Preface
___________________
Description of the device 1
2
___________________
Installation
SIMATIC NET
___________________
Connecting up 3
Industrial Remote Communication
Remote Networks ___________________
Dimension drawing 4
SCALANCE M874, M876
___________________
Technical specifications 5
Operating Instructions
___________________
Approvals A
07/2014
C79000-G89760-C331-03
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
Further documentation
● System manual "Industrial Ethernet"
The system manual contains information on other SIMATIC NET products that you can
operate along with the devices of this product line in an Industrial Ethernet network.
There, you will find among other things optical performance data of the communications
partner that you require for the installation.
The "SIMATIC NET Industrial Ethernet" system manual can be found on the Internet
pages of Siemens Industry Online Support under the following entry ID:27069465
(http://support.automation.siemens.com/WW/view/wn/27069465)
Security messages
Note
Siemens offers IT security mechanisms for its automation and drive product portfolio in order
to support the safe operation of the plant/machine. Our products are also continuously
developed further with regard to IT security. We therefore recommend that you regularly
check for updates of our products and that you only use the latest versions. You will find
information in:
(http://support.automation.siemens.com/WW/llisapi.dll?func=cslib.csinfo2&aktprim=99&lang=
en)
Here, you can register for a product-specific newsletter.
For the safe operation of a plant/machine, however, it is also necessary to integrate the
automation components into an overall IT security concept for the entire plant/machine,
which corresponds to the state-of-the-art IT technology. You will find information on this in:
(http://www.siemens.com/industrialsecurity)
Products from other manufacturers that are being used must also be taken into account.
License conditions
Note
Open source software
Read the license conditions for open source software carefully before using the product.
You will find license conditions in the following documents on the supplied data medium:
● DOC_OSS-SCALANCE-M_74.pdf
● DC_LicenseSummaryScalanceM874_76.htm
● DC_LicenseSummaryScalanceM876_76.htm
Preface ................................................................................................................................................... 3
1 Description of the device ......................................................................................................................... 9
1.1 Product characteristics ................................................................................................................... 9
1.1.1 SCALANCE M874-2, M874-3 ........................................................................................................ 9
1.1.2 SCALANCE M876-3 ....................................................................................................................10
1.2 Unpacking and checking ..............................................................................................................12
1.3 Accessories ..................................................................................................................................13
1.4 LED display ..................................................................................................................................14
1.4.1 SCALANCE M874-2, M874-3 ......................................................................................................14
1.4.2 SCALANCE M876-3 ....................................................................................................................16
1.5 SET button ...................................................................................................................................18
1.6 C-PLUG and KEY-PLUG .............................................................................................................20
2 Installation ............................................................................................................................................ 23
2.1 Securing the housing ...................................................................................................................24
2.2 Wall mounting ..............................................................................................................................25
2.3 Installing on the DIN rail ...............................................................................................................26
2.4 Installing on the S7-300 standard rail ..........................................................................................27
2.5 Installing on the S7-1500 standard rail ........................................................................................28
3 Connecting up....................................................................................................................................... 31
3.1 Safety when connecting up ..........................................................................................................31
3.2 SIM card .......................................................................................................................................33
3.3 Power supply................................................................................................................................34
3.4 Grounding ....................................................................................................................................36
3.5 Digital input/output .......................................................................................................................37
3.6 Antennas ......................................................................................................................................39
3.7 Ethernet port ................................................................................................................................42
3.8 Replacing the PLUG ....................................................................................................................43
4 Dimension drawing ............................................................................................................................... 45
4.1 SCALANCE M874-2, M874-3 ......................................................................................................45
4.2 SCALANCE M876-3 ....................................................................................................................47
Interfaces
Functionality M874-2
M874-3
Connectors for external antennas 1
SMA antenna connector
Ethernet interface 2 x RJ-45 10 / 100 Mbps
Digital input/output 1/1
Scope of delivery
The following components ship with the product:
● One device
● A 5-pin terminal block for the power supply
● A 2-pin terminal block for the digital output
● A 2-pin terminal block for the digital input
● Product CD
Note
Not included with the product
The following components do not ship with the product:
• KEY-PLUG / C-PLUG
You will find more detailed information in "C-PLUG and KEY-PLUG (Page 20)".
• Antennas
You will find more detailed information in "Accessories (Page 13)".
• SIM card
Use the SIM card from the chosen mobile wireless provider
Order numbers
Interfaces
Functionality M876-3
Connectors for external antennas 2
SMA antenna connector
Ethernet interface 4 x RJ-45 10 / 100 Mbps
Digital input/output 1/1
Scope of delivery
The following components ship with the product:
● One device
● A 5-pin terminal block for the power supply
● A 2-pin terminal block for the digital output
● A 2-pin terminal block for the digital input
● Product CD
Note
Not included with the product
The following components do not ship with the product:
• KEY-PLUG / C-PLUG
You will find more detailed information in "C-PLUG and KEY-PLUG (Page 20)".
• Antennas
You will find more detailed information in "Accessories (Page 13)".
• SIM card
Use the SIM card from the chosen mobile wireless provider
Order numbers
WARNING
Do not use any parts that show evidence of damage
If you use damaged parts, there is no guarantee that the device will function according to
the specification.
If you use damaged parts, this can lead to the following problems:
• Injury to persons
• Loss of the approvals
• Violation of the EMC regulations
Use only undamaged parts.
1.3 Accessories
You will find further information on the accessories program for the M874 in the Industry Mall
(https://eb.automation.siemens.com/goos/WelcomePage.aspx?regionUrl=/en&language=en)
.
Antennas
ON Connection established
Q OFF No reception
Signal strength: < -109 dBm
Flashing Signal strength poor: -89 dBm to -109 dBm
ON VPN established
ON Connection established
Q OFF No reception
Signal strength: < -109 dBm
Flashing Signal strength poor: -89 dBm to -109 dBm
ON VPN established
How it works
The C-PLUG or KEY-PLUG is used to transfer the configuration of the old device to the new
device when a device is replaced.
NOTICE
Do not remove or insert a C-PLUG / KEY-PLUG during operation!
A PLUG may only be removed or inserted when the device is turned off.
The device checks whether or not a PLUG is present at one second intervals. If it is
detected that the PLUG was removed, there is a restart.
If a valid KEY-PLUG was inserted in the device, the device changes to a defined error state
following the restart.
When the new device starts up with the PLUG, it then continues automatically with exactly
the same configuration as the old device. One exception to this can be the IP configuration if
it is set over DHCP and the DHCP server has not been reconfigured accordingly.
A reconfiguration is necessary if you use functions based on MAC addresses.
If an incorrect PLUG, for example from another product or a damaged PLUG is inserted, the
device signals an error with the "F" LED.
You can either remove the PLUG again or select the option to reformat the PLUG.
In terms of the PLUG, devices work in two modes:
● Without PLUG
The device stores the configuration in internal memory. This mode is active when no
PLUG is inserted.
● With PLUG
The configuration stored on the PLUG is displayed in WBM in "Information > PLUG". If
changes are made to the configuration, the device stores the configuration directly on the
PLUG and in the internal memory. This mode is active as soon as a PLUG is inserted. As
soon as the device is started with a PLUG inserted, the device starts up with the
configuration data on the PLUG.
Order numbers
See also
Replacing the PLUG (Page 43)
WARNING
WARNING
WARNING
To comply with EC Directive 94/9 (ATEX95) or the conditions of IECEx, this enclosure must
meet the requirements of at least IP54 in compliance with EN 60529.
Types of installation
For the device, you have the following options:
● Wall mounting
● Installation on a DIN rail
● Installing on the S7-300 standard rail
● Installing on the S7-1500 standard rail
Note
The wall mounting must be capable of supporting four times the weight of the device, but at
least 50 N. For information on the weight, refer to the section "Technical specifications
(Page 49)".
Requirement
There is a SIM card for the device.
Installation
1. Insert the SIM card, see section "SIM card (Page 33)".
2. Prepare the drill holes for wall mounting. For the precise dimensions, refer to the section
"Dimension drawing (Page 45)".
3. Secure the device to the wall with two screws. When mounting on a wall, use mounting
fittings suitable for the type of wall.
1. Connect the power supply, refer to the section "Power supply (Page 34)".
2. Fit the connectors for the digital input and digital output, refer to the section "Digital
input/output (Page 37)".
3. Connect the antenna, refer to the section "Antennas (Page 39)".
4. Connect the device to the local network, refer to the section "Ethernet port (Page 42)".
Requirement
There is a SIM card for the device.
Installation
1. Insert the SIM card, see section "SIM card (Page 33)".
2. Place the third housing guide of the device on the top edge of the DIN rail ①.
3. Press the device down against the DIN rail until the spring catch locks in place ②.
4. Connect the power supply, refer to the section "Power supply (Page 34)".
5. Fit the connectors for the digital input and digital output, refer to the section "Digital
input/output (Page 37)".
6. Connect the antenna, refer to the section "Antennas (Page 39)".
7. Connect the device to the local network, refer to the section "Ethernet port (Page 42)".
Dismantling
1. Disconnect all connected cables.
2. Using a screwdriver, pull down the catch on the rear of the device.
3. Pull lower part of the device away from the DIN rail.
Requirement
There is a SIM card for the device.
Installation
1. Insert the SIM card, see section "SIM card (Page 33)".
2. Place the second housing guide of the device on the top edge of the standard rail ①.
3. Press the device down against the standard rail until the spring catch locks in place ②.
4. Connect the power supply, refer to the section "Power supply (Page 34)".
5. Connect the connectors for the digital input to the digital output, see section "Digital
input/output (Page 37)".
6. Connect the antenna, refer to the section "Antennas (Page 39)".
7. Connect the device to the local network, refer to the section "Ethernet port (Page 42)".
Dismantling
1. Disconnect all connected cables.
2. Using a screwdriver, pull down the catch on the rear of the device.
3. Remove the device from the standard rail.
Requirement
There is a SIM card for the device.
Installation
1. Insert the SIM card, see section "SIM card (Page 33)".
2. Place the first housing guide of the device on the top edge of the standard rail ①.
3. Using a screwdriver, pull down the catch ② on the rear of the device.
4. Swing the device down while pulling down the catch ③. After it is released, the spring
catch locks in place.
5. Connect the power supply, refer to the section "Power supply (Page 34)".
6. Fit the connectors for the digital input and digital output, refer to the section "Digital
input/output (Page 37)".
7. Connect the antenna, refer to the section "Antennas (Page 39)".
8. Connect the device to the local network, refer to the section "Ethernet port (Page 42)".
Dismantling
1. Disconnect all connected cables.
2. Using a screwdriver, pull down the catch on the rear of the device.
3. Remove the device from the standard rail.
Safety notices
When connecting up the device, keep to the safety notices listed below.
WARNING
The equipment is designed for operation with Safety Extra-Low Voltage (SELV) by a
Limited Power Source (LPS).
This means that only SELV / LPS complying with IEC 60950-1 / EN 60950-1 / VDE 0805-1
must be connected to the power supply terminals. The power supply unit for the equipment
power supply must comply with NEC Class 2, as described by the National Electrical Code
(r) (ANSI / NFPA 70).
If the equipment is connected to a redundant power supply (two separate power supplies),
both must meet these requirements.
WARNING
EXPLOSION HAZARD
SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION
2 OR ZONE 2.
WARNING
EXPLOSION HAZARD
DO NOT OPEN WHEN ENERGIZED.
WARNING
Take measures to prevent transient voltage surges of more than 40% of the rated voltage.
This is the case if you only operate devices with SELV (safety extra-low voltage).
WARNING
EXPLOSION HAZARD
DO NOT CONNECT OR DISCONNECT EQUIPMENT WHEN A FLAMMABLE OR
COMBUSTIBLE ATMOSPHERE IS PRESENT.
Safety notices when using the device according to Hazardous Locations (HazLoc)
If you use the device under HazLoc conditions you must also keep to the following safety
notices in addition to the general safety notices for protection against explosion:
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or non-
hazardous locations only.
This equipment is suitable for use in Class I, Zone 2, Group IIC or non-hazardous locations
only.
WARNING
EXPLOSION HAZARD
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS.
NOTICE
Turn off the power supply before replacing SIM cards
Before you insert or remove the SIM card, turn off the power supply of the M-800.
Do not open the compartment for the SIM card during operation. This can damage the SIM
card and the device.
Procedure
1. The compartment for the SIM card is located on the back of the device. Directly beside to
the compartment for the SIM card in the opening in the housing, there is a small button.
To open the drawer, press the button with a sharp object, for example a pencil.
2. Place the SIM card in the tray so that the card audibly locks in place and so that its gold-
plated contacts remain visible.
3. Then push the tray with the SIM card completely back into the housing.
Note
Permitted external power supplies
The power supply unit to supply the SCALANCE M-800 must comply with the requirements
for a limited power source according to IEC/EN 60950-1, section 2.5.
The external power supply for the SCALANCE M-800 must meet the requirements for NEC
class 2 circuits as specified in the National Electrical Code ® (ANSI/NFPA 70).
Refer to the section Connecting up (Page 31) and the installation instructions and
instructions for use of the manufacturer of the power supply, the battery or the accumulator.
3.4 Grounding
A functional grounding must be established for example by connecting a cable from
terminal 5 to the DIN rail, refer to the section "Power supply (Page 34)". Such a cable should
be kept as short as possible.
CAUTION
Damage due to voltage being too high or too low
The voltage at the digital input/output must not exceed 30 VDC and not fall below -30 VDC,
otherwise the digital input/output will be destroyed.
Digital input
The 2-pin terminal block has the following assignment:
DI+ 24 VDC
DI- (input ground) -
If there is an adequate switching voltage at the digital input, the digital input is active and the
"DI" LED is lit. This means that, for example a local application connected to the in port can
trigger an alarm message by SMS outside the IP data connection.
Digital output
The 2-pin terminal block has the following assignment:
3.6 Antennas
Note
Use the antennas from the accessories program for the M-800 device. You will find more
detailed information in "Accessories (Page 13)". If you use a different antenna, there is no
guarantee that the device will function according to the specification.
The antenna socket for connecting the antenna is of the type SMA. The antenna used
should have an impedance of about 50 ohms.
CAUTION
Minimum clearance to the device
The device may only be operated when the distance between the device (or antenna) and
user is at least 20 cm.
WARNING
Danger due to lightning strikes
Antennas installed outdoors must be within the area covered by a lightning protection
system. Make sure that all conducting systems entering from outdoors are protected by
lightning protection electrical bonding.
When implementing your lightning protection concept, make sure you adhere to the
requirements of the VDE 0182 or IEC 62305 standards.
Suitable lightning protectors are available in the range of accessories of SIMATIC NET
Industrial WLAN:
● Lightning protector LP798-1N (order no. 6GK5798-2LP00-2AA6)
● Lightning protector LP798-2N (order no. 6GK5798-2LP10-2AA6)
Note
We recommend that you use the maintenance-free lightning protector LP798-2N.
Exception:
When there is also DC power supplied via the antenna cable. In this case, only the
lightning protector LP798-1N can be used.
WARNING
Danger due to lightning strikes
Installing this lightning protector between an antenna and a SCALANCE M-800 is not
adequate protection against a lightning strike. The LP798-1N lightening protector only
works within the framework of a comprehensive lightning protection concept. If you have
questions, ask a qualified specialist company.
Note
The requirements of EN61000-4-5, "Surge Immunity Test" on power supply lines with 24
VDC are met only when a Blitzductor is used:
24 VDC: BVT AVD 24 type no. 918 422
Vendor: DEHN+SÖHNE GmbH+Co.KG, Hans Dehn Str. 1, Postfach 1640, D -
92306 Neumarkt, Germany
Signal quality
During installation make sure that there is a good signal strength of > -73 dBm.
If the "Q" LED is lit permanently, the signal quality is good. For more detailed information,
refer to the section "LED display (Page 14)".
Avoid large metal objects in the immediate vicinity.
Note
Do not use the M-800 as a router between internal subnets.
Connect the local network with the local applications to the Ethernet port, for example a
programmable logic controller, a machine with an Ethernet interface for remote monitoring or
a PC.
To set up the M-800, connect the Admin PC with a Web browser to one of the connectors.
For the connection, use a path cable with an RJ-45 plug. You will find the properties of the
Ethernet interface in the technical specifications.
NOTICE
Do not remove or insert a C-PLUG / KEY-PLUG during operation!
A PLUG may only be removed or inserted when the device is turned off.
The device checks whether or not a PLUG is present at one second intervals. If it is
detected that the PLUG was removed, there is a restart. If a valid KEY-PLUG was inserted
in the device, the device changes to a defined error state following the restart. With
SCALANCE M, the wireless interface is deactivated in this case.
M874-2
Order number 6GK5 874-2AA00-2AA2
Ethernet interface
Attachment to Industrial Quantity 2
Ethernet
Design RJ-45 jack
Characteristics:
• 10/100BASE-T
• Ethernet IEEE 802
• 10/100 Mbps
Wireless interface
Antenna connector Quantity 1
Design SMA socket (straight)
Impedance 50 Ω nominal
Frequency band GPRS 850, 900, 1800, 1900 MHz
EGPRS Properties Multislot class 12, end device class B
• Coding scheme downlink: CS 1 ... 4,
MCS 1 ... 9
• Coding scheme uplink: CS 1 ... 4, MCS 1
... 9
Transmission speed • Downlink: 237 kbps
• Uplink: 237 kbps
GPRS Properties Multislot class 12, end device class B,
coding scheme 1 … 4
Transmission speed • Downlink: 85.6 kbps
• Uplink: 85.6 kbps
GSM (CSD dial-in) Properties Radio Link Protocol (RLP) V.110, non-
transparent
Transmission speed max. 14.4 kbps
SMS (TX) Properties Text mode, SMSoverIP
M874-2
Electrical data
Power supply Input voltage 12 ... 24 VDC
min. 10.8 VDC, max. 28.8 V
Power consumption max. 8 W
Digital input Quantity 1
Design Terminal block, 2 terminals
Characteristics: Rated voltage 24 VDC Safe Extra Low
Voltage (SELV)
For state "1": 13 to 30 VDC
For state "0": -30 to 3 VDC
Maximum input current 8 mA
Maximum cable length 30 m
Inputs isolated from electronics.
Digital output Quantity 1
Design Terminal block, 2 terminals
Properties Rated voltage 24 VDC Safe Extra Low
Voltage (SELV)
Relay, internally not current limited
Maximum current carrying capacity 1 A
Maximum cable length 30 m
Output isolated from electronics
Permitted ambient conditions
Ambient temperature During operation -20 ℃ to +60 ℃
During storage -40 ℃ to +70 ℃
During transportation -40 ℃ to +70 ℃
Relative humidity During operation ≤ 95% at 25 °C, no condensation
Design, dimensions and weight
Module format Compact module S7-1500
Degree of protection IP20
Weight 290 g
Dimensions (W x H x D) 34.8 x 150.9 x 134.7 mm
Installation options • Wall mounting
• Mounting on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Installation direction Vertical (ventilation openings at the top and
bottom)
M874-2
Product functions
Firewall and security • Stateful inspection
• Packet filter
• IPsec VPN for up to 20 connections
• Password protection
Router functions • NAPT (port forwarding)
• NAT (IP masquerading)
• NAT traversal
• 1:1 NAT
• Dynamic DNS client
• DNS cache
• NTP
• Remote logging
• Connection monitoring
• Alarm SMS
• Sending SMS messages from the local
area network
Configuration / management • Web-based administration user interface
(WBM)
• Remote access with HTTPS
• SNMP and SNMP traps
M874-3
Order number 6GK5 874-3AA00-2AA2
Ethernet interface
Attachment to Industrial Quantity 2
Ethernet
Design RJ-45 jack
Characteristics:
• 10/100BASE-T
• Ethernet IEEE 802
• 10/100 Mbps
Wireless interface
Antenna connector Quantity 1
Design SMA socket (straight)
Impedance 50 Ω nominal
Frequency bands UMTS 800, 850, 900, 1900, 2100 MHz
GPRS 850, 900, 1800, 1900 MHz
UMTS with HSPA+ Transmission speed • HSDPA (downlink): 14.4 Mbps
• HSUPA (uplink): 5.76 Mbps
EGPRS Properties Multislot class 12, end device class B
• Coding scheme downlink: CS 1 ... 4, MCS 1
... 9
• Coding scheme uplink: CS 1 ... 4, MCS 1 ...
9
Transmission speed • Downlink: 237 kbps
• Uplink: 237 kbps
GPRS Properties Multislot class 12, end device class B, coding
scheme 1 … 4
Transmission speed • Downlink: 85.6 kbps
• Uplink: 85.6 kbps
GSM (CSD dial-in) Properties Radio Link Protocol (RLP) V.110, non-
transparent
Transmission speed max. 14.4 kbps
SMS (TX) Properties Text mode, SMSoverIP
M874-3
Electrical data
Power supply Input voltage 12 ... 24 VDC
min. 10.8 VDC, max. 28.8 V
Maximum power 8W
consumption
Digital input Quantity 1
Design Terminal block, 2 terminals
Characteristics: Rated voltage 24 VDC Safe Extra Low Voltage
(SELV)
For state "1": 13 to 30 VDC
For state "0": -30 to 3 VDC
Maximum input current 8 mA
Maximum cable length 30 m
Inputs isolated from electronics.
Digital output Quantity 1
Design Terminal block, 2 terminals
Properties Rated voltage 24 VDC Safe Extra Low Voltage
(SELV)
Relay, internally not current limited
Maximum current carrying capacity 1 A
Maximum cable length 30 m
Output isolated from electronics
Permitted ambient conditions
Ambient temperature During operation -20 ℃ to +60 ℃
During storage -40 ℃ to +70 ℃
During transportation -40 ℃ to +70 ℃
Relative humidity During operation ≤ 95% at 25 °C, no condensation
Design, dimensions and weight
Module format Compact module S7-1500
Degree of protection IP20
Weight 290 g
Dimensions (W x H x D) 34.8 x 150.9 x 134.7 mm
Installation options • Wall mounting
• Mounting on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Installation direction Vertical (ventilation openings at the top and
bottom)
M874-3
Product functions
Firewall and security • Stateful inspection
• Packet filter
• IPsec VPN for up to 20 connections
• Password protection
Router functions • NAPT (port forwarding)
• NAT (IP masquerading)
• NAT traversal
• 1:1 NAT
• Dynamic DNS client
• DNS cache
• NTP
• Remote logging
• Connection monitoring
• Alarm SMS
• Sending SMS messages from the local
area network
Configuration / management • Web-based administration user interface
(WBM)
• Remote access with HTTPS
• SNMP and SNMP traps
M874-3
Order number 6GK5876-3AA02-2BA2
Ethernet interface
Attachment to Industrial Quantity 4
Ethernet
Design RJ-45 jack
Characteristics:
• 10/100BASE-T
• Ethernet IEEE 802
• 10/100 Mbps
Wireless interface
Antenna connector Quantity 2
Design SMA socket (straight)
Impedance 50 Ω nominal
Frequency bands GPRS/EGPRS 850, 900, 1800, 1900 MHz
UMTS with HSPA+ 800, 850, 900, 1900, 2100 MHz
CDMA 800, 1900 MHz
UMTS with HSPA+ Transmission speed • HSDPA (downlink): 14.4 Mbps
• HSUPA (uplink): 5.76 Mbps
CDMA Properties EV-DO Rev.A
Transmission speed • Forward link: max. 3.1 Mbps
• Reverse link: max. 1.8 Mbps
EGPRS Properties Multislot class 12, end device class B
• Coding scheme downlink: CS 1 ... 4, MCS 1
... 9
• Coding scheme uplink: CS 1 ... 4, MCS 1 ...
9
Transmission speed • Downlink: 237 kbps
• Uplink: 237 kbps
GPRS Properties Multislot class 12, end device class B, coding
scheme 1 … 4
Transmission speed • Downlink: 85.6 kbps
• Uplink: 85.6 kbps
GSM (CSD dial-in) Properties Radio Link Protocol (RLP) V.110, non-
transparent
Transmission speed max. 14.4 kbps
SMS (TX) Properties Text mode, SMSoverIP
M874-3
Electrical data
Power supply Input voltage 12 ... 24 VDC
min. 10.8 VDC, max. 28.8 V
Maximum power 8W
consumption
Digital input Quantity 1
Design Terminal block, 2 terminals
Characteristics: Rated voltage 24 VDC Safe Extra Low Voltage
(SELV)
For state "1": 13 to 30 VDC
For state "0": -30 to 3 VDC
Maximum input current 8 mA
Maximum cable length 30 m
Inputs isolated from electronics.
Digital output Quantity 1
Design Terminal block, 2 terminals
Properties Rated voltage 24 VDC Safe Extra Low Voltage
(SELV)
Relay, internally not current limited
Maximum current carrying capacity 1 A
Maximum cable length 30 m
Output isolated from electronics
Permitted ambient conditions
Ambient temperature During operation -20 ℃ to +60 ℃
During storage -40 ℃ to +70 ℃
During transportation -40 ℃ to +70 ℃
Relative humidity During operation ≤ 95% at 25 °C, no condensation
Design, dimensions and weight
Module format Compact module S7-1500
Degree of protection IP20
Weight 290 g
Dimensions (W x H x D) 34.8 x 147 x 134.7 mm
Installation options • Wall mounting
• Mounting on a DIN rail
• Mounting on an S7-300 standard rail
• Mounting on an S7-1500 standard rail
Installation direction Vertical (ventilation openings at the top and
bottom)
M874-3
Product functions
Firewall and security • Stateful inspection
• Packet filter
• IPsec VPN for up to 20 connections
• Password protection
Router functions • NAPT (port forwarding)
• NAT (IP masquerading)
• NAT traversal
• 1:1 NAT
• Dynamic DNS client
• DNS cache
• NTP
• Remote logging
• Connection monitoring
• Alarm SMS
• Sending SMS messages from the local
area network
Configuration / management • Web-based administration user interface
(WBM)
• Remote access with HTTPS
• SNMP and SNMP traps
Approvals issued
Note
Issued approvals on the type plate of the device
The specified approvals apply only when the corresponding mark is printed on the product.
You can check which of the following approvals have been granted for your product by the
markings on the type plate.
A.2 INSTALLATION
WARNING
Personal injury and property damage can occur
The installation of expansions that are not approved for SIMATIC NET products or their
target systems may violate the requirements and regulations for safety and electromagnetic
compatibility.
Only use expansions that are approved for the system.
Note
The test was performed with a device and a connected communications partner that also
meets the requirements of the standards listed above.
When operating the device with a communications partner that does not comply with
these standards, adherence to the corresponding values cannot be guaranteed.
National approvals
You will find an overview of the country-specific wireless approvals of SIMATIC NET devices
with GSM or UMTS services on the Internet pages of Siemens Automation Customer
Support. You will find the link to the document on the following page:
ik-Info (www.siemens.com/simatic-net/ik-info)
When used for its intended purpose, the product is compliant with the requirements of the
following European directives:
● Directive 1999/5/EC (R&TTE) of 9 March 1999 of the European Parliament and of the
Council on Radio Equipment and Telecommunications Terminal Equipment and the
mutual recognition of their conformity
Applied standards:
– EN 301 511: v.9.0.2 (2003-03)
– 3GPP TS 51.010-1: v. 5.10.0
Classification
– Telecommunication equipment,
– Wireless device
– Device class 1
● EN 301 489-1 V1.9.2 (2011-09)
Electromagnetic compatibility and radio spectrum matters (ERM) - Electromagnetic
compatibility for radio equipment and services - Part 1 : Common technical requirements.
● EN 301 489-7 V1.3.1 (2005-11)
Electromagnetic compatibility and radio spectrum matters (ERM) - Electromagnetic
compatibility for radio equipment and services - Part 7 : Specific conditions for mobile and
portable radio and ancillary equipment of digital cellular radio telecommunications
systems (GSM and DCS).
● EN 301 489-24 v1.5.1 (2010-10)
Electromagnetic compatibility and radio spectrum matters (ERM) - Electromagnetic
compatibility for radio equipment and services - Part 24 : Specific conditions for mobile
and portable IMT-2000 CDMA Direct Spread (UTRA) radio and ancillary equipment.
● EN 301 908-1 v5.2.1 (2011-05)
IMT cellular networks - Harmonized EN covering the essential requirements of article 3.2
of the R&TTE directive - Part 1: Introduction and common requirements
● EN 301 908-2 v6.1.1 (2013-02)
IMT cellular networks - Harmonized EN covering the essential requirements of article 3.2
of the R&TTE directive - Part 2: CDMA Direct Spread (UTRA FDD) User Equipment (UE).
You will find the EC declaration of conformity for these products on the Internet under the
following entry IDs/Internet page specified here:
ID = 80046561 (http://support.automation.siemens.com/WW/view/en/80046561)
● Entry list
● Entry type "Certificates"
● Type of certificate "Declaration of Conformity"
Maximum antenna gain
Users and installers must be provided with antenna installation instructions and transmitter
operating conditions that must be followed to avoid exceeding the permitted RF exposure.
A.4 ATEX
WARNING
When using (installing) SIMATIC NET products in hazardous area zone 2, make absolutely
sure that the associated conditions are adhered to:
You will find these conditions on the SIMATIC NET Manual Collection.
• "Approval of SIMATIC/ SIMATIC NET Products for Direct Installation in Ex-Zone 2"
ATEX code:
II 3 G Ex nA IIC T4 Gc
Test type certificate
KEMA 07 ATEX 0145X
The product meets the requirements of the standards
● EN 60079-0:2009 (Explosive atmospheres - Part 0: Equipment - General requirements)
● and EN 60079-15: 2010 (electrical apparatus for potentially explosive atmospheres; Type
of protection "n")
A.5 IECEx
IECEx
The SIMATIC NET products meet the requirements of explosion protection according to
IECEx.
IECEx classification:
Ex nA IIC T4 Gc
DEK 14.0025X
The products meet the requirements of the following standards:
● IEC 60079-15 : 2010 (Explosive atmospheres - Part 15: Equipment protection by type of
protection "n"
● IEC 60079-0 : 2011 (Explosive atmospheres - Part 0: Equipment - General requirements)
A.9 FM certification
FCC approval
Applied standards
● FCC Part 15
● FCC Part 15.19
● FCC Part 15.21
Mandatory user information
FCC Part 15
This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to Part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio frequency
energy.
If not installed and used in accordance with the instructions, this may cause harmful
interference to wireless communications. There can be no guarantee with certain
installations, even when complying with the instructions, that no interference will occur. If this
equipment does cause harmful interference to radio or television reception that can be
determined by turning the equipment off and on, the user is recommended to try to combat
the interference with the following measures:
● Change the orientation of the receiving antenna or install it at a different location.
● Increase the distance between the SCALANCE M874-3, M876-3 and the radio or
television receiver.
● Connect the device to an outlet on a circuit different from that to which the receiver is
connected.
● Consult the dealer / installer or an experienced radio / TV technician for help.
FCC Part 15.19
This device complies with Part 15 of the FCC Rules. Operation is subject to the following
conditions:
1. This device may not cause harmful interference, and
2. this device must accept any interference received, including interference that may cause
undesired operation.
FCC Part 15.21
Modifications not expressly approved by this company could void the user's authority to
operate the equipment.
The SCALANCE M874-3, M876-3 may only be operated with an antenna belonging to the
accessories of the SCALANCE M874-3, M876-3 .
The installation of the SCALANCE M874-3 and the antenna as well as servicing must be
performed by qualified technical personnel only. When servicing the antenna, or working at
distances closer than those listed below, make sure that the transmitter has been disabled.
Applied standards
● UL 60950-1 (Information Technology Equipment)
● UL 508 (Industrial Control Equipment)
● CSA C22.2 No.60950-1 (Information Technology Equipment)
A L
Accessories, 13 LED display, 14, 16
C P
Connecting up Power supply, 34
Digital input, 37 Product property, 9, 10
Digital output, 38
Ethernet interface, 42
Grounding, 36 S
Power supply, 34
S7-1500 standard rail, 28
SIM card, 33
S7-300 standard rail, 27
C-PLUG, 20
Safety notices
for installation, 23
Use in hazardous areas, 23, 31
D
when connecting up, 31
Digital input, 37 Scope of delivery, 9, 10
Digital output, 38 SET button, 18
Dimension drawing Signal quality, 40
SCALANCE M874-2, 45, 47 SIM card, 33
SCALANCE M874-3, 45, 47 SIMATIC NET glossary, 5
DIN rail, 26 System manual, 60
E W
Ethernet interface, 42 Wall mounting, 25
G
Glossary, 5
Grounding, 36
I
Installation
DIN rail, 26
S7-1500 standard rail, 28
S7-300 standard rail, 27
Wall, 25
K
KEY-PLUG, 20