0 ratings0% found this document useful (0 votes) 74 views2 pagesFxaq20pve - 7,500 Btu - Split Pared - 220V - 1F
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
”’ DAIKIN
EDMT391908
R-410A
Engineering Data
TRY
Indoor Units Only
60 Hz”” DAIKIN
EDMT391908
Model FXAQ20PVE
Power supply 1 phase, 220-240/220V, 50/60Hz
kealfh 4,900
41 3 Cooling capacity Biuih 7,500
kW 22
kealfh 2,200
+23 Healing capacity Biuih 8,500
KW 25
Casing colour White (3.078.5/05)
Dimensions: (HxWxD) mm 290795238
Model (QCL9661M
Type ‘Gross flow fan
aoe |W ‘
Fan m/min 75/45
Airflow rate (H/L) Us 125775
cfm 265/159
Drive Direct drive
Temperature control Micoprogsssor thermostat for
‘Sound absorbing thermal insulation material reames Polethyions
ir filter, Resin net (Washable)
Liquid pipes mm 96.4 (Flare connection)
Piping __—_[ Gas pipes mm (127 (Flare connection)
connections _ VP13
Drain pipe mm (External dia. 18, internal dia. 13)
Mass kg 4
3&4 Sound pressure level (HL) dB(A) 35/34
Safety devices Fuse
Refrigerant control Electronic expansion valve
‘Operation manual. Installation
manual. Installation panel. Paper
Standard accessories pattern fr installation. Insulation pe,
lamps. Screws.
- Specification ©:8D077064A
Drawing No.
‘Sound level (©: 4077090
Notes:
Indoor temp : 27°CDB, 19°CWB / outdoor temp.: 36°CDB / Equivalent piping length: 7.5 m, level difference: 0m,
Indoor temp.. 20°CDB, 15°CWB / outdoor temp... 7°CDB, 6°CWB / Equivalent piping length: 7.5 m,
1
2,
#8
A,
level difference: Om.
Capacities are net, including a deduction for cooling (an addition for heating) for indaor fan motor heat.
‘Anechoic chamber conversion value, measured at a point 1 min front of the unit and 11m downward. During
actual operation, these values are normally somewhat higher as a result of ambient conditions.
‘Conversion formulae
keallh=KW=860
BHWh=KWW%3412
imine 35 3
min 1000/60