Product datasheet
Specifications
Medium Voltage Variable Speed
Drive ATV6000 - 11 kV - 12500 kVA
ATV6000M125A1111NA3
Main
Range Of Product Altivar Process ATV6000
Product Or Component Type Medium voltage variable speed drive
Device Short Name ATV6000
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Specific Application Process and utilities
Assembly Style In floor-standing enclosure
Provided Equipment Power cells
Human machine interface
Plinth
Cooling fans
Enclosure
Phase-shifting transformer
Medium voltage arrestors
Colour Of Enclosure Light grey (RAL 7035)
Ip Degree Of Protection IP31 conforming to IEC 60529
Type Of Cooling Forced convection
Input Type 54 pulse diode rectifier bridge
Output Type IGBT inverter cells multilevel PWM
[Us] Rated Supply Voltage 11 kV +/- 10 %
Supply Frequency 50 Hz +/- 5 %
Network Number Of Phases 3 phases
Prospective Line Isc 31.5 kA for 150 ms
Output Voltage <= power supply voltage
Permissible Temporary Current 1.2 x In during 60 s (normal duty)
Boost 1.5 x In during 3 s (normal duty)
1.5 x In during 60 s (heavy duty)
1.8 x In during 3 s (heavy duty)
Speed Drive Output Frequency 0.1…120 Hz
Frequency Resolution 0.01 Hz
Product Destination Asynchronous motors
Permanent magnet motors
Synchronous motors
Asynchronous Motor Control Closed loop vector control
Profile U/F vector control
Energy saving control
Vector control with slip compensation in open loop
Synchronous Motor Control Permanent magnet control in open loop
Profile Permanent magnet control in close loop
Line start permanent magnet motor
Apparent Power 12500 kVA
Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.
Apr 15, 2024 1
Maximum Thdi <3 % conforming to IEEE 519-1992
Power Factor 96
Motor Power Kw 10000 kW for normal duty
9170 kW for heavy duty
Continuous Output Current 576 A heavy duty
628 A normal duty
Maximum Transient Current 1080 A during 3 s (heavy duty)
942 A during 3 s (normal duty)
Line Current 597 A heavy duty
656 A normal duty
Energy Efficiency Ratio 0.985 inverter
0.965 total drive including transformer
Power Losses 378.4 kW normal duty
347 kW heavy duty
Cable Entry Bottom
Width 15690.0 mm
Depth 1800.0 mm
Height 3151.0 mm
Net Weight 30750.0 kg
Volume Of Cooling Air 110542 m3/h
Noise Level 85 dB
Emc Filter Integrated conforming to IEC 61800-3 category C3 control
Integrated conforming to IEC 61800-3 category C4 power
Display Type 10 inch LCD touch screen multi-language
Complementary
Protection Type Line supply overvoltage: drive
Line supply undervoltage: drive
Line supply phase loss: drive
Overvoltages on the DC bus: drive
Thermal overload for transformer: drive
Cabinet overheating: drive
Overcurrent: drive
Overload: drive
Short-circuit protection: drive
IGBT for each cell: drive
Thermal protection: motor
Motor phase break: motor
Motor earth fault: motor
Break on the control circuit: drive
Fan monitoring: drive
Option Card Slot A: communication module for Profibus DP V1
Slot A: communication module for PROFINET
Slot A: communication module for DeviceNet
Slot A: communication module for CANopen daisy chain RJ45
Slot A: communication module for CANopen SUB-D 9
Slot A: communication module for CANopen screw terminals
Slot A: communication module for EtherCAT
Slot B: 5/12 V digital encoder interface module
Slot B: analog encoder interface module
Slot B: resolver encoder interface module
Slot B: HTL encoder interface module
Slot A/slot B: digital and analog I/O extension module
Slot A/slot B: output relay extension module
Connector Type 2 RJ45 (on the control block) for Ethernet IP/Modbus TCP
1 RJ45 (on the control block) for Modbus serial
Communication Port Protocol Ethernet IP/Modbus TCP
2 Apr 15, 2024
Supply Internal supply for digital inputs and PoE 24 V DC 21…27 V, <200 mA overload and
short-circuit protection
Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10
mA overload and short-circuit protection
External supply for digital inputs 24 V DC 19…30 V
External supply for control circuit 100...240 V AC 47...63 Hz
External supply for control circuit 120...370 V DC +/- 10 % 1 kVA
Auxiliary power supply 230 V AC +/- 10 %
External supply for cooling fan 400 V AC +/- 10 % 74 kVA
Analogue Input Type configurable voltage: 0...10 V DC, impedance: 30 kOhm, resolution: 12 bits
configurable current: 0...20 mA, impedance: 250 Ohm, resolution: 12 bits
Discrete Input Number 10
Discrete Input Type DI1...DI8 programmable, 24 V DC (<= 30 V), impedance: 3.5 kOhm
DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
POEA, POEB PWM output enable, 24 V DC (<= 30 V), impedance: > 2.2 kOhm
Analogue Output Number 2
Analogue Output Type Configurable voltage: 0...10 V DC impedance 470 Ohm, resolution 10 bits
Configurable current: 0...20 mA impedance 500 Ohm, resolution 10 bits
Discrete Output Number 2
Discrete Output Type Logic output <= 30 V DC 100 mA
Relay Output Number 3
Relay Output Type Configurable relay logic R1: fault relay NO/NC
Configurable relay logic R2: sequence relay NO
Configurable relay logic R3: sequence relay NO
Isolation Electrical between power and control
Overvoltage Category II conforming to IEC 61800-5-1 motor side
III conforming to IEC 61800-5-1 line side
III conforming to IEC 61800-5-1 low voltage connections
Environment
Electromagnetic Compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to
IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Pollution Degree 2 conforming to IEC 61800-5-1
Environmental Characteristic 3K3 conforming to IEC 60721-3-3
3B1 conforming to IEC 60721-3-3
3C2 conforming to IEC 60721-3-3
3S1 conforming to IEC 60721-3-3
3M1 conforming to IEC 60721-3-3
Relative Humidity 5…95 % without condensation conforming to IEC 60068-2-3
Ambient Air Temperature For 0…40 °C
Operation 40…50 °C with derating factor
-25…70 °C during transport
Ambient Air Temperature For 0…50 °C
Storage
Operating Altitude <= 1000 m without derating
1000...2000 m with derating factor
Standards IEC 61800-3
EN/IEC 61800-4
IEC 61800-5-1
IEC 60529
IEEE 519:1992
EN/IEC 60076
Marking CE
EAC
Apr 15, 2024 3
Product datasheet ATV6000M125A1111NA3
Dimensions Drawings
Dimensions and Clearance
Front View
Left view
B Maintenance Space
4 Apr 15, 2024
Product datasheet ATV6000M125A1111NA3
Connections and Schema
Interface Diagram
(1) : Remote command 3 wires control (external fault, Reverse, Forward, Stop)
(2) : Clients Mains Power Off
(3) : Embedded Modbus
(4) : Embedded Ethernet 1 and 2
SLOT A, SLOT B : Option Bus I/O, Encoder
QF1 : Main circuit breaker
POEA, POEB : Power Outputs
DI1 to DI8 : Digital Inputs
AI1, AI2, AI3 : Analog Inputs
DQ : Digital Output
AQ1, AQ2 : Analog Outputs 10/20 mA
R1, R2, R3 : Relay Outputs
Apr 15, 2024 5