IOM 7.5-25ton Commercial Rooftop-240325
IOM 7.5-25ton Commercial Rooftop-240325
YMMRZC090-150BAAKBKX
YMMRZC090-150BAJKBGX
YMFE15-25RCSMJMOWC
.PEFM/P YMFE15-25RCQMJMOWC
YMFE15-25RCSMJMOWX
YMFE15-25RCQMJMOWX
Issue Date
Mar.25 2024
Table of Contents
General Information . . . . . . . . . . . . . . . . . . . . . . . . 1
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Unit Foundation . . . . . . . . . . . . . . . . . . . . . . . . . 10
General Unit Requirements. . . . . . . . . . . . . . . 10
Main Unit Power. . . . . . . . . . . . . . . . . . . . . . . . . 12
External Unit Power Supply . . . . . . . . . . . . . . 15
Pre Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Verifying Proper Air Flow (Units with
Belt Drive Indoor Fan) . . . . . . . . . . . . . . . . . . . . 15
Electromechanical Controls – Test
Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Fan Belt Adjustment-Belt Drive
Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Monthly Maintenance. . . . . . . . . . . . . . . . . . . . 22
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Standard Troubleshooting . . . . . . . . . . . . . . . 25
Resetting Cooling and Heating
Lockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
CONFIGURATION. . . . . . . . . . . . . . . . . . . . . . . . . . 28
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Digital Display and Button Settings. . . . . . . . . 28
General Information
Warnings and Cautions appear at appropriate locations WARNING
throughout this manual.
Read these carefully. Never use a flammable spray such as hair spray, lacquer
or paint near the unit. It may cause a fire.
WARNING: Indicates a potentially hazardous situation
which, if not avoided, could result in death or serious Never inspect or service the unit by yourself.
injury. Ask a qualified service person to perform this work.
CAUTION: Indicates a potentially hazardous situation
Keep far away from high-frequency equipment.
which, if not avoided, may result in minor or moderate
injury.It may also be used to alarm against unsafe Keep away from the following places:
practices and where property-damage-only accidents A place where it is full of oil, gas; places where salty air
could occur. surrounding(near the coast); and a place where is caustic
gas(the sulfide in hotspring). Location in above places
may cause malfunction or shorten the life span of the
CAUTION manchine.
Do not insert fingers, rods or other objects into the air Check the electric wire, water and gas pipeline layout
inlet or outlet. inside the wall, floor and ceiling before installation. Do not
implement drilling unless confirm safety with the user,
When the fan is rotating at high speed, it will cause injury.
especially for the hidden power wire. An electroprobe can
Bodily injury can result from high voltage electrical be used to test whether a wire is passing by at the drilling
components, fast moving fans. For protection from these location, to prevent physical injury or death caused by
inherent hazards during installation and servicing, the insulation broken cords.
electrical supply must be disconnected.
Check the power supply before installation. Ensure that the
Do not operate the unit without the evaporator fan access power supply must be reliably grounded following local,
panel in place. Reinstall the access panel after performing state and National Electrical Codes. If not, for example, if
any maintenance. Operating the unit without the access the ground wire is detected charged, installation is
panel may result in severe personal injury or death. prohibited before it is rectified. Otherwise, there is a risk of
fire and electric shock, causing physical injury or death.
1
CAUTION CAUTION
Do not dry out the air filter under direct sunshine or heat. This unit is not intended for use by persons (including
children) with reduced physical, sensory or mental
Re-install the air filter capabilities, or lack of experience and knowledge, unless
they have been given supervision or instruction
Condenser coil concerning use of the appliance by a person responsible
Unfiltered air circulates through the unit's condenser coil for their safety. Children should be supervised to ensure
can cause the coil's surface to become clogged with that they do not play with the unit.
dust, etc. Clean the coil, vertically (i.e., with the fins), and
stroke the coil surface with a soft brush. Be sure to keep Disconnect the power supply before cleaning and
all vegetation away from the condenser coil area. maintenance.
Maintenance performed by serviceman. The unit shall be installed in accordance with national
To keep your unit operating safely and efficiently, the wiring regulations.
manufacturer recommends that a qualified serviceman
check the entire system at least once each year and any DISPOSAL: Do not dispose this product as
other time that you feel one is needed. Your serviceman unsorted municipal waste. Collection of such waste
should examine these areas of your unit: separately for special treatment is necessary.
Filters
Do not dispose of electrical appliances as unsorted
Motors and drive system components municipal waste, use separate collection facilities.
Economizer gaskets (for possible replacement) Contact you local government for information regarding
the collection systems available.
Safety controls (for mechanical cleaning)
If electrical appliances are disposed of in landfills or
Electrical components and wiring (for possible dumps, hazardous substances can leak into the
replacement and connection tightness) Condensate drain groundwater and get into the food chain, damaging your
(for cleaning) health and well-being.
2
Unit Description
Before shipment, each unit is leak tested, dehydrated,
charged with refrigerant and compressor oil, and run
tested for proper control operation.
Direct-drive, vertical discharge condenser fans are
provided with built-in thermal overload protection.
3
Dimensional Data
Below figure illustrates the minimum operating and Providing less than the recommended clearances may
service clearances for either a single or multiple unit result in condenser coil starvation, “short-circuiting” of
installation. These clearances are the minimum exhaust and economizer airflows, or recirculation of
distances necessary to assure adequate serviceability, hot condenser air.
cataloged unit capacity, and peak operating efficiency.
Figure 1. Typical installation clearance for single and multiple unit applications (in inches)
END TO END
NOTE 2,3
SIDE BY SIDE
NOTE 2
NOTE 1
4’ 0”
1’ 6” Minimum clearance
3’ 0” Side condensate drain is used
NOTES:
≥ 39-3/8"
1.FOR HORIZONTAL DISCHARGE UNIT,
Overhead air THIS MEASURE IS REDUCED TO 1’ 6”
Clearance≥ 118-1/8" TO MINIMIZE DUCT EXTENSIONS.
≥ 39-3/8"
2.WHEN EQUIPPED WITH ECONOMIZER
OR BAROMETRIC RELIEF DAMPER,
CLERANCE DISTANCE IS TO BE
MEASURE FROM PROTRUDING HOOD
INSTEAD OF BASE.
CONDENSATE
DRAIN
CONNECTION
Figure 3. 7.5-15 Ton units — front and side views (in inches)
2-3/4”
Ø2
Ø1-3/8”
2-3/4”
48-5/16”
48-3/4”
Ø2
44-3/16”
Ø1-3/8”
30-3/16”
Ø7/8”
14-7/16”
2-5/16”
7-3/4” 23-3/4” 7-3/4”
88-7/16” 58-7/8”
5
Figure 4. 7.5-15 Ton units — bottom view (in inches)
88-7/16”
25-5/8”
29-5/8” 14” 3-7/16”
12-7/16”
37-5/8”
40-11/16”
27-5/16”
12-3/8”
36-7/16” 3-7/16”
NOTES:
1.THROUGH THE BASE GAS AND ELECTRICAL IS NOT STANDARD ON ALL UNITS.
2.VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION.
Figure 5. 7.5-15 Ton units — back view (horizontal configuration) (in inches)
SUPPLY RETURN
36-7/16”
14”
5-5/8”
4-15/16”
23”
53-3/16”
6
Figure 6. Roof curb for 7.5-15 Ton units (in inches)
15 1/2”
15 13/16” 45 1/8”
37 15/16”
RETURN
3 9/16”
14.000
1 3/4”
54 9/16”
84 13/16”
UNIT OUTLINE
39 11/16” 54 5/8”
CLEARANCE 48”
CLEARANCE 60”
7
Figure 8. 20-25 Ton units-overview
/16 ”
7 15
1/32”
25 1
11 19/32”
3 15/16”
SUPPLY RETURN
27 9/16”
39 3/8”
Fresh air
Figure 9. 20-25 Ton units- front and side views (in inches)
A
3 15/16”
3/4” NPT
1 7/8”
27 9/16”
2 15/32” A
87 13/32”
8
Figure 10. 20-25 Ton units- bottom view (in inches)
19 11/16”
35 7/16”
19 11/16”
6 5/16”
41 15/16” 35 7/16” 23 21/32”
1 31/32”
65 5/32”
RETURN
29 7/32”
SUPPLY
4
5 5/8”
27 3/8” 35 27/32”
113 19/32”
9
Installation
Unit Foundation
WARNING
Risk of Roof Collapsing! Spreader bars
10
The checklist listed below is a summary of the steps N o t e : Use PVC pipe to connect to the drain pan
required to successfully install a commercial unit. This outlet provided in the unit. This is a slip fit joint
checklist is intended to acquaint the installing (no threads). Do not use PVC glue to connect
personnel with what is required in the installation condensate drain, thread sealing compound or
process. It does not replace the detailed instructions Teflon tape may be used.
called out in the applicable sections of this manual. A condensate trap must be installed at the unit due to
☐ Check the unit for shipping damage and material the drain connection being on the “negative pressure”
shortage; file a freight claim and notify appropriate side of the fan.
sales representative. A condensate drain line must be connected to the P-
☐ Verify correct model, options and voltage from Trap. Pitch the drain lines at least 0.5-inch for every 10
nameplate. feet of horizontal run to assure proper condensate flow.
Do not allow the horizontal run to sag causing a
☐ Verify that the installation location of the unit will
possible doubletrap condition which could result in
provide the required clearance for proper
condensate backup due to “air lock”.
operation.
☐ Assemble and install the roof curb (if applicable). Filter Installation
Refer to the latest edition of the curb installers Each unit ships with filters installed. The quantity of
guide that ships with each curb kit. filters is determined by unit size. Access to the filters
☐ Fabricate and install ductwork; secure ductwork to is obtained by removing the filter access panel.
curb.
N o t e : Do not operate the unit without filters.
☐ Rigging the unit.
☐ Set the unit onto the curb; check for levelness. Field Installed Power Wiring
☐ Ensure unit-to-curb seal is tight and without buckles An overall dimensional layout for the standard field
or cracks. installed wiring entrance into the unit is illustrated in
☐ Install and connect a condensate drain line to the
“Dimensional Data,” p. 4. To insure the unit’s supply
power wiring is properly sized and installed, follow the
evaporator drain connection.
guidelines outlined below.
Main Electrical Power Requirements N o t e : All field installed wiring must conform to
☐ Verify that the power supply complies with the unit Local codes.
nameplate specifications. Verify that the power supply available is compatible
☐ Inspect all control panel components; tighten any with the unit’s nameplate ratings. The available supply
loose connections. power must be within 10 percent of the rated voltage
☐ Connect properly sized and protected power supply stamped on the nameplate. Use only copper
wiring to a field-supplied/ installed disconnect conductors to connect the power supply to the unit.
switch and to the main power terminal block in the
unit control panel. NOTICE
☐ Install proper grounding wires to an earth ground. Use Copper Conductors Only!
N o t e : All field-installed wiring must comply with Failure to use copper conductors could result in
applicable local codes. equipment damage as the equipment was not
d e s i g n e d o r q u a l i ffiie d t o a c c e p t o t h e r t y p e s o f
Condensate Drain Configuration conductors.
An evaporator condensate drain connection is I m p o r t a n t : A field supplied disconnect switch must be
provided on each unit. Refer to “Dimensional Data,” p. installed at or near the unit in accordance
4 for the appropriate drain location. with the Local Electrical Code .
Table 1. electrical data
COMPRESSOR A COMPRESSOR B CONDENSER FAN INDOOR FAN MAIN POWER SUPPLY
VOLTS MODEL
RLA-VOLTS LRA RLA-VOLTS LRA FLA-VOLTS HP FLA-VOLTS HP MCA MOP
7.5T 11.6-208 123 10.4-208 73 1.5-208 0.34 7.2-208 2 36 45
10T 15.6-208 93 18.6-208 137 1.5-208 0.34 12-208 3 54 70
220V 12.5T 23.2-208 164 15.6-208 93 4.5-208 0.76 12-208 3 66 80
15T 23.2-208 164 23.2-208 164 4.5-208 0.76 14.6-208 5 76 90
20T 39.2-208 240 39.2-208 240 7.0-208 3.07 20.1-208 7.33 123 150
25T 48.2-208 245 48.2-208 245 7.0-208 3.07 20.1-208 7.33 143 175
7.5T 6.0-460 60 6.4-460 38 0.87-460 0.34 3.5-460 2 20 25
10T 6.5-460 60 7.8-460 52 0.87-460 0.34 8.7-460 3 27 30
460V 12.5T 11.2-460 75 6.5-460 60 2.1-460 0.76 8.7-460 3 34 40
15T 11.2-460 75 11.2-460 75 2.1-460 0.76 10.3-460 5 40 50
20T 17.1-460 142 17.1-460 142 4.65-460 3.07 9.4-460 7.33 58 70
25T 20.9-460 147 20.9-460 147 4.65-460 3.07 9.4-460 7.33 66 80
The power supply designation is YJV.
11
Main Unit Power
Controls using 24 Vac
Standard Wiring Before installing any connecting wiring, refer to
“Dimensional Data,” p. 4 for the electrical access
The electrical service must be protected from over locations provided on the unit and for AC conductor
current and short circuit conditions in accordance with sizing guidelines.
local requirements.
Protection devices must be sized according to the NOTICE
electrical data on the nameplate.
Use Copper Conductors Only!
• A field supplied disconnect switch must be installed Failure to use copper conductors could result in
at or near the unit in accordance with the Local equipment damage as the equipment was not
Electrical Code . d e s i g n e d o r q u a l i ffiie d t o a c c e p t o t h e r t y p e s o f
• Location of the applicable electrical service conductors.
entrance is illustrated in “Dimensional Data,” p. 4.
1. Use copper conductors unless otherwise specified.
Complete the unit’s power wiring connections onto
either; the main terminal block inside the unit 2. Ensure that the AC control wiring between the
control panel, or the electric heat terminal block. controls and the unit’s termination point does not
Refer to the customer connection diagram that exceed three (3) ohms/conductor for the length of
shipped with the unit for specific termination the run.
points.
N o t e : Resistance in excess of 3 ohms per conductor
• Provide proper grounding for the unit in accordance could cause component failure due to
with Local codes. insufficient AC voltage supply.
The 24-volt control power transformers are to be used 4. Do not run the AC low voltage wiring in the same
only with the accessories called out in this manual. conduit with the high voltage power wiring.
0 - 30 feet 22 gauge
31 - 50 feet 20 gauge
51 - 75 feet 18 gauge
12
Figure 12. Conventional thermostat field wiring diagram
13
226 - 221
100 X = 2.2%
226
The 2.2 percent imbalance in this example exceeds the 4. Observe the ABC and CBA phase indicator lights on
maximum allowable imbalance of 2.0 percent. This the face of the sequencer. The ABC indicator light
much imbalance between phases can equal as much as will glow if the phase is ABC. If the CBA indicator
a 20 percent current imbalance with a resulting light glows, open the disconnect switch or circuit
increase in motor winding temperatures that will protection switch and reverse any two power wires.
decrease motor life. 5. Restore the main electrical power and recheck the
If the voltage imbalance is over 2 percent, notify the phasing. If the phasing is correct, open the
proper agencies to correct the voltage problem before disconnect switch or circuit protection switch and
operating this equipment. remove the phase sequence indicator.
• Gray (phase C) to L3 ☐ Verify that the correct size and number of filters are
in place.
3. Close the field supplied main power disconnect
switch or circuit protector switch that provides the ☐ Inspect the interior of the unit for tools and debris
supply power to the unit. and install all panels in preparation for starting the
unit.
WARNING
Live Electrical Components!
Failure to follow all electrical safety precautions
when exposed to live electrical components could
result in death or serious injury.
When it is necessary to work with live electrical
c o m p o n e n t s , h a v e a q u a l i ffiie d l i c e n s e d e l e c t r i c i a n
or other individual who has been properly trained
in handling live electrical components perform
these tasks.
14
External Unit Power Supply Pre Start
Unit Disconnect Wiring Plan
Verifying Proper Air Flow (Units
1. Field connections are made by first removing the with Belt Drive Indoor Fan)
compressor access panel on the front of the unit.
Unscrew the assembly around the outside of the Much of the systems performance and reliability is
disconnect switch. This assembly is located in the closely associated with, and dependent upon having
condenser section of the unit. the proper airflow supplied both to the space that is
being conditioned and across the evaporator coil.
Both high and low voltage power can be routed
through the base or through the front corner post The indoor fan speed is changed by opening or closing
where the disconnect enclosure is mounted. The the adjustable motor sheave.
hole is sized for 1 1/2–in. conduit. Before starting the SERVICE TEST, set the minimum
2. If the conduit required for your application is larger position setpoint for the economizer to 0% using the
than 1 1/2–in., remove the termination plate and setpoint potentiometer located on the Economizer
connect to the larger hole using field supplied Control (ECA), if applicable.
reducing washers.
3. Route the power wires and ground conductor
through conduit and into the bottom of a field-
installed disconnect switch. Connect the power WARNING
conductors to the lugs provided. Connect the
ground wire to the unit ground lug.
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings
4. Route low voltage (class II), control wiring through
hole in base of unit but not through high voltage
exactly could result in serious injury,
conduit. Feed control wiring through bushing death or property damage.
provided on side panel. Route wires through loose
wire ties provided.
Never test for gas leaks with an open
5. Tighten the wire ties. Secure the excess wire bundle
under the wire ties in the outdoor section. Do not
flame. Use a commercially available
leave excess wire in the electrical enclosure. Use soap solution made specifically for the
the unit wiring diagram to make the low voltage detection of leaks to check all
connections.
connections. A fire or explosion may
result causing property damage,
personal injury or loss of life.
Electromechanical Controls –
Test Procedure
F a n T e s t a n d M i n i m u m V e n t i l a t i o n . Connect the
short circuit between R and G.
Connect the short circuit between R and Y1.
C o o l 1 . Connect the short circuit between R and Y1.
C o o l 2 . Connect the short circuit between R and Y2.
H e a t 1 . Connect the short circuit between R and W1.
H e a t 2 . Connect the short circuit between R and W2.
15
Parameter For Air Volunme
7.5Ton
10Ton
16
12.5Ton
15Ton
17
20Ton
18
25Ton
19
Start Up
● Is the wiring properly sized and run according to the unit wiring
diagram?
● Has the unit been properly grounded and fused with the
recommended fuse size? See Wiring Data.
● Does the condenser fan and indoor blower fan free without
rubbing, and are they tight on the shafts?
● Are all covers and access panels in place to prevent air loss
and safety hazards?
Voltage
With the unit operating, check the line voltage of the unit. The
voltage should be within the range shown on the unit
nameplate.
If low voltage is encountered, check the size and length of
the supply line from the main disconnect to the unit. The line
may be undersized for the length of the run.
20
Maintenance
WARNING deflection value determined in Step 1b.
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD 3. Set the small O-ring at zero on the force scale of the
gauge plunger.
Failure to follow safety warnings exactly could
result in dangerous 4. Place the large end of the gauge at the center of the
belt span; then depress the gauge plunger until the
operation, serious injury, death or property damage.
large O-ring is even with the top of the next belt or
Improper servicing could result in dangerous even with a straightedge placed across the fan and
operation, serious injury, motor sheaves.
death or property damage.
5. Remove the belt tension gauge. The small O-ring
• Before servicing, disconnect all electrical power now indicates a number other than zero on the
to unit. plunger’s force scale. This number represents the
• When servicing controls, label all wires prior to force (in pounds) required to give the needed
disconnecting. Reconnect wires correctly. deflection.
• Verify proper operation after servicing. 6. Compare the “force” scale reading (Step 5) with the
Make sure all personnel are standing clear of the unit appropriate “force” value listed in the Belt tension
before proceeding. The system components will start table. If the “force” reading is outside the range,
when the power is applied. readjust the belt tension.
N o t e : Actual belt deflection “force” must not
Fan Belt Adjustment-Belt Drive exceed the maximum “force” value shown in
the Belt tension measurement and deflection
Units ranges table.
7. Recheck the belt tension at least twice during the
WARNING first 2 to 3 days of operation. Belt tension may
Rotating Components! decrease until the new belts are “run in”.
Failure to disconnect power before servicing could
Figure 13. Belt tension gauge
result in rotating components cutting and slashing
technician which could result in death or serious
injury.
Disconnect all electric power, including remote
disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power
can not be inadvertently energized.
21
Table 3. Belt tension measurement and deflection ranges (in/lb)
Filters
Inspect the return air filters. Clean or replace them if
necessary.
22
WARNING Coil Cleaning
Rotating Components! Regular coil maintenance, including annual cleaning
enhances the unit’s operating efficiency by minimizing
Failure to disconnect power before servicing
the following:
could result in rotating components cutting
and slashing technician which could result in • Compressor head pressure and amperage draw
death or serious injury. • Evaporator water carryover
During installation, testing, servicing and
• Fan brake horsepower
troubleshooting of this product it may be
necessary to work with live and exposed • Static pressure losses
r o t a t i n g c o m p o n e n t s . H a v e a q u a l i ffiie d o r • Airflow reduction
licensed service individual who has been
At least once each year, or more often if the unit is
properly trained in handling exposed rotating
located in a “dirty” environment, clean the condenser
components, perform these tasks.
coils using the instructions outlined below. Be sure to
follow these instructions as closely as possible to avoid
NOTICE damaging the coils.
Equipment Damage!
Forcibly turning the motor shaft can damage
CAUTION
the gear train and motor beyond repair. Hazardous Chemicals!
Never turn the motor shaft by hand or with a Coil cleaning agents can be either acidic or highly
wrench. alkaline and can burn severely if contact with skin
or eyes occurs.
☐ Verify that all damper linkages move freely;
Handle chemical carefully and avoid contact with
lubricate with white grease, if necessary.
skin. ALWAYS wear Personal Protective
☐ Check supply fan motor bearings; repair or replace Equipment (PPE) including goggles or face shield,
the motor as necessary. chemical resistant gloves, boots, apron or suit as
☐ Check the fan shaft bearings for wear. Replace the required. For personal safety refer to the cleaning
bearings as necessary. agent manufacturer’s Materials Safety Data Sheet
and follow all recommended safe handling
☐ Check the supply fan belt(s). If the belts are frayed practices.
or worn, replace them. Refer to the “Fan Belt
Adjustment-Belt Drive Units,” p. 18 for belt
replacement and adjustments. Microchannel (MCHE) Coils
☐ Verify that all wire terminal connections are tight.
☐ Remove any corrosion present on the exterior NOTICE
surfaces of the unit and repaint these areas. Coil Damage!
☐ Generally inspect the unit for unusual conditions (e. Failure to follow instructions below could result in
g., loose access panels, leaking piping connections, coil damage.
etc.) DO NOT use any detergents with microchannel
☐ Make sure that all retaining screws are reinstalled in condenser coils.
the unit access panels once these checks are Use pressurized water or air ONLY, with pressure
complete. no greater than 600psi.
For additional information regarding the proper
☐ With the unit running, check and record the
microchannel coil cleaning procedure.
following:
– ambient temperature
Due to the soft material and thin walls of the MCHE
– compressor oil level (each circuit) coils, the traditional field maintenance method
– compressor suction and discharge pressures recommended for Round Tube Plate Fin (RTPF) coils
(each circuit) does not apply to microchannel coils. Moreover,
– superheat and subcooling (each circuit)
Record this data on an “operator’s maintenance log”
like the one shown in Sample maintenance log table in
Final Process Section. If the operating pressures
indicate a refrigerant shortage, measure the system
superheat and system subcooling.
23
chemical cleaners are a risk factor to MCHE due to the
material of the coil. The manufacturer does not
recommend the use of chemical cleaners to clean
microchannel coils. Using chemical cleaners could lead
to warranty claims being further evaluated for validity
and failure analysis.
The recommended cleaning method for microchannel
condenser coils is pressurized water or air with a non-
pinpoint nozzle and an ECU of at least 180 with
pressure no greater than 600 psi. To minimize the risk
of coil damage, approach the cleaning of the coil with
the pressure washer aimed perpendicular to the face of
the coil during cleaning. Optimum clearance between
the sprayer nozzle and the microchannel coil is 1”–3”.
Final Process
For future reference, record the unit data below in the
blanks provided.
24
Troubleshooting
6. If no abnormal operating conditions appear in the
WARNING test mode, exit the test mode by turning the power
Hazardous Service Procedures! “Off” at the main power disconnect switch and
Failure to follow all precautions in this manual and removing the test mode connections.
on the tags, stickers, and labels could result in
death or serious injury.
Technicians, in order to protect themselves from
Failures
potential electrical, mechanical, and chemical Simultaneous Heat and Cool Failure
hazards, MUST follow precautions in this manual Emergency Stop is activated.
and on the tags, stickers, and labels, as well as the
f o l l o w i n g i n s t r u c t i o n s : U n l e s s s p e c i ffiie d o t h e r w i s e , To Clear an Alarm
disconnect all electrical power including remote
disconnect and discharge all energy storing Once the alarm has been identified and the cause has
devices such as capacitors before servicing. been removed (for example, replaced faulty sensor),
Follow proper lockout/tagout procedures to the alarm can be cleared from the display.
ensure the power can not be inadvertently
energized. When necessary to work with live Resetting Cooling and Heating
e l e c t r i c a l c o m p o n e n t s , h a v e a q u a l i ffiie d l i c e n s e d
electrician or other individual who has been Lockouts
trained in handling live electrical components Cooling Failures and Heating Lockouts are reset in an
perform these tasks. identical manner.
Method 1 section explains resetting the system from
Standard Troubleshooting the space; Method 2 section explains resetting the
system at the unit.
Before turning the main power disconnect switch N o t e : Before resetting Cooling Failures and Heating
“Off”, follow the steps below to check the Mainboard. Lockouts check the Failure Status Diagnostics by
the methods previously explained. Diagnostics
To prevent injury or death from electrocution, it is the will be lost when the power to the unit is
responsibility of the technician to recognize this disconnected.
hazard and use extreme care when performing service
procedures with the electrical power energized. Method 1
To reset the system from the space, turn the “Mode”
1. Verify that the Digital Display on the mainboard is
displaying “E0”,if it is displaying “E0”,correct After approximately 30 seconds, turn the “Mode”
supply power fault. selection switch at the thermostat to the “Off” position.
selection switch to the desired mode, i.e. Heat, Cool or
2. Verify that the Digital Display on the mainboard is Auto.
displaying “–”. If the Digital Display is right, go to
Step 4.
25
Method 2
To reset the system at the unit, cycle the unit power by
turning the disconnect switch “Off” and then “On”.
Incorrect refrigerant charge Charge per procedure attached to unit service panel.
Insufficient cooling
Air, non-condensible or moisture in system Recover refrigerant, evacuate & recharge, add filter drier
Registers sweat Low evaporator airflow Increase speed of blower or reduce restriction - replace air
filter
Restriction in liquid line, expansion device or filter
Remove or replace defective component
drier
High head-low vapor pressure Flow check piston size too small Change to correct size piston
26
Table 5. Troubleshooting chart (continued)
Symptom Possible Cause Remedy
Increase speed of blower or reduce restriction - replace air
Low evaporator airflow
filter
Low vapor - cool compressor -
iced evaporator coil
Moisture in system Recover refrigerant - evacuate & recharge - add filter drier
Fluctuating head and vapor hunting Check air distribution on coil -replace Throttle
pressure
Air or non-condensible in system Recover refrigerant - evacuate and recharge
Gurgle or pulsing noise at
Air or non-condensible in system Recover refrigerant - evacuate and recharge
expansion device or liquid line
Circulating air blower and Manual reset overtemperature control tripped Reset or replace
inducer run continuously,
compressor will not start Wire loose in limit circuit Check wiring
27
CONFIGURATION
Overview Menu mode
This chapter describes how the system configuration 1. Press and hold the SW4 button for 3 seconds
can be implemented once the installation is complete to enter menu mode, and the digital display displays
and other relevant information. “n1”.
It contains the following information: 2. Press the SW4 button to Switch circularly in the Tier 1
● Using the Check function. of menu.
3. Press the SW3 button to enter the specified Tier 2 of
● Implement field settings
menu.
4. Press the SW3 button to Switch circularly in the Tier 2
of menu.
Digital Display and Button Settings 5. Press the SW4 button to confirm and exit.
Figure 14
CAUTION
DSP1
SW3 SW4
Operate the switches and push buttons with an
insulated stick (such as a closed ball-point
pen) to avoid touching live parts.
28
Table 8
Tier 1 of menu Tier 2 of menu Description Default
1ZY The latest error code of the outdoor fan A -
2ZY The second-to-last error code of the outdoor fan A -
n1 3ZY The third-to-last error code of the outdoor fan A -
4ZY The fourth-to-last error code of the outdoor fan A -
5ZY The Fifth-to-last error code of the outdoor fan A -
1ZY The latest error code of the outdoor fan B -
2ZY The second-to-last error code of the outdoor fan B -
n2 3ZY The third-to-last error code of the outdoor fan B -
4ZY The fourth-to-last error code of the outdoor fan B -
5ZY The Fifth-to-last error code of the outdoor fan B -
00 Auto dust-clean function unavailable √
n3
01 Auto dust-clean function available -
29
Johnson Controls, Inc. Milwaukee, USA www.johnsoncontrols.com Form:
Middle East and Africa Customer Care Email : [email protected]
Johnson Controls reserve the right to change product features without prior notice.