ELEN 20023
ELECTRICAL PLAN
Niña Raquel P. Ronario
BSCE 2-5
LEGEND
Ceiling Mounted Light
Wall Mounted Light
Switch
Convenience Outlet
ACU
Laundry Circuit
Range
Ground Floor
Lighting Layout
Second Floor
Lighting Layout
Ground Floor
Power Layout
Second Floor
Power Layout
SCHEDULE OF LOADS
LOAD SERVICE LOAD LOAD CB SIZE
CKT NO. WIRE SIZE
DESCRIPTION VOLTAGE WATTS AMPS POLE AF AT
Lighting - GF
1 (1-LP) 230V 600 VA 2.6 2 50 15 2.0 mm2
(5 lights)
Lighting - GF
2 (2-LP) 230V 960 VA 4.2 2 50 15 2.0 mm2
(8 lights)
Lighting - SF
3 (3-LP) 230V 480 VA 2.1 2 50 15 2.0 mm2
(4 lights)
Lighting - SF
4 (4-LP) 230V 600 VA 2.6 2 50 15 2.0 mm2
(5 lights)
C. Outlet - GF
5 (1-PP)) 230V 360 VA 1.6 2 50 15 2.0 mm2
(2 C.O.)
C. Outlet - GF
6 (2-PP) 230V 540 VA 2.3 2 50 15 2.0 mm2
(3 C.O.)
7 (3-PP) ACU Guestroom 230V 1840 VA 8 2 50 30 2.0 mm2
C. Outlet - GF
8 (4-PP) 230V 540 VA 2.3 2 50 15 2.0 mm2
(3 C.O.)
9 (5&6-PP) Laundry 230V 240 VA 1.04 2 50 15 2.0 mm2
10 (7-PP) Range 230V 8000 VA 34.8 2 50 50 3.5 mm2
C. Outlet - SF
11 (8-PP) 230V 540 VA 2.3 2 50 15 2.0 mm2
(3 C.O.)
C. Outlet - SF
12 (9-PP) 230V 540 VA 2.3 2 50 15 2.0 mm2
(3 C.O)
ACU Master’s
13 (10-PP) 230V 2300 VA 10 2 50 30 2.0 mm2
Bedroom
14 (11-PP) ACU Bedroom 1 230V 2300 VA 10 2 50 30 2.0 mm2
15 (12-PP) ACU Bedroom 2 230V 1840 VA 8 2 50 30 2.0 mm2
16 Spare 230V 1500 VA 6.5 2 50 15
TOTAL 230V 23180 VA 100.64
COMPUTATIONS
1. LIGHTING – Ground Floor 7. ACU – Guest Room
5 × 120VA = 600VA 1 hp = 8 A
600𝑉𝐴 8 A × 230 V = 1840 VA
= 2.6 A
230𝑉
8 A × 1.25 = 10 (Ampacity)
2.6 A × 1.25 = 3.25 (Ampacity)
8 A × 2.50 = 20 (Circuit Breaker)
2.6 A × 1.25 = 3.25 (Circuit Breaker)
8. CONVENIENCE OUTLET – Ground Floor
2. LIGHTING – Ground Floor
3 × 180VA = 540VA
8 × 120VA = 960VA 540𝑉𝐴
960𝑉𝐴 = 2.3 A
= 4.2 A 230𝑉
230𝑉
2.3 A × 1.25 = 2.875 (Ampacity)
4.2 A × 1.25 = 5.25 (Ampacity)
2.3 A × 1.25 = 2.875 (Circuit Breaker)
4.2 A × 1.25 = 5.25 (Circuit Breaker)
9. LAUNDRY
3. LIGHTING – Second Floor
2 × 120VA = 240VA
4 × 120VA = 480VA 240𝑉𝐴
480𝑉𝐴 = 1.04 A
= 2.1 A 230𝑉
230𝑉
1.04 A × 1.25 = 2.875 (Ampacity)
2.1 A × 1.25 = 2.625 (Ampacity)
1.04 A × 1.25 = 2.875 (Circuit Breaker)
2.1 A × 1.25 = 2.625 (Circuit Breaker)
10. RANGE
4. LIGHTING – Second Floor
8000VA
5 × 120VA = 600VA 8000𝑉𝐴
600𝑉𝐴 = 34.8 A
= 2.6 A 230𝑉
230𝑉
34.8 A × 1.25 = 43.5 (Ampacity)
2.6 A × 1.25 = 3.25 (Ampacity)
34.8 A × 1.25 = 43.5 (Circuit Breaker)
2.6 A × 1.25 = 3.25 (Circuit Breaker)
11. & 12. CONVENIENCE OUTLET – Second Floor
5. CONVENIENCE OUTLET – Ground Floor
3 × 180VA = 540VA
2 × 180VA = 360VA 540𝑉𝐴
360𝑉𝐴 = 2.3 A
= 1.6 A 230𝑉
230𝑉
2.3 A × 1.25 = 2.875 (Ampacity)
1.6 A × 1.25 = 2.0 (Ampacity)
2.3 A × 1.25 = 2.875 (Circuit Breaker)
1.6 A × 1.25 = 2.0 (Circuit Breaker)
13. ACU – Master’s Bedroom
6. CONVENIENCE OUTLET – Ground Floor
1.5 hp = 10 A
3 × 180VA = 540VA
540𝑉𝐴 10 A × 230 V = 2300 VA
230𝑉
= 2.3 A 10A × 1.25 = 12.50 (Ampacity)
2.3 A × 1.25 = 2.875 (Ampacity) 10 A × 2.50 = 25.0 (Circuit Breaker)
2.3 A × 1.25 = 2.875 (Circuit Breaker)
14. ACU – Bedroom 1
1.5 hp = 10 A
10 A × 230 V = 2300 VA
10A × 1.25 = 12.50 (Ampacity)
10 A × 2.50 = 25.0 (Circuit Breaker)
15. ACU – Bedroom 2
1 hp = 8 A
8 A × 230 V = 1840 VA
8 A × 1.25 = 10 (Ampacity)
8 A × 2.50 = 20 (Circuit Breaker)
APPLICATION OF DEMAND FACTORS
Total = 23180VA
First 3000VA @ 100% DF = 3000VA
Remainder @ 35% DF = (20180 × 0.35)
= 7063VA