Power and Control Fuses
Power and Control Fuses
FUSE DEFINITIONS
Bolt-in Fuse
Ampacity A fuse which is intended to be bolted directly to bus bars, con-
The current a conductor can carry continuously without exceed- tact pads or fuse blocks.
ing its temperature rating. Ampacity is a function of cable size,
insulation type and the conditions of use. Contacts
The external live parts of the fuse which provide continuity
Ampere Rating between the fuse and the balance of the circuit. Also referred to
The continuous current carrying capability of a fuse under as ferrules, blades or terminals.
defined laboratory conditions. The ampere rating is marked on
each fuse. Class L fuses and E rated fuses may be loaded to Coordination
100% of their ampere rating. For all other fuses, continuous load The use of overcurrent protective devices which will isolate only
current should not exceed 80% of fuse ampere rating. that portion of an electrical system which has been overloaded or
faulted. See Selectivity.
Available Fault Current
The maximum short circuit current that can flow in an unprotect- Current-Limiting Fuse
ed circuit. A fuse which will limit both the magnitude and duration of cur-
rent flow under short circuit conditions.
L2
APPLICATION INFORMATION
FUSE DEFINITIONS (Continued)
Overload
Current-Limiting Range The operation of conductors or equipment at a current level that
The available fault currents a fuse will clear in less than 1/2 cycle, will cause damage if allowed to persist.
thus limiting the actual magnitude of current flow.
Peak Let-Thru Current (lp)
Dual Element Fuse The maximum instantaneous current passed by a current- limit-
Often confused with time delay, dual element is a term describing ing fuse when clearing a fault current of specified magnitude.
fuse element construction. A fuse having two current responsive
elements in series. Rejection Fuse Block
A fuse block which will only accept fuses of a specific UL class.
Element Rejection is a safety feature intended to prevent the insertion of a
A calibrated conductor inside a fuse which melts when subjected fuse with an inadequate voltage or interrupting rating.
to excessive current. The element is enclosed by the fuse body
and may be surrounded by an arc-quenching medium such as Rejection Fuse
silica sand. The element is sometimes referred to as a link. A current-limiting fuse with high interrupting rating and with
unique dimensions or mounting provisions.
Fault
An accidental condition in which a current path becomes avail- Renewable Fuse
able which by-passes the connected load. A fuse which can be restored for service by the replacement of
its element.
Fault Current
The amount of current flowing in a faulted circuit. Renewable Element or Link
The field-replaceable element of a renewable fuse. Also referred
Fuse to as a renewal link.
An overcurrent protective device containing a calibrated current
carrying member which melts and opens a circuit under speci- Selectivity
fied overcurrent conditions. A main fuse and a branch fuse are said to be selective if the
branch fuse will clear all overcurrent conditions before the main
I2t (Ampere Squared Seconds) fuse opens. Selectivity is desirable because it limits outage to
2 that portion of the circuit which has been overloaded or faulted.
A measure of the thermal energy associated with current flow. I t
is equal to (lRMS)2 x t, where t is the duration of current flow in Also called selective coordination.
seconds.
Semiconductor Fuse
Clearing I2t is the total I2t passed by a fuse as the fuse An extremely fast acting fuse intended for the protection of power
clears a fault, with t being equal to the time elapsed from semiconductors. Sometimes referred to as a rectifier or
the initiation of the fault to the instant the fault has been ultra fast fuse.
cleared.
Melting I2t is the minimum I2t required to melt the fuse Short Circuit
element. Excessive current flow caused by insulation breakdown or wiring
error.
Interrupting Rating (Abbreviated I.R.)
The maximum current a fuse can safely interrupt. Some special Threshold Current
purpose fuses may also have a “Minimum Interrupting Rating”. The minimum available fault current at which a fuse is current
This defines the minimum current that a fuse can safely interrupt. limiting.
L3
APPLICATION INFORMATION
FUSE DESCRIPTIONS ➤ PT Fuses - Potential transformers require current limiting
fuses or equivalent on the primary connection side. Standard
High voltage (over 34,500V) PT primary voltages range from 2.4kV to 36kV. Since the power
Expulsion-Type power fuses are available for nominal voltages of requirement is low (for relays, metering, etc.) fuses of the proper
46, 69, 115, 138 and 161KV in current ratings up to 400 voltage are applied in the 1/2 to 5 ampere range. Several voltage
amperes. ANSI (American National Standards Institute) Standards ratings are available, physical sizes vary among
are followed. manufacturers.
OTHER TYPES
1000 Glass & Ceramic 0-30 up to 10 Automotive and electronic, 1/4” dia., 5 mm dia.
Many sizes UL Listed & CSA certified
600 Cable protector 4/0-750 kcmil 200 Crimp type, bolt type or solid stud
Cu or Al cables
L4
APPLICATION INFORMATION
L5
APPLICATION INFORMATION
HOW TO READ A TIME-CURRENT CURVE
➤ If a fuse has been selected, the designer can use the curve
for that fuse to check its opening time versus a given overcurrent.
Example: Using the 30 ampere fuse curve, what is the fuse open-
ing time in seconds at a current of 160 amperes? At the bottom
of the sheet (Current in Amperes) find 160 amperes (Pt. A) and
follow that line straight up to the point where it intersects the
30A curve (Pt. B). Then follow that line to the left edge (Time in
Seconds) and read 10 seconds. (pt. C). This tells us that the
AJT30 will open in 10 seconds on a current of 160 amperes.
Time in Seconds
➤ Likewise, for the same fuse we might want to know what cur-
rent will open the fuse in .1 second. At the side of the sheet
(Time in Seconds) find .1 second (Pt. D) and follow that line to
the right until it intersects the 30A curve (Pt. E). Then follow that
line straight down to the bottom line (Current in Seconds) and
read 320 amperes (Pt. F). This shows that the AJT30 requires an
overcurrent of 320 amperes to open in .1 second.
Sometimes the fuse family or type has not been chosen, so a Current in Amperes
design requirement can be presented to several family character-
istic curves. One fuse type will emerge as a good choice. Voltage
rating, interrupting rating, physical size, time delay, etc. are all
considerations in the final choice.
L6
APPLICATION INFORMATION
LOW VOLTAGE FUSES FOR MOTOR PROTECTION
Disconnect
Code Requirements
The NEC or CEC requires that motor branch circuits be protected
against overloads and short circuits. Overload protection may be
provided by fuses, overload relays or motor thermal protectors. Fuse
Short circuit protection may be provided by fuses or circuit
breakers.
Contactor
Overload Protection
The NEC or CEC allows fuses to be used as the sole means of
overload protection for motor branch circuits. This approach is often
practical with small single phase motors. If the fuse is the sole Overload Relay
means of protection, the fuse ampere rating must not exceed the
values shown in Table 1.
Motor
Most integral horsepower 3 phase motors are controlled by a motor
starter which includes an overload relay. Since the overload relay
provides overload protection for the motor branch circuit, the fuses Motor Branch Circuit
may be sized for short circuit protection.
Table 1- Maximum Fuse Rating for Overload Protection
Short Circuit Protection
MOTOR SERVICE FACTOR or FUSE RATING AS %*
The motor branch circuit fuses may be sized as large as shown MARKED TEMPERATURE RISE MOTOR FULL LOAD
in Table 2 when an overload relay or motor thermal protector is
included in the branch circuit. Time delay fuse ratings may be Service factor of 1.15 or greater 125
increased to 225% and non-time delay fuse ratings to 400% Marked temperature rise
(300% if over 600 amperes) if the ratings shown in Table 2 will not exceeding 40°C 125
not carry motor starting current. All others 115
Some manufacturers’ motor starters may not be adequately pro- * These percentages are not to be exceeded.
tected by the maximum fuse sizing shown in Table 2. If this is
the case, the starter manufacturer is required by UL 508 to label
the starter with a maximum permissible fuse size. If so labeled, Table 2- Maximum Fuse Rating For
this maximum value is not be be exceeded. Short Circuit Protection
FUSE RATING AS
Where the percentages shown in Table 2 do not correspond to % MOTOR FULL LOAD*
standard fuse ratings the next larger fuse rating may be used. TYPE OF MOTOR FUSE TYPE
Standard fuse ratings in amperes: NON-TIME DELAY TIME DELAY
15 20 25 30 35 40 45 50 All Single-phase AC motors 300 175
60 70 80 90 100 110 125 150
175 200 225 250 300 350 400 450 AC polyphase motors other than
wound-rotor:
500 600 700
2500 3000 4000 5000 6000
800 1000 1200 1600 2000 Squirrel Cage
Other than Design E
Design E
300
300
175
175
L
Synchronous 300 175
Fuse Selection Guidelines Wound rotor 150 150
What fuse type and ampere rating is best for a given application? Direct-current (constant voltage) 150 150
The answer depends upon the application and objective to be
met. Here are some suggestions. * The non-time delay ratings apply to all class CC fuses.
L7
APPLICATION INFORMATION
LOW VOLTAGE FUSES FOR MOTOR PROTECTION Single Phase Motor Fuse Selection
(Continued) UL Class RK5 - Tri-onic® (TR)
FULL RECOMMENDED FUSE AMPERE RATING
Time Delay vs. Non-Time Delay MOTOR LOAD MINIMUM TYPICAL HEAVY
Time delay fuses are the most useful fuses for motor branch circuit HP AMPERES 1.0 SF 1.15 SF LOAD
application. A time delay fuse can be sized closer to motor full 115V-RK5-TR (Tri-onic)
load current, providing a degree of overload protection, better short 1/6 4.4 5-6/10 5-6/10 6-1/4 8
circuit protection, and possible use of a smaller disconnect switch. 1/4 5.8 7 8 9 12
1/3 7.2 9 10 12 15
Which Fuse Class? 1/2 9.8 12 12 15 17.5
UL Classes RK5, RK1, and J are the most popular. The Class 3/4 13.8 15 17-1/2 20 25
RK5 ( Tri-onic® ) is the least expensive. The Class RK1 (Amp-trap®) 1 16 17-1/2 20 25 30
1-1/2 20 20 25 30 35
is used where a higher degree of current limitation is required for
2 24 25 30 35 40
improved component protection or system coordination. The RK5 3 34 35 40 50 60
and RK1 are dimensionally interchangeable. 5 56 60 70 80 100
7-1/2 80 90 100 125 150
Since its 1983 introduction, the Class J time delay fuse 10 100 110 125 150 175
(Shawmut AJT) has become an increasingly popular choice. The 115V-CC-ATDR
AJT provides a higher degree of current limitation than the RK1. 1/8 4.4 8 - 15 17-1/2
More important, the AJT is approximately half the 1/4 5.8 12 - 20 20
physical size of the Class RK5 and RK1 fuses. 1/3 7.2 15 - 25 25
1/2 9.8 20 - 30 -
What Ampere Rating? 3/4 13.8 30 - - -
The selection of fuse ampere rating is a matter of experience and 230V-RK5-TR (Tri-onic)
personal preference. Some prefer to size time delay fuses at 1/6 2.2 2-1/2 2-8/10 3-1/2 4
125% of motor full load amperes. This sizing will provide a 1/4 2.9 3-2/10 3-1/2 4-1/2 5.6
degree of overload protection for motors with a service factor of 1/3 3.6 4 4-1/2 5-6/10 7
1.15. Sizing fuses at 125% of motor nameplate amperes in some 1/2 4.9 5-6/10 6-1/4 7 9
applications may result in nuisance fuse openings. Time delay 3/4 6.9 8 9 10 15
fuses sized at 125% may open at motor locked rotor current 1 8 9 10 12 15
1-1/2 10 10 12 15 17-1/2
before some NEMA Class 20 overload relays operate. Nuisance 2 12 12 15 17-1/2 25
fuse openings may result if Class RK1 or Class J fuses are sized 3 17 17-1/2 20 25 30
at 125% of motor full load current. These fuses are more current 5 28 30 35 40 50
limiting than the RK5 and have less short time current carrying 7-1/2 40 45 50 60 70
capability. 10 50 60 60 75 90
230V-CC-ATDR
Sizing time delay fuses between 125% and 150% of motor full 1/8 2.2 4 - 7 8
load current provides advantages. The fuse will coordinate with 1/4 2.9 6 - 9 10
NEMA Class 20 overload relays. Nuisance fuse opening will 1/3 3.6 7 - 12 15
virtually be eliminated and effective short circuit protection will 1/2 4.9 10 - 15 17-1/2
be maintained. 3/4 6.9 15 - 20 25
1 8 17-1/2 - 25 30
1-1/2 10 20 - 30 -
Protecting IEC Style Motor Starters 2 12 25 - - -
The new IEC European style motor starters and contactors are
becoming increasingly popular but they present different problems
Minimum - Largest fuse rating which will provide both overload and short
in protection. These devices represent substantial savings in circuit protection per the code. Choosing this fuse rating eliminates the
space and cost but they have a lower withstand capability than need for an overload relay. Nuisance fuse opening may occur if motor is
their NEMA counterparts. used with repetative cycle loads.
In order to achieve the same level of protection for IEC style Typical - Suggested rating when fuse is used in conjunction with an
overload relay. Fuse sized near 150% of motor full load current.
devices that we expect for NEMA devices, the AJT Class J Time
Delay fuse is the best choice, sized at 1.25 to 1.50 times motor Heavy Load - In accordance with Table 2. If this fuse is not sufficient to
full load amperes. Also, the AJT has the advantage of being half start the load, it may be increased to a maximum of 225% of full-load
the size of RK5 and RK1 fuses and thereby fits the trim IEC package. amperes. This column should be used for Design E and high efficiency
Design B motor fuse sizing.
L8
APPLICATION INFORMATION
LOW VOLTAGE FUSES FOR MOTOR PROTECTION (Continued)
Minimum - Fuses are sized near 125% of motor load current. This sizing is not recommended if motor acceleration time exceeds 2 seconds. Minimum
sizing will provide close overload relay back-up protection but may not coordinate with some NEMA Class 20 overload relays. Also, for RK1 and J fuses,
minimum sizing may not be heavy enough for motors with code letter G or higher.
Typical - Suggested for most applications. Will coordinate with NEMA Class 20 overload relays. Suitable for motor acceleration times up to 5 seconds.
Heavy Load - In accordance with Table 2. If this fuse is not sufficient to start the load, it may be increased to a maximum of 225% of full-load
amperes. This column should be used for Design E and high efficiency Design B motor fuse sizing.
L9
APPLICATION INFORMATION
LOW VOLTAGE FUSES FOR MOTOR PROTECTION (Continued)
Minimum - Fuses are sized near 125% of motor load current. This sizing is not recommended if motor acceleration time exceeds 2 seconds. Minimum
sizing will provide close overload relay back-up protection but may not coordinate with some NEMA Class 20 overload relays. Also, for RK1 and J fuses,
minimum sizing may not be heavy enough for motors with code letter G or higher.
Typical - Suggested for most applications. Will coordinate with NEMA Class 20 overload relays. Suitable for motor acceleration times up to 5 seconds.
Heavy Load - In accordance with Table 2. If this fuse is not sufficient to start the load, it may be increased to a maximum of 225% of full-load amperes
This column should be used for Design E and high efficiency Design B motor fuse sizing.
L 10
APPLICATION INFORMATION
LOW VOLTAGE FUSES FOR MOTOR PROTECTION (Continued)
Minimum - Fuses are sized near 125% of motor load current. This sizing is not recommended if motor acceleration time exceeds 2 seconds. Minimum
sizing will provide close overload relay back-up protection but may not coordinate with some NEMA Class 20 overload relays. Also, for RK1 and J fuses,
minimum sizing may not be heavy enough for motors with code letter G or higher.
Typical - Suggested for most applications. Will coordinate with NEMA Class 20 overload relays. Suitable for motor acceleration times up to 5 seconds.
Heavy Load - In accordance with Table 2. If this fuse is not sufficient to start the load, it may be increased to a maximum of 225% of full-load amperes
This column should be used for Design E and high efficiency Design B motor fuse sizing.
L 11
APPLICATION INFORMATION
LOW VOLTAGE FUSES FOR MOTOR PROTECTION (Continued)
Minimum - Fuses are sized near 125% of motor load current. This sizing is not recommended if motor acceleration time exceeds 2 seconds. Minimum
sizing will provide close overload relay back-up protection but may not coordinate with some NEMA Class 20 overload relays. Also, for RK1 and J fuses,
minimum sizing may not be heavy enough for motors with code letter G or higher.
Typical - Suggested for most applications. Will coordinate with NEMA Class 20 overload relays. Suitable for motor acceleration times up to 5 seconds.
Heavy Load - In accordance with Table 2. If this fuse is not sufficient to start the load, it may be increased to a maximum of 225% of full-load amperes
This column should be used for Design E and high efficiency Design B motor fuse sizing.
L 12
APPLICATION INFORMATION
MEDIUM VOLTAGE MOTOR PROTECTION Fuse/Overload Relay Crossover Point
Fuse Application Guidelines
The guidelines for applying R-rated fuses are significantly differ-
ent from those applying to low voltage motor fuses. This is
because R-rated fuses are special purpose devices which are
intended to provide short circuit protection only for medium volt-
age starters and motors.
TIME
An R-rated fuse is not designed to protect itself or other circuit
components during long term overloads. This is why these fuses
are given an R rating, and not an ampere rating. An R-rated fuse will
safely interrupt any current between its minimum interrupting rating
and its maximum interrupting rating. The minimum interrupting
rating is verified during UL tests for UL component recognition.
CURRENT
R-rated fuses must be applied in combination with an overload
relay and a contactor. The time current characteristics of the fuse
and overload relay should be matched so that the contactor inter- where B ≥ 1.2 x locked rotor amperes
rupts currents below the fuse’s minimum interrupting rating
while the fuse interrupts fault currents, thus easing duty on the
contactor and extending the interrupting ability of the controller.
Motor Full Load Currents for R-Rated Fuses*
A medium voltage starter is usually engineered for a specific MAX. MOTOR FULL-LOAD CURRENT
motor and application. For this reason the starter manufacturer FUSE FOR FULL VOLTAGE START - AMPERES
generally selects the proper fuse R rating and provides the fuses R RATING 10 sec. start 3 sec. start
as part of the starter package. Unless the user has good reason,
no deviation should be made from the R rating recommended by 2R 28 32
the starter manufacturer. If the user has an existing starter which 3R 40 45
is to be applied to a new or different motor, the application 4R 55 65
should be reviewed with the starter manufacturer. Recalibration of 6R 80 95
the overload relay(s) or fuses of a different R rating may be 9R 125 140
required. 12R 165 190
18R 250 280
Properly sized R-rated fuses should provide a service life approach- 24R 330 360
ing that of the contactor. If fuse openings are experienced with no 36R 500 550
faults present, the fuses, overload relay or both may be improperly
sized. The table in this section is offered as a guideline and shows *Note: Always round up to the next larger R rating.
the maximum motor full load current appropriate for a given R rating.
In addition to this table it is advisable to compare the fuse minimum
melt time-current curve and the nominal time-current characteristic
curve for the overload relay. These curves should intersect at (B) no
less than 120% of motor locked rotor current (see figure). This will
assure that the contactor will open before the fuse during locked
rotor conditions.
L 13
APPLICATION INFORMATION
TRANSFORMER PROTECTION Secondary Fuses
Selecting fuses for the secondary is simple once rated secondary
The National Electrical Code and the Canadian Electrical Code current is known. Fuses are sized at 125% secondary FLA or next
cover overcurrent protection of transformers. Some of the higher rating or at maximum 167% of secondary FLA depending
requirements in this article are summarized here. on secondary current. The preferred sizing is 125% of rated
secondary current Isec) or next higher fuse rating. To determine
Transformers - Primary 600 Volts or Less Isec, first determine transformer rating (VA or kVA), secondary
If secondary fuse protection is not provided, primary fuses are to voltage (Vsec) and use formula’s below.
be selected according to Table 1. If both primary and secondary 1. Single Phase : Isec = Transformer VA
fuses are used, they are to be selected according to Table 2. Vsec
or Transformer kVA x 1000
Table 1- Primary Fuse Only Vsec
2. Three Phase : Isec = Transformer VA
TRANSFORMER 1.73 x Vsec
PRIMARY MAXIMUM PRIMARY
AMPERES FUSE % RATING or Transformer kVA x 1000
1.73 x Vsec
9 or more 125*
2 to less than 9 167 When Isec is determined, multiply it by 1.25 and choose that
less than 2 300 fuse rating or next higher rating. [ Isec x 1.25 = Fuse Rating ]
Table 2- Primary & Secondary Fuses Transformers - Primary Over 600 Volts
If In unsupervised locations, fuses are to be selected according
TRANSFORMER MAXIMUM % RATING to Table 3. Where the required fuse rating does not correspond to
SECONDARY a standard ampere rating, the next higher standard rating shall be
AMPERES PRIMARY FUSE SECONDARY FUSE permitted. In supervised locations,fuses are to be selected
according to Table 4.
9 or more 250 125*
less than 9 250 167
* If 125% does not correspond to a standard ampere rating, the next higher stan-
dard rating shall be permitted.
Table 3- Unsupervised Locations
Transformer Magnetizing Inrush Currents MAXIMUM % RATING
TRANSFORMER
When voltage is switched on to energize a transformer, the trans- SECONDARY FUSE
RATED % PRIMARY
former core normally saturates. This results in a large inrush cur- IMPEDANCE FUSE OVER 600V 600V or LESS
rent which is greatest during the first half cycle (approximately
.01 second) and becomes progressively less severe over the next 6 or less 300* 250* 125*
several cycles (approximately .1 second) until the transformer More than 6 &
not more than 10 300* 225* 125*
reaches its normal magnetizing current.
* Where fuse sizes doe not correspond to a standard ampere rating, the next
higher standard rating shall be permitted.
L 14
APPLICATION INFORMATION
PRIMARY FUSES FOR THREE PHASE LOW VOLTAGE TRANSFORMERS
Recommended Primary Fuses for 480 & 600 Volt, Three Phase Transformers
480 VOLT PRIMARY 600 VOLT PRIMARY
PRIMARY PRIMARY FUSE RATING PRIMARY PRIMARY FUSE RATING
TRANSFORMER FULL LOAD AJT* or FULL LOAD AJT* or
RATING KVA AMPS TRS-R A6D-R* A4BT* A4BY* A4BQ* AMPS TRS-R A6D-R* A4BT* A4BY* A4BQ*
3 3.6 4-1/2 6 - - - 2.9 4 5 - - -
5 6.0 8 12 - - - 4.8 6 10 - - -
7-1/2 9.0 12 15 - - - 7.2 9 15 - - -
9 11 15 25 - - - 9.0 12 17-1/2 - - -
15 18 25 35 - - - 14 20 25 - - -
30 36 45 60 - - - 29 35 45 - - -
45 54 70 100 - - - 43 60 80 - - -
75 90 125 175 - - - 72 90 150 - - -
100 120 150 225 - - - 96 125 200 - - -
112-1/2 135 175 300 - - - 108 150 225 - - -
150 180 225 400 - - - 144 200 300 - - -
225 271 350 500 - - - 217 300 450 - - -
300 361 450 600 - - - 289 350 500 - - -
500 601 - - 1000 1000 1200 481 600 - 700 900 1000
750 902 - - 1400 1600 2000 722 - - 1200 1400 1600
1000
1500
2000
1203
1804
2406
-
-
-
-
-
-
1800
-
-
2000
3000
4000
2500
4000
5000
962
1443
1925
-
-
-
-
-
-
1600
2000
-
1800
2500
4000
2000
3000
4000
L
2500 3007 - - - 5000 6000 2406 - - - 5000 5000
*When using these fuses, the secondary of the transformer must be fused to comply with the Code.
L 15
APPLICATION INFORMATION
E-RATED PRIMARY FUSES FOR THREE PHASE POWER TRANSFORMERS
1 Minimum fuse size shown will carry transformer magnetizing inrush current of 12 times full load amperes for .1 second.
133% fuse size permits continuous operation of transformer at 133% of its self cooled KVA rating.
2 The self-cooled rating of the transformer. (If a forced-air cooled KVA rating is given, use that rating to size the fuse and be sure the fuse will carry the higher load current.)
Recommended Fuses
Ferraz Shawmut CS-3: 5KV-A055F, 8KV-A825X*, 15KV-A155F, CL-14: 5KV-A055C, A055B, 15KV-A155C
* Consult factory for technical information.
Examples:
1. A new installation has a 300KVA transformer with 4160V 2. What is the normal fuse size recommended for a 1000KVA
primary. It is not fully loaded. What is minimum size primary transformer with 832OV primary?
fuse recommended?
8320V
4160V Source
Source
Unless special conditions are noted, the 133% primary fuse
A 50E rating (Ferraz Shawmut A055F1DORO-50E or equivalent) rating is correct. For this application use a 100E rating
is correct. Lower ratings may open when transformer is energized. A155F2DORO-100E or equivalent which will allow normal
overload operations of transformer up to 133% of rating.
L 16
APPLICATION INFORMATION
E-RATED PRIMARY FUSES FOR THREE PHASE POWER TRANSFORMERS (Continued)
112-1/2 5.4 10E 10E 5.2 10E 10E 4.9 10E 10E
150 7.0 10E 10E 7.0 10E 10E 6.6 10E 10E
225 10.8 15E 15E 10.4 15E 15E 9.8 15E 15E
300 14.4 20E 20E 14 15E 20E 13 15E 20E
500 24 30E 40E 23 25E 30E 22 25E 30E
750 36 40E 50E 35 40E 50E 33 40E 50E
1000 48 65E 65E 46 50E 65E 44 50E 65E
1500 72 80E 100E 70 80E 100E 66 80E 100E
2000 96 125E 150E 92 100E 125E 88 100E 125E
2500 120 125E 200E 116 125E 200E 109 125E 150E
3000 144 150E 200E 139 150E 200E 131 150E 200E
1 Minimum fuse size shown will carry transformer magnetizing inrush current of 12 times full load amperes for .1 second.
133% fuse size permits continuous operation of transformer at 133% of its self cooled KVA rating.
2 The self-cooled rating of the transformer. (If a forced-air cooled KVA rating is given, use that rating to size the fuse and be sure the fuse will carry the higher load current.)
Recommended Fuses
Ferraz Shawmut CS-3: 5KV-A055F, 15KV-A155F, CL-14: 5KV-A055C, A055B, 15KV-A155C
L
Maximum Fuse Size
The Code allows primary fuses to be sized up to 250% of transformer primary current rating. Sizing this large may not provide adequate
protection. Maximum fuse size should determined by making sure the fuse total clearing curve does not exceed transformer damage curve.
The transformer manufacturer should be consulted to determine transformer overload and short circuit withstand capability.
L 17
APPLICATION INFORMATION
CONTROL CIRCUIT TRANSFORMERS inrush. We recommend that fuses be selected to withstand 40 x
FLA for .01 sec. and to stay within the NEC guidelines specified
Control circuit transformers used as part of a motor control above.
circuit are to be protected as outlined in Tables 1 & 2 (p. AP13)
with one important exception. Primary fuses may be sized up to For example: 300VA Transformer, 600 V primary.
500% of transformer rated primary current if the rated primary
current is less than 2 amperes. Ipri = Transformer VA = 300 = 1/2A = FLA
Primary V 600
When a control circuit transformer is energized,the typical magne-
tizing inrush will be 25-40 times rated primary full load current The fuse time-current curve must lie to the right to the point
(FLA) for the first 1/2 cycle and dissipates to rated current in a 40 x (1/2A) = 20A @ .01 sec.
few cycles. Fuses must be sized so they do not open during this
Recommended Primary Fuses for Single Phase Control Transformers
600 VOLT PRIMARY 480 VOLT PRIMARY
TRANS
FLA ATQR ATMR A6D-R+ AJT+ TRS-R FLA ATQR ATMR A6D-R+ AJT+ TRS-R
VA
25 .042 1/10 2/10 2/10 - 1/10 .052 1/10 1/4 1/4 - 1/10
50 .083 1/4 3/10* 4/10 - 2/10 .104 1/4 1/2* 1/2 - 2/10
75 .125 1/4 1/2* 6/10 - 2/10 .156 3/10 3/4* 6/10 - 2/10
100 .167 3/10 3/4* 8/10 - 3/10 .208 4/10 1 1 1 3/10
130 .22 4/10 1 1-1/4 1-1/4 4/10 .27 1/2 1 1-4/10 1-1/2 4/10
150 .25 1/2 1* 1-1/4 1 4/10 .313 1/2 1-1/2 1-4/10 1-1/2 4/10
200 .33 1/2 1-1/2 1-6/10 1-1/2 6/10 .417 6/10 2 2 2 6/10
250 .42 6/10 2 2 2 6/10 .52 8/10 2 2-1/2 2-1/2 6/10
300 .50 1 2 2-1/2 2 8/10 .62 1-1/2 3 3 3 8/10
350 .583 1-1/4 2 2-8/10 2 1 .73 1-1/2 3-1/2 3-1/2 3-1/2 1
500 .833 1-1/2 4 4 4 1-1/4 1.04 2 5 4 4 1-4/10
750 1.25 2-1/2 6 4 4 1-6/10 l.56 3 7 5 5 2
1000 1.67 3 8 5 5 2-1/4 2.08 4+ - 5 5 3
1500 2.5 5+ - 6 6 4 3.125 7+ - 6-1/4 6-1/4 4
2000 3.33 8+ - 8 8 5 4.17 10+ - 7 7 5
3000 5.00 12+ - 12 12* 8 6.25 15+* - 15* 15 8
5000 8.33 20+ - 20* 20** 12 10.4 25+** - 25* 25* 15
7500 12.5 30+ - 30* 30* 17-1/2 15.6 - - 35** 35** 20
10000 16.7 - - 40* 40* 25 20.8 - - 50** 50** 30
240 VOLT PRIMARY 120 VOLT PRIMARY
25 .104 2/10 1/2 1/2 - 2/10 .21 4/10 1 1 1 3/10
50 .21 4/10 1 1 1 3/10 .42 6/10 2 2 2 6/10
75 .31 1/2 1-1/2 1-4/10 1-1/2 4/10 .6 1 3 3 3 8/10
100 .42 6/10 2 2 2 6/10 .83 1-1/2 4 4 4 1
130 .54 1 2-1/2 2-1/2 2-1/2 8/10 1.08 2-1/2 5 4 4 1-6/10
150 .625 1 3 3 3 8/10 1.25 2-1/2 6 4 4 1-6/10
200 .83 1-1/2 4 3-1/2 3-1/2 1 1.67 3+ 8 5 5 2-1/4
250 1.04 2 5 4 4 1-4/10 2.08 4+ - 5 5 2-8/10
300 1.25 2-1/2 6 4 4 1-6/10 2.5 5+ - 6 6 3-2/10
350 1.46 3 7 5 5 2 2.92 7+ - 6 6 4
500 2.08 4+ - 5 5 2-8/10 4.17 10+ - 10 6 5.6
750 3.13 7+ - 6-1/4 6-1/4 4 6.25 15+ - 15** 15 8
1000 4.2 10+ - 7 7 5-6/10 8.33 20+ - 20** 20* 12
1500 6.25 15+ 15 15 8 12.5 30+ - 30 30 15
2000 8.3 20+ - 20** 20** 12 16.7 - - 40** 40 25
3000 12.5 30+ - 30** 30** 15 25 - - 60** 60* 35
5000 20.8 - - 50** 50* 25 41.7 - - 100** 100** 60
7500 31.3 - - 70** 70** 40 62.5 - - 150** 150** 90
10000 41.7 - - 100** 100** 60 83.3 - - 200** 200** 125
The above fuses will withstand 40 x FLA for .01 second except where noted.
+ Secondary fusing required. * Fuse will withstand 30 x FLA for .01 second. ** Fuse will withstand 35 x FLA for .01 second.
L 18
APPLICATION INFORMATION
SEMICONDUCTOR PROTECTION Solid state devices have relatively short thermal time constants.
An overcurrent which may not harm an electro-mechanical
Solid State devices have progressed through several generations device can cause catastrophic failure of a solid state device.
of sophistication since their introduction in the 1940s. Fuse
designs have changed to match solid state protection demands. Many solid state devices have an overcurrent withstand rating
which is termed “I2t for fusing”. These values are found in most
The protection task looks simple- choose a fuse of correct volt- power semiconductor application handbooks.
age and ampere rating which will protect a solid state device
(diode, silicon-controlled rectifier, triac, etc.) through a wide Fuses intended for solid state device protection are rated in
range of overcurrents, yet carry normal rated loads without dete- terms of total clearing I2t.. Fuses and devices are matched so that
rioration through a long life. the total clearing I2t of the fuse is less than the withstand I2t for
the device.
Solid state power devices operate at high current densities.
Cooling is a prime consideration. The fuse should be cooled with The published fuse total clearing I2t values are derived from
the solid state device. Cycling conditions must be considered. short-circuit test oscillograms of the fuse under controlled
The ability of solid state devices to switch high currents at high conditions. The end application can vary significantly from the
speed subjects fuses to thermal and mechanical stresses. Proper tested conditions. The specifier must take these differences into
fuse selection is mandatory for long-term reliability. account since they will affect fuse clearing I2t.
For application guidelines, request the Ferraz Shawmut publication titled Power Semiconductor Fuse Application Guide,
and the software program, Select a Fuse for Power Electronics.
DC CIRCUIT PROTECTION Graph A- Current as a Function of Time During
AC applications are more common than DC. this is why fuses a DC Short Circuit
are generally designed, tested and rated for AC. Fuses rated for
AC are also capable to DC circuit interruption. The key question
is how much DC voltage interrupting capability does an AC rated
fuse have? There is no safe rule of thumb that will convert AC
voltage rating to a DC voltage rating. Testing is required to
determine the DC voltage rating of a fuse, and Technical Services
must be consulted.
DC Circuit Parameters
The degree of difficulty of interrupting a DC circuit is a function Time Constants (n)
of the voltage, current and circuit time constant. The higher the
voltage and time constant, the more difficult the interruption is Instantaneous Current (I inst) = Isc [I - e-n]
for the fuse.
Time constant is defined as t = L/R where:
t is time constant in seconds
RMS Current (l rms) = Isc √1 + 2e-n -2n
- e - 1.5
2n
n n
L is inductance in henrys
R is resistance in ohms Where Isc = short circuit current, n = number of time constants
Example.
If rated voltage is applied, 63% of rated current will be reached
Given: Voltage = 600VDC
in one time constant.
Circuit Resistance (R) = 0.1 ohm
DC Short Circuit
Graph A shows the relationship of current as a function of time
Circuit Inductance (L) = 1.0 x 10-3 henry
L 19
APPLICATION INFORMATION
DC CIRCUIT PROTECTION (Continued) protection of trailing cables in mines. UL198M is equivalent to
the requirements of MSHA, which are administered by the United
Typical Time Constants States Department of Labor. The MSHA requirements for approval
The time constant of a circuit is a function of the resistance and of DC rated fuses are specified in the Code of Federal
inductance of the components in the circuit. Here are typical Regulations, Title 30, Part 28.
time constants associated with the different DC voltage sources:
Table 1 shows the voltage ratings and time constants associated
Less than 10 milliseconds Battery supply of capacitor bank with these standards.
Less than 25 milliseconds Bridge circuit
10 to 40 milliseconds Armature circuit of DC motor Ferraz Shawmut fuses which have been tested and rated for DC
1 second* Field winding of DC motor by third party certification agencies are shown in Table 2 and
* Where time constants exceed 100 milliseconds, we do not Table 3. The Ferraz Shawmut Applications Engineering
recommend the use of fuses. A fuse can be used to interrupt Department should be contacted for assistance with applications
short circuits in these cases, but only under conditions where not served by these products.
the inductance (load) is effectively by-passed.
Maximum parallel conductor inductance can be assumed to be less Table 1- DC Parameters of UL and MSHA Standards
than .5 x 10–6 henry per foot of conductor. Graph B approximates
conductor inductance based on conductor size and spacing. STANDARD VOLTAGE TIME CONSTANT TEST CURRENT
Peak let-thru current (lp) and I2t are two measures of the degree
of current limitation provided by a fuse. Maximum allowable lp
and I2t values are specified in UL standards for all UL listed
current-limiting fuses, and are available on all
semiconductor fuses. Figure 3 illustrates the use of the peak let-thru current graph.
Assume that a 200 ampere Class J fuse (#AJT200) is to be
applied where the available fault current is 35,000 amperes
RMS. The graph shows that with 35,000 amperes RMS available,
the peak available current is 80,500 amperes (35,000 x 2.3) and
that the fuse will limit the peak let-thru current to 12,000
amperes.
Current
Why is the peak available current is 2.3 times greater than the
RMS available current. In theory the peak available fault current
can be anywhere from 1.414 x (RMS available) to 2.828 x (RMS
available) in a circuit where the impedance is all reactance with
no resistance. In reality all circuits include some resistance and
Time
the 2.3 multiplier has been chosen as a practical limit.
Let-Thru Current
Let-thru current is that current passed by a fuse while the fuse is
interrupting a fault within the fuse’s current-limiting range. Figure
1 illustrates this. Let-thru current is expressed as a peak instanta-
neous value (lp).
Ip
Ip data is generally presented in the form of a graph. Let’s review
the key information provided by a peak let-thru graph. Figure 2
shows the important components.
(2)
symmetrical amperes.
The Y-axis is labeled as “Instantaneous Peak Let-Thru
L
Current” in amperes.
(3) The line labeled “Maximum Peak Current Circuit Can
Produce” gives the worst case peak current possible
with no fuse in the circuit.
(4) the fuse characteristic line is a plot of the peak let-thru
currents which are passed by a given fuse at various
available fault currents.
L 21
APPLICATION INFORMATION
2
LET-THRU CURRENT AND I t (Continued) FUSE LET-THRU TABLES
2
Ip versus I t Apparent RMS Symmetrical Let-Thru Current
Ip has a rather limited application usefulness. Two fuses can Although the current-limiting characteristics of current-limiting
have the same Ip but different total clearing times. See Figure 4. fuses are represented in Peak Let-Thru charts, an increasingly
easy to use method of presenting this data uses Peak Let-Thru
tables. The tables are based on Peak Let-Thru charts and reflect
fuse tests at 15% power factor at rated voltage with prospective
fault currents as high as 200,000 amperes. At each prospective fault
current, let-thru data is given in two forms for an individual fuse -
lrms and lp. Where lrms is the “Apparent RMS Symmetrical
Current” and lp is the maximum peak instantaneous current passed
by the fuse, the lp let-thru current is 2.3 times lrms. This relation-
ship exists between peak current and RMS available current under
o
worst-case test conditions (i.e. closing angle of 0 at 15% power
factor).
The fuse that clears in time A will provide better component Let-thru tables are easier to read than let-thru charts. Presenting
protection than will the fuse that clears in time B. let-thru data in table versus chart format reduces the possibility
of misreading the information and saves time. These tables are
Fuse clearing I2t takes into account Ip and total clearing time. also helpful when comparing the current-limiting capability of
Fuse clearing I2t values are derived from oscillograms of fuses various fuses.
tested within their current-limiting range and are calculated as
follows:
The “t” in the equation is the total clearing time for the fuse.
To be proper, I2t should be written as (IRMS)2t. It is generally
understood that the “I” in I2t is really IRMS, and the RMS is
dropped for the sake of brevity.
L 22
APPLICATION INFORMATION
FUSE LET-THRU TABLES
Table 1- Class L, A4BQ Fuses at 600 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT BY FUSE RATING IN AMPERES
CIRCUIT
RMS. SYM 601 800 1000 1200 1600 2000 2500 3000 4000 5000 6000
AMPERES irms lp irms lp irms lp irms lp irms lp irms lp irms lp irms lp irms lp Irms lp Irms lp
10,000 7.4 17 8.7 20 10 23 10 23 10 23 10 23 10 23 10 23 10 23 10 23 10 23
15,000 8.3 19 10 23 12 27 13 30 15 35 15 35 15 35 15 35 15 35 15 35 15 35
20,000 9.1 21 11 25 13 29 14 33 17 39 20 46 20 46 20 46 20 46 20 46 20 46
25,000 9.8 23 12 27 13 31 15 35 18 42 22 50 25 58 25 58 25 58 25 58 25 58
30,000 10 24 13 29 14 33 16 37 20 45 23 53 29 66 30 69 30 69 30 69 30 69
35,000 11 25 13 30 15 35 17 39 20 47 24 56 30 69 35 81 35 81 35 81 35 81
40,000 12 27 14 32 16 37 18 41 21 49 25 58 31 72 36 83 40 92 40 92 40 92
50,000 13 29 15 34 17 40 19 44 23 53 27 63 34 78 39 89 48 111 50 115 50 115
60,000 13 30 16 36 18 42 20 47 25 57 29 67 36 83 41 94 51 118 60 138 60 138
80,000 14 33 17 40 20 46 23 52 27 62 32 73 40 91 45 104 57 130 67 153 77 176
100,000 16 36 19 43 22 50 24 56 29 67 34 79 43 98 49 112 61 140 72 165 83 190
150,000 18 41 21 49 25 57 28 64 33 77 39 90 49 112 56 128 70 160 82 189 94 217
200,000 20 45 24 54 27 63 31 71 37 84 43 100 53 123 61 141 77 176 90 208 104 239
Table 2 - Class L, A4BY Fuses at 600 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT BY FUSE RATING IN AMPERES
CIRCUIT
RMS. SYM 601 800 1000 1200 1600 2000 2500 3000 4000
AMPERES irms lp irms lp irms lp irms lp irms lp irms lp irms lp irms lp irms lp
15,000 11 24 13 29 15 35 15 35 15 35 15 35 15 35 15 35 15 35
20,000 12 26 14 32 16 37 19 43 20 46 20 46 20 46 20 46 20 46
25,000 13 29 15 34 18 40 20 46 24 55 25 58 25 58 25 58 25 58
30,000 13 30 16 36 19 43 21 49 25 58 29 67 30 69 30 69 30 69
35,000 14 32 17 38 20 45 23 52 27 61 30 70 33 76 35 81 35 81
40,000 15 34 17 40 21 47 24 54 28 64 32 73 35 79 37 86 40 92
50,000 16 36 19 43 22 51 25 58 30 68 34 78 37 86 41 95 50 115
60,000 17 38 20 45 24 54 27 62 31 72 37 84 40 91 44 100 53 121
80,000 18 42 22 50 26 59 29 67 35 80 40 92 44 100 48 110 58 133
100,000 20 45 24 54 28 64 32 73 38 87 43 99 47 108 52 119 62 143
150,000 23 52 27 62 32 73 37 84 43 99 49 113 54 123 59 137 73 167
200,000 25 56 29 67 35 80 40 91 48 110 54 123 59 136 65 150 79 181
Table 3 - Class L, A4BT Fuses at 600 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT CIRCUIT BY FUSE RATING IN AMPERES
RMS. SYM 800 1000 1200 1600 2000
AMPERES irms lp irms lp irms lp irms lp irms lp
15,000 14 33 15 35 15 35 15 35 15 35
20,000
25,000
30,000
16
17
18
36
39
41
18
19
21
41
45
48
20
22
23
46
50
54
20
25
28
46
58
63
20
25
30
46
58
69
L
35,000 19 43 22 50 25 56 29 67 34 79
40,000 20 45 23 52 26 59 30 70 35 81
50,000 21 49 25 56 28 63 33 75 38 87
60,000 23 52 26 60 29 67 35 80 40 93
80,000 25 57 29 66 32 74 38 88 44 102
100,000 27 62 31 71 35 80 41 95 48 110
150,000 31 70 35 81 40 92 47 109 55 126
200,000 34 78 39 89 44 101 52 120 60 139
L 23
APPLICATION INFORMATION
FUSE LET-THRU TABLES (Continued)
Apparent RMS Symmetrical Let-Thru Current
Table 4 - Class RK1, A6K Fuses at 600 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT CIRCUIT BY FUSE RATING IN AMPERES
RMS. SYM 30 60 100 200 400 600
AMPERES irms lp irms lp irms lp irms lp irms lp irms lp
5,000 .63 1.4 1.4 3.2 2.0 4.6 3.2 7.4 4.6 11 5.0 11.5
10,000 .80 1.8 1.7 3.9 2.6 6.0 4.0 9.2 5.8 13 7.5 17
15,000 .91 2.1 2.0 4.6 2.9 6.7 4.6 11 6.7 15 8.6 20
20,000 1.0 2.3 2.2 5.1 3.2 7.4 5.0 12 7.4 17 9.5 22
25,000 1.1 2.5 2.4 5.5 3.5 8.1 5.4 12 7.9 18 10 23
30,000 1.2 2.6 2.5 5.8 3.7 8.5 5.8 13 8.4 19 11 25
35,000 1.2 2.8 2.6 6.0 3.9 9.0 6.1 14 8.9 20 11 26
40,000 1.3 2.9 2.8 6.4 4.1 9.4 6.3 14 9.3 21 12 27
50,000 1.4 3.1 3.0 6.9 4.4 10 6.8 16 10 23 13 30
60,000 1.4 3.3 3.2 7.4 4.7 11 7.3 17 11 24 14 32
80,000 1.6 3.7 3.5 8.1 5.1 12 8.0 18 12 27 15 35
100,000 1.7 3.9 3.7 8.5 5.5 13 8.6 20 13 29 16 37
150,000 2.0 4.5 4.4 9.9 6.3 14 9.9 23 14 33 19 43
200,000 2.2 4.9 4.7 11 7.0 16 11 25 16 37 20 47
Table 5 - Class RK1,A6D Fuses at 600 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT CIRCUIT BY FUSE RATING IN AMPERES
RMS. SYM 30 60 100 200 400 600
AMPERES irms lp irms lp irms lp irms lp irms lp irms lp
5,000 .80 1.8 1.5 3.5 2.0 4.6 3.5 8.0 5.0 12 - -
10,000 1.0 2.3 1.9 4.4 2.5 5.8 4.4 10.1 7.1 16.4 10 23
15,000 1.2 2.7 2.2 4.9 2.9 6.6 5.0 11.6 8.2 18.8 12 27
20,000 1.3 2.9 2.4 5.4 3.1 7.1 5.5 12 9.0 20.7 13 29
25,000 1.4 3.2 2.6 5.9 3.4 7.8 6.0 13.8 9.7 22.3 14 32
30,000 1.5 3.4 2.7 6.2 3.6 8.3 6.3 14.6 10.3 23.6 15 33
35,000 1.5 3.5 2.9 6.6 3.8 8.7 6.7 15.4 10.8 24.9 15 35
40,000 1.6 3.7 3.0 6.9 4.0 9.1 7.0 16.5 11.3 26 16 37
50,000 1.7 4.0 3.2 7.4 4.3 9.8 7.5 16.5 12.2 28 17 40
60,000 1.8 4.2 3.4 7.8 4.5 11.0 8.0 17 13 30 18 42
80,000 2.0 4.7 3.8 8.6 5.0 12 8.8 20.3 13 33 20 46
100,000 2.2 5.0 4.1 9.3 5.4 12 9.5 20 14 35 22 50
150,000 2.5 5.8 4.6 11 6.1 14 10.9 25 16 40 25 57
200,000 2.8 6.3 5.1 12 6.8 16 11 25 19 45 27 63
Table 6 - Class J, A4J Fuses at 600 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT CIRCUIT BY FUSE RATING IN AMPERES
RMS. SYM 30 60 100 200 400 600
AMPERES irms lp irms lp irms lp irms lp irms lp irms lp
5,000 .85 2.0 1.4 3.2 2.0 4.6 3.1 7.2 4.5 10 5.0 12
10,000 1.1 2.5 1.8 4.4 2.8 6.4 3.6 8.2 5.7 13 8.7 20
15,000 1.2 2.8 2.0 4.6 2.9 6.6 4.1 9.4 6.5 15 9.9 23
20,000 1.4 3.1 2.4 5.1 3.2 7.3 4.5 10 7.1 16 11 25
25,000 1.5 3.4 2.4 5.5 3.8 8.7 5.3 12 7.7 18 12 27
30,000 1.6 3.6 2.5 5.8 4.0 9.2 5.5 13 8.2 19 13 29
35,000 1.6 3.7 2.7 6.2 4.2 9.7 5.9 14 8.6 20 13 30
40,000 1.7 3.9 2.8 6.4 4.5 10 6.0 14 9.0 21 14 32
50,000 1.8 4.2 3.0 6.9 4.7 11 6.1 14 9.7 22 15 34
60,000 2.0 4.5 3.2 7.4 5.0 11 6.5 15 10 23 16 36
80,000 2.2 4.9 3.5 8.1 5.5 12 7.1 16 11 25 17 40
100,000 2.3 5.3 3.8 9.5 6.0 14 7.7 18 12 28 19 43
150,000 2.7 6.1 4.7 10.9 6.8 16 8.8 20 14 32 21 49
200,000 2.9 6.7 4.8 11 7.5 17 9.7 22 15 35 24 54
L 24
APPLICATION INFORMATION
FUSE LET-THRU TABLES (Continued)
Apparent RMS Symmetrical Let-Thru Current
Table 7 - Class J, AJT Fuses at 600 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT CIRCUIT BY FUSE RATING IN AMPERES
RMS. SYM 30 60 100 200 400 600
AMPERES irms lp irms lp irms lp irms lp irms lp irms lp
5,000 .79 1.8 1.2 2.8 1.8 4.0 3.1 7.0 4.8 11 5.0 12
10,000 1.0 2.3 1.6 3.6 2.2 5.1 3.8 8.8 6.0 14 8.3 19
15,000 1.2 2.6 1.8 4.1 2.5 5.8 4.4 10 6.9 16 9.5 22
20,000 1.3 2.9 2.0 4.5 2.8 6.4 4.8 11 7.6 18 11 24
25,000 1.4 3.1 2.1 4.8 3.0 6.9 5.2 12 8.2 19 11 26
30,000 1.4 3.3 2.2 5.1 3.2 7.4 5.5 13 8.7 20 12 28
35,000 1.5 3.5 2.4 5.4 3.4 7.7 5.8 13 9.1 21 13 29
40,000 1.6 3.7 2.5 5.6 3.5 8.1 6.1 14 9.6 22 13 30
50,000 1.7 3.9 2.7 6.1 3.8 8.7 6.6 15 10.3 24 14 33
60,000 1.8 4.2 2.8 6.4 4.0 9.2 7.0 16 11 25 15 35
80,000 2.0 4.6 3.1 7.1 4.4 10 7.7 18 12 28 17 38
100,000 2.2 4.9 3.3 7.6 4.8 11 8.3 19 13 30 18 41
150,000 2.5 5.7 3.8 8.7 5.4 12 9.5 22 15 34 21 47
200,000 2.7 6.2 4.2 9.7 6.0 14 10.4 24 16 37 23 59
Table 8 - Class T, A6T Fuses at 600 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT CIRCUIT BY FUSE RATING IN AMPERES
RMS. SYM 30 60 100 200 400 600 800
AMPERES irms lp irms lp irms lp irms lp irms lp irms lp Irms Ip
5,000 .62 1.4 1.2 2.8 1.6 3.8 2.6 6.0 4.2 9.7 5.0 12 5.0 12
10,000 .78 1.8 1.5 3.5 2.1 4.8 3.3 7.5 5.3 12 8.2 19 10 22
15,000 .89 2.1 1.7 4.0 2.4 5.4 3.7 8.6 6.1 14 9.4 22 11 26
20,000 .98 2.3 1.9 4.4 2.6 6.0 4.1 9.5 6.7 15 10 24 12 28
25,000 1.1 2.4 2.0 4.8 2.8 6.5 4.4 10 7.2 17 11 26 13 31
30,000 1.1 2.6 2.2 5.0 3.0 6.9 4.7 11 7.7 18 12 27 14 32
35,000 1.2 2.7 2.3 5.3 3.1 7.2 5.0 11 8.1 19 12 29 15 34
40,000 1.2 2.9 2.4 5.6 3.3 7.5 5.2 12 8.5 19 13 30 16 36
50,000 1.3 3.1 2.6 6.0 3.5 8.1 5.6 13 9.1 21 14 32 17 38
60,000 1.4 3.3 2.8 6.4 3.8 8.6 5.9 14 9.7 22 15 34 18 41
80,000 1.6 3.6 3.0 7.0 4.1 9.5 6.5 15 11 25 16 38 20 45
100,000 1.7 3.9 3.2 7.5 4.5 10 7.0 16 11 26 18 40 21 48
150,000 1.9 4.4 3.8 8.6 5.1 12 8.1 19 13 30 20 46 24 55
200,000 2.1 4.9 4.1 9.5 5.6 13 8.9 20 14 33 22 51 27 61
Table 9 - Class T, A3T Fuses at 300 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT CIRCUIT BY FUSE RATING IN AMPERES
RMS. SYM 30 60 100 200 400 600 800 1200
AMPERES irms lp irms lp irms lp irms lp irms lp irms lp irms lp irms lp
5,000
10,000
15,000
.53
.66
.76
1.2
1.5
1.7
.95
1.2
1.4
2.2
2.8
3.2
1.4
1.7
2.0
3.1
3.9
4.5
2.0
2.5
2.9
4.6
5.8
6.6
3.0
3.8
4.4
6.9
8.7
10
4.5
5.6
6.4
10
13
15
5.0
7.2
8.2
12
16
19
5.0
9.3
11
12
21
24
L
20,000 .83 1.9 1.5 3.5 2.1 4.8 3.1 7.1 4.8 11 7.0 16 9.0 21 12 27
25,000 .90 2.1 1.6 3.7 2.3 5.3 3.4 7.8 5.2 12 7.6 17 9.7 22 13 29
30,000 .96 2.2 1.7 3.9 2.5 5.6 3.6 8.3 5.5 13 8.1 19 10 24 13 31
35,000 1.0 2.3 1.8 4.1 2.6 6.0 3.8 8.7 5.8 13 8.5 20 11 25 14 32
40,000 1.1 2.4 1.9 4.4 2.7 6.2 4.0 9.2 6.0 14 8.9 20 11 26 15 34
50,000 1.1 2.6 2.1 4.7 2.9 6.7 4.3 9.9 6.5 15 9.6 22 12 28 16 37
60,000 1.2 2.8 2.2 5.1 3.1 7.1 4.5 10 6.9 16 10 23 13 30 17 39
80,000 1.3 3.1 2.4 5.5 3.4 7.8 5.0 12 7.6 17 11 26 14 33 19 43
100,000 1.4 3.3 2.6 6.0 3.7 8.4 5.4 12 8.2 19 12 28 15 35 20 46
150,000 1.6 3.7 3.0 6.8 4.2 9.7 6.1 14 9.4 22 14 32 18 41 23 53
200,000 1.8 4.1 3.3 7.5 4.6 11 6.8 16 10 24 15 35 19 45 25 58
L 25
APPLICATION INFORMATION
FUSE LET-THRU TABLES (Continued)
Apparent RMS Symmetrical Let-Thru Current
Table 10- Class RK1, A2K Fuses at 250 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT CIRCUIT BY FUSE RATING IN AMPERES
RMS. SYM 30 60 100 200 400 600
AMPERES irms lp irms lp irms lp irms lp irms lp irms lp
5,000 .61 1.4 1.4 3.2 1.7 4.0 2.9 6.7 4.4 10 5.0 12
10,000 .77 1.8 1.7 4.0 2.2 5.0 3.7 8.5 5.5 13 7.4 17
15,000 .88 2.0 2.0 4.6 2.5 5.8 4.2 9.7 6.3 14 8.5 19
20,000 .97 2.2 2.2 5.0 2.8 6.3 4.6 11 6.9 16 9.3 21
25,000 1.1 2.4 2.4 5.4 3.0 6.8 5.0 12 7.4 17 10 23
30,000 1.1 2.6 2.5 5.8 3.2 7.3 5.3 12 7.9 18 11 25
35,000 1.2 2.7 2.6 6.0 3.3 7.7 5.6 13 8.3 19 11 26
40,000 1.2 2.8 2.8 6.3 3.5 8.0 5.9 13 8.7 20 12 27
50,000 1.3 3.0 3.0 6.8 3.8 8.6 6.3 14 9.4 22 13 29
60,000 1.4 3.2 3.2 7.2 4.0 9.2 6.7 15 10 23 13 31
80,000 1.5 3.5 3.5 8.0 4.4 10 7.4 17 11 25 15 34
100,000 1.7 3.8 3.7 8.6 4.7 11 7.9 18 12 27 16 37
150,000 1.9 4.4 4.3 9.8 5.4 12 9.1 21 14 31 18 42
200,000 2.1 4.8 4.7 11 6.0 14 10 23 15 34 20 46
Table 11 - Class RK1, A2D Fuses at 250 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT CIRCUIT BY FUSE RATING IN AMPERES
RMS. SYM 30 60 100 200 400 600
AMPERES irms lp irms lp irms lp irms lp irms lp irms lp
5,000 .77 1.8 1.4 3.2 2.0 4.6 3.2 7.3 5.0 12 5.0 12
10,000 .97 2.2 1.8 4.0 2.5 5.8 4.0 9.2 6.4 15 8.0 18
15,000 1.1 2.6 2.0 4.6 2.9 6.6 4.6 11 7.3 17 9.2 21
20,000 1.2 2.8 2.2 5.1 3.2 7.3 5.0 12 8.1 19 10 23
25,000 1.3 3.0 2.4 5.5 3.4 7.9 5.4 12 8.7 20 11 25
30,000 1.4 3.2 2.5 5.8 3.6 8.3 5.8 13 9.2 21 12 27
35,000 1.5 3.4 2.7 6.1 3.8 8.8 6.1 14 9.7 22 12 28
40,000 1.5 3.5 2.8 5.7 4.0 9.2 6.4 15 10 23 13 29
50,000 1.7 3.8 3.0 6.9 4.3 9.9 6.8 16 11 25 14 32
60,000 1.8 4.0 3.2 7.3 4.6 11 7.3 17 12 27 15 34
80,000 1.9 4.5 3.5 8.1 5.0 12 8.0 18 13 29 16 37
100,000 2.1 4.8 3.8 8.7 5.4 12 8.6 20 14 32 17 40
150,000 2.4 5.5 4.3 9.9 6.2 14 9.9 23 16 36 20 46
200,000 2.6 6.0 4.8 11 6.8 16 11 25 17 40 22 50
Table 12 - Class RK5, TRS Fuses at 600 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT CIRCUIT BY FUSE RATING IN AMPERES
RMS. SYM 30 60 100 200 400 600
AMPERES irms lp irms lp irms lp irms lp irms lp irms lp
5,000 1.7 3.9 3.2 7.4 3.4 7.8 5.0 12 - - - -
10,000 2.1 4.8 4.0 9.2 4.2 9.7 6.2 14 10 23 10 23
15,000 2.4 5.5 4.6 11 4.8 11 7.1 16 12 27 15 35
20,000 2.7 6.2 5.1 12 5.3 12 7.8 18 13 30 18 42
25,000 2.9 6.7 5.5 13 5.7 13 8.4 19 14 32 20 45
30,000 3.1 7.1 5.8 13 6.1 14 8.9 20 15 35 21 48
35,000 3.3 7.6 6.1 14 6.4 15 9.4 22 16 36 22 50
40,000 3.4 7.8 6.4 15 6.7 15 9.8 23 17 38 23 53
50,000 3.7 8.5 6.9 16 7.2 17 11 24 18 41 25 57
60,000 3.9 9.0 7.3 17 7.7 18 11 26 19 43 26 60
80,000 4.3 9.9 8.1 19 8.5 20 12 29 21 48 29 66
100,000 4.6 11 8.7 20 9.1 21 13 31 22 52 31 72
150,000 5.3 12 9.9 23 10 24 15 35 26 59 36 82
200,000 5.8 13 11 25 12 26 17 39 28 65 39 90
L 26
APPLICATION INFORMATION
FUSE LET-THRU TABLES (Continued)
Apparent RMS Symmetrical Let-Thru Current
Table 13 - Class RK5, TR Fuses at 250 Volts AC, 15% Power Factor
PROSPECTIVE FUSE LET-THRU CURRENT IN KILO-AMPERES
SHORT CIRCUIT BY FUSE RATING IN AMPERES
RMS. SYM 30 60 100 200 400 600
AMPERES irms lp irms lp irms lp irms lp irms lp irms lp
5,000 1.4 3.2 3.0 6.9 3.2 7.4 5.0 12 - - - -
10,000 1.8 4.1 3.8 8.7 4.1 9.4 6.6 15 10 23 10 23
15,000 2.1 4.8 4.4 10 4.7 11 7.6 17 13 29 15 35
20,000 2.3 5.3 4.8 11 5.1 12 8.4 19 14 32 19 44
25,000 2.5 5.6 5.2 12 5.5 13 9.0 21 15 34 21 48
30,000 2.6 6.0 5.5 13 5.9 14 9.6 22 16 37 22 50
35,000 2.7 6.2 5.8 13 6.2 14 10 23 17 38 23 53
40,000 2.9 6.7 6.1 14 6.5 15 11 24 18 40 24 56
50,000 3.1 7.1 6.5 15 7.0 16 11 26 19 43 26 60
60,000 3.3 7.6 7.0 16 7.4 17 12 27 20 46 28 63
80,000 3.6 8.3 7.7 18 8.1 19 13 31 22 51 30 70
100,000 3.9 9.0 8.3 19 8.8 20 14 33 24 55 33 75
150,000 4.4 10 9.4 22 10 23 16 38 27 62 38 86
200,000 4.9 11 11 24 11 26 18 41 30 69 41 95
Example:
In a 480V circuit with 100,000A available short-circuit current,
125,000
150,000
270,000
330,000
6000A
6000A
6000A
6000A
6000A
6000A L
what maximum size fuse can be used to protect feeder bus duct * 30A to 600A fuses – Class J (*time delay AJT)
which has a 42,000 short-circuit rating? Class RK1 (A2K/A6K or time delay A2D/A6D)
800 to 6000A fuses – Class L (A4BQ)
Answer:
From the table, A Ferraz Shawmut 1600A Class L fuse
A4BQ1600 will protect this bus duct up to 100,000 amperes.
L 27
APPLICATION INFORMATION
CAPACITOR PROTECTION
The primary responsibility of a capacitor fuse is to isolate a
shorted capacitor before the capacitor can damage surrounding
equipment or personnel. Typical capacitor failure occurs when
the dielectric in the capacitor is no longer able to withstand the
applied voltage. A low impedance current path results. The
excessive heat generated builds pressure and can cause violent
case rupture. A fuse will isolate the shorted capacitor before case
rupture occurs.
Fuse Placement
The Code requires that an overcurrent device be placed in each
ungrounded conductor of each capacitor bank (see Figure 1).
The Code further requires that the rating or setting of the over
current device be as low as practicable. A separate overcurrent
device is not required if the capacitor is connected on the load
side of a motor-running overcurrent device.
Fusing per the Code provides reasonable protection if the Steady state capacitor current is proportional to the applied volt-
capacitors are the metalized film self-healing type. If not, each age and frequency. Since voltage and frequency are fixed in
capacitor should be individually fused as shown in Figure 2. power factor correction applications, the capacitor is not expect-
ed to be subjected to an overload. Therefore, capacitor fuses are
Fusing each individual capacitor is especially important in not selected to provide overload protection for the capacitor.
large banks of parallel capacitors. Should one capacitor fail, the
parallel capacitors will discharge into the faulted capacitor and KVAR vs. AMPS
violent case rupture of the faulted capacitor can result. Individual The capacitor’s current rating can be derived from its KVAR rat-
capacitor fusing eliminates this problem. ing by using the following formula:
If the capacitors are to be placed in banks comprised of both KVAR x 1000 = amps
series and parallel combinations, the capacitor manufacturer volts 1 KVAR = 1000VA (Reactive)
must be consulted for fuse placement recommendations. The
opening of improperly placed fuses can cause overvoltage and Example: What fuse would you recommend for a three phase
result in damage to other capacitors in the network. capacitor rated 100KVAR at 480 volts?
L 28
APPLICATION INFORMATION
CABLE PROTECTION Placement of Cable Protectors
In single phase applications where a single transformer supplies
Using Cable Protectors the service and there are only one or two conductors per phase,
Cable Protectors are special purpose limiters which are used to a single Cable Protector per cable may be used. The Cable
protect service entrance and distribution cable runs. Though not Protector should be located at the supply end of the cable. In all
required by the Code for overcurrent protection, the Code does other applications, Cable Protectors should be placed at both
recognize the use of Cable Protector as current limiting devices. ends of each cable. This allows a faulted cable to be isolated
from the source end and from a back feed at its load end.
When unprotected cables are paralleled, a singe conductor faulting Isolation of a faulted cable is only possible if there are 3 or more
to ground can result in damage to and eventual loss of all parallel parallel cables per phase.
conductors. The resultant cost of cable replacement, loss of
service, and down time can be significant. This cost can be Cable Protector Ampacity
minimized by the use of Cable Protectors. Cable Protectors are not ampere rated. They are not intended to
provide overload protection for the cable. Cable Protectors are
When each phase consists of three or more parallel conductors, designed to open in case of a short circuit or after a cable has
Cable Protectors are installed at each end of each conductor. faulted. Thus total system reliability is maximized. For these
Should one cable fault, the Cable Protectors at each end of the reasons Cable Protectors are rated in terms of the cable material
faulted cable will open and isolate the faulted cable. The unfaulted (aluminum or copper) and the cable cable size (250kcmil,
cables will maintain service. 500kcmil, etc.)
L 29
APPLICATION INFORMATION
WELDER PROTECTION Special Applications
UL class fuses sized according to the Code may not be suitable
General in some welding applications. High ambient temperatures, high
Articles 630-12 and 630-32 of the National Electrical Code cycle rates and high available fault currents may require the use
requires that electric welders and their supply conductors have of Ferraz Shawmut Welder Protectors.
overcurrent protection. The Code further requires that each
welder have a nameplate which provides information necessary Welder Protectors (A4BX Type 150 or Type 150J) are special
for the selection of the appropriate supply conductors and purpose limiters which have been designed specifically for
overcurrent protection devices. welding applications to protect equipment in case of short
circuits. They have twice the thermal rating of UL Class fuses
While either circuit breakers or fuses may be used for overcurrent yet provide a low clearing I2t . This combination minimizes fuse
protection, the typically high available fault currents and the need fatigue and allows effective coordination with upstream devices.
for overall system selective coordination favor the use of current- Welder Protectors may be sized closer to welder primary ampere
limiting fuses. rating than UL Class fuses, hence may allow the use of smaller
disconnect switches.
Supply Conductor Protection Welder Protectors are intended for short circuit protection and
For AC transformer, DC rectifier and motor-generator arc welders are not intended for overload protection. They should never be
the supply conductors should be fused at not more than 200% of used as the only protective device on any welder application.
the conductor ampere rating. For resistance welders the Code allows Thermal overload protection must be provided in the welder by
fusing at up to 300% of conductor ampere rating. In both appli- some other device.
cations a time delay RK5 fuse such as the Tri-onic® is generally
recommended.
Welder Protection
To comply with the Code, AC transformer, DC rectifier and motor-
generator arc welders should be fused at not more than 200% of
their primary current rating (shown on welder nameplate).
Resistance welders should be fused at not more than 300% of
their primary current rating. As with supply conductors, RK5 time
delay fuses such as the Tri-onic® are recommended. It should be
noted that the Code states that a separate overcurrent device is
not required for the welder if the supply conductors are protected
by an overcurrent device which will satisfy the welder overcurrent
protection requirements.
L 30
APPLICATION INFORMATION
SELECTIVITY BETWEEN 240, 480 OR 600 VOLT if the downstream fuse opens while the upstream fuse remains
operable under all conditions of overcurrent. The term
MAIN AND BRANCH FUSES “discrimination” is synonymous with selectivity and is the
preferred international term for this definition.
Definition
Coordination is defined as properly localizing a fault condition to The word all is key. Fuse selectivity cannot be assured by com-
restrict outages to the equipment affected, accomplished by paring fuse time current curves alone. These curves stop at .01
choice of selective fault protective devices. second. Fuse performance under high fault conditions must also
be evaluated. Fuse I2t is the best tool for assuring coordination
Coordination (selectivity, discrimination) is desirable and often under high fault current conditions. If the total clearing I2t of the
times mandatory. A lack of coordination can represent a hazard to downstream fuse is less than the melting I2t of the main
people and equipment. When designing for coordination, fuses upstream fuse, the fuses will be selective under high fault con-
provide distinct advantages over other types of overcurrent pro- ditions.
tective devices.
To simplify presenting weighty I2t data, selectivity information can
To coordinate a circuit breaker protected system, it is generally simply be found in selectivity ratio tables.
necessary intentionally to delay the short circuit response of
upstream breakers. Though coordination may be achieved, short The ratios found in the following tables are conservative and are
circuit protection is compromised. The speed and consistency appropriate for all overcurrents up to 200,000 amperes RMS. In
of response of fuses allows coordination without compromising some cases smaller ratios than shown may be used. Consult your
component protection. Ferraz Shawmut representative for specific recommendations.
The terms coordination and selectivity are often used inter-
changeably. The term coordination should be used to describe a
system as defined above, while two fuses are said to be selective
Fuse Selectivity Ratios - 600 and 480 Volt Applications Up to 200,000 RMS Symmetrical Amperes
R ATIO*
BRANCH M A I N F U SE
FUSE A4BQ A4BY A4BT TRS A6K A6D A4J AJT A6T
A4BQ 2:1 2:1 2:1 - - - - - -
A4BY - 2.5:1 2:1 - - - - - -
A4BT 2.5:1 2.5:1 2:1 - - - - - -
TRS 4:1 4:1 3:1 2:1 4:1 4:1 4:1 3:1 4.5:1
A6K 2:1 2:1 1.5:1 1.5:1 2:1 2:1 3:1 2:1 3.5:1
A6D 2:1 2:1 1.5:1 1.5:1 2:1 2:1 3:1 2:1 3.5:1
A4J 2:1 2:1 1.5:1 1.5:1 2:1 2:1 2:1 2:1 3:1
AJT 2:1** 2:1** 2:1 1.5:1 2:1 2:1 2.5:1 2:1 3.5:1
A6T 3:1 2.5:1 2:1 1.5:1 2:1 2:1 2:1 2:1 2.5:1
Fuse Selectivity Ratios - 240 Volt Applications Up to 200,000 RMS Symmetrical Amperes
R ATIO*
BRANCH M A I N F U SE
FUSE A4BQ A4BY A4BT TR A2K A2D A4J AJT A3T
A4BQ 2:1 2:1 2:1 - - - - - -
A4BY
A4BT
TR
-
2.5:1
4:1
2.5:1
2.5:1
4:1
2:1
2:1
4:1
-
-
1.5:1
-
-
4:1
-
-
3:1
-
-
4:1
-
-
3:1
-
-
5:1
L
A2K 2:1 2:1 1.5:1 1.5:1 2:1 1.5:1 2:1 1.5:1 3:1
A2D 2.5:1 2.5:1 2:1 1.5:1 2:1 1:5:1 2:1 2:1 3:1
A4J 2:1 2:1 1.5:1 1.5:1 2:1 1.5:1 2:1 2:1 3:1
AJT 2:1 2:1 2:1 1.5:1 2.5:1 2:1 2.5:1 2:1 3:1
A3T 1.5:1 1.5:1 1.5:1 1.5:1 1.5:1 1.5:1 1.5:1 1.5:1 2:1
L 31
APPLICATION INFORMATION
SELECTIVITY BETWEEN TWO E-RATED FUSES FUSE R ATINGS
IN SERIES 2400, 4160 or 4800V SYSTEMS 6.9 thru 14.4KV SYSTEMS
MAX. BRANCH MIN. MAIN MAX. BRANCH MIN. MAIN
A selective system eliminates unnecessary power outages and
10E 20E 10E 20E
costly downtime in the remainder of the system not directly
15E 25E 15E 25E
affected by the fault condition. This results in significant savings
20E 40E 20E 30E
and safety for the user.
25E 40E 25E 50E
In a properly designed selective system a branch fuse must open 30E 50E 30E 65E
the circuit under fault conditions without damaging the main 40E 65E 40E 65E
fuse. This is accomplished by making sure that the required 50E 80E 50E 80E
Minimum Melting energy of the main fuse is greater than the 65E 125E 65E 125E
Total Clearing energy required to “open” the branch fuse.
80E 150E 80E 150E
Example: 100E 200E 100E 200E
In a 4160V system fed by a 200E main fuse (A055F1DORO-200E 125E 250E - -
or equivalent), what is the maximum branch fuse allowable to 150E 250E - -
maintain selectivity between the two?
200E 400E - -
From the table, the maximum E-rated branch fuse is 100E 250E 400E - -
(AO55F1DORO-100E or equivalent). 300E 450E - -
400E - - -
L 32
APPLICATION INFORMATION
SELECTIVITY OF E-RATED PRIMARY AND LOW SEC.
VOLTAGE SECONDARY FUSES FUSE MINIMUM PRIMARY FUSE RATING*
AMPERE PRIMARY VOLTAGE
Good design dictates that transformer secondary fuses should RATING 2400 4160 4800 6900 13,800
clear overcurrents before transformer primary fuses open. The 480 Secondary
following table shows the smallest primary fuse E rating which 200 50E (80E) 30E (50E) 25E (40E) 20E (30E) 10E (15E)
will be selective with a given secondary fuse. 400 100E (125E) 50E (80E) 50E (65E) 40E (50E) 20E (25E)
600 125E (200E) 100E (125E) 80E (125E) 65E (100E) 30E (50E)
Fuses are assumed to be Ferraz Shawmut Type CS-3 or CL-14 for 800 250E 150E 125E 100E 50E
primary, A4BY or A4BQ (Class L) for secondary 800 amperes 1000 300E 150E 150E 125E 50E
and larger, Class J or Class RK1 for secondary 600 amperes and 1200 350E 200E 200E 125E 65E
smaller. 1600 500E 250E 250E 150E 100E
2000 600E 300E 300E 200E 100E
The critical point for coordinating E-rated to low voltage fuses is 2500 - 450E 400E - 125E
in the 5-second to 10-second region of the fuse time current 3000 - 500E 450E - 150E
curves. This means that non-time delay secondary fuses will be 4000 - - 600E - 200E
selective with a lower E-rated primary fuse than will time delay 5000 - - - - -
secondary fuses. For this reason two E ratings are shown for 6000 - - - - -
most 600 ampere and smaller secondary fuses. The lower E rating 240V Secondary
will be selective with a non-time delay Class J or Class RK1. The 200 25E (40E) 15E (25E) 15E (20E) 10E (15E) 10E
higher E rating shown is required for selectivity with a time delay 400 50E (80E) 30E (50E) 25E (40E) 20E (30E) 10E (15E)
Class J or Class RK1. 600 80E (125E) 50E (65E) 40E (65E) 30E (40E) 15E (20E)
800 125E 80E 65E 50E 25E
The worst case condition for secondary fuse to primary fuse 1000 150E 100E 80E 65E 30E
selectivity occurs when a line-to-line secondary fault develops 1200 200E 125E 100E 65E 40E
on a delta-to-wye transformer. One of the primary fuses will see 1600 250E 125E 125E 100E 50E
116% of the turns ratio current. This worst case condition was 2000 300E 150E 150E 125E 65E
assumed when the tables that follow were developed. 2500 400E 250E 200E 150E 80E
3000 450E 250E 250E 150E 100E
Example 1:. 4000 600E 400E 300E 200E 125E
With A6K400R (400A Class RK1) fuses as 480V secondary 5000 - 400E 400E - 125E
mains of a 13,800V/480V supply transformer, what is the mini- 6000 - 500E 450E - 150E
mum 13,800V primary fuse necessary for selectivity? 208V Secondary
200 20E (40E) 15E (25E) 10E (20E) 10E (15E) 10E
400 50E (80E) 25E (40E) 25E (40E) 15E (25E) 10E (15E)
600 65E (100E) 40E (65E) 40E (50E) 25E (40E) 15E (20E)
800 125E 65E 65E 50E 20E
1000 125E 80E 65E 50E 25E
1200 150E 100E 80E 65E 30E
1600 200E 125E 125E 80E 40E
Answer: 2000 250E 150E 125E 100E 50E
Since the A6K400R is not a time delay fuse it will coordinate 2500 350E 200E 200E 125E 80E
with a 20E primary fuse (A155F1DORO-20E or equivalent). 3000 400E 200E 200E 150E 80E
4000 600E 300E 250E 200E 125E
Example 2: 5000 - 400E 350E - 125E
6000 - 450E 400E - 150E
A 416OV distribution transformer supplies a 3000A, 208V main
panel. What minimum 4160V primary fuse is needed to assure * ( ) indicates primary fuse rating when secondary fuse is time delay type L
Recommended Fuses: Ferraz Shawmut
Secondary, 200-600A - Class J (A4J or AJT) or RK1 (A2K or A2D 250V) (A6K or A6D 600V)
Secondary, 800-6000A - Class L (A4BY or A4BQ)
CS-3: 5kV-A055F, 8kV-A825X,* 15kV-A155F
CL-14: 5kV-A055C, A055B, 15kV-A155C
*Consult factory for information on A825X Series.
selectivity?
Answer:
A 200E primary fuse (A055F1DORO-200E or equivalent).
L 33
APPLICATION INFORMATION
SELECTIVITY BETWEEN E-RATED PRIMARY
AND E-RATED SECONDARY FUSES
Some applications require selectivity between transformer
secondary fuses and transformer primary fuses. The table
below shows the smallest 15.5KV E-rated primary fuse
which will be selective with a given E-rated secondary
fuse. The table assures selectivity for Ferraz Shawmut Type
CS-3 and CL-14 E-rated fuses under all current levels and
under the worst case situation. The worst case situation
exists when the following conditions occur simultaneously:
- Transformer is delta primary and wye secondary
(see figure).
- A line-to-line secondary fault occurs.
- The fault current through a primary fuse is equal
to the primary fuse 0.01 second melt current.
The worst case condition rarely occurs. In most cases
selectivity will be maintained with a primary fuse one size
smaller than shown in this table.
L 34
APPLICATION INFORMATION
SELECTIVITY BETWEEN E-RATED PRIMARY FUSES Selective Primary and Secondary
AND R-RATED SECONDARY MOTOR FUSES Motor Fuse Ratings
Good design dictates that transformer secondary fuses shall clear SECONDARY MINIMUM PRIMARY FUSE E RATING
overcurrents and not allow the primary fuse to open, thereby FUSE PRIMARY VOLTAGE
maintaining selectivity between the two. R RATING 4160V 4800V 6900V 13.8KV
2R - - - 40E
3R - - - 65E
4R - - - 80E
6R - - - 125E
9R - - - 150E
12R - - - 200E
18R - - - -
Recommended Fuses: Ferraz Shawmut
R-rated - A24OR, A48OR, A72OR or equivalent
E-rated - CS-3: 5KV-A055F, 8KV-A825X,* 15KV-A155F
CL-14: 5KV-A055C, A055B, 15KV-A155C
* Consult factory for information on A825X Series.
Example:
In a 13800V/2400V distribution system, what is the maximum
L
size 2400V motor fuse which can be used if the distribution
transformer primary is fused at 65E?
Answer:
From the table, a 9R motor fuse (Ferraz Shawmut A240R9R) is
the maximum size which can be used. If the 9R motor fuse
opens on any overcurrent, it will not affect the 65E primary fuse,
and selectivity is maintained.
L 35
APPLICATION INFORMATION
SELECTIVITY BETWEEN E-RATED MAIN FUSE Selective Main and Motor Fuse Ratings in Series
AND R-RATED MOTOR FUSE IN SERIES 2400, 4160, 4800, 6900 or 7200V SYSTEMS
MOTOR FUSE MINIMUM MAIN FUSE
Feeder fuses and motor fuses in series must be selective. R RATING E RATING
Selectivity assures that the motor fuse only will open, and not 2R 80E
the feeder fuse, thus eliminating power outages to the remainder 3R 125E
of the branch circuits. 4R 150E
6R 200E
Selectivity is accomplished by assuring that the required minimum 9R 300E
melting energy of the feeder fuse is greater than the total clearing 12R 400E
energy required to open the motor fuse. 18R 600E
24R -
36R -
With any system involving R-rated fuses, a contactor and over-
load relay must be employed to open on low overhead currents. Recommended Fuses: Ferraz Shawmut
R-rated - A24OR, A48OR, A72OR* or equivalent
This table assumes that the overload relay is properly selected E-rated - CS-3: 5KV-A055F, 8KV-A825X,* 15KV-A155F
and that the R-rated fuse is only required to open on overcurrents CL-14: 5KV-A055C, A055B, 15KV-A155C
which are large enough to open the fuse in 20 seconds or less. *Consult factory for information on A825X Series.
Answer:
From the table, a 3R motor fuse (Ferraz Shawmut A480R3R-1)
requires a minimum 125E distribution fuse (Ferraz Shawmut
A055F1DORO-125E) upstream for proper selectivity. If the 3R
motor fuse opens on any overcurrent, it will not affect the 125 E
feeder fuse.
L 36
APPLICATION INFORMATION
QUICK THREE PHASE SHORT CIRCUIT To find the short circuit current at any point in the system, simply
CALCULATIONS add the factors as they appear in the system from service
entrance to fault point and read the available current on Scale 1.
Short circuit current levels must be known before fuses or other
equipment can be correctly applied. For fuses, unlike circuit Example 2:
breakers, there are four levels of interest. These are 10,000, If the primary short circuit power were 50MVA (instead of 500MVA)
50,000, 100,000 and 200,000 RMS symmetrical amperes. in this same system, what would Isc be at the transformer? At the
end of the bus duct run?
Rigorous determination of short circuit currents requires accurate
reactance and resistance data for each power component from the Answer:
utility generating station down to the point of the fault. It is time- From the Primary MVA correction factor table A1, the factor for
consuming for a plant engineer to collect all this information and 50MVA (at 480V) is 1.74. The new factor at the transformer is then
yet he is the one most affected by short circuit hazards. 4.80 + 1.74 = 6.54 and Isc is reduced to 18,000A (Scale 1).
The new factor at the bus duct is 9.21 + 1.74 = 10.95 Isc =
There have been several approaches to “easy” short circuit 11,000A (Scale 1).
calculations which have been cumbersome to be of practical
use. The method described here is not new but it is the simplest
of all approaches.
Example 1:
What is the potential short circuit current at various points in a
480V, 3-phase system fed by a 1000KVA, 5.75%Z transformer?
(Assume primary short circuit power to be 500MVA.)
Cable and bus factors are based on 100 foot lengths. Shorter or
longer lengths have proportionately smaller or larger factors (i.e.
50’ length = 1/2 factor; 200’ length = 2 x factor). Basic compo-
nent factors are listed on following pages in tables A through D.
L 37
APPLICATION INFORMATION
QUICK THREE PHASE SHORT CIRCUIT CALCULATIONS (Continued)
3f to 3f
480V 208V
40,000A 14,500A
100kVA
L 38
APPLICATION INFORMATION
QUICK THREE PHASE SHORT CIRCUIT CALCULATIONS (Continued)
A3- Factors for Single Phase Transformer in A3- Single Phase Transformer Factors
Three Phase System FACTOR
TRANSFORMER 1 PHASE VOLTAGE
Transformer connections must be known before factor can be
120V 240V 120V
determined. See Figures A and B.
KVA %Z FIG. A FIG. A FIG. B
1. Determine system factor at 1f transformer primary, with 480V 15 2.5 34.6 48.0 24.0
pri., 120/240V sec. (Figure A) 25 2.5 20.7 28.8 14.4
Example: Isc @480V = 40,000, 3f. Factor is 3.00 (from 37.5 2.8 16.6 23.0 11.5
Scale 1). 50 3.0 12.5 17.3 8.65
75 3.0 8.28 11.5 5.75
100 3.0 6.22 8.64 4.32
1f factor = 3f factor = 3.00 = 3.46 150 2.5 3.46 4.80 2.40
.866 .866
167 2.5 3.10 4.31 2.16
225 2.5 2.30 3.20 1.60
2. Adjust factor in proportion to voltage ratio of 480/240V transformer.
300 3.0 2.07 2.88 1.44
Example: For 240V, 1f factor is (240 ∏ 480) 3.46 = 1.73 500 4.5 1.86 2.59 1.30
Note: Factor varies with %Z.
Example: 50KVA, 240V secondary with a 1.5%Z has a factor of
3. Add factor for 1f transformer with Figure A connection. (1.5%Z ∏ 3.0%Z) x 17.3 = 8.65
Example: Factor for 100KVA, 120/240V, 3%Z transformer is:
a. 120V--total factor = 6.22 + 1.73 = 7.95
(Isc = 15,000A)
b. 240V--total factor = 8.64 + 1.73 = 10.37
(Isc = 11,600A)
L 39
APPLICATION INFORMATION
QUICK THREE PHASE SHORT CIRCUIT CALCULATIONS (Continued)
Note: For parallel runs divide factor by number of conductors per phase.
Example: If factor for a single 500KCmil conductor is 2.49 then the factor for a run having 3-500KCmil per phase
is 2.49 ∏ 3 = .83 (Example from Table B, 480 volts)
L 40
APPLICATION INFORMATION
QUICK THREE PHASE SHORT CIRCUIT CALCULATIONS (Continued) Isc = 120,000
Total Factor
Component Factor Tables - Bus Duct
SHORT CIRCUIT CURRENT
1200 1.21 1.06 .53 .42 1.60 1.36 .66 .54 75,000
1350 1.17 1.01 .51 .40 1.32 1.14 .57 .46
1600 1.03 .89 .45 .36 1.19 1.03 .52 .41 70,000
2000 .90 .78 .39 .31 .90 .77 .39 .31
2500 .63 .54 .27 .22 .70 .60 .30 .24 65,000
3000 .51 .44 .22 .18 .60 .52 .26 .21
4000 .37 .32 .16 .13 .43 .38 .19 .15
5000 .30 .26 .13 .10 -- -- -- -- 2 60,000
* These factors may be used with feeder duct manufactured by I-T-E, GE, Square D and Westinghouse. 55,000
50,000
2.5
FACTOR
DUCT 3 PHASE VOLTAGE
3 40,000
AMPERE COPPER ALUMINUM
RATING 208 240 480 600 208 240 480 600
35,000
400 2.53 2.18 1.09 .89 3.88 3.34 1.67 1.36
600 2.53 2.18 1.09 .89 2.41 2.07 1.04 .84 4 30,000
800 1.87 1.61 .81 .66 2.41 2.07 1.04 .84
1000 1.87 1.61 .81 .66 1.69 1.45 .73 .59 25,000
5
1200 1.47 1.26 .63 .51 1.43 1.22 .61 .50
1350 1.26 1.08 .54 .44 1.30 1.12 .56 .45 6 20,000
1600 .91 .78 .39 .32 1.09 .94 .47 .38 7
2000 .79 .68 .34 .28 .89 .77 .38 .31 8 15,000
9
10
2500 .61 .52 .26 .21 .66 .57 .28 .23 11
3000 .48 .42 .21 .17 .59 .51 .25 .21 12 10,000
L
4000 .43 .37 .18 .15 .46 .40 .20 .16 14 9,000
16 8,000
5000 .38 .33 .16 .13 .35 .30 .15 .12 7,000
18
20 6,000
** These factors may be used with plug-in duct manufactured by GE, Square D and Westinghouse. 22
24 5,000
40 3,000
60 2,000
80 1,500
100
120 1,000
SCALE 1
L 41
APPLICATION INFORMATION
PROPERTIES OF MATERIALS
FUSE BLOCKS, FUSE HOLDERS, POWER DISTRIBUTION BLOCKS, FUSES & ACCESSORIES
ASTM POLYBUTYLENE POLYSULFONE
PROPERTY UNITS TEST PHENOLIC POLYCARBONATE POLYAMIDE TERPHTHALATE COPOLYMER POLYPHTALAMIDE
Note: Above data represents approximate values and are for reference only.
L 42
APPLICATION INFORMATION
L 43
APPLICATION INFORMATION
RULES FOR EQUIPMENT SHORT CIRCUIT RATING 10 REASONS FOR USING CURRENT-LIMITING FUSES
The National Electric Code (1999) states: ➤ RELIABILITY
No moving parts to wear or become contaminated by dust,
110-9. Interrupting Rating oil or corrosion.
“Equipment intended to interrupt current at fault levels shall have
an interrupting rating sufficient for the nominal circuit voltage ➤ LONG LIFE
and the current that is available at the line terminals of the equip- The speed of response of a fuse will not change or slow
ment. Equipment intended to interrupt current at other than fault down as the fuse ages. In other words, the fuse’s ability to
levels shall have an interrupting rating at nominal circuit voltage provide protection is not adversely affected by the passage
sufficient for the current that must be interrupted.” of time.
Enclosed fusible switches whether for individual wall mounting ➤ MINIMAL MAINTENANCE
or in equipment assemblies, are “equipment intended to Fuses do not require periodic recalibration as do electro
interrupt current”. With this in mind, both the switch and the mechanical overcurrent protective devices.
fuse must be adequately rated to satisfy code requirements.
➤ COMPONENT PROTECTION
The fuse must have an interrupting rating greater than the short The current limiting action of a fuse minimizes or eliminates
circuit current available at the line terminals of the switch. The component damage.
switch must have a short circuit current withstand rating greater
than the short circuit current available at the line terminals of the ➤ NORTH AMERICAN STANDARDS
switch. Tri-national Standards specify fuse performance and
maximum allowable fuse Ip and I2t let-thru values.
UL98 “Enclosed and Dead-Front Switches” requires that Listed
switches be tested with fuses to establish the short circuit cur- ➤ SELECTIVITY
rent withstand rating of the switch. The switch is then required to Fuses may be easily coordinated to provide selectivity under
be marked with its withstand rating, the appropriate UL fuse class both overload and short circuit conditions.
and maximum circuit voltage.
➤ HIGH INTERRUPTING RATING
You don’t pay a premium for high interrupting capacity.
Most low voltage current limiting fuses have a 200,000
FERRAZ SHAWMUT INSTRUCTIONAL VIDEOS ampere interrupting rating.
L 44
APPLICATION INFORMATION
L 45