
and energy-monitoring function, 2-way,
Flange, PN 16 (Energy Valve)

• Nominal voltage AC/DC 24 V


• Control modulating, communicative, hybrid,
Cloud
• For closed cold and warm water systems
• For modulating control of air-handling and
heating systems on the water side
• Ethernet 10/100 Mbit/s, TCP/IP, integrated
web server
• Communication via BACnet, Modbus, Belimo
MP-Bus or conventional control
• optional Belimo Cloud connection
• Glycol monitoring

Type Overview

Type DN V'nom V'nom V'nom kvs theor. PN


[l/s] [l/min] [m³/h] [m³/h]
EV065F+BAC 65 8 480 28.8 50 16
EV080F+BAC 80 11 660 39.6 75 16
EV100F+BAC 100 20 1200 72 127 16
EV125F+BAC 125 31 1860 111.6 195 16
EV150F+BAC 150 45 2700 162 254 16
kvs theor.: Theoretical kvs value for pressure drop calculation

Technical data

Electrical data Nominal voltage AC/DC 24 V


Nominal voltage frequency 50/60 Hz
Nominal voltage range AC 19.2...28.8 V / DC 21.6...28.8 V
Power consumption in operation 7W
Power consumption in rest position 5W
Power consumption for wire sizing 6 VA (DN 65, 80)
11 VA (DN 100, 125, 150)
Connection supply / control Cable 1 m, 6x 0.75 mm²
Connection Ethernet RJ45 socket
Parallel operation Yes (note the performance data)

Data bus communication Communicative control BACnet IP, BACnet MS/TP


Modbus TCP, Modbus RTU
MP-Bus
Cloud
Number of nodes BACnet / Modbus see interface description
MP-Bus max. 8

Functional data Operating range Y 2...10 V


Input impedance 100 kΩ
Operating range Y variable 0.5...10 V
Position feedback U 2...10 V
Position feedback U note Max. 1 mA
Position feedback U variable 0...10 V
0.5...10 V
Sound power level Motor 45 dB(A)

www.belimo.com EV..F+BAC • en-gb • 2023-09-15 • Subject to change 1 / 13


Technical data sheet EV..F+BAC

Functional data V'max adjustable 30...100% of V'nom


Control accuracy ±5% (of 25...100% V'nom) @ 20°C / Glycol 0%
vol.
Control accuracy note ±10% (of 25...100% V'nom) @ -10...120°C /
Glycol 0...50% vol.
Min. controllable flow 1% of V'nom
Parametrisation via integrated web server / ZTH EU
Fluid Cold and warm water, water with glycol up to
max. 50% vol.
Fluid temperature -10...120°C [14...248°F]
Close-off pressure ∆ps 690 kPa
Differential pressure Δpmax 340kPa
Flow characteristic equal percentage, optimised in the opening
range (switchable to linear)
Leakage rate air-bubble tight, leakage rate A (EN 12266-1)
Pipe connection Flange
according to EN 1092-2
Installation orientation upright to horizontal (in relation to the stem)
Servicing maintenance-free
Manual override with push-button, can be locked

Temperature measurement Measuring accuracy absolute temperature ± 0.35°C @ 10°C (Pt1000 EN60751 Class B)
± 0.6°C @ 60°C (Pt1000 EN60751 Class B)
Measuring accuracy temperature difference ±0.18 K @ ΔT = 10 K
±0.23 K @ ΔT = 20 K
Resolution 0.05°C

Flow measurement Measuring principle Ultrasonic volumetric flow measurement


Measuring accuracy flow ±2% (of 25...100% V'nom) @ 20°C / glycol 0%
vol.
Measuring accuracy flow note ±6% (of 25...100% V'nom) @ -10...120°C / glycol
0...50% vol.
Min. flow measurement 0.5% of V'nom

Glycol monitoring Measurement display glycol 0...40% or >40%


Measuring accuracy glycolmonitoring ±4% (0...40%)

Safety data Protection class IEC/EN III, Protective Extra-Low Voltage (PELV)
Degree of protection IEC/EN IP40
IP54 when using protective cap or protective
grommet for RJ45 socket
Pressure equipment directive CE according to 2014/68/EU
EMC CE according to 2014/30/EU
Type of action Type 1
Rated impulse voltage supply / control 0.8 kV
Pollution degree 3
Ambient humidity Max. 95% RH, non-condensing
Ambient temperature -30...50°C [-22...122°F]
Storage temperature -40...80°C [-40...176°F]

Materials Valve body EN-GJL-250 (GG 25)


Flow measuring pipe EN-GJL-250 (GG 25), with protective paint
Closing element Stainless steel AISI 316

www.belimo.com EV..F+BAC • en-gb • 2023-09-15 • Subject to change 2 / 13


Technical data sheet EV..F+BAC

Technical data
Materials Spindle Stainless steel AISI 304
Spindle seal EPDM
Seat PTFE, O-ring Viton
Immersion sleeve Stainless steel AISI 316

Safety notes

• This device has been designed for use in stationary heating, ventilation and air-conditioning
systems and must not be used outside the specified field of application, especially in aircraft or
in any other airborne means of transport.
• Outdoor application: only possible in case that no (sea) water, snow, ice, insolation or
aggressive gases interfere directly with the device and that it is ensured that the ambient
conditions remain within the thresholds according to the data sheet at any time.
• Only authorised specialists may carry out installation. All applicable legal or institutional
installation regulations must be complied with during installation.
• The device contains electrical and electronic components and must not be disposed of as
household refuse. All locally valid regulations and requirements must be observed.

Product features

Operating mode The HVAC performance device is comprised of four components: characterised control valve
(CCV), measuring pipe with volumetric flow sensor, temperature sensors and the actuator itself.
The adjusted maximum flow (V'max) is assigned to the maximum control signal DDC (typically
10 V / 100%). Alternatively, the control signal DDC can be assigned to the valve opening angle or
to the power required on the heat exchanger (see power control). The HVAC performance
device can be controlled via communicative or analogue signals. The fluid is detected by the
sensor in the measuring pipe and is applied as the flow value. The measured value is balanced
with the setpoint. The actuator corrects the deviation by changing the valve position. The angle
of rotation α varies according to the differential pressure through the control element (see flow
rate curves).

Flow rate curves

www.belimo.com EV..F+BAC • en-gb • 2023-09-15 • Subject to change 3 / 13


Technical data sheet EV..F+BAC

Transmission behaviour HE Heat exchanger transmission behaviour


Depending on the construction, temperature spread, fluid characteristics and hydronic circuit,
the power Q is not proportional to the water volumetric flow V' (Curve 1). With the classical type
of temperature control, an attempt is made to maintain the control signal Y proportional to the
power Q (Curve 2). This is achieved by means of an equal-percentage flow characteristic (Curve
3).

Power control Alternatively, the control signal DDC can be assigned to the output power required at the heat
exchanger.
Depending on the water temperature and air conditions, the Energy Valve ensures the amount
of water V' required to achieve the desired power.

Maximum controllable power on heat exchanger in power control mode:

Control characteristics The specially configured control parameters in connection with the precise velocity sensor
ensure a stable quality of control. They are, however, not suitable for rapid control processes,
i.e. for domestic water control.

Power control
Q'nom is the maximum possible power output on the heat exchanger.

Q'max is the maximum power output on the heat exchanger which has been set with the
highest control signal DDC. Q'max can be set between 1% and 100% of Q'nom.

Q'min 0% (non-variable).

www.belimo.com EV..F+BAC • en-gb • 2023-09-15 • Subject to change 4 / 13


Technical data sheet EV..F+BAC

Flow control
V'nom is the maximum possible flow.

V'max is the maximum flow rate which has been set with the highest control signal. V'max can
be set between 30% and 100% of V'nom.

Creep flow suppression Given the very low flow speed in the opening point, this can no longer be measured by the
sensor within the required tolerance. This range is overridden electronically.

Opening valve
The valve remains closed until the flow required by the control signal DDC corresponds to 1% of
V'nom. The control along the flow characteristic is active after this value has been exceeded.

Closing valve
The control along the flow characteristic is active up to the required flow rate of 1% of V'nom.
Once the level falls below this value, the flow rate is maintained at 1% of V'nom. If the level falls
below the flow rate of 0.5% of V'nom required by the control signal DDC, then the valve will
close.

Configurable actuators The factory settings cover the most common applications. Single parameters can be modified
with the Belimo service tools MFT-P or ZTH EU.

www.belimo.com EV..F+BAC • en-gb • 2023-09-15 • Subject to change 5 / 13


Technical data sheet EV..F+BAC

Communication The parametrisation can be carried out through the integrated web server (RJ45 connection to
the web browser) or by communicative means.
Additional information regarding the integrated web server can be found in the separate
documentation.

"Peer to Peer" connection


http://belimo.local:8080
The Notebook must be set to "DHCP".
Make sure that only one network
connection is active.

Standard IP address:
http://192.168.0.10:8080
Static IP address

Password (read-only):
User name: «guest»
Password: «guest»

Control signal inversion This can be inverted in cases of control with an analogue control signal DDC. The inversion
causes the reversal of the standard behaviour, i.e. at a control signal DDC of 0%, regulation is to
V'max or Q'max, and the valve is closed at a control signal DDC of 100%.

Hydronic balancing Via the integrated web server, the maximum flow rate (equivalent to 100% requirement) can be
adjusted on the device itself, simply and reliably, in a few steps. If the device is integrated in the
management system, then the balancing can be handled directly by the management system.

Delta-T manager If a heating or cooling register is operated with a differential temperature that is too low and
thus with a flow rate that is too high, this will not result in an increased power output.
Nevertheless, heating or cooling machines must provide the energy at a lower degree of
efficiency. This means, that pumps circulate too much water and increase energy consumption
unnecessarily.
With the aid of the Energy Valve, it is simple to discover that operation is being carried out at a
differential temperature that is too low, resulting in the inefficient use of energy.
Necessary setting adjustments can now be carried out quickly and easily at any time. The
integrated differential temperature limiting offers the user the possibility of defining a low limit
value. The Energy Valve limits the flow rate automatically to prevent the level from falling below
this value.
The settings of the Delta-T manager can be made either directly on the web server or via the
Belimo Cloud a direct analysis of the Delta-T behavior is carried out by Belimo experts.

Power output of the heating or cooling


registers 1
Diff. temperature between supply and
return 2
Loss zone (heating or cooling register
saturation) 3
Adjustable minimum differential
temperature 4

Combination analogue - communicative With conventional control by means of an analogue control signal DDC, the integrated web
(hybrid mode) server, BACnet, Modbus or MP-Bus can be used for the communicative position feedback.

www.belimo.com EV..F+BAC • en-gb • 2023-09-15 • Subject to change 6 / 13


Technical data sheet EV..F+BAC

Product features
Power and energy monitoring function The HVAC performance device is equipped with two temperature sensors. One sensor (T2) is
integrated in the measuring pipe, the second sensor (T1) is included with the system, prewired,
and must be installed in the water circuit on site. The sensors are used to record the fluid
temperature of the supply and return lines of the consumer (heating/cooling coil). As the water
quantity is also known, thanks to the flow measurement integrated in the system, the power
released from the consumer can be calculated. Furthermore, the heating/cooling energy is also
determined automatically by means of the evaluation of the power over time.
The current data, e.g. temperatures, volumetric flow volumes, exchanger energy consumption
etc. can be recorded and accessed at any time by means of web browsers or communication.

Data recording The recorded data (integrated data recording for 13 months) can be used for the optimisation
of the overall system and for the determination of the performance of the consumer (heating/
cooling coil).
Download csv files through web browser.

Belimo Cloud Additional services are available if the Energy Valve is connected to the Belimo Cloud: for
instance, several devices may be managed via Internet. Also, Belimo experts may help analyse
the delta-T behaviour or provide written reports about the Energy Valve performance. Under
certain conditions, the product warranty according to the applicable Terms and Conditions of
Sale may be prolonged. The "Terms of Use for Belimo Cloud Services" in their currently valid
version apply to the use of Belimo Cloud services. Further details may be found under
[www.belimo.com/ext-warranty]

Glycol monitoring Glycol monitoring measures the actual glycol content, which is necessary for safe operation and
optimised heat exchange.

Manual override Manual override with push-button possible (the gear train is disengaged for as long as the
button is pressed or remains locked).

High functional safety The actuator is overload protected, requires no limit switches and automatically stops when the
end stop is reached.

Accessories

Electrical accessories Description Type


Grommet for RJ connection module, Multipack 50 pcs. Z-STRJ.1
Stem heater flange F05 (30 W) ZR24-F05
Tools Description Type
Service tool, with ZIP-USB function, for parametrisable and ZTH EU
communicative Belimo actuators, VAV controller and HVAC performance
devices
Connecting cable 5 m, A: RJ11 6/4 ZTH EU, B: 6-pin for connection to ZK1-GEN
service socket

Electrical installation

Supply from isolating transformer.


Parallel connection of other actuators possible. Observe the performance data.
The wiring of the line for BACnet MS/TP / Modbus RTU is to be carried out in accordance with
applicable RS-485 regulations.
Modbus / BACnet: Supply and communication are not galvanically isolated. Connect earth signal
of the devices with one another.

www.belimo.com EV..F+BAC • en-gb • 2023-09-15 • Subject to change 7 / 13


Technical data sheet EV..F+BAC

Electrical installation
Wire colours: Functions:
1 = black C1 = D- = A (wire 6)
2 = red C2 = D+ = B (wire 7)
3 = white
5 = orange
6 = pink
7 = grey

Conventional operation

Connection of a notebook for


parametrisation and manual
Cable colours: control via RJ45.
1 = black
2 = red Optional connection via RJ45
3 = white (direct connection Notebook /
5 = orange connection via Intranet or
6 = pink Internet) for access to the
7 = grey integrated web server

MP-Bus, supply via 3-wire connection MP-Bus via 2-wire connection, local power supply

A) additional MP-Bus nodes A) additional MP-Bus nodes


(max. 8) (max. 8)

Functions

Functions when operated on MP-Bus


MP-Bus Network topology

There are no restrictions for the


network topology (star, ring,
tree or mixed forms are
permitted).
Supply and communication in
one and the same 3-wire cable
• no shielding or twisting
necessary
• no terminating resistors
required

Functions with specific parameters (parametrisation necessary)


BACnet MS/TP / Modbus RTU

C₁ = D- = A
C₂ = D+ = B

www.belimo.com EV..F+BAC • en-gb • 2023-09-15 • Subject to change 8 / 13


Technical data sheet EV..F+BAC

Functions
Functions with specific parameters (parametrisation necessary)
BACnet IP / Modbus TCP MP-Bus with analog setpoint (hybrid mode)

BACnet MS/TP / Modbus RTU with analog setpoint (hybrid mode) BACnet IP / Modbus TCP with analog setpoint (hybrid mode)

Override control and limiting with DC 24 V with relay contacts (with conventional control or hybrid mode)

1) Position control
2) Flow control
3) Power control

www.belimo.com EV..F+BAC • en-gb • 2023-09-15 • Subject to change 9 / 13


Technical data sheet EV..F+BAC

Operating controls and indicators

2 LED display green

Off: No power supply or wiring error


On: In operation
Flickering: Internal communication (Valve/Sensor)

3 Push-button and LED display yellow

On: Adaptation or synchronisation process active


Press button: Triggers angle of rotation adaptation, followed by standard mode

4 Manual override button

Press button: Gear train disengages, motor stops, manual override possible
Release button: Gear train engages, standard mode

5 Service plug
For connecting parametrisation and service tools

Installation notes

Permissible installation orientation The ball valve can be installed upright to horizontal. The ball valve may not be installed in a
hanging position, i.e. with the spindle pointing downwards.

Installation location in return Installation in the return is recommended.

Water quality requirements The water quality requirements specified in VDI 2035 must be adhered to.
Belimo valves are regulating devices. For the valves to function correctly in the long term, they
must be kept free from particle debris (e.g. welding beads during installation work). The
installation of a suitable strainer is recommended.

Spindle heater In cold water applications and warm humid ambient air can cause condensation in the
actuators. This can lead to corrosion in the gear box of the actuator and causes a breakdown of
it. In such applications, the use of a spindle heater is recommended.
The spindle heater must be enabled only when the system is in operation, because it does not
have temperature control.

Servicing Ball valves, rotary actuators and sensors are maintenance-free.


Before any service work on the control element is carried out, it is essential to isolate the rotary
actuator from the power supply (by unplugging the electrical cable if necessary). Any pumps in
the part of the piping system concerned must also be switched off and the appropriate slide
valves closed (allow all components to cool down first if necessary and always reduce the
system pressure to ambient pressure level).
The system must not be returned to service until the ball valve and the rotary actuator have
been correctly reassembled in accordance with the instructions and the pipeline has been
refilled by professionally trained personnel.

www.belimo.com EV..F+BAC • en-gb • 2023-09-15 • Subject to change 10 / 13


Technical data sheet EV..F+BAC

Installation notes
Flow direction The direction of flow, specified by an arrow on the housing, is to be complied with, since
otherwise the flow rate will be measured incorrectly.

Inlet section In order to achieve the specified measuring accuracy, a flow-calming section or inflow section in
the direction of the flow is to be provided upstream from the flow sensor. Its dimensions should
be at least 5x DN.

Mounting of immersion sleeve and The valve is equipped with two temperature sensors:
temperature sensor • T2: One sensor is already installed in the valve unit.
• T1: The second sensor must be mounted at the installation site ahead of the consumer (valve
in the return line; recommended) or after the consumer (valve in the supply line). The
immersion sleeve required is supplied with the valve unit.

The temperature sensor is already wired with the valve.

Note
The cable between valve unit and temperature sensor may not be either shortened or
lengthened.

Split installation The valve-actuator combination may be mounted separately from the flow sensor. The direction
of flow of both components must be observed.

www.belimo.com EV..F+BAC • en-gb • 2023-09-15 • Subject to change 11 / 13


Technical data sheet EV..F+BAC

General notes

Minimum differential pressure (pressure The minimum required differential pressure (pressure drop through the valve) for achieving the
drop) desired volumetric flow V'max can be calculated with the aid of the theoretical kvs value (see
type overview) and the below-mentioned formula. The calculated value is dependent on the
required maximum volumetric flow V'max. Higher differential pressures are compensated for
automatically by the valve.

Formula

Example (DN 100 with the desired maximum flow rate = 50% V'nom)

Behaviour in case of sensor failure In case of a flow sensor error, the Energy Valve will switch from either power or flow control to
position control (Delta-T manger will be deactivated).
Once the error disappears, the Energy Valve will switch back to the normal control setting
(Delta-T manager activated)

Dimensions

Dimensional drawings

If Y <180 mm, the extension of the hand crank must be demounted as necessary.

www.belimo.com EV..F+BAC • en-gb • 2023-09-15 • Subject to change 12 / 13


Technical data sheet EV..F+BAC

Further documentation

• Tool connections
• BACnet Interface description
• Modbus Interface description
• Description Data-Pool Values
• Overview MP Cooperation Partners
• MP Glossary
• Introduction to MP-Bus Technology
• General notes for project planning
• Instruction Webserver

www.belimo.com EV..F+BAC • en-gb • 2023-09-15 • Subject to change 13 / 13

You might also like