ATV6000 11kV 12500kVA Drive Specs

The document provides specifications for a medium voltage variable speed drive called the ATV6000M125A1111NA3. It has a rated supply voltage of 11 kV, output voltage up to the supply voltage, and is designed for applications such as process and utilities. The drive has a power rating of 12500 kVA and 10000 kW for normal and heavy duty.

Uploaded by

Shivam More
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
90 views5 pages

ATV6000 11kV 12500kVA Drive Specs

The document provides specifications for a medium voltage variable speed drive called the ATV6000M125A1111NA3. It has a rated supply voltage of 11 kV, output voltage up to the supply voltage, and is designed for applications such as process and utilities. The drive has a power rating of 12500 kVA and 10000 kW for normal and heavy duty.

Uploaded by

Shivam More
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Product datasheet

Specifications

Medium Voltage Variable Speed


Drive ATV6000 - 11 kV - 12500 kVA
ATV6000M125A1111NA3

Main
Range Of Product Altivar Process ATV6000

Product Or Component Type Medium voltage variable speed drive

Device Short Name ATV6000

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product Specific Application Process and utilities

Assembly Style In floor-standing enclosure

Provided Equipment Power cells


Human machine interface
Plinth
Cooling fans
Enclosure
Phase-shifting transformer
Medium voltage arrestors

Colour Of Enclosure Light grey (RAL 7035)

Ip Degree Of Protection IP31 conforming to IEC 60529

Type Of Cooling Forced convection

Input Type 54 pulse diode rectifier bridge

Output Type IGBT inverter cells multilevel PWM

[Us] Rated Supply Voltage 11 kV +/- 10 %

Supply Frequency 50 Hz +/- 5 %

Network Number Of Phases 3 phases

Prospective Line Isc 31.5 kA for 150 ms

Output Voltage <= power supply voltage

Permissible Temporary Current 1.2 x In during 60 s (normal duty)


Boost 1.5 x In during 3 s (normal duty)
1.5 x In during 60 s (heavy duty)
1.8 x In during 3 s (heavy duty)

Speed Drive Output Frequency 0.1…120 Hz

Frequency Resolution 0.01 Hz

Product Destination Asynchronous motors


Permanent magnet motors
Synchronous motors

Asynchronous Motor Control Closed loop vector control


Profile U/F vector control
Energy saving control
Vector control with slip compensation in open loop

Synchronous Motor Control Permanent magnet control in open loop


Profile Permanent magnet control in close loop
Line start permanent magnet motor

Apparent Power 12500 kVA

Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.

Apr 15, 2024 1


Maximum Thdi <3 % conforming to IEEE 519-1992

Power Factor 96

Motor Power Kw 10000 kW for normal duty


9170 kW for heavy duty

Continuous Output Current 576 A heavy duty


628 A normal duty

Maximum Transient Current 1080 A during 3 s (heavy duty)


942 A during 3 s (normal duty)

Line Current 597 A heavy duty


656 A normal duty

Energy Efficiency Ratio 0.985 inverter


0.965 total drive including transformer

Power Losses 378.4 kW normal duty


347 kW heavy duty

Cable Entry Bottom

Width 15690.0 mm

Depth 1800.0 mm

Height 3151.0 mm

Net Weight 30750.0 kg

Volume Of Cooling Air 110542 m3/h

Noise Level 85 dB

Emc Filter Integrated conforming to IEC 61800-3 category C3 control


Integrated conforming to IEC 61800-3 category C4 power

Display Type 10 inch LCD touch screen multi-language

Complementary
Protection Type Line supply overvoltage: drive
Line supply undervoltage: drive
Line supply phase loss: drive
Overvoltages on the DC bus: drive
Thermal overload for transformer: drive
Cabinet overheating: drive
Overcurrent: drive
Overload: drive
Short-circuit protection: drive
IGBT for each cell: drive
Thermal protection: motor
Motor phase break: motor
Motor earth fault: motor
Break on the control circuit: drive
Fan monitoring: drive

Option Card Slot A: communication module for Profibus DP V1


Slot A: communication module for PROFINET
Slot A: communication module for DeviceNet
Slot A: communication module for CANopen daisy chain RJ45
Slot A: communication module for CANopen SUB-D 9
Slot A: communication module for CANopen screw terminals
Slot A: communication module for EtherCAT
Slot B: 5/12 V digital encoder interface module
Slot B: analog encoder interface module
Slot B: resolver encoder interface module
Slot B: HTL encoder interface module
Slot A/slot B: digital and analog I/O extension module
Slot A/slot B: output relay extension module

Connector Type 2 RJ45 (on the control block) for Ethernet IP/Modbus TCP
1 RJ45 (on the control block) for Modbus serial

Communication Port Protocol Ethernet IP/Modbus TCP

2 Apr 15, 2024


Supply Internal supply for digital inputs and PoE 24 V DC 21…27 V, <200 mA overload and
short-circuit protection
Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10
mA overload and short-circuit protection
External supply for digital inputs 24 V DC 19…30 V
External supply for control circuit 100...240 V AC 47...63 Hz
External supply for control circuit 120...370 V DC +/- 10 % 1 kVA
Auxiliary power supply 230 V AC +/- 10 %
External supply for cooling fan 400 V AC +/- 10 % 74 kVA

Analogue Input Type configurable voltage: 0...10 V DC, impedance: 30 kOhm, resolution: 12 bits
configurable current: 0...20 mA, impedance: 250 Ohm, resolution: 12 bits

Discrete Input Number 10

Discrete Input Type DI1...DI8 programmable, 24 V DC (<= 30 V), impedance: 3.5 kOhm
DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
POEA, POEB PWM output enable, 24 V DC (<= 30 V), impedance: > 2.2 kOhm

Analogue Output Number 2

Analogue Output Type Configurable voltage: 0...10 V DC impedance 470 Ohm, resolution 10 bits
Configurable current: 0...20 mA impedance 500 Ohm, resolution 10 bits

Discrete Output Number 2

Discrete Output Type Logic output <= 30 V DC 100 mA

Relay Output Number 3

Relay Output Type Configurable relay logic R1: fault relay NO/NC
Configurable relay logic R2: sequence relay NO
Configurable relay logic R3: sequence relay NO

Isolation Electrical between power and control

Overvoltage Category II conforming to IEC 61800-5-1 motor side


III conforming to IEC 61800-5-1 line side
III conforming to IEC 61800-5-1 low voltage connections

Environment
Electromagnetic Compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to
IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6

Pollution Degree 2 conforming to IEC 61800-5-1

Environmental Characteristic 3K3 conforming to IEC 60721-3-3


3B1 conforming to IEC 60721-3-3
3C2 conforming to IEC 60721-3-3
3S1 conforming to IEC 60721-3-3
3M1 conforming to IEC 60721-3-3

Relative Humidity 5…95 % without condensation conforming to IEC 60068-2-3

Ambient Air Temperature For 0…40 °C


Operation 40…50 °C with derating factor
-25…70 °C during transport

Ambient Air Temperature For 0…50 °C


Storage
Operating Altitude <= 1000 m without derating
1000...2000 m with derating factor

Standards IEC 61800-3


EN/IEC 61800-4
IEC 61800-5-1
IEC 60529
IEEE 519:1992
EN/IEC 60076

Marking CE
EAC

Apr 15, 2024 3


Product datasheet ATV6000M125A1111NA3

Dimensions Drawings

Dimensions and Clearance

Front View

Left view

B Maintenance Space

4 Apr 15, 2024


Product datasheet ATV6000M125A1111NA3

Connections and Schema

Interface Diagram

(1) : Remote command 3 wires control (external fault, Reverse, Forward, Stop)
(2) : Clients Mains Power Off
(3) : Embedded Modbus
(4) : Embedded Ethernet 1 and 2
SLOT A, SLOT B : Option Bus I/O, Encoder
QF1 : Main circuit breaker
POEA, POEB : Power Outputs
DI1 to DI8 : Digital Inputs
AI1, AI2, AI3 : Analog Inputs
DQ : Digital Output
AQ1, AQ2 : Analog Outputs 10/20 mA
R1, R2, R3 : Relay Outputs

Apr 15, 2024 5