TRANSMISSION MATERIALS STANDARD SPECIFICATION 10-TMSS-07, Rev.
6.0 DATA SCHEDULE
SUBSTATION GROUNDING MATERIALS
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.2.4 Ratings:
Weight of conductor per km (kg) *
Length of conductor in one
(M) *
drum
Net weight of one drum with
(kg) *
conductor
Gross weight of one drum with
(kg) *
conductor
Cu / XLPE / PVC 1kV RM IEC 60502-1 FR-IEC 60332-3-24
4.2.5 Annealed, soft insulated copper Annealed, soft insulated
conductor copper conductor
Name of manufacturer * Bahra Cables Company
Country of origin * KSA
Installation Grounding Grounding
Material conductivity (%) 100 100
Max. operating conductor Temp= 90°C
Maximum copper temperature (ºC) 250 Max. conductor short circuit Temp for 5 Seconds= 250°C
XLPE insulation material with color: Green
Color of insulation Green-yellow PVC outer-sheath material with color: Green with yellow strips
Compacted / Non-compacted * Round Non Compacted
Conductor size (mm2) * (50,120,240) mm2
Maximum current carrying
(A) * 175 Size 50 mm2 *
capacity 326 Size 120 mm2 *
505 Size 240 mm2 *
7.15 Size 50 mm2 Calculated based on initial
17.17 Size 120 mm2 conductor Temp=90°C Max.
Short circuit capability (1s) (kA) * 34.34 Size 240 mm2 conductor short circuit = 250°C
Weight of conductor per km (kg) 404 Size 50 mm22
1016 Size 120 mm2
m2
2074 Size 240 mm2
m2
Length of conductor in one drum (M) * 1000 (+/- 5%)
Net weight of one drum with Cable weight
(kg) * 518 Size 50 mm22
conductor 1205 Size 120 mm2
2
2397 Size 240 mm2
2
10TMSS07R0/KVJ Date of Approval: September 19, 2021 PAGE
PA
P AGE
GE 113
3 OFOF 1717
License=Bahra Cable Company/SA-823-T Not For Resale ,11/3/2021 4:52:08 PM Saudi Time *Laid in air @ 40 °C
C Amb
Ambient
bie
ie
ien
en
nt Temperature
Tem
Tem
e mp
pe
per
eerra
attu
atu
turre
e
Free In Trefoil Shape
pe
TRANSMISSION MATERIALS STANDARD SPECIFICATION 10-TMSS-07, Rev. 0
6.0 DATA SCHEDULE
SUBSTATION GROUNDING MATERIALS
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.2.5 Ratings:
(Drum weight + Cable weight)
Gross weight of one drum with 553 Size 50 mm2
(kg) * 1280 Size 120 mm2
conductor 2527 Size 240 mm2
Insulation voltage for Surge
(kV) 5
Arrestor grounding conductor 5 KV
Conductor size of above (mm2) * N/A
4.2.6 Copper cladded steel ground rod
Manufacturer’s Drawing No: *
Nominal diameter (mm) *
Actual diameter (mm) *
Thickness of copper (mm) 0.25
Length of Rod (mm) *
4.2.7 Ground rod accessories
Coupling
Manufacturer’s Drawing No: *
Overall length (mm) *
Outside diameter (mm) *
Inside diameter (mm) *
Wall Thickness (mm) *
Length of slip fit over rod (mm) *
Material
*
10TMSS07R0/KVJ Date of Approval: September 19, 2021 PAGE
PA
P AG
GE
E114
4 OF
OF 1
177
License=Bahra Cable Company/SA-823-T Not For Resale ,11/3/2021 4:52:08 PM Saudi Time